SECTION 1
1
2
3
4
1
2
3
4
4 3 12
6
7
6
1 2 43
8
5
5
3 421
2 134
HV
L V
230V 460V
240V 480V
220V 440V
11.5V 23V
12V 24V
11V 22V
2
3
4
5
2
3
4
5
1
6
1
8
7
7
3 2456 1 56 4 2 13
L V
21 3 4HV5 6 21 3 4 5 6
230V 460V
240V 480V
220V 440V
11.5V 23V
12V 24V
11V 22V
SECTION 9
Group D
HPS IMPERATOR
TM
PH***QR Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
240 230 220 1-2, 3-4 1, 4 Unfused
480 460 440 2-3 1, 4 Unfused
240 230 220 1-2, 3-4 6, 7 1-5, 4-8
480 460 440 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
24 23 22 2-3 1, 4 Unfused
12 11.5 11 3-4, 1-2 4, 6 1-5
24 23 22 2-3 4, 6 1-5
SECTION 1
© Hammond Power Solutions Inc.
PH***QR Schematic for 150VA to 500VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
240 230 220 2-3, 4-5 2, 5 Unfused
480 460 440 3-4 2, 5 Unfused
240 230 220 2-3, 4-5 1, 6 2-7, 5-8
480 460 440 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 4-5, 2-3 2, 5 Unfused
24 23 22 3-4 2, 5 Unfused
12 11.5 11 4-5, 2-3 1, 5 2-7
24 23 22 3-4 1, 5 2-7
55