SECTION 1
IndustrIal open-style control
SECTION 9
HPS Spartan and HPS Fusion - Wiring Schematic Drawings continued
Group I
General purpose enclosed
208V 416V
200V 400V
190V 380V
H1 H3 H4H2 H2 H4H3H1
H1
X4
X3 X1X2X4
120V 240V
115V 230V
110V 220V
HV
H3
X2
X4 X2 X1X3
LV
H2
X3
H4
X1
SP***SP Schematic Connections for 208 X 416 to 120 X 240
FS***SP Schematic Connections for 208 X 416 to 120 X 240
High Voltage (HV)
(Primary Volts)
208 200 190 H1-H3, H2-H4 H1, H4
416 400 380 H2-H3 H1, H4
Low Voltage (LV)
(Secondary Volts)
120 115 110 X1-X3, X2-X4 X1, X4
240 230 220 X2-X3 X1, X4
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Supply Lines
Connect To
Load Lines
Connect To
SECTION 1
Group J
208V 416V
200V 400V
190V 380V
H1 H3 H4H2 H2 H4H3H1
H1
X4
12V 24V
11.5V 23V
11V 22V
HV
H3
X2
X3 X1X2X4
H2
X3
X4 X2 X1X3
H4
X1
LV
© Hammond Power Solutions Inc.
SP***SR Schematic Connections for 208 X 416 to 12 X 24
FS***SR Schematic Connections for 208 X 416 to 12 X 24
High Voltage (HV)
(Primary Volts)
208 200 190 H1-H3, H2-H4 H1, H4
416 400 380 H2-H3 H1, H4
Low Voltage (LV)
(Secondary Volts)
12 11.5 11 X1-X3, X2-X4 X1, X4
24 23 22 X2-X3 X1, X4
77
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Data subject to change without notice.
Supply Lines
Connect To
Load Lines
Connect To