Hammond Power Solutions Group I Wiring Diagrams

SECTION 1 HPS IMPERATOR
2
6
1
5
4
3
3
4
2
1
7
8
7
Dotted line represents supplied jumper lead.
L V
HV
480V/460V/440V
240V/230V/220V
208V/200V
25V/24V/23V
120V/115V/110V
2
6
1
5
4
3
2
4
1
7
8
Dotted line represents supplied jumper lead.
L V
HV
480V/460V/440V
240V/230V/220V
208V/200V
25V/24V/23V
120V/115V/110V
HPS Im p e r a t o r Series - Wiring Schematic Drawings continued
Group I
PH***MLI Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To
480 460 440 None 1, 3 Unfused 240 230 220 None 1, 7 Unfused 208 200 None 1, 2 Unfused 480 460 440 3-8 6, 4 1-5, 4-8 240 230 220 8-7 6, 4 1-5, 4-8 208 200 2-8 6, 4 1-5, 4-8
TM
SECTION 1
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To
120 115 110 None 1, 4 Unfused 25 24 23 None 1, 3 Unfused 120 115 110 None 4, 6 1-5 25 24 23 None 3, 6 1-5
PH***MLI Schematic for 150VA to 500VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To
480 460 440 None 2, 6 Unfused 240 230 220 None 2, 4 Unfused 208 200 None 2, 3 Unfused 480 460 440 5-6 1, 8 2-7, 5-8 240 230 220 4-5 1, 8 2-7, 5-8 208 200 3-5 1, 8 2-7, 5-8
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 None 2, 4 Unfused 25 24 23 None 2, 3 Unfused 120 115 110 None 1, 4 2-7 25 24 23 None 1, 3 2-7
PH***MLI Schematic for 750VA and 1000VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To
480 460 440 None 2, 6 Unfused
© Hammond Power Solutions Inc.
240 230 220 None 2, 4 Unfused 208 200 None 2, 3 Unfused 480 460 440 5-6 1, 8 2-7, 5-8 240 230 220 4-5 1, 8 2-7, 5-8 208 200 3-5 1, 8 2-7, 5-8
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 None 1, 4 Unfused 25 24 23 None 1, 2 Unfused
Note: secondary fuse clips for 24V tap not available on the PH750MLI or PH1000MLI units.
60
Data subject to change without notice.