halstead Eden X Type VBX 18 Propane User guide

SINGLE PAGES 20/9/10 09:58 Page 1
VBX 18 & 30
INSTALLATION AND SERVICING INSTRUCTIONS
TO BE GIVEN TO THE USER
0086
EC 87/BP/35
G.C. Appliance No. 41-260-15 (Eden VBX 18)
G.C. Appliance No. 41-260-14 (Eden VBX 30) G.C. Appliance No. 41-260-18 (Eden VBX 18 Propane) G.C. Appliance No. 41-260-17 (Eden VBX 30 Propane)
OPEN VENT CONDENSING BOILER
SINGLE PAGES 20/9/10 09:58 Page 2
CONTENTS INTRODUCTION
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
1.1 Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION
1
2 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1 Gas Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4 Overall Dimensions & Minimum Clearances. . . . . . . . . . . . . . . . . . . . . . . . . 4
2.5 Concentric Air / Flue Duct Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.6 Additional Concentric Flue Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Appliance Hydraulic Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Statutory Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Appliance Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3 Flue Terminal Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Ventilation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Condensate Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.6 Gas Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.7 Central Heating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.8 Draining Tap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.9 Safety Valve Open Vented System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.10 Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.11 Flow Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.12 Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.13 Open Vented Hot Water System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.14 Domestic Hot Water Cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.15 Sealed Hot Water Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.16 Safety Valve Water System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.17 Expansion Vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.18 Pressure Gauge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.19 Water Makeup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.20 Filling a Sealed Water System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.21 Electricity Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.22 External Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 Appliance Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Unpacking The Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 Preparing The Wall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.3 Mounting The Appliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.4 Central Heating Service Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.5 Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.6 Condensate Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7 Air / Flue Duct Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.8 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.1 Filling the Water System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 Commissioning the Appliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.3 Final Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.4 Lockout/Reset Indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.5 Frost Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.6 Overheat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.7 Other Features: Anti Cycle Device, CH Soft start Device, Service Mode. . . 22
5.8 Users Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.9 Appliance Log Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.10 Gas Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6 Routine Servicing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.1 Combustion Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.2 Gas Control Valve, Fan & Burner Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.3 Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.4 Ignition & Detection Electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.5 Combustion Chamber & Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.6 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.7 Sealed Water System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.8 Re-assembly & Re-commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.9 Final Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7 Internal Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.1 Functional Flow Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8 Fault Finding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.2 Diagnostic LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.3 Faulting Finding Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.4 Central Heating Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9 Replacement Of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.1 Ignition and Detection Electrodes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.2 Ignitor Unit and Ignition Leads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.3 Gas Control Valve including Air Inlet Cowl. . . . . . . . . . . . . . . . . . . . . . . . . . . 31
9.4 Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
9.5 Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
9.6 Combustion Chamber Front Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9.7 Combustion Chamber Rear Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9.8 Heat Exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9.9 Flue Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.10 Water Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.11 Flue Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.12 Condensate Drain System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.13 Control PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10 Short Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1
The Halstead VBX range are high efficiency condensing, fully automatic, wall mounted gas appliances suitable for either room sealed or opened flued applications, for use with natural gas (G20) and LPG (G31). They are designed for use with either sealed or open vented central heating systems.
The appliances feature an attractive white powder coated casing, with inset control panels. The flue systems are in white powder coat to give a clean attractive appearance to the installation.
A telescopic horizontal concentric air/flue duct terminal is available, suitable for room sealed applications. The duct assembly is connected to the appliance via a turret, which can be orientated to provide different horizontal duct directions. Extension ducts may be fitted in accordance with and up to the maximum dimensions stated in these instructions.
A vertical concentric outlet kit is also available for installations where an outside wall is not accessible or where it is desired to fit the duct 'through the roof'. Installation using the horizontal duct is described in the main text of these instructions and additional information is provided in the vertical outlet kit for the vertical installation option. (Note: If the vertical outlet kit is to be used, access to the roof is necessary).
Other flue kits are available for open flued (B23), split flued (C53), and special (C13) applications, contact Halstead Glen Dimplex service helpline Tel: 0844 371 1111, for further details, ONLY APPROVED FLUE
KITS OR EXTENSIONS MAY BE USED WITH THESE APPLIANCES.
SINGLE PAGES 20/9/10 09:58 Page 3
IMPORTANT INFORMATION
1.1
IT IS A STATUTORY REQUIREMENT THAT ALL GAS APPLIANCES ARE INSTALLED BY COMPETENT PERSONS, (i.e. CORGI REGISTERED INSTALLERS) IN ACCORDANCE WITH THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS (CURRENT EDITION). FAILURE TO COMPLY WITH THESE REGULATIONS MAY LEAD TO PROSECUTION.
These appliances have been tested and certified in order to satisfy the necessary European Directives and comply with the latest Building Regulations, including the efficiency requirements of the SEDBUK scheme.
Gas Appliance Directive 90/396/EEC Efficiency of Hot Water Boilers Directive 92/42/EEC Low Voltage Directive 93/68/EEC Electromagnetic Compatibility Directive 92/31/EEC No modifications to these appliances should be made unless they are
fully approved by the manufacturer. Appliance installation must be carried out by a competent person and
must be in accordance with the current legislation in force at the time of installation, in the country of destination.
The manufacturer's instructions must not be taken as overriding any statutory requirements.
GAS LEAKS. DO NOT OPERATE ANY ELECTRICAL SWITCHES, OR USE A NAKED FLAME. TURN OFF THE
!
