Halton KVL, KVR, KVM, SWR, EO Operator's Manual

...
Operators Manual
Manual provides
Installation, Operation, and Maintenance Instructions
Models : KVE (SJ-SK) KVC (SJ-SK), KVW (SJ-SK), KVR, KVO, KVL and KVM SWR / EO / DW / CH SWS / SBS / SIR5
2
GENERAL DESCRIPTION
All Halton Capture Jet® hood systems provide solutions for a variety of commercial foodservice ventilation applications over virtually any cooking process. Halton’s Capture Jet® technology gives the most efcient system on the market. To achieve the optimum performance from your hood system (s) please use the following guidelines provided within the pages of this Installation, Operation, and Maintenance Manual.
In addition to this information our ofces or local representatives are available at any time to provide additional technical support for products, applications, installation, commissioning or in any aspect that you may have.
RECOMMENDATION
Upon receipt of the Halton hood (s), inspect unit (s) immediately for any shipping damage and notify carrier immediately if damage is found. Halton will not accept responsibility for any shipping damage. All systems are thoroughly inspected before leaving our factories, however Halton will assist in ling a claim if needed.
GENERAL INSTALLATION
It is the responsibility of the installing contractor to see that the system installation is completed in accordance with the project plans and specications and that it meets all specic requirements of local code ofcials. The local authority having jurisdiction could over rule some of the installation details written in this manual. The installation shall be in accordance with NFPA-96. All electrical systems shall be installed following local and national codes.
The owner and/or operator should be instructed in the proper operation, care and maintenance of the system.
If questions or complications should arise during the installation of the Halton hood (s) that cannot be solved using the instructions provided please contact the Halton ofce at 1-800-442-5866, or (1-800-4-HALTON).
Note: There are no instructions contained within this manual for installation or maintenance of fan packages. **See appropriate manufacturers manual for detailed instructions.
EXHAUST AIRFLOWS
Because the listed exhaust airows rates were established under controlled laboratory conditions, please see submittal drawings or contact the manufacturer for exhaust air ow rates.
INSTALLATION INSTRUCTIONS
1. Inspect the crating carefully. If there are signs of damage, call the freight carrier before uncrating the units. Carefully uncrate the units. Check all local codes prior to installation, special requirements may be necessary
depending on local building material construction.
** Important note ** Do not leave unit (s) exposed to extreme temperatures for an extended period
of time, this may cause the protective PVC coating around the unit (s) to become very difcult to remove.
Position the hood near the actual installation site. In case of multiple hoods, check the engineered set of
2. drawings for locations. Pay close attention to collar sizes and re protection layouts, matching the hood systems to the correct location shown on the drawings provided. **Check item numbers on crates / hoods vs. drawing item numbers.
3
3.
Once the hood is carefully removed from the shipping crate and set in position, the unit is now ready for
installation. If Halton Company has supplied a backsplash assembly, then the splash assembly should be installed rst, for installation procedures. (See pg. 4)
4. Hang the hood using ½” threaded rods by attaching the rods to the hood through the hanger brackets that are welded to the top of the hood. Use of turnbuckles will make nal adjustment easier. Standard hanging height for canopy hoods ranges from 78” min. to 84” max. above the nished oor (per local codes having jurisdiction). **Noted in installation instructions - (see pg. 6).
**All typical installations for Capture Jet
5. If Closure Panels are supplied by Halton (see pg. 8) for details on the installation.
6. For multiple hoods end to end, or back to back (see pg. 7) for Installation of Splice Strips and U-Channels.
7. For hoods equipped with a supply re damper, it is very important to make sure that the re damper is set in an open position before connecting the supply duct.
For units with exhaust re dampers, (see pg. 9), or supply re dampers, (see pg. 10) for installation
details.
8. Electrical circuits should be connected according to standard switch panel wiring diagram, shown on (pg. 11). For Halton Capture Jet® series hoods, a typical wiring diagram is shown on (pg. 12).
®
series hoods shown on pages 18-22.
9. Grease lters and grease cups must be installed in place before start-up.
10. Install 100 watt maximum light bulbs in standard incandescent lights or uorescent bulbs (36” L or 48”L) in uorescent lights. **Note: Halton does not provide bulbs.
11. Protect the hood from damage under normal job site conditions, until all work is complete and system is ready to be put into operation.
