Hammond Power Solutions C1F002LES Wiring Diagrams

Page 1
GENERAL INFORMATION
SCD 1
SCHEMATIC CONNECTIONS
H1 H3 H2 H4
X4 X2 X3 X1
SCD 2
SCHEMATIC CONNECTIONS
H1 H2 H1 H2
HV HV
7 8642135 7 8642135
X4 X1X3X2
LV
OR
OR
X4 X1X3X2
LV LV
LV
Primary Volts Connect lines to Inter-connect
240 480 416 H1, H4 H2-H3 120 240 208 H1, H4 H1-H3, H2-H4
Secondary Volts Connect lines to Inter-connect
24 32 48 240 X1, X4 X2-X3 12/24 16/32 24/48 120/240 X1, X2, X4 X2-X3 12 16 24 120 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
504 440 437 218 291 277 440 H1, H2 1-2 492 426 213 284 H1, H2 2-3 480 416 416 208 277 240 416 H1, H2 3-4 468 406 203 270 H1, H2 4-5 456 400 395 198 263 208 400 H1, H2 5-6 444 385 192 256 H1, H2 6-7 432 380 374 187 249 120 380 H1, H2 7-8 220 H1, H2 H1-2, H2-1 240 208 208 H1, H2 H1-4, H2-3 228 200 198 H1, H2 H1-6, H2-5 216 190 187 H1, H2 H1-8, H2-7
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2- X3 120 X1, X2 X2-X4, X1-X3 120/240 X1, X2, X4 X2-X3
SCD 3
SCHEMATIC CONNECTIONS
1
H2
2
3
4
5
6
7
H1
H3
X1
© Hammond Power Solutions Inc.
X2
X0
X3
Primary Volts Connect lines to Inter-connect
630 H1, H2, H3 1-H1, 1-H2, 1-H3 615 H1, H2, H3 2-H1, 2-H2, 2-H3 600 H1, H2, H3 3-H1, 3-H2, 3-H3 585 H1, H2, H3 4-H1, 4-H2, 4-H3 570 H1, H2, H3 5-H1, 5-H2, 5-H3 480 H1, H2, H3 6-H1, 6-H2, 6-H3 456 H1, H2, H3 7-H1, 7-H2, 7-H3 432 H1, H2, H3 8-H1, 8-H2, 8-H3
Secondary Volts Connect lines to Inter-connect
208 480 X1, X2, X3 ­ 120 120 X1, X0 ­ X2, X0 ­ X3, X0 -
269
Data subject to change without notice.
GENERAL
INFORMATION
Page 2
GENERAL INFORMATION
SCD 4
SCHEMATIC CONNECTIONS
H1 H2
X4 X3X2 X1
SCD 5
SCHEMATIC CONNECTIONS
H1 H2
3 421
Primary Volts Connect lines to Inter-connect
208 277 347 380 416 600 2400 3300 4160 4800 6600 7200 H1, H2 ---
Secondary Volts Connect lines to Inter-connect
240 24 X1, X4 X2-X3 120/240 12/24 X1, X2, X4 X2-X3 120 12 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
120 208 240 277 380 416 480 600 H1, H2 1-2 114 198 228 263 361 395 456 570 H1, H2 2-3 108 188 216 249 347 374 432 540 H1, H2 3-4
GENERAL
X4 X3X2 X1
SCD 6
SCHEMATIC CONNECTIONS
H1 H2 H1 H2
X4 X1 X3 X2
HV HV
OR
6 4 2 1 3 5 6 4 2 1 3 5
OR
LV
X4 X1 X3 X2
LV LV
SCD 7
SCHEMATIC CONNECTIONS
INFORMATION
H1
1
2
3
H2
X1
H3
X2
LV
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
218 277 291 437 504 630 2520 4368 H1, H2 1-2 213 - 284 426 492 615 2460 4264 H1, H2 2-3 208 240 277 416 480 600 2400 4160 H1, H2 3-4 203 - 270 406 468 585 2340 4056 H1, H2 4-5 198 208 263 395 456 570 2280 3952 H1, H2 5-6
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3
120/240 X1, X2, X4 X2-X3
120 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
208 218 242 252 437 480 483 504 604 630 H1, H2, H3 1 198 208 230 240 416 456 460 480 575 600 H1, H2, H3 2 187 198 219 228 395 432 437 456 546 570 H1, H2, H3 3
X0
Secondary Volts Connect lines to
X3
208 230 240 380 416 460 480 600 X1, X2, X3 120 133 139 220 240 265 277 347 X1, X0 X2, X0 X3, X0
© Hammond Power Solutions Inc.