Control of Substances Hazardous to Health
Under Section 6 of the Health and Safety at Work Act 1974, it is required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insulation Pads - These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaints you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Gas and Electricity Consumer Council (Energywatch)
Energywatch is an independent organisation, which protects the interests of gas users. If you need advice concerning energy issues, they may be contacted on their consumer help line number: 08459 060708, or via their web site; http://www.energywatch.org.uk.
GAS SUPPLY. VENTILATE THE AREA BY OPENING DOORS AND WINDOWS. CALL OUT YOUR LOCAL GAS SUPPLIER TEL: 0800 111 999.
GENERAL DESCRIPTION
1.2
The appliances incorporate a microprocessor based, fully modulating air/gas ratio control system with direct burner ignition, which provides a modulated heat output to central heating (CH) demand, and with internal frost protection provided as standard.
The heat exchanger is constructed from stainless steel, and there is the option for routing the flow and return connections either via top or bottom connections.
The appliance may be used with any certified mains voltage room thermostat, and can operate without the need for an automatic bypass valve in the CH circuit, however, it is recommended that one radiator in the room where the room thermostat is fitted is installed without thermostatic radiator valves to allow the pump overrun facility to operate correctly.
WHEN INSTALLING, COMMISSIONING OR SERVICING A GAS APPLIANCE THAT INCORPORATES A PRE-MIX
!
THAT THE GAS SUPPLY IS METERED AND ASCERTAIN WHETHER IT IS POSSIBLE TO MEASURE THE GAS RATE. IF THE GAS INPUT RATE CAN BE MEASURED THEN THE REQUIREMENTS OF GSIUR 26(9) CAN BE MET, INCLUDING ANY SPECIFIC REQUIREMENTS IN MANUFACTURER’S INSTRUCTIONS.
IF GAS INPUT RATE CANNOT BE MEASURED THEN, TO SATISFY THE INTENT OF GSIUR 26(9), THE ENGINEER SHALL MEASURE THE COMBUSTION QUALITY OF THE APPLIANCE IN ACCORDANCE WITH BS 7967 OR THE MANUFACTURER’S INSTRUCTIONS.
IF THE ENGINEER DOES NOT HAVE THE REQUIRED EQUIPMENT AND NO ALTERNATIVE TEST IS SPECIFIED BY THE MANUFACTURER THEN THE APPLIANCE SHALL BE TURNED OFF AND DISCONNECTED AS AN UN-COMMISSIONED APPLIANCE UNTIL SUCH TIME THAT EQUIPMENT IS AVAILABLE TO UNDERTAKE SUCH TESTS.
BURNER AND ZERO-SET GOVERNOR, BECAUSE IT IS NOT POSSIBLE TO MEASURE AN OPERATING PRESSURE THE ENGINEER SHOULD FIRST CHECK
1
SINGLE PAGES 20/9/10 09:58 Page 4
2
2.1
These appliances are certified to comply with the requirements of EN 483, EN 677, and EN 625 for use in GB and IE (Great Britain and Ireland) using the following gas categories:
Eden VBX 30, Eden VBX 18:
II
(G20 with a governed gas supply at 20 mbar (8 in.wg) inlet
2H3P
pressure).
2.2
Appliance VBX30 VBX18 VBX30 VBX18
Mode Rate Central Heating Output Max
(non-condensing) (80 - 60 °C)
Central Heating Output (condensing) (50 - 30 °C) (Btu/h) (109500) (65900) (109500) (65900)
Central Heating Input Max Rate
Central Heating Input Min Rate
Central Heating Gas Rate (after 10 min operation - hot)
TECHNICAL SPECIFICATIONS
GAS CATEGORIES
PERFORMANCE DATA
Eden VBX 30 Propane, Eden VBX 18 Propane:
(G31 (Propane) with a regulated gas supply at 37 mbar (14.9 in.wg)
II
2H3P
inlet pressure). The appliance classification (as defined in EN 483) may be any of the
following depending on the chosen flue option: C
kW 30.0 18.0 30.0 30.0
(Btu/h) (102400) (61400) (102400) (61400)
Min
Max
Net
Gross
Net
Gross
Max (ft3/h) (113.7) (68.9)
kW 8.2 5.9 8.2 5.9
(Btu/h) (28200) (20100) (28000) (20100)
kW 32.1 19.3 32.1 19.3
kW 30.4 18.4 30.4 18.4
(Btu/h) (103700) (62800) (103700) (62800)
kW 33.8 20.4 33.0 20.0
(Btu/h) (115300) (69600) (112700) (68300)
kW 7.6 5.5 7.6 5.5
(Btu/h) (26000) (18800) (26000) (18800)
kW 8.4 6.1 8.3 6.0
(Btu/h) (28600) (20800) (28300) (20500)
m3/h 3.22 1.95
kg/h 2.36 1.43
, C33, C53, or B
13
Propane Propane
23
Seasonal Efficiency % 90.4 90.3 92.4 92.3 Seasonal Efficiency (SEDBUK) Band “A” Nox Classification Class “5” Min Central Heating System Pressure (Head) Bar 0.1 (1m H2O) Max Central Heating System Pressure (Head) Bar 3.0 Max Central Heating Flow Temperature °C 80 Min Central Heating Flow Temperature °C 30
2
SINGLE PAGES 20/9/10 09:59 Page 5
GENERAL SPECIFICATIONS
2.3
Natural Gas and Propane versions
Appliance VBX30 VBX18 Total weight (full) kg 38.1 32.6 Total weight (empty) kg 36.1 31.3 Max lift weight kg 28.1 24.7 Total water capacity l 2.0 1.3 Electrical supply 230V 50Hz Fuse at 3A Internal fuse T4H 4A 250V Maximum power consumption W 47 30 IP Rating IP20 Flue gas temperature Nat Gas 80/60 (Propane) °C 73 (76) 74 (72) Flue gas temperature Nat Gas 50/30 °C 41 43
value max rate (Nat Gas) %
CO
2
CO2value min rate (Nat Gas) ref only % 8.9 ± 0.1 8.4 ± 0.1 CO value max rate (Nat Gas) % 0.01 ± 0.005
