SECTION 9
Group H
HPS IMPERATOR
TM
PH***MBMH Schematic for 50 and 75VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
600 575 550 None 1, 3 Unfused
480 460 440 None 1, 7 Unfused
240 230 220 None 1, 2 Unfused
600 575 550 3-8 6, 4 1-5, 4-8
480 460 440 8-7 6, 4 1-5, 4-8
240 230 220 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse
(Secondary Volts) Links Between Terminals Connect To Clips To
120 115 110 None 1, 4 Unfused
100 95 90 None 1, 3 Unfused
120 115 110 None 4, 6 1-5
100 95 90 None 3, 6 1-5
SECTION 1
PH***MBMH Schematic for 100VA to 1500VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
600 575 550 None 2, 6 Unfused
480 460 440 None 2, 4 Unfused
240 230 220 None 2, 3 Unfused
600 575 550 5-6 1, 8 2-7, 5-8
480 460 440 4-5 1, 8 2-7, 5-8
240 230 220 3-5 1, 8 2-7, 5-8
© Hammond Power Solutions Inc.
Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse
(Secondary Volts) Links Between Terminals Connect To Clips To
120 115 110 None 2, 4 Unfused
100 95 90 None 2, 3 Unfused
120 115 110 None 1, 4 2-7
100 95 90 None 1, 3 2-7