Hammond Power Solutions Group E, Group F Connection Diagram

SECTION 1
IndustrIal open-style control
SECTION 9
HPS Fusion and HPS Spartan - Wiring Schematic Drawings continued
Group E
General purpose enclosed
H1
X4
120V
347V
X2
HV
380V
LV
X3
X4 X2 X1X3X3 X1X2X4
H2
X1
240V
H3
FS***KHP Schematic Connections for 380/347 to 120 X 240
High Voltage (HV)
(Primary Volts)
380 None H1, H3
347 None H1, H2
Low Voltage (LV)
(Secondary Volts)
120 X1-X3, X2-X4 X1, X4
240 X2-X3 X1, X4
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Supply Lines
Connect To
Load Lines
Connect To
SECTION 1
Group F
HV
H1
X4
12V
347V
X2
380V
X3
X4 X2 X1X3X3 X1X2X4
LV
H3
H2
X1
24V
© Hammond Power Solutions Inc.
SP***KHR Schematic Connections for 380/347 to 12 X 24
FS***KHR Schematic Connections for 380/347 to 12 X 24
High Voltage (HV)
(Primary Volts)
380 None H1, H3
347 None H1, H2
Low Voltage (LV) (Secondary Volts)
12 X1-X3, X2-X4 X1, X4
24 X2-X3 X1, X4
75
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Data subject to change without notice.
Supply Lines
Connect To
Load Lines
Connect To
Loading...