SECTION 1 HPS IMPERATOR
4
1
4
3
2
1
2 134
6
6
7
4 3 12
5
5
8
HV
L V
1 2 43
575V
600V
550V
115V 230V
120V 240V
110V 220V
5
2
5
4
3
2
3 2456 1
1
1
6
56 4 2 13
7
7
8
L V
21 3 4HV5 6
575V
600V
550V
115V 230V
120V 240V
110V 220V
HPS Im p e r a t o r Series - Wiring Schematic Drawings
Group A
PH***AJ Schematic for 50, 75 and 100VA Units
TM
SECTION 1
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
(Primary Volts) Links Between Terminals Connect To Clips To
600 575 550 None 1, 4 Unfused
600 575 550 None 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 3-4, 1-2 4, 6 1-5
240 230 220 2-3 4, 6 1-5
PH***AJ Schematic for 150VA to 1500VA Units
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
(Primary Volts) Links Between Terminals Connect To Clips To
600 575 550 None 2, 5 Unfused
600 575 550 None 1, 6 2-7, 5-8
© Hammond Power Solutions Inc.
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 4-5, 2-3 1, 5 2-7
240 230 220 3-4 1, 5 2-7
52
Data subject to change without notice.