270
Data subject to change without notice.
Page 3
GENERAL INFORMATION
SCD 8
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
218 242 252 437 483 504 604 630 2520 4368 H1, H2, H3 1-2 208 230 240 416 460 480 575 600 2400 4160 H1, H2, H3 2-3 198 219 228 395 437 456 546 570 2280 3952 H1, H2, H3 3-4
Secondary Volts Connect lines to
X3
208 230 240 380 416 460 480 600 X1, X2, X3 120 133 139 220 240 265 277 347 X1, X0 X2, X0 X3, X0
Primary Volts Connect lines to Inter-connect
218 242 252 437 483 504 604 630 H1, H2, H3 1 213 236 246 426 472 492 589 615 H1, H2, H3 2 208 230 240 416 460 480 575 600 H1, H2, H3 3 203 224 234 406 449 468 561 585 H1, H2, H3 4 198 219 228 395 437 456 546 570 H1, H2, H3 5
X0
Secondary Volts Connect lines to Inter-connect
X3
208 380 416 480 600 X1, X2, X3 ­ 120 220 240 277 347 X1, X0 ­ X2, X0 ­ X3, X0 -
4
2
1
3
SCD 9
1
2
3
4
5
H1
H2
X1
H3H1
X2
X0
SCHEMATIC CONNECTIONS
H2
X1
H3
X2
SCD 10
SCHEMATIC CONNECTIONS
H2
6
4
2
1
3
5
H1
X1
H3
© Hammond Power Solutions Inc.
X2
X0
X3
Primary Volts Connect lines to Inter-connect
218 242 252 437 483 504 604 630 2520 4368 H1, H2, H3 1-2 213 236 246 426 472 492 589 615 2460 4264 H1, H2, H3 2-3 208 230 240 416 460 480 575 600 2400 4160 H1, H2, H3 3-4 203 224 234 406 449 468 561 585 2340 4056 H1, H2, H3 4-5 198 219 228 395 437 456 546 570 2280 3952 H1, H2, H3 5-6
Secondary Volts Connect lines to Inter-connect
208 380 416 480 600 X1, X2, X3 ­ 120 220 240 277 347 X1, X0 ­ X2, X0 ­ X3, X0 -
271
Data subject to change without notice.
GENERAL
INFORMATION
Page 4
GENERAL INFORMATION
X3
SCD 11
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
630 H1, H2, H3 1-H1, 1-H2, 1-H3 615 H1, H2, H3 2-H1, 2-H2, 2-H3 600 H1, H2, H3 3-H1, 3-H2, 3-H3 585 H1, H2, H3 4-H1, 4-H2, 4-H3 570 H1, H2, H3 5-H1, 5-H2, 5-H3 504 H1, H2, H3 6-H1, 6-H2, 6-H3 492 H1, H2, H3 7-H1, 7-H2, 7-H3 480 H1, H2, H3 8-H1, 8-H2, 8-H3
X0
468 H1, H2, H3 9-H1, 9-H2, 9-H3 456 H1, H2, H3 10-H1, 10-H2, 10-H3
Secondary Volts Connect lines to Inter-connect
208 480 X1, X2, X3 ­ 120 277 X1, X0 ­ X2, X0 ­ X3, X0 -
H1
1
2
3
4
5
6
7
8
9
10
H2
X2
X1
H3
SCD 12
SCHEMATIC CONNECTIONS
H2 X2
4
2
1
3
H1 H3 X1 X3
SCD 13
SCHEMATIC CONNECTIONS
X2H2
4
2
1
3
H1 H3 X1 X3
120 120
X6
Primary Volts Connect lines to Inter-connect
480 600 H1, H2, H3 1-2 456 570 H1, H2, H3 2-3 432 540 H1, H2, H3 3-4
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3 -
Primary Volts Connect lines to Inter-connect
480 600 H1, H2, H3 1-2 456 570 H1, H2, H3 2-3 432 540 H1, H2, H3 3-4
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3 ­ 120 X1, X6 ­ X3, X6 -
GENERAL
SCD 14
INFORMATION
© Hammond Power Solutions Inc.
