Hammond Power Solutions Group C, Group D Connection Diagram

SECTION 1
HPS SPARTAN® & HPS FUSION
HPS Fusion and HPS Spartan - Wiring Schematic Drawings continued
Group C
240V 480V 230V 460V 220V 440V
H1 H3 H4H2 H2 H4H3H1
H1
SECTION 1
X4
120V 240V 115V 230V 110V 220V
SP***MQMJ Schematic Connections for 240 X 480 to 120 X 240
HV
FS***MQMJ Schematic Connections for 240 X 480 to 120 X 240
H3
X2
X3 X1X2X4
H2
X3
X4 X2 X1X3
LV
H4
X1
High Voltage (HV)
(Primary Volts)
240 230 220 H1-H3, H2-H4 H1, H4
480 460 440 H2-H3 H1, H4
Low Voltage (LV)
(Secondary Volts)
120 115 110 X1-X3, X2-X4 X1, X4
240 230 220 X2-X3 X1, X4
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Supply Lines
Connect To
Load Lines
Connect To
Group D
240V 480V 230V 460V 220V 440V
H1 H3 H4H2 H2 H4H3H1
H1
X4
12V 24V
11.5V 23V 11V 22V
HV
H3
X2
X3 X1X2X4
H2
X3
X4 X2 X1X3
H4
X1
LV
© Hammond Power Solutions Inc.
SP***QR Schematic Connections for 240 X 480 to 12 X 24
FS***QR Schematic Connections for 240 X 480 to 12 X 24
High Voltage (HV)
(Primary Volts)
240 230 220 H1-H3, H2-H4 H1, H4
480 460 440 H2-H3 H1, H4
Low Voltage (LV)
(Secondary Volts)
12 11.5 11 X1-X3, X2-X4 X1, X4
24 23 22 X2-X3 X1, X4
Install Supplied Jumpers
Between Terminals
Install Supplied Links Between
Terminals
Supply Lines
Connect To
Load Lines
Connect To
74
Data subject to change without notice.