SECTION 1 HPS IMPERATOR
1
2
3
4
1
3
4 3 12
6
4
6
7
2
5
2 134
5
8
L V
120V
240V
HV
Dotted line represents
supplied jumper lead.
380V
277V
208V
2
3
4
5
2
6
5 4 23
1
5
1
4
3
7
7
8
3 245
L V
120V
240V
HV
Dotted line represents
supplied jumper lead.
380V
277V
208V
SECTION 1
HPS Im p e r a t o r Series - Wiring Schematic Drawings continued
Group K
PH***MGJ Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
380 None 1, 3 Unfused
277 None 1, 7 Unfused
208 None 1, 2 Unfused
SECTION 1
380 3-8 6, 4 1-5, 4-8
277 8-7 6, 4 1-5, 4-8
208 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 3-4, 1-2 1, 4 Unfused
240 2-3 1, 4 Unfused
120 3-4, 1-2 4, 6 1-5
240 2-3 4, 6 1-5
HPS IMPERATOR
TM
TM
PH***MGJ Schematic for 150VA to 1000VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
380 None 2, 6 Unfused
277 None 2, 4 Unfused
208 None 2, 3 Unfused
380 5-6 1, 8 2-7, 5-8
277 4-5 1, 8 2-7, 5-8
© Hammond Power Solutions Inc.
208 3-5 1, 8 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 4-5, 2-3 2, 5 Unfused
240 3-4 2, 5 Unfused
120 4-5, 2-3 1, 5 2-7
240 3-4 1, 5 2-7
62
Data subject to change without notice.