SCHEMATIC CONNECTIONS
H2 H5 X8 X5 X2
X3
X6
X9
H6
X1
X4
X7
H4
H1
H3
Connect to Step Down Step Up
Lines from Supply H1, H2, H3 X1, X2, X3
Lines to Load X1, X2, X3 H1, H2, H3
272
Data subject to change without notice.
Page 5
GENERAL INFORMATION
SCD 15
SCHEMATIC CONNECTIONS
SCD 16
H1
H2 H5
X2
X3
H6
X1
H4
H1
H3
SCHEMATIC CONNECTIONS
H2
1 2 3 4 5
X1
H3
X2
X3
Connect to Step Down Step Up
Lines from Supply H1, H2, H3 X1, X2, X3
Lines to Load X1, X2, X3 H1, H2, H3
Primary Volts Connect lines to Inter-connect
504 630 H1, H2, H3 1 492 615 H1, H2, H3 2 480 600 H1, H2, H3 3 468 585 H1, H2, H3 4 456 570 H1, H2, H3 5
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3
SCD 17
SCHEMATIC CONNECTIONS
H1 H3 H2 H4 H1 H3 H2 H4
HV HV
7 8 6 4 2 1 3 5 7 8 6 4 2 1 3 5
X4 X1 X3 X2
LV
OR
OR
X4 X1 X3 X2
LV LV
LV
SCD 18
SCHEMATIC CONNECTIONS
H1 H2H3H4 H2H3H4H1
HV HV
X4 X1X3X2
LV
OR
OR
X4 X1X3X2
LV LV
LV
Primary Volts Connect lines to Inter-connect
504 H1, H4 1-H2, 2-H3, H2-H3 492 H1, H4 3-H2, 2-H3, H2-H3 480 H1, H4 3-H2, 4-H3, H2-H3 468 H1, H4 5-H2, 4-H3, H2-H3 456 H1, H4 5-H2, 6-H3, H2-H3 444 H1, H4 7-H2, 6-H3, H2-H3 432 H1, H4 7-H2, 8-H3, H2-H3 252 H1, H4 1-H2, 2-H3, H1-H3, H2-H4 240 H1, H4 3-H2, 4-H3, H1-H3, H2-H4 228 H1, H4 5-H2, 6-H3, H1-H3, H2-H4 216 H1, H4 7-H2, 8-H3, H1-H3, H2-H4
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2- X3 120 X1, X2 X2-X4, X1-X3 120/240 X1, X2, X4 X2-X3
Primary Volts Connect lines to Inter-connect
218 252 277 291 437 504 630 H1, H4 ­ 208 240 240 277 416 480 600 H1, H3 ­ 198 228 208 263 395 456 570 H1, H2 -
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120 X1, X2 X2-X4, X1-X3 120/240 X1, X2, X4 X2-X3
GENERAL
INFORMATION
© Hammond Power Solutions Inc.
273
Data subject to change without notice.