value max rate (Propane) %
CO
2
CO2value min rate (Propane) ref only % 10.0 ± 0.1 9.7 ± 0.1 CO value max rate (Propane) % 0.019 ± 0.005 Flue products mass flow rate g/s 13.7 8.3 Flue products mass flow rate (Propane) g/s 13.7 8.3 Gas Valve Offset @ min rate Pa -3.0
9.2 ± 0.3 case on
9.0 ± 0.2 case off
10.7 ± 0.3 case on
10.5 ± 0.2 case off
Connections
Gas 15mm compression CH Flow 22mm tail CH Return 22mm tail Condensate Drain 21.5 - 22mm plastic overflow pipe
3
Vertical flue kit - Part no. 956081
with flat roof flashing plate
Vertical flue kit - Part no. 956081
Flue system application
Vertical flue kit - Part no. 956081
Split pipe vertical flue outlet kit
- Part no. 956080
with flat roof flashing plate
Raised external flue outlet kit
- Part no. 956084
Chimney flue liner kit
- Part no. 956082
External vertical flue kit
- Part no. 956085
Telescopic horizontal flue kit
- Part no. 956120
SINGLE PAGES 20/9/10 09:59 Page 6
OVERALL DIMENSIONS AND MINIMUM CLEARANCES
2.4 1
D
F
EDEN VBX18 320 280 150 97 100 694 200 540 400 200 5 5 200 EDEN VBX30 360 320 150 97 100 694 200 540 400 200 5 5 200
CONCENTRIC AIR / FLUE DUCT SPECIFICATIONS
2.5
A
B
C
E
J
K
G
H
I
ABCDEFGHI JKLM
L
M
The EDEN 'x-type' range can be installed to a number of different concentric flue systems. The different flue applications as shown in Figure 2 are available as kits usually comprising the connecting parts
2
The following systems are available for the EDEN ‘x-type’ range.
4
FLUE OPTIONS
to the appliance and end terminal. Flue extension ducts and extension elbows are available as accessories.
SINGLE PAGES 20/9/10 09:59 Page 7
2.5.1
KIT A + TELESCOPIC HORIZONTAL WALL TERMINAL (C13) - PART NO. 956120
3a
Traditional concentric flue system, Figure 3a, with a maximum length of 10m*. The flanged flue elbow is designed with 3° slope towards the appliance so that the condensate can easily drain off. It has to be considered that for every metre horizontal flue length the terminal exit centreline is approx. 45 mm higher than the elbow’s centreline. The standard telescopic terminal is 615mm max length and 430mm min length, but can be cut to a minimum flue length of 250mm, which is suitable for single, 100mm (4"), brick walls.
Standard concentric (ø100/60) vertical flue application, Figures 3b, 3c, through roof attics with a maximum length of 12m*. The kit comprises of the roof terminal, vertical adaptor with sampling point and bracket. The maximum length is measured from the top of the appliance casing to the underside of the air cowl.
The maximum length is measured from the top of the appliance casing to the underside of the air cowl.
For installation details refer to the flue kit instructions.
* Note: Flues which exceed 7mtrs in length will be subject to a small percentage decrease in heat input (below the standard tolerance) as shown in graph ‘A’ below.
GRAPH A
102.0
101.0
100.0
99.0
98.0
97.0
96.0
Heat input (%)
95.0
94.0
93.0
92.0
Horizontal flues (
Reduction in heat input as flue length increases
0123456789 1011
Flue Length (m)
C33) up to 10m in length, or equivalent, may be used, however a reduction in the heat input will occur. The graph shows details.
3c
a
Roof terminal with rain cover and pitched roof flashing kit.
b
2.5.2
3b
KIT B VERTICAL CONCENTRIC FLUE TERMINAL (C33) - HBL PART 956081
Fig 3(c) Offset vertical flue.
‘a’ measured from boiler flue outlet centre line to the centre line of the extension elbow.
‘b’ measured from the top of the boiler to the underside of the air cowl. Maximum allowable length of a + b = 8900mm
2.5.3
KIT C: HORIZONTAL ANTI-PLUME FLUE KIT (C13) - PART NO. 956084
If the standard horizontal terminal is likely to cause nuisance to a neighbour or buildings, because of excess pluming, then this particular flue kit raises the flue gas outlet point to a higher elevation with the minimum amount of changes. The flue gas duct is teed-off from the concentric part and covered by an 80mm outer tube to protect the flue duct from freezing. The air in-take remains at the lower level (see Figure 3d).
If choosing this option then the external flue duct length should be taken into account when calculating equivalent flue length.
For installation details refer to the flue kit instructions.
5
SINGLE PAGES 20/9/10 09:59 Page 8
3d
2.5.4
3e
KIT D EXTERNAL VERTICAL FLUE - (C33) PART NO. 956085
2.5.5
KIT E CHIMNEY FLUE LINER KIT (B23) - PART NO. 956082
This kit is suitable for open flue application in accordance with BS5440 where a room sealed flue installation is impractical. The kit comprises of a flue adaptor from the appliance to the chimney, a flexible plastic flue liner with connection parts and chimney terminal (see Figure 3f). Where an open flue system is used, then an air vent must be provided in the same room or internal space as the flue duct air inlet, see section 3.4.