4
OPERATION OF SYSTEM
1. After installation is complete, it will be necessary to check and balance the airows. On the Capture Jet® line of hoods, Halton supplies T.A.B. (testing and balancing) ports for measuring the pressure drop. These ports are located on the inside of the canopy on each plenum. (Exhaust and Capture Jet®).
For details on their use (see pg. 13). For hoods without ports, use of standard practices (duct traverse / average velocity / etc) for measuring airows will be required.
**It is very important that the fan for the Capture Jet® air be balanced according to specications.
See the job specic information for required airows. Adjustments to the Capture Jet® fan can be made with the speed controller supplied with the fan. This speed controller will be mounted inside or on top of the hood, or mounted in an electrical enclosure.
Information regarding the fan and speed controller (see pg. 12).
®
2. Each Halton Capture Jet packaged separately, inside the hood, the box will be labeled “Attn: Kitchen Mgr. “ Model KFR instructions on (pg. 14). The KFR will assist in removal of the lters for assembly and cleaning.
3. After the exhaust and supply airows have been properly balanced, a nal inspection should be made to ensure proper system operation.
hood system will have a “KSA” lter remover (model KFR). The “KFR” will be
HOOD MAINTENANCE
1. Clean the hood canopy inside and out as needed with mild soap and water. Never use harsh or abrasive cleaners on Stainless Steel or Painted surfaces, making sure to wipe clean all interior and exterior surfaces of the hood including the light xtures.
** Never clean the hood canopy when any of the surfaces are hot.
2. Clean the lters and grease cup(s) daily, rst washing by hand, and then placing them into a dishwasher or by steam cleaning.
** Handle the Grease lters carefully **
Screw through top of ange to wall. *( screw head will not interfere with hood)
Screw backsplash to wall or attach with adhesive.
5
1” Insulated Backsplash Assembly
Halton canopy hoods should be installed from 78” min.- 84” max. above the nished oor.
Flat Sheet Backsplash Assembly
6
Typical Hood Installation Details
*Optional Unistrut / Turn
Buckle Detail
Hanger Bracket / Turn
Buckle Detail -
Welded to top of hood.
18 ga. material All
Thread (By Others)
Hang the hood using 1/2” threaded rods by attaching the rods to the hood through the hanger brackets (as shown) which are welded to the top of the hood, using the turnbuckles will make nal adjustments easier. Hanging height of Canopy hoods should be per local building codes, verify with “Authority Having Jurisdiction” for hanging height in your project location.
Standard hanging height is 78” minimum to 84” maximum above the nished oor.
Recommended
Exhaust Duct
Installation Details
7
Exhaust
Duct Options Available
Supply Duct
Exhaust Duct per code
Supply Duct
Supply Duct may be attached to supply collar with sheet metal screws or pop rivets and sealed with duct tape.
Screws or Rivets are not to interfere with the operation of the re damper (if equipped).
8
Fig. 1
Splice Strip / U-Channel Assemblies
B
Splice Strip
A
Fig. 1
Hoods shown back to back
B
A
U-Channel
Installation Notes:
U-Channel:
For hood models that are placed back to back (as shown in Fig. 1): Slide the U-Channel A up over the back of the hood systems, and secure with sheet metal screws.
For hood models that are placed end to end (as shown in Fig. 2): Pry apart the U-Channel at one end and slide over the end panels, fastening in place,  tting around the perimeter of the hood systems.
Splice Strip:
For hoods placed back to back: Slide Splice Strip B over bottom of hoods  rst, then over top, secure by welding together.
For hoods placed end to end: Slide over bottom front edge  rst then over top, secure by welding together, or as an option using screws for models with supply plenum.
Hoods shown end to end
Fig. 2
B
A
B
Splice Strip
U-Channel
A
Closure Panel Assembly
D
C
C
B
B
A
Installation Notes:
1) Panels “A” and “B” are to set on top of the hood perimeter.
*Vertical ange at the bottom of closure panel and vertical
ange on top of hood should line up.
E
9
2) Hammer clips “C” over the two vertical anges.
3) Attach panels “B” to wall using appropriate hardware “D”.
4) Slide front panel “A” into place.
5) Attach panels “A” and “B” together using hardware “E” *(Hardware not provided by Halton)
E
D
B
B
A
C
C
10
Exhaust Fire Damper Assembly
Optional in Models : SWR / SWS / SIR5 / DW / KVE / KVC / KVW
1. Remove grease lters.
2. Uncoil Stainless Steel cable attached at clip (A)
3. Thread end of cable from eyebolt at clip (A) going through eyebolt at clip (B), then thread through eyebolt at clip (C).