Page 6
GENERAL INFORMATION
SCD 19
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
1
H2
2
3
4
5
6
7
H1
SCD 20
SCHEMATIC CONNECTIONS
H2
8
6
4
2
1
3
5
7
H1 H3
X2
X1
H3
X2
X1
218 504 630 H1, H2, H3 1-H1, 1-H2, 1-H3 213 492 615 H1, H2, H3 2-H1, 2-H2, 2-H3 208 480 600 H1, H2, H3 3-H1, 3-H2, 3-H3 203 468 585 H1, H2, H3 4-H1, 4-H2, 4-H3
X0
198 456 570 H1, H2, H3 5-H1, 5-H2, 5-H3 193 444 556 H1, H2, H3 6-H1, 6-H2, 6-H3 188 432 542 H1, H2, H3 7-H1, 7-H2, 7-H3
X3
Secondary Volts Connect lines to Inter-connect
208 480 X1, X2, X3 ­ 120 277 X1,X0 | X2,X0 | X3,X0 -
Primary Volts Connect lines to Inter-connect
218 504 630 H1, H2, H3 1-2 213 492 600 H1, H2, H3 2-3 208 480 570 H1, H2, H3 3-4 203 468 H1, H2, H3 4-5
X0
198 456 504 H1, H2, H3 5-6 193 444 480 H1, H2, H3 6-7 188 432 456 H1, H2, H3 7-8
X3
Secondary Volts Connect lines to Inter-connect
208 X1, X2, X3 ­ 120 X1,X0 | X2,X0 | X3,X0 -
GENERAL
INFORMATION
SCD 21
1
2
3
4
5
6
7
H1
SCD 22
8
6
4
2
1
3
5
7
H1
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
504 H1, H2, H3 1-H1, 1-H2, 1-H3 492 H1, H2, H3 2-H1, 2-H2, 2-H3 480 H1, H2, H3 3-H1, 3-H2, 3-H3
H2
X2
468 H1, H2, H3 4-H1, 4-H2, 4-H3 456 H1, H2, H3 5-H1, 5-H2, 5-H3 444 H1, H2, H3 6-H1, 6-H2, 6-H3 432 H1, H2, H3 7-H1, 7-H2, 7-H3
H3
X1
120V 120V
X6
Secondary Volts Connect lines to Inter-connect
X3
240 X1, X2, X3 ­ 120 X1, X6 ­ X3, X6 -
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
504 H1, H2, H3 1-2 492 H1, H2, H3 2-3 480 H1, H2, H3 3-4 468 H1, H2, H3 4-5 456 H1, H2, H3 5-6 444 H1, H2, H3 6-7 432 H1, H2, H3 7-8
Secondary Volts Connect lines to Inter-connect
X3
240 X1, X2, X3 ­ 120 X1, X6 ­ X3, X6 -
H3 X1
X2H2
120V 120V
X6
© Hammond Power Solutions Inc.
274
Data subject to change without notice.
Page 7
GENERAL INFORMATION
SCD 23
SCHEMATIC CONNECTIONS
H2
H1
SCD 24
X2
4
2
1
3
H0
H3
X1
X3
SCHEMATIC CONNECTIONS
H1
X1
X3
H3
X2
H2
Primary Volts Connect lines to Inter-connect
208 240 X1, X2, X3 1-2 198 228 X1, X2, X3 2-3 188 216 X1, X2, X3 3-4
Secondary Volts Connect lines to
230 260 460 480 H1, H2, H3 133 139 265 277 H1, H0 H2, H0 H3, H0
Connect to Step Down Step Up
Lines from Supply H1, H2, H3 X1, X2, X3
Lines to Load X1, X2, X3 H1, H2, H3
SCD 25
4
2
1
3
SCD 26
H2
H1
SCD 27
SCHEMATIC CONNECTIONS
H2
X2
X0
X1
H3H1
X3
Primary Volts Connect lines to Inter-connect
208 240 416 480 600 H1, H2, H3 1-2 198 228 395 456 570 H1, H2, H3 2-3 187 216 374 432 540 H1, H2, H3 3-4
Secondary Volts Connect lines to Inter-connect
208 380 416 480 600 X1, X2, X3 ­ 120 220 240 277 347 X1, X0 X2, X0 X3, X0 -
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
218 252 X1, X2, X3 1 213 246 X1, X2, X3 2 208 240 X1, X2, X3 3 203 234 X1, X2, X3 4 198 228 X1, X2, X3 5
X3
Secondary Volts Connect lines to Inter-connect
460 480 600 H1, H2, H3 ­ 265 277 347 H1, H0 H2, H0 H3, H0 -
H0
H3
X1
X2
5
4
3
2
1
GENERAL
INFORMATION
SCHEMATIC CONNECTIONS
H1
H2
4 2 1 3
X1
H3
X2
X3
© Hammond Power Solutions Inc.