For installation details refer to the flue kit instructions.
Max flexi liner length = 30mtrs Min flexi liner length = 5mtrs
Max concentric length = 2000mm Min concentric length = 100mm
3f
Suitable for installations if the appliance can’t be repositioned and where other horizontal flue options may causes some nuisance to neighbours or buildings. The flue kit contains some additional 45° elbows and extension ducts as well as a special wall bracket to pass the guttering (see Figure 3e). The concentric flue will be routed vertically alongside the outside wall to above the roofline. Special seals are required to prevent rainwater penetrating the pipe joints.
For installation details refer to the flue kit instructions.
6
A flue system can be built up from the components detailed in the table on the next page, but the total flue resistance must not exceed the maximum stated.
SINGLE PAGES 20/9/10 09:59 Page 9
FLUE LENGTHS
Length supplied in standard kit - horizontal 815mm Max horizontal length (from boiler to chimney - 60/100mm) 2000mm Min horizontal length (from boiler to chimney - 60/100mm) 100mm Max vertical length (from boiler to chimney - 60/100mm) 2000mm Min vertical length (from boiler to chimney - 60/100mm) 200mm Length supplied in standard kit - vertical (available in 10m, 20m and 30m length) N/A
FLEXITUBE MUST BE PURCHASED AS AN ACCESSORY TO COMPLETE THE KIT
Flexi tube min length 5m Flexi tube max length 30m
(See below)
ACCESSORIES
Description Part No. Resistive Length
HORIZONTAL - 60/100 Accessories
Flue extension duct - 500mm 956092 450mm Flue extension duct - 1000mm (Incl. 1 x support bracket) 956093 950mm 93° extension elbow 956091 1550mm 45° extension elbow (pair) 956090 775mm Air inlet duct - included in kit N/A N/A Straight adapter (60/80) - included in kit N/A N/A
91.5° adapter elbow (80/80) - included in kit N/A N/A Support bracket - 100mm 840517 N/A 93° flanged elbow - included in kit 956082 N/A Vertical turret socket 956087 N/A
VERTICAL - Accessories
Flexi tube - 10m 956110 10m Flexi tube - 20m 956111 20m Flexi tube - 30m 956112 30m Straight duct (80) - included in kit N/A N/A Chimney terminal - included in kit N/A N/A
NOTE: RESISTIVE LENGTH INFORMATION ONLY REQUIRED FOR COAXIAL FLUE PARTS. THE CORRUGATED (FLEXI TUBE) FLUE PARTS ARE FIXED AND ALL PARTS ARE REQUIRED FOR EVERY APPLICATION.
7
SINGLE PAGES 20/9/10 09:59 Page 10
2.5.6
KIT F: TWIN FLUE SYSTEM (C53) PART NO. 956080
This flue system kit is designed for installations where the air intake position is different than the flue duct exit point. The kit comprises of a twin adaptor from which the air intake is taken from the adjacent outside wall (see example Figure 3g) and the flue duct is routed vertically through the roof.
It has to be noted that the flue duct is under pressure when the appliance is in operation and the duct can leak poisonous carbon monoxide if the duct components are not correctly assembled. It is not recommended to route the flue duct through living space areas, i.e. bed rooms, living rooms etc.
For installation details refer to the instructions provided with the twin flued kit.
For C53 flue systems the terminal for the supply of combustion air and for the evacuation of combustion products shall not be installed on opposite walls of the building.
Maximum flue resistance permitted for a twin flued system = 52 Pa Minimum flue resistance permitted for a twin flued system = 23.5 Pa
Flue Component Flue Resistance (Pa) Part Number
Twin Flue Adaptor (required) 9.5 ­Air Inlet Terminal (required) 3 ­Chimney Terminal (required) 0.5 ­80 mm dia straight duct 1 metre 1 956101 80 mm dia straight duct 2 metre 2 956102 90° Elbow (80/80) 8 956100
45° Elbow (80/80) 4 956099
3g
A flue system can be built up from the components detailed in the table, but the total flue resistance must not exceed the maximum stated.
ADDITIONAL CONCENTRIC FLUE KITS
2.6
The following additional concentric kits are available as optional extras. Flue Extension Ducts - 1000 mm and 500 mm long, (each duct extends
the flue length by up to 950 mm and 450 mm respectively). 93° Extension Elbow - Allows an additional bend in the flue, and has an
'equivalent length' of 1550 mm. This elbow is mechanically different from the flanged elbow supplied as standard with the appliance, but has the same equivalent length.
45° Extension Elbow - Allows an additional bend in the flue and has an 'equivalent length' of 775 mm.
Vertical Turret Socket - For use with elevated horizontal flues and vertical terminals.
Vertical Roof Terminal - For use where an external wall is not available, or where it is desirable to route the ducts vertically.
For installation details refer to the instructions provided with the individual flue kits.
These optional kits may be used with the standard flue kits to produce an extensive range of flue options, providing that the following rules are strictly obeyed.
a) The maximum/minimum permissible length of the room sealed flue
system are:
Horizontal flue terminal (all orientations) maximum 10000 mm (197 in) Horizontal flue terminal (rear exit) minimum 250 mm (10 in) Vertical flue terminal maximum 12000 mm (472 in) Vertical flue terminal minimum 600 mm (23
1
/2in)
8
The 'equivalent' flue length must not exceed the maximum values stated.
b) The standard terminal must always be fitted horizontally; horizontal
ducts must have a continuous fall towards the appliance of 2.5°. This ensures condensate runs back into the appliance from the flue system. The vertical terminal must always be used if a vertical outlet is required.
c) The concentric flue system must use either a flanged elbow or a
vertical flue turret socket at the entry/exit to the appliance.
d) All joints must be correctly made and secured in accordance with
the installation instructions. When cutting ducts, avoid swarf, uneven and sharp edges to maintain duct integrity.