4. Hold re damper in maximum open position to attach “S” hooks at point (D), close “S” hooks to secure.
5. For nal adjustment of re damper, tighten eye bolts at clips (A), (B) and (C) so that cable has no slack, and assure maximum open position is obtained.
** (Access to re protection exhaust duct nozzle to be provided by others)
The collar is supported by a 1/2” ange located on the inside perimeter of the damper.
Secure “S” hook to damper as shown.
**Located in below detail as (D).
Clip (A)
Eye bolt
Fusable Link
Clip (B)
D
Clip (C)
Supply Fire Damper Assembly
Optional in Models: SWR / SWS / SIR5
1. It is important that damper is set in open position before installing supply duct.
2. Hold damper in maximum open position, fasten “S” hook at end of stainless steel cable onto the hole located in the middle of the supply re damper ange, closing ends of the “S” hook to secure.
3. On nal adjustment of the supply re damper, tighten cable using eyebolts to assure maximum open position.
The collar is supported by a 1/2” ange located on the inside perimeter of the damper.
11
Secure “S” hook to damper as shown.
**Located in below detail marked (D).
D
Eye bolt
Fusible Link
12
Standard Switch Panel Wiring
*(For Hoods not equipped with Capture Jet®)
---- ---- ---- ---- ----- By Electrician
- #5
------------------------------ By Halton
Wires Numbered as shown in junction box.
Capture Jet® Fan Installation
Integrated Capture Jet ® fan
(Standard)
13
This style is standard for Model KVL
KSA Filter
T.A.B. Ports
Speed Controller
Models KVE, KVC, KVR and KVW are equipped with an Integrated Capture Jet® fan package, as shown above.
Typical Wiring of Capture Jet® Fan
w/ Halton supplied Switch Panel
(Optional)
Capture Jet Fan
Top of Hood
®
Front of Hood
Capture Jet Plenum
5 AMP Speed Controller wired on top of hood or located in the Control Panel
®
14
T.A.B.™ - Testing and Balancing Ports
Exhaust T.A.B. Readings vs. Airflow
Capture Jet® T.A.B. Port Readings
Hood Model Design T.A.B.
(inches WC)
KVE/KVC 0.25
KVW 0.25
KVR 0.25
KVL 0.29
This example shows how to determine the correct T.A.B. port reading for the exhaust hoods.
In this example, a design airow of 1700 cfm is selected from the Airow axis, and a vertical line is drawn up to the T.A.B. pressure curve for this hood.
A horizontal line is then drawn for the T.A.B. pressure curve to the T.A.B. reading axis on the left-hand side of the chart and the corresponding pressure is read off the chart as 0.19 inches of Water Column.
0.35
0.30
0.25
0.20
0.15
0.10
T.A.B. Reading (In. WC)
0.05
0.00 800 1050 1300 1550 1800 2050 2300
Airflow (cfm)
Measured Pressure
Th e Captu re Jet® an d exhau st air fl ows are easily and ac curate ly dete rmined b y measu ring the p ressur e di fferen ce from the T.A.B . (Tes ting and Balancing) po rts mounte d in each plenum . The cor respon ding ai r flow s can be rea d from the d iagram provi ded.
To prope rly measure T.A. B. port reading s use a ma gnehel ic gauge or digit al manom eter and for ex haust plenum re ading hookup ho se fro m negative co nnecti on on instrument to T.A .B. Port on exh aust pl enum. Leave po sitive connect ion o n instru ment op en to atmosp here.
Closeup view of T.A.B. Port
**** It is very important the cooking equipment is in operation to create a thermal plume, prior to the air balancer, to be able to use the T.A.B. ports.
****For accurate results, the balance contractor should receive a copy of the job specic hood plans with the design T.A.B. readings from the hood supplier prior to balancing.
Halton AccuFlow
15
Overview
The AccuFlow by Halton is a Bluetooth equipped device intended to monitor the exhaust airflow rate of Halton Capture Jet hoods and alarm kitchen staff if the hood is above or below design. The device (shown below in Photo 1) has two taps (Photo 2) that are connected to the exhaust hood to monitor the differential pressure between ambient air and the exhaust plenum; the T.A.B Port reading. AccuFlow installs in Capture Jet plenum for easy viewing and access. The device shares an electrical circuit with the Capture Jet fan.