Primary Volts Connect lines to Inter-connect
630 H1, H2, H3 1-2 600 H1, H2, H3 2-3 570 H1, H2, H3 3-4
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3 -
275
Data subject to change without notice.
Page 8
GENERAL INFORMATION
SCD 28
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
480 (60Hz) H1, H10 H5-H6
H1
H2 H3 H4 H5 H6 H7 H8 H9 H10
X4 X3 X2 X1
440 H1, H10 H5-H6 416 H1, H9 H4-H6 400 H1, H8 H3-H6 380 H1, H7 H2-H6 240 (60 Hz) H1, H10 H1-H6, H5-H10 220 H1, H10 H1-H6, H5-H10 208 H1, H9 H1-H6, H4-H9 200 H1, H8 H1-H6, H3-H8 190 H1, H7 H1-H6, H2-H7
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3
GENERAL
SCD 29
SCHEMATIC CONNECTIONS
H2
6 4 2
1
3 5
H1
X1
H3
SCD 30
SCHEMATIC CONNECTIONS
H1 H3 H2 H4 H1 H3 H2 H4
INFORMATION
HV HV
7 8 6 4 2 1 3 5 7 8 6 4 2 1 3 5
X4 X1 X3 X2
LV
OR
OR
X4 X1 X3 X2
X2
X3
LV LV
LV
Primary Volts Connect lines to Inter-connect
630 504 H1, H2, H3 1-2 615 492 H1, H2, H3 2-3 600 480 H1, H2, H3 3-4 585 468 H1, H2, H3 4-5 570 456 H1, H2, H3 5-6
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3
Primary Volts Connect lines to Inter-connect
440 H1, H4 1-H2, 2-H3, H2-H3 416 H1, H4 3-H2, 4-H3, H2-H3 400 H1, H4 5-H2, 6-H3, H2-H3 380 H1, H4 7-H2, 8-H3, H2-H3 220 H1, H4 1-H2, 2-H3, H1-H3, H2-H4 208 H1, H4 3-H2, 4-H3, H1-H3, H2-H4 200 H1, H4 5-H2, 6-H3, H1-H3, H2-H4 190 H1, H4 7-H2, 8-H3, H1-H3, H2-H4
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2- X3 120 X1, X2 X2-X4, X1-X3 120/240 X1, X2, X4 X2-X3
© Hammond Power Solutions Inc.
276
Data subject to change without notice.
Page 9
GENERAL INFORMATION
SCD 31
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
H1 H2 H3 H4 H5 H6
X4 X2 X3 X1
H1 H2 H3 H4 H5 H6
X4 X2 X3 X1
SCD 32
SCHEMATIC CONNECTIONS
H1 H2 H3 H4 H1 H2 H3 H4
X4 X2 X3 X1
X4 X2 X3 X1
218 291 437 504 630 H1, H6 ­ 213 284 426 492 615 H1, H5 ­ 208 277 416 480 600 H2, H5 ­ 203 270 406 468 585 H2, H4 ­ 198 263 395 456 570 H3, H4 -
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
208 277 416 480 600 H1, H4 ­ 198 263 395 456 570 H1, H3 ­ 188 249 374 432 540 H2, H3 -
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
SCD 33
SCHEMATIC CONNECTIONS
H1 H2 H3 H2 H3H1
HV HV
X4 X1X3X2
LV
SCD 34
SCHEMATIC CONNECTIONS
H1 H4H2H3
X4 X1X3X2
OR
OR
X4 X1X3X2
LV LV
4213
LV
Primary Volts Connect lines to Inter-connect
380 H1, H3 ­ 347 H1, H2 -
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
480 H1, H4 1-H2, 2-H3, H2-H3 456 H1, H4 2-H3, 3-H2, H2-H3 432 H1, H4 3-H2, 4-H3, H2-H3 240 H1, H4 1-H2, 2-H3, H1-H3, H2-H4 216 H1, H4 3-H2, 4-H3, H1-H3, H2-H4
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
GENERAL
INFORMATION
© Hammond Power Solutions Inc.