Refer to Figures 2 and 3 to determine which option kits are required before commencing the installation. Instructions for installing the appliance with a horizontal flue and straight extension ducts are included in the main text of these instructions (section 4.8).
SINGLE PAGES 20/9/10 09:59 Page 11
2.6.1
PLUME DIVERTER TERMINAL INSTALLATION
Plume Diverter Kit Part No: 956103
(For use with Standard horizontal flue kit - Part no 956083 - only) This kit is provided to assist in fitting a condensing boiler with reduced
clearances when fitted in good practice according to the Guide to Condensing Boiler Installation published by DEFRA/HMSO.
This kit allows the boiler flue outlet to be directed to the left or to the right only.
INSTALLATION INSTRUCTIONS
Under certain operating conditions condensing appliances have a tendency to form a plume of water vapour at the terminal. Therefore consideration should be given when fitting the Plume Diverter in terms of plume dispersal onto adjacent surfaces and neighbouring properties.
a) Refer to section 2.5 for instructions on fitting the flue system.
Also see Figure 5 for all other clearances.
3h
The resistance of the diverter is equivalent to 0.5 metre of flue length. Ensure this is used when calculating the maximum allowable flue length. (maximum horizontal flue length restricted to 9.5 metres when using the plume diverter).
The diverter allows the terminal clearance to be reduced as follows (see diagrams below):
Clearance H – From a surface facing the terminal - 600mm. Clearance F – From internal or external clearances - 300mm. b) Choose the direction required to deflect the flue products
(left or right only)
c) Push the diverter elbow onto the angled outlet of the flue terminal
in the desired rotational position and ensure the diverter is pushed up to the shoulder to fully engage the rubber seal.
d) Fix the diverter to the flue terminal with the self drilling screw
provided. Do not use a power tool to fit screw.
3i
Note. The Plume Diverter terminal must not under any circumstances deflect flue products downwards.
9
SINGLE PAGES 20/9/10 09:59 Page 12
APPLIANCE HYDRAULIC CIRCUITS
2.7 4
BURNER &
BURNER
FLANGE
CH FLOW
CH RETURN
PRIMARY HEAT
EXCHANGER
FLUE
PRODUCTS
CH RETURN THERMISTOR
CH FLOW THERMISTOR
CH FLOW
CH RETURN
CONDENSATE TRAP
CONDENSATE
OUTLET
10
SINGLE PAGES 20/9/10 09:59 Page 13
3
3.1
GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1996 (AS AMENDED)
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.
In GB, a CORGI Registered Installer must carry out the installation. It must be carried out in accordance with the relevant requirements of the:
Gas Safety (Installation and Use) Regulations
The appropriate Building Regulations either The Building Regulations, The Building Regulations (Scotland), Building Regulations (Northern Ireland).
The Water Fitting Regulations or Water Byelaws in Scotland. The Current I.E.E Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard code of Practice.
In IE, the installation must be carried out by a Competent Person and installed in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
It should also be in accordance with the relevant recommendations in the current editions of the following British Standards and Codes of Practice: BS 5449, BS 5546, BS 5440-1, BS 5440-2, BS 6798, BS 6891, Institute of Gas Engineer document IGE/UP-7, BS 7074 (expansion vessel), BS 5482 (propane installations) and IS813 for IE.
IMPORTANT NOTE: Manufacturer's instruction must NOT be taken in any way as overriding statutory obligations.
3.2
THE FOLLOWING LIMITATIONS MUST BE OBSERVED WHEN SITING THE APPLIANCE:
a) The appliance is not suitable for external installations. The position
selected for installation should be within the building, unless otherwise protected by a suitable enclosure and MUST allow adequate space for installation, servicing and operation of the appliance and for air circulation around it (Section 2.4 and 3.4).
b) This position MUST allow for a suitable flue system and terminal
position. The appliance must be installed on a flat vertical wall, which is capable of supporting the weight of the appliance and any ancillary equipment.
c) If the appliance is to be fitted in a timber framed building it should
be fitted in accordance with the British Gas publication 'Guide for Gas Installations In Timber Frame Housing', Institute of Gas Engineers document IGE/UP-7. If in doubt, advice must be sought from the Local Gas Supplier.
d) The appliance is approved to a protection rating of IP20. Therefore
if the appliance is to be installed in a room containing a bath or a shower, any electrical switch or control utilising mains electricity must be so situated that it cannot be touched by a person using the bath or shower. Attention is drawn to the requirements of the current BS 7671 (I.E.E Wiring Regulations) and in Scotland the electrical provisions of the Building Regulations applicable in Scotland.