Photo 1 – Halton AccuFlow
Photo 2 – AccuFlow Pressure Taps
Exhaust airflow rate is determined in the same fashion as other Halton Capture Jet hoods; each hood has a unique K-Factor dependent upon model. The actual airflow is compared to the design value and an alarm is enabled if airflow is above or below the specified range.
Connects to ambient (room) air
Connects to T.A.B. port
Plastic tubing connected to (-) port of Accuflow device
16
Operation
Each AccuFlow is programmed at a Halton Company manufacturing facility. To program the device, the Bluetooth feature is enabled and personnel input necessary parameters. Programming can be completed with a Windows Mobile enable smart-phone (PDA) or PC with the required software installed. Programmed values include: Design Airflow, High Airflow Delta, Low Airflow Delta and K-Factor.
Design Airflow is determined using the Halton HELP software and the Low and High Airflow Delta are defined as +/- ten percent of design airflow. K-Factors have been determined by Halton Research and Development personnel.
Bluetooth capability also allows an Authorized Service Agent to determine the airflow of an exhaust hood on site if an alarm is present. This information can be conveyed to Halton personnel for troubleshooting.
Alarms
Alarms are enabled when design airflow is above or below ten percent of design airflow. An alarm is visible on the front of the Accuflow, see Photo 3 below.
Photo 3 – AccuFlow Alarm Location
Indications of alarm status (under or over design) are printed on the device. If the LED indicator is steady, the hood is at design airflow. Alarms are differentiated by the number of blinks per second; 1 blink per second indicates the hood is under design, 2 blinks per second indicates the hood is over design.
Troubleshooting AccuFlow
Problem Probable Cause Solution
17
No lights Illuminated on AccuFlow device
Low airflow alarm
Failure Bad Device - Replace
Loose or improper electrical connections
-Not reaching design airflow
-Plastic tubing disconnected from Accuflow device or TAB port
-Broken plastic tubing
-Dirty or plugged TAB port in exhaust plenum
- Verify or reconnect electrical connections
-Increase fan speed
-Reconnect
-Replace tubing
-Clean TAB port
18
KSA Filter Removal
with Model KFR
S.S. Coupling
S.S. Pipe
16 ga. S.S. Bracket
To assemble the KFR lter remover:
Screw together stainless steel pipe, coupling, and bracket and tighten all joints. (as shown in above picture)
Filter Installation and Removal
To remove lter:
Insert bracket into the inside KSA lter slots, and lift upward until lter slides out of plenum.
To install lter:
Place lter on KFR (lter removal tool) bracket, raise lter into place inside exhaust plenum. Slide upward until top lip of lter is locked into place and bottom lip of lter slides in place inside the exhaust plenum.
*** It is very Important to lock top lip of lter in place in installation as shown in reference drawing.
To remove lter
To install lter
Round / Oval Style Hood Systems
Model KVR & KVO
19
3D Plan view of round KVR
Model KVR Round and Oval hoods can be shipped in pieces for eld assembly. If pieces are shipped loose, parts will be marked for easy assembly, and an Operation and Installation, and Maintenance manual will be provided.
45º min
lter angle
3D Plan view of oval KVR
minimum
height
24”
Cross section of KVR
20
Model EO
Typical Installation
UL listed upblast fan for restaurant cooking appliances
16 ga. duct all welded per code
Filters
Incandescent Lights
78”-84” A.F.F. Standard
**(Verify with Authority in project location for min. hanging height)
Model DW
Exhaust Air
Incandescent Lights
KSA Filters
Model CH
Typical Installation
21
78”-84” A.F.F. Standard
**(Verify with Authority in project location for hanging height requirements).
CH w/ 2 bafes - option
Bafes
**Available with and without bafes
Perimeter Gutter
S.S. Drain
22
40 “ min.
**Incandescent or Fluorescent lighting available.
Model KVE
Typical Installation
UL listed upblast fan for restaurant cooking appliances
16 ga. duct work all welded per code
Optional Capture Jet® intake location **(standard top mounted Capture Jet® intake)
KSA Filters
78”-84” A.F.F. Standard
**(Verify with Authority in project location for min. hanging height)
Capture Jet Airow
40” min.
Model KVC
Typical Installation
120” min.
23
Filtered MUA unit on the roof
16 ga. duct work all welded per code
Stainless Steel KSA lters
78” - 84” A.F.F. 78” Std.
**(Verify with Authority in project location for min. hanging height)
Make-up airow
Capture Jet
®
air
24
40” min.
