1447S Single Door Disconnect Enclosures - NEMA 12, 13
ABB Controls, Allen Bradley, Cutler Hammer, General Electric, Siemens I-T-E Max-Flex™, Square D
Disconnect
Cutout Detail
Application
Designed to house the following
Wallmount Enclosures
safety disconnect equipment:
•
ABB Controls flange-mounted
variable depth operating
mechanism for disconnect switches
and circuit breakers. Also cable
version for circuit breakers.
Allen Bradley 1494V variable depth
•
flange mounted disconnect switches
and circuit breaker operators. Will
not accept Allen Bradley 1494F
disconnect switches, 1494D circuit
breaker operators.
C-H Westinghouse C361 flange
•
mounted variable depth operating
mechanism with disconnect switches
and C371 flange mounted variable
depth operating mechanisms for
circuit breakers. Also Flex-Shaft™
handle mechanisms for circuit
breakers.
General Electric Type STDA
•
flange handles and variable depth
operating mechanism for disconnect
switches and circuit breakers. Also
SpectraFlex™ cable operators for
circuit breakers.
Siemens I-T-E Max-Flex™ flange
•
mounted variable depth handles
for disconnect switches and circuit
breakers.
Square D class 9422 disconnect
•
switches with flange mounted
variable depth operating
mechanisms or cable mechanisms
and Class 9422 flange-mounted
variable depth operating
mechanisms or cable mechanisms
for circuit breakers. Will not accept
Square D Class 9422 bracketmounted disconnect devices,
9422TG1 or TG2 devices.
Technical references and DXF downloads available at www.hammfg.com All dimensions in inches unless specified otherwise
Standards
UL 508 Type 12, 13
•
CSA Type 12, 13
•
Complies with
•
NEMA Type 12 and 13
•
JIC EGP-1-1967
•
IEC 60529, IP54
•
Appropriate components are
•
required to maintain these
standards.
Construction
Formed 14-gauge steel.
•
•
Continuously welded seams.
•
Larger sizes include door and body
stiffeners.
•
Welded brackets provide for
enclosure mounting.
•
Formed lip on door and enclosure
exclude flowing liquids and
contaminants.
•
Cutouts and holes are provided
to suit the handle, operating
mechanism and door closing
mechanism.
Continuously hinged doors may be
•
removed by pulling the hinge pin.
Latch pivots and cover interlock
•
brackets are welded to the door.
Cover latch bars for door handles
•
are provided.
Collar studs are provided for
•
mounting inner panels.
•
A removable 12 gauge inner panel
is included.
Oil resistant gaskets are
•
permanently secured and
mechanically retained.
•
A bonding stud is provided on
the door and a grounding stud is
provided in the enclosure.
•
A literature pocket is provided.
Note:
Disconnects, operating mechanisms
•
and door hardware are not provided
with the enclosure, and must
be ordered separately from the
manufacturer.
Enclosures with an "A" dimension
•
under 40" require 2 point door
closing hardware.
Enclosures with an "A" dimension
•
40" or more require 3 point door
closing hardware.
Finish
Door and enclosure are
•
phosphatized and finished in ANSI
61 gray recoatable powder coating
on the outside.
•
Enclosure interior is finished in white
powder coating.
Inner panel is finished in white
•
powder coating.
Accessories
Additional inner panels...see page 433
•
Air conditioners...see page 389
•
Blowers...see page 406
•
Breather kits...see page 423
•
Doorstop kits...see page 447
•
Drip shield kits...see page 447
•
Enclosure stabilizers...see page 451
•
Filter fans...see page 413-414
•
Floor stand kits...see page 448
•
Heaters...see page 418-420
•
Thermostats...see page 421
•
Window kits...see page 444
•
144
Quality Enclosures. Service Excellence.
© Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 USA: 716.630.7030 Data Subject to change without notice
1447S Single Door Disconnect Enclosures - NEMA 12, 13
ABB Controls, Allen Bradley, Cutler Hammer, General Electric, Siemens I-T-E Max-Flex™, Square D
Disconnect
Wallmount Enclosures
When A= M=
36 9.00
42 9.88
48 11.38
60 14.38
Technical references and DXF downloads available at www.hammfg.com All dimensions in inches unless specified otherwise
Quality Enclosures. Service Excellence.
© Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 USA: 716.630.7030 Data Subject to change without notice
145
1447S Single Door Disconnect Enclosures - NEMA 12, 13
ABB Controls, Allen Bradley, Cutler Hammer, General Electric, Siemens I-T-E Max-Flex™, Square D
Disconnect
Part No.