INSTALLATION REQUIREMENTS
STATUTORY REQUIREMENTS
APPLIANCE LOCATION
FLUE TERMINAL POSITION
3.3
DETAILED RECOMMENDATIONS FOR FLUE INSTALLATION ARE GIVEN IN BS 5440-1. THE FOLLOWING NOTES ARE FOR GENERAL GUIDANCE.
a) The appliance MUST be installed so that the terminal is exposed to
the external air.
b) It is important that the position of the terminal allows free passage
of air across it at all times.
c) It is ESSENTIAL TO ENSURE that products of combustion
discharging from the terminal cannot re-enter the building or any other adjacent building, through ventilators, windows, doors, other sources of natural air infiltration, or forced ventilation / air conditioning.
d) The minimum acceptable dimensions from the terminal to
obstructions and ventilation openings are specified in Figure 6.
e) If the terminal discharges into a pathway or passageway check that
combustion products will not cause nuisance and that the terminal will not obstruct the passageway.
f) Where the lowest part of the terminal is fitted less than 2000 mm (78
in) above the ground, above a balcony or above a flat roof to which people have access, the terminal MUST be protected by a purpose designed K6 terminal guard (optional extra: Part No. 951507).
g) The air inlet / flue outlet MUST NOT be closer than 25 mm (1 in) to
combustible material.
h) Condensing appliances have a tendency to form a plume of water
vapour at the terminal under certain operating conditions. This is normal but positions where this would cause damage or a nuisance should be avoided. Consideration should be given to the dispersal of the plume in terms of adjacent surfaces and neighbouring properties. A special flue terminal, (Kit C), is available to raise the flue discharge point; use of this terminal will limit the maximum flue length available.
For further information contact: Halstead Glen Dimplex service helpline Tel: 0844 371 1111.
VENTILATION REQUIREMENTS
3.4
Detailed recommendations for air supply are given in BS 5440-2. The following notes are for general guidance. a) It is not necessary to have a purpose provided air vent in the room
or internal space in which a room-sealed appliance is installed.
b) Cupboard or compartment ventilation is not necessary for a room-
sealed appliance providing that the minimum clearances are maintained.
c) Where an open flued, (B23), system is used, then an air vent must be
provided in the same room or internal space as the flue duct air inlet, with a minimum free-area of at least:
VBX 30 117 cm VBX 18 57 cm
d) If the appliance is installed in a room or internal space with other
opened flued appliances, then the size of the air vent necessary should be calculated in accordance with BS 5440-2 Table 2.
2
2
11
SINGLE PAGES 20/9/10 09:59 Page 14
FLUE TERMINAL POSITION
5
SPECIAL REQUIREMENTS FOR A VERTICALLY BALANCED FLUE
Position Minimum spacing
A Directly below an openable window, 300mm 12in
air vent, or any other ventilation opening
B Below gutter, drain/soil pipe 75mm 3in C Below eaves 200mm 8in D Below a balcony 200mm 8in
E From vertical drain pipes and 150mm 6in
soil pipes
F From internal or external corners 300mm 12in
*internal corners *1000mm 40in
G Above adjacent ground or
balcony level 300mm 12in
H From a surface facing the terminal 600mm 24in
I Facing terminals 1200mm 48in
J From opening (door/window) in 1200mm 48in
carport into dwelling *not recommended
K Vertically from a terminal on the 1500mm 60in
same wall
L Horizontally from a terminal on the 300mm 12in
same wall
M Adjacent to opening 300mm 12in N Below carport 600mm 24in
O From adjacent wall 300mm 12in P From adjacent opening window 1000mm 40in Q From another terminal 600mm 24in R Minimum height 300mm 12in
*2500mm 98in
*2500mm 98in
*2500mm 98in
*not recommended
e) Where an open flued system is used, and the flue duct air inlet is
within a compartment then high and low level air vents are necessary in the compartment, the size of the vents should be calculated in accordance with BS 5440-2 Table 2.
CONDENSATE DISPOSAL
3.5
The condensate drain connection is suitable for either 21.5 mm or 22 mm plastic push fit or adhesive overflow pipes and fittings. It should be piped to drain, preferably within the building, maintaining a continuous 2.5° fall away from the appliance. If the drain is routed to outside it should be to a drain or soak away, and any external pipe work should be in 32 mm. Insulation to protect from freezing in cold weather conditions is also advisable. Note if the appliance is installed in a garage all pipe work should be in 32 mm. Ensure that the condensate discharge system complies with any local regulations in force.
GAS SUPPLY
3.6
a) The Gas Supplier should be consulted at the installation planning
stage in order to establish the availability of an adequate supply of gas.
b) An existing service pipe MUST NOT be used without prior
consultation with the Gas Supplier.
c) A gas meter can only be connected by the Gas Supplier or by
their contractor.
d) An existing meter and/or pipe work should be of sufficient size
to carry the maximum appliance input plus the demand of any other installed appliance. (BS 6891: 1988).
A minimum of 22 mm diameter pipe work is recommended within 1000 mm of the appliance gas cock.
e) Natural gas appliances: The governor at the meter must give a
constant outlet pressure of 20 mbar (8 in.wg) when all appliances on the system are running.
Propane appliances: The regulator must give a constant outlet pressure of 37 mbar (14.9 in.wg) when all appliances on the system are running.
f) The gas supply line should be purged. WARNING: Before purging
open all doors and windows, also extinguish any cigarettes, pipes, and any other naked lights.
g) The complete installation must be tested for gas tightness.
CENTRAL HEATING SYSTEM
3.7
a) The appliances incorporate all the components necessary to allow
them to be connected to a sealed central heating system. Refer to Figure 7a for a typical system design, which incorporates radiators, and a drain facility that must be provided at the lowest point in the system to allow complete drain down.
b) The installation should be designed to operate with a flow
temperature of up to 95 °C.
c) A sealed system must only be filled by a competent person. d) The available pump head for the appliances are given in
Figure 6.
e) If thermostatic radiator valves are fitted, a radiator must be fitted
with two lock shield valves, to enable correct operation of the pump-overrun facility.