KVL Typical Installation
UL listed upblast fan for restaurant cooking appliances
16 ga. duct work all welded per code
Capture Jet® fan
St ainless Steel KSA lters
Capture Jet® air
**(Verify with Authority in project location for min. hanging height)
58” -64” A.F.F.
**Note: on Model KVL the Capture Jet fan is mounted on top of hood .
®
40” min.
KVM Typical Installation
16 ga. duct work all welded per code
25
UL listed upblast fan for restaurant cooking appliances
St ainless Steel KSA lters
**Note: on Model KVM the Capture Jet fan is integral .
Capture Jet® air
Side Skirt Install
* NOTE: Side Skirts are shipped
separately and must be attached
permanently in the eld.
®
26
Model KVW
Typical Installation
See page (22) for supply options
UL listed upblast fan for restaurant cooking appliances
40” min.
Integrated Capture Jet® location
78” - 84” A.F.F. (78” Std.)
**(Verify with Authority in project location for min. hanging height)
Side view of typical install
Exhaust Air
Incandescent
lights
Integrated
Capture Jet® fan
T.A.B. Ports
S.S. KSA
Filters
Model KVW Typical Installation
27
Incandescent
lighting
KSA lters
Exhaust Air
(W/ 1 Perf Plenum)
Supply Air
Integrated
Capture Jet®
fan
T.A.B. Ports
S.S. Perf
(Low Velocity)
Capture Jet® Air
Supply Air
Incandescent
lighting
KSA Filters
Exhaust Air
(W / 2 Perf Plenum)
Supply Air
Integrated
Captur Jet®
fan
T.A.B. Ports
Capture Jet® Air
S.S. Perf
(Low Velocity)
HALTON LIMITED WARRANTY
Halton (“Manufacturer”). Warrants only to its direct purchasers and to no others, that all products manufactured by the Manufacturer shall be free from defect in materials and workmanship for a period of twelve (12) months from the date of the original installation and start-up or eighteen (18) months from date of shipment, whichever occurs first. All products sold but not manufactured by Manufacturer will be warranted for a period of twelve (12) months from date of shipment.
For products manufactured by the Manufacturer we agree to pay any reasonable labor costs necessary to repair or replace, at Manufacturers option, defective parts or materials for a period of twelve (12) months from date of original installation and start-up or eighteen (18) months from date of shipment, whichever occurs first. All labor costs subject hereto shall be performed during standard work hours at straight-time rates.
For products sold but not manufactured by the Manufacturer we agree to pay any reasonable labor costs necessary to repair or replace, at Manufacturers option, defective parts or materials for a period of (90) days from date of original installation and start-up or (12) months from date of shipment, whichever occurs first. All labor costs subject hereto shall be performed during standard work hours at straight­time rates.
Purchaser shall pay incurred premium labor charge, including overtime, weekends and holidays. Travel time, service charges, miscellaneous tools, material charges, and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer.
This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the installation and Care Instruction Manuals. Purchaser shall be solely responsible for adhering to the instructions and procedures set forth in the said instruction manuals.
This LIMITED WARRANTY SHALL NOT BE APPLICABLE to any damage or defect resulting from fire, flood, freezing or any Act of God, abuse, misuse, accident, neglect or failure to adhere to all instructions set forth in the installation and Care Instruction Manuals. Furthermore, this limited warranty shall not apply to any product that has been altered, unless such alteration has been approved in writing by a duly authorized representative of the manufacturer. In no event shall the manufacturer be liable for any loss, expense, personal injury or consequential damage, of any kind or character, as may result from a defect in material, and/or workmanship, however caused.
EXCEPT AS IS EXPRESSLY SET FORTH IN THIS LIMITED WARRANTY, MANUFACTURER MAKES NO WARRANTY OF MARKETABILITY FOR FITNESS OR ANY PARTICULAR PURPOSE. NEITHER DOES MANUFACTURER MAKE ANY WARRANTY, EXPRESSED OR IMPLIED, WITH RESPECT TO PRODUCTS SOLD BY MANUFACTURER OR AS TO THE USE THEREOF.
Continuous product improvement is a Halton policy, therefore specications and design are subject to change without notice.
Halton Company 101 Industrial Drive, Scottsville, KY 42164, USA Phone 270 237 5600 Fax 270 237 5700
Website: www.haltoncompany.com
Halton Indoor Climate Systems, Ltd. 1021 Brevik Place, Mississauga, ON L4W 3R7, Canada Phone 905 624 0301 Fax 905 624 0301
Website: www.haltoncanada.com
Loading...