1447SA8
1447SB8
1447SC8
1447SD8
1447SE8
1447SF8
1447SG8
1447SH8
1447SJ8
1447SK8
1447SL8
1447SA10
1447SB10
1447SC10
1447SD10
1447SE10
1447SF10
Wallmount Enclosures
1447SG10
1447SH10
1447SJ10
1447SK10
1447SL10
1447SE12
1447SG12
1447SH12
1447SJ12
1447SK12
1447SL12
1447S46L12
1447SG16
1447SK16
1447SL16
2
Center stiffener; N = Not Included I = Included
A B C D E F G
20 21.38 8 17 17 15.38 21.25 51 N
24 21.38 8 21 17 15.38 25.25 60 N
24 25.38 8 21 21 19.38 25.25 71 N
30 21.38 8 27 17 15.38 31.25 74 N
30 25.38 8 27 21 19.38 31.25 87 N
36 25.38 8 33 21 19.38 37.25 98 N
36 31.38 8 33 27 25.38 37.25 121 N
42 31.38 8 39 27 25.38 43.25 135 I
42 37.38 8 39 33 31.38 43.25 154 I
48 37.38 8 45 33 31.38 49.25 172 I
60 37.38 8 57 33 31.38 61.25 248 I
20 21.38 10 17 17 15.38 21.25 52 N
24 21.38 10 21 17 15.38 25.25 63 N
24 25.38 10 21 21 19.38 25.25 71 N
30 21.38 10 27 17 15.38 31.25 80 N
30 25.38 10 27 21 19.38 31.25 90 N
36 25.38 10 33 21 19.38 37.25 100 N
36 31.38 10 33 27 25.38 37.25 126 N
42 31.38 10 39 27 25.38 43.25 143 I
42 37.38 10 39 33 31.38 43.25 193 I
48 37.38 10 45 33 31.38 49.25 180 I
60 37.38 10 57 33 31.38 61.25 255 I
30 25.38 12 27 21 19.38 31.25 100 N
36 31.38 12 33 27 25.38 37.25 130 N
42 31.38 12 39 27 25.38 43.25 150 I
42 37.38 12 39 33 31.38 43.25 200 I
48 37.38 12 45 33 31.38 49.25 220 I
60 37.38 12 57 33 31.38 61.25 265 I
60 37.38 12 57 34.5 31.38 61.25 265 1
36 31.38 16 33 27 25.38 37.25 150 N
48 37.38 16 45 33 31.38 49.25 200 I
60 37.38 16 57 33 31.38 61.25 265 I
Panel Size
Mounting Center
Ship
Wt. lbs
Center
Stiffener
2
146
Space Occupied by Disconnect
Note: "K" = 4.75 when "C" = 8.00
"K" = 7.09 when "C" = 10.00
"K" = 11.62 when "C" = 12.00
"K" = 11.62 when "C" = 16.00
"K" = 18.38 for 1447S46L12
"P" = Wiring Space
Disconnects will occupy space on panel
shown by dimensions "K", "L" and "M".
Wiring space "P" is available when
disconnect is installed in the enclosure.
*The disconnect information and space
occupied tables based on data supplied
by disconnect manufacturer’s bulletins.
Hammond Manufacturing not responsible for
dimensional accuracy.
Technical references and DXF downloads available at www.hammfg.com All dimensions in inches unless specified otherwise
Quality Enclosures. Service Excellence.
© Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 USA: 716.630.7030 Data Subject to change without notice
1447S Single Door Disconnect Enclosures - NEMA 12, 13
Selection Guide
Hammond Series 1447S
ABB Controls
Allen
Bradley
Cutler
Hammer
General
Electric
I-T-E
Siemens
Square D
Disconnect Switch
Circuit Breaker
1494V Flange
Disconnect Switch
1494V Flange
Circuit Breaker
Type C361
Disconnect Switch
Type C371 Circuit
Breaker
C-H Westinghouse
Circuit Breaker
w/FlexShaft
Type STDA Flange
Disconnect Switch
Type STDA Flange
Circuit Breaker
Circuit Breaker
w/SpectraFlex
Max-Flex Flange
Disconnect Switch
Max-Flex Flange
Circuit Breaker
Class 9422
Disconnect Switch
Class 9422 Circuit
Breaker
Class 9422 “T”
Disconnect
Switch w/ cable
mechanism
Circuit Breaker w/
cable mechanism
Shaft: 8-12” dp enclosures, use DSFHS-12; 16” dp enclosures, use DSFHS-17
Door Hardware: 2 pt. Latching, use KDH2R; 3 pt. Latching, use KDH3R and FH-3RL
Shaft: 8-12” dp enclosures, use K7FHD-S12; 16” dp enclosures, use K7FHD-S17
Door Hardware: 2 pt. Latching, use FH-DHK; 3 pt. Latching, use FH-DHK and FH-3RL
Handle: Bulletin 1494V-H1 (except for Hammond part # 1447S46L12, use 1494V-H2)
Connecting rod: 8-10” dp enclosures, use 1494V-RA1; 12-16” dp enclosures, use 1494V-RA2
Door Hardware: 2 pt. Latching, use 1494V-L1; 3 pt. Latching, use 1494VL2
Connecting rod: 8-10” dp enclosures, use 1494V-RA1; 12-16” dp enclosures, use 1494V-RA2
Door Hardware: 2 pt. Latching, use 1494V-L1; 3 pt. Latching, use 1494VL2
Door Hardware: 2 pt. Latching, use C361KJ4 or KJ6; 3 pt. Latching,
Handle: 150 amp, use C371H1 or H3; 250-600 amp, use C371H5 or H7
Door Hardware: 2 pt. Latching, use C361KJ4 or KJ6; 3 pt. Latching, use C361KJ4 or KJ6, and C361KR
Door Hardware: 2 pt. Latching, use C361KJ4 or KJ6; 3 pt. Latching, use C361KJ4 or KJ6, and C361KR
Door Hardware: 2 pt. Latching, use TDV-1; 3 pt. Latching, use TDV-1 and TDV-3
Door Hardware: 2 pt. Latching, use TDV-1; 3 pt. Latching, use TDV-1 and TDV-3
Flange Mt. Handle: 150-600 amp, use STDA1; SK1200, use STDA3
Door Hardware: 2 pt. Latching, use TDV-1; 3 pt. Latching, use TDV-1 and TDV-3
Door Hardware: 2 pt. Latching, use DKR2; 3 pt. Latching, use DKR3
Handle: Flange mount FHOH (except for Hammond part # 1447S46L12, use FHOHN)
Door Hardware: 2 pt. Latching, use DKR2; 3 pt. Latching, use DKR3
Door Hardware: 2 pt. Latching, use 9423-M4 or M9; 3 pt. Latching, use 9423-M4 or M9, and 9423-M3
Door Hardware: 2 pt. Latching, use 9423-M4 or M9; 3 pt. Latching, use 9423-M4 or M9, and 9423-M3
Door Hardware: 2 pt. Latching, use 9423-M4; 3 pt. Latching, use 9423-M4 or M9, and 9423-M3
Door Hardware: 2 pt. Latching, use 9423-M4; 3 pt. Latching, use 9423-M4 or M9, and 9423-M3
Flange operated switch (fusible or non-fusible)
Handle: DSFHN-HS12
Circuit breaker: ABB
Operating Mechanism: see ABB chart
Handle: K7FHD-HS12
Disconnect switch and operating mechanism: Bulletin 1494V
(except for Hammond part # 1447S46L12, use 1494V-RB2 (2))
Trailer fuse block kit (if required): Bulletin 1494V
Fuse kit (if required)
Line and load connectors (if required)
Circuit breaker: C-H Westinghouse
Operating mechanism: Bulletin 1494V
Handle: Bulletin 1494V-H11
Disconnect switch and operating mechanism
Handle: C361-H1 or H3
use C361KJ4 or KJ6, and C361KR
Circuit breaker: C-H Westinghouse
Operating mechanism
Circuit breaker
Complete Flex-Shaft handle mechanism
Disconnect switch Type QMR or QMW
Handle: STDA1 or STDA2
Fuse kit (if required)
Variable depth operating mechanism
Circuit breaker
Handle: STDA1 or STDA2
Variable depth operating mechanism
Circuit breaker
Breaker mounted mechanism.
Operating cable
Disconnect switch: MCS
Fuse Kit (if required)
Handle: Flange mount FHOHS
Switch operator mechanism
Operating cable (standard 36.0”)
Circuit breaker
Pressure wire connectors
Circuit breaker operator mechanism
Operating cable: 125-600 amp, use 36”; 800 amp, use 48”
Disconnect switch and operating mechanism 9422
Handle: Type A-1
Circuit breaker
Operating mechanism: Class 9422
Handle: Type A-1
Disconnect switch and operating mechanism 9422, Type T
Handle: Type A-1
Cable mechanism: Class 9422 CFT_O - 3, 5, or 10 foot
Circuit breaker: Square D
Handle: Type A-1
Technical references and DXF downloads available at www.hammfg.com All dimensions in inches unless specified otherwise
Disconnect
Wallmount Enclosures
Quality Enclosures. Service Excellence.
© Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 USA: 716.630.7030 Data Subject to change without notice
147