277
Data subject to change without notice.
Page 10
GENERAL INFORMATION
X3
SCD 35
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
1
H1
H2
H3
2
3
4
5
CENTURION 1
Angular Displacement
or -30°
* Standard 2-2.5% FCAN and 2-2.5% FCBN primary taps for 208V H2EM units only available up to 75 kVA. Please consult factory for standard taps on 208V primary units over 75 kVA.
X1
X2
X3
X0
SCD 36
218* 504 630 H1, H2, H3 1-H1, 1-H2, 1-H3 213* 492 615 H1, H2, H3 2-H1, 2-H2, 2-H3 208* 480 600 H1, H2, H3 3-H1, 3-H2, 3-H3 203* 468 585 H1, H2, H3 4-H1, 4-H2, 4-H3 198* 456 570 H1, H2, H3 5-H1, 5-H2, 5-H3
Secondary Volts Connect lines to Inter-connect
208 480 600 X1, X2, X3 ­ 120 277 347 X1,X0 | X2,X0 | X3,X0 -
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
218* 504 630 H1, H2, H3 1-2
H1
6
4
2
1
3
5
H2
H3
CENTURION 2
Angular Displacement
0°, -30°
or
-15, -45
* Standard 2-2.5% FCAN and 2-2.5% FCBN primary taps for 208V H2EM units only available up to 75 kVA. Please consult factory for standard taps on 208V primary units over 75 kVA.
X1
X2
X3
X0,Y0
Y1
Y2
Y3
213* 492 615 H1, H2, H3 2-3 208* 480 600 H1, H2, H3 3-4 203* 468 585 H1, H2, H3 4-5 198* 456 570 H1, H2, H3 5-6
Secondary Volts Connect lines to Inter-connect
208 480 600 X1, X2, X3 ­ 120 277 347 Y1, Y2, Y3 - X1, X0/Y0 ­ X2, X0/Y0 ­ X3, X0/Y0 ­ Y1, X0/Y0 ­ Y2, X0/Y0 ­ Y3, X0/Y0 -
SCD 37
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
1
2
3
H2
X2
480 H1, H2, H3 1 456 H1, H2, H3 2 432 H1, H2, H3 3
GENERAL
INFORMATION
H1
H3
© Hammond Power Solutions Inc.
X1
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3 -
278
Data subject to change without notice.
Page 11
GENERAL INFORMATION
X3
SCD 38
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
504 H1, H2, H3 1 492 H1, H2, H3 2 480 H1, H2, H3 3 468 H1, H2, H3 4 456 H1, H2, H3 5 444 H1, H2, H3 6 432 H1, H2, H3 7
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3 -
Primary Volts Connect lines to Inter-connect
H2
218 291 437 504 630 H1, H2 1 213 284 426 492 615 H1, H2 2
12345
208 277 416 480 600 H1, H2 3 203 270 406 468 585 H1, H2 4 198 263 395 456 570 H1, H2 5
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
1
2
3
4
5
6
7
H1
SCD 39
H1
X4 X1 X3 X2
H2
X1
H3
X2
SCHEMATIC CONNECTIONS
H2
HV HV
LV
H1
OR
12345
X4 X1 X3 X2
OR
LV LV
LV
SCD 40
SCHEMATIC CONNECTIONS
H2
H0
H3
H1
SCD 41
SCHEMATIC CONNECTIONS
H1 H4
HV HV
X4 X1 X3 X2
LV
H2
X2
3
2
1
Primary Volts Connect lines to Inter-connect
208 240 X1, X2, X3 1 198 228 X1, X2, X3 2 188 216 X1, X2, X3 3
X1
X3
Secondary Volts Connect lines to
230 260 460 480 H1, H2, H3 133 139 265 277 H1, H0 H2, H0 H3, H0
Primary Volts Connect lines to Inter-connect
H5H3
H1
OR
H2
H5H3
H4
277 H1, H5 ­ 240 H1, H4 ­ 208 H1, H3 -
GENERAL
INFORMATION
120 H1, H2 -
OR
X4 X1 X3 X2
LV LV
LV
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
© Hammond Power Solutions Inc.
