![](/html/89/89ab/89ab36159ed52460b789fc50c6e9c6ef7ee299a64fa74ecd9e5c71f71a2a6f5e/bg1.png)
SECTION 1
HPS SPARTAN® & HPS FUSION
™
HPS Spartan and HPS Fusion - Wiring Schematic Drawings continued
Group G
H1
SECTION 1
X2
HV
277V
120V
LV
H2
X1
SP***NJ Schematic Connections for 277 to 120
FS***NJ Schematic Connections for 277 to 120
High Voltage (HV)
(Primary Volts)
277 None H1, H2
Low Voltage (LV)
(Secondary Volts)
120 None X1, X2
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Supply Lines
Connect To
Load Lines
Connect To
Group H
SP***PR Schematic Connections for 120 X 240 to 12 X 24
FS***PR Schematic Connections for 120 X 240 to 12 X 24
120 115 110 H1-H3, H2-H4 H1, H4
240 230 220 H2-H3 H1, H4
H3
X2
HV
H2
X3
X4 X2 X1X3
H4
X1
120V 240V
115V 230V
110V 220V
H1 H3 H4H2 H2 H4H3H1
H1
X4
X3 X1X2X4
12V 24V
11.5V 23V
11V 22V
LV
© Hammond Power Solutions Inc.
High Voltage (HV)
(Primary Volts)
Low Voltage (LV)
(Secondary Volts)
12 11.5 11 X1-X3, X2-X4 X1, X4
24 23 22 X2-X3 X1, X4
76
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Data subject to change without notice.
Supply Lines
Connect To
Load Lines
Connect To