*Recommended by the boiler manufacturing industry to prevent pluming
12
nuisance and damage to buildings.
Pressure Drop (m H
O)
SINGLE PAGES 20/9/10 09:59 Page 15
f) The following paragraphs outline the specifications of the items
fitted to the appliances.
PUMP - The available pump head shown in Figure 6 is that in excess of the appliance hydraulic resistance, i.e. that available for the system.
APPLIANCE HYDRAULIC RESISTANCE
6
VBX 30
4
3.5
3
2
2.5
2
1.5
1
0.5
0
3.8
A draining tap must be provided at the lowest point of the system, which will allow the entire system and hot water system to be drained.
Draining taps shall be to the current issue of BS 2879.
3.9
A safety valve need not be fitted to an open vented system. (See 3.16 for sealed systems)
3.10
The pump should be fitted on the flow pipe from the boiler and have isolating valves each side.
A variable duty pump should be set to give a temperature difference of no greater than 20°C between the flow and return, with the thermostat set at “MAX”, which is approximately 80° to give a flow rate as shown in table 1.
See figure 6 for pressure loss of the boiler. High resistance microbore systems may require a higher duty pump.
VBX 18
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Flow Rate ltr/min
DRAINING TAP
SAFETY VALVE OPEN VENTED SYSTEM
PUMP
24
3.11
If it is necessary to alter the flow rate, the system can be fitted with a lockable balancing valve in the main flow or return pipes shown as valve “A” in figure 7. The flow rate through the boiler must not be allowed to fall below that given in table 1.
3.12
WATER TREATMENT, CLEANSING AND FLUSHING THE HEATING SYSTEM
NOTE: British Standard BS7593: 1992 stresses the importance of
cleansing and flushing of the system to ensure it continues to run efficiently with the minimum of maintenance necessary. Halstead Boilers fully support this professional approach and recommend that the system is cleansed with an effective chemical cleanser and protected long term with a suitable inhibitor. Such products are available from Fernox and Sentinal.
3.13
The boiler must be supplied from an unrestricted water supply taken from a feed and expansion cistern situated at a maximum height of 27 metres (90ft) above the boiler.
The cold feed must be 15mm minimum size. The vent must rise continuously and be unrestricted. It is important that the relative positions of the pump, cold feed and open
vent are as shown in figure 8.
3.14
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE The domestic hot water cylinder must be of the double feed fully indirect
coil type.
3.15
The installation must comply with the appropriate requirements of the current issue of BS4814, BS5449, BS6759, BS6798 and BS7074 Part 1 and 2.
See figure 7 for a suggested layout.
FLOW RATE
Table 1. Flow Rate
MINIMUM FLOW RATE
200 l/h
This is equal to 20°C differential at minimum heat input.
WATER TREATMENT
OPEN VENTED HOT WATER SYSTEM
DOMESTIC HOT WATER CYLINDER
SEALED HOT WATER SYSTEMS
3.16
A safety valve must be fitted to a sealed system. It shall be preset, non-adjustable with a lift pressure of 3 bar,
incorporating seating of a resilient material, a test device and a connection for drain.
The drain from the safety valve must be routed outside the building, must not discharge above an entrance or window or any type of public access area, be clear of any electrical fittings and positioned so that any discharge can be seen.
SAFETY VALVE SEALED SYSTEM
13
SINGLE PAGES 20/9/10 09:59 Page 16
3.17
EXPANSION VESSEL
A diaphragm type expansion vessel, conforming to the current issue of BS4814 (see also BS7074 Part 1 and 2) must be connected at a point close to the inlet side of the circulating pump, see the diagrammatic layout, figure 7 unless laid down differently by the manufacturer.
The expansion vessel volume depends on the total water system volume and the initial system design pressure. For any system an accurate calculation of vessel size is given in the current issue of BS5449 and BS7074 Part 1.
Example: For an initial design pressure of 0.7 bar, the minimum total vessel volume required is 0.063 x Total System Volume.
Expansion Vessel Requirements
Vessel charge and initial system pressure
bar 0.5 0.75 1.0 1.5
Total water content for system using 8L (1.54 gal) capacity expansion vessel
L 96 84 73 50 supplied with appliance For systems having a
larger capacity, multiply the total system capacity in litres (gallons) by these
0.0833 0.093 0.109 0.156 factors to obtain the total minimum expansion vessel capacity required in litres.
Note: A higher initial design pressure requires a larger volume expansion vessel.
The charge pressure must not be less than the static head of the system, that is, the height of the highest point of the system above the expansion vessel.
The water content of the boiler is given in 2.3 General Specifications.
3.18
PRESSURE GAUGE
A pressure gauge with a set pointer and covering at least 0 to 4 bar (0 to 60 lb/in) shall be fitted permanently to the system in a position where it can be seen when filling the system.
3.19
WATER MAKEUP
Provision should be made for replacing water loss from the system using a make up bottle mounted in a position higher than the top point of the system, connected through a non-return valve to the return side of either the heating circuit or the hot water cylinder.
Alternatively, provision for make up can be made using a filling loop.
3.20
FILLING A SEALED WATER SYSTEM
Provision for filling the system at low level must be made, see figure 8. There must be no permanent connection to the mains water supply, even through a non-return valve.
CONTROLS. As a minimum it is recommended that a room thermostat be installed to control the appliance. Thermostatic radiator valves may be fitted to the system, however they must not be fitted in the room where the room thermostat is fitted. There must be at least one radiator installed with lock shield valves that should not be closed. Further guidance can be obtained from the Domestic Heating and Hot Water Guide to the building regulations.