279
Data subject to change without notice.
Page 12
GENERAL INFORMATION
SCD 42
SCHEMATIC CONNECTIONS
H1
X3 X1
SCD 43
SCHEMATIC CONNECTIONS
H1 H2
3 4 2 1
X2
H2 H3
Primary Volts Connect lines to Inter-connect
480 H1, H3 ­ 277 H1, H2 -
Secondary Volts Connect lines to Inter-connect
277 X1, X3 ­ 208 X1, X2 -
Primary Volts Connect lines to Inter-connect
480 H1, H2 1-2 277 H1, H2 3-4
GENERAL
INFORMATION
X4 X6 X5 X3
X2 X1
SCD 44
SCHEMATIC CONNECTIONS
H1 H2 H1 H2
X4 X1 X3 X2
HV HV
4 2 1 3 4 2 1 3
LV
OR
OR
X4 X1 X3 X2
LV LV
LV
SCD 45
SCHEMATIC CONNECTIONS
X2
H1
1
H2
2
3
4
5
Secondary Volts Connect lines to Inter-connect
277 X1, X2 X5-X6 208 X1, X2 X3-X4
Primary Volts Connect lines to Inter-connect
380 H1, H2 1-2 347 H1, H2 3-4
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X2 X2-X4, X1-X3
Primary Volts Connect lines to Inter-connect
630 H1, H2, H3 1 615 H1, H2, H3 2 600 H1, H2, H3 3 585 H1, H2, H3 4 570 H1, H2, H3 5
H3
X1
X3
© Hammond Power Solutions Inc.
Secondary Volts Connect lines to Inter-connect
240 X1, X2, X3 -
280
Data subject to change without notice.
Page 13
GENERAL INFORMATION
SCD 46
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
480 (60Hz) H1, H2 1-2 440 H1, H2 1-2
H1 H2 H1 H2
HV HV
7 8642135 7 8642135
X4 X1X3X2
LV
OR
OR
X4 X1X3X2
LV LV
LV
416 H1, H2 3-4 400 H1, H2 5-6 380 H1, H2 7-8 240 (60Hz) H1, H2 H1-2, H2-1 220 H1, H2 H1-2, H2-1 208 H1, H2 H1-4, H2-3 200 H1, H2 H1-6, H2-5 190 H1, H2 H1-8, H2-7
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2- X3 120 X1, X2 X2-X4, X1-X3 120/240 X1, X2, X4 X2-X3
SCD 47
SCHEMATIC CONNECTIONS
1
H1
2
3
4
5
6
8
H2
H3
SCD 48
SCHEMATIC CONNECTIONS
H1 H2
X4 X2 X3 X1 X1X3X2X4
13
24 4 2
X1
X2
X0
3 1
Primary Volts Connect lines to Inter-connect
630 H1, H2, H3 1-H1, 1-H2, 1-H3 615 H1, H2, H3 2-H1, 2-H2, 2-H3 600 H1, H2, H3 3-H1, 3-H2, 3-H3 585 H1, H2, H3 4-H1, 4-H2, 4-H3 570 H1, H2, H3 5-H1, 5-H2, 5-H3 480 H1, H2, H3 6-H1, 6-H2, 6-H3 456 H1, H2, H3 7-H1, 7-H2, 7-H3
X3
432 H1, H2, H3 8-H1, 8-H2, 8-H3
Secondary Volts Connect lines to Inter-connect
480 X1, X2, X3 ­ 277 X1,X0 | X2,X0 | X3,X0 -
Primary Volts Connect lines to Inter-connect
H2H1
347 H1, H2 H2-3 & 4 380 H1, H2 H2-1 & 2
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3 120 X1, X2 X1-X3, X2-X3 120/240 X1, X2, X4 X2-X3
GENERAL
INFORMATION
© Hammond Power Solutions Inc.
281
Data subject to change without notice.
Loading...