14
7
SEALED WATER SYSTEM
ROOM THERMOSTAT
FLOW
RETURN
NOTE: No automatic by-pass required. However, it is recommended to leave one radiator open and to fit a system by-pass in the DHW circuit to ensure pump over-run functionality.
TANK THERMOSTAT
HOT
WATER
CYLINDER
DRAIN COCK
MAKE UP BOTTLE Observe minimum static head requirements
SAFETY
VALV E
CH/DHW
2 CHANNEL
PROGRAMMER
CH/DHW SWITCHED LIVE
AUTOMATIC
AIR VENT
TERMINAL
BLOCK
LOCKABLE
BALANCING
VALVE “A”
NON RETURN VALV E
SYSTEM BYPASS
APPLIANCE
MOTORISED
VALV E
AIR RELEASE
VALV E
3-WAY VALV E
PUMP
EXPANSION
VESSEL
FILL POINT NON-RETURN VALV E
PRESSURE GAUGE
SINGLE PAGES 20/9/10 09:59 Page 17
3.21
ELECTRICITY SUPPLY
a) Wiring external to the appliance must be in accordance with the
current I.E.E Wiring regulations (BS 7671) for electrical installation and any local regulations, which apply.
b) The mains cable must be at least 0.75 mm2 (24/0.2 mm) PVC
insulated to BS 6500 table 16.
c) THIS APPLIANCE MUST BE EARTHED. Failure to provide a
satisfactory earth connection will result in appliance malfunction.
8
OPEN VENT WATER SYSTEM with flow and return connected to bottom pipes
COLD WATER STORAGE
TO DRAIN
OFF TAP
TANK
THERMOSTAT
STOP
VALV E
DRAIN
CH/DHW
2 CHANNEL
PROGRAMMER
TERMINAL
BLOCK
ROOM
THERMOSTAT
HOT WATER CYLINDER
SWITCHED LIVE
LOCKSHIELD
VALV E
SYSTEM BYPASS
NOTE:- Flow and return pipes must be run in copper for a minimum of 1.5mtrs
RETURN
FLOW
from the boiler.
OPEN VENT WATER SYSTEM with flow and return connected to top pipes
The VBX appliances may be used with any certified programmer/room thermostat, as described in section 4. For further information contact: Halstead Glen Dimplex service helpline Tel: 0844 371 1111.
3.22
EXTERNAL CONTROLS
d) The method of connection to the mains supply must facilitate
complete electrical isolation of the appliance. Either a 3A fused three pin plug and un-switched shuttered socket outlet, both complying with BS 1363, or a 3A fused double pole switch having a 3 mm contact separation in both poles and serving only the boiler (and its external controls) may be used.
RECOMMENDATION ONLY NOTE: PUMP REQUIRES OPTIMISATION TO PREVENT PUMP OVER INTO FEED & EXPANSION TANK
AUTOMATIC AIR VENT
3-WAY VALV E
MOTORISED
VALV E
MOTORISED VALV E
EXPANSION
APPLIANCE
COLD FEED
CH FEED &
EXPANSION TANK
NOTE: No automatic by-pass required. However, it is recommended to leave one radiator open and to fit a system by-pass in the DHW
circuit to ensure
DRAIN
pump over-run functionality.
STOP
VALV E
DRAIN
CH/DHW
2 CHANNEL
PROGRAMMER
COLD WATER STORAGE
TO DRAIN
OFF TAP
THERMOSTAT
RETURN
THERMOSTAT
HOT WATER CYLINDER
TERMINAL
BLOCK
ROOM
TANK
SWITCHED LIVE
FLOW
LOCKSHIELD
VALV E
AUTOMATIC AIR VENT
SYSTEM BYPASS
3-WAY VALV E
MOTORISED
CH FEED &
EXPANSION TANK
VALV E
MOTORISED VALV E
COLD FEED
EXPANSION
150mm MAX
APPLIANCE
AUTOMATIC AIR VENT
DRAIN
15
SINGLE PAGES 20/9/10 09:59 Page 18
4
Before installing the appliance, check that the chosen location is suitable (section 3.2) and that the requirements for flue position (section
3.3) and minimum clearances (Figure 1b) are satisfied.
4.1
The appliance is supplied in one box. Flue kits are provided separately, the various flue kits available as described in sections 2.5 - 2.7. If the appliance is to be installed without access to an external wall, a wall liner kit is also required.
Unpack the boxes and check the contents:
G
Complete appliance
G
Paper wall mounting template
G
Wall mounting plate
G
Installation and Servicing Instruction
G
User's Instructions
G
Warranty Card
G
Hardware pack containing: 50mm x No 10 Wood Screws - 4 off
Rawl Plug to suit - 4 off
APPLIANCE INSTALLATION
UNPACKING THE APPLIANCE
Manual Handling Note:
During the appliance installation it will be necessary to employ caution and assistance whilst lifting, as the appliance exceeds the recommended weight for a one-man lift. Take care to avoid trip hazards, slippery or wet surfaces.
PREPARING THE WALL
4.2
a) Fix the paper template in the required position (ensuring that the
necessary clearances are achieved). Ensure squareness by hanging a plumb line.
b) Mark the position of the wall mounting plate-fixing holes (4). Select
one from each group. Refer to Figure 10.
c) Mark the position of the flue outlet. For side flue installation extend
the flue centre line on to the sidewall, where the flue length exceeds 775 mm, a flue slope angle of 2.5° needs to be taken into account. Refer to Figure 10. Remove the paper template.
d) Cut the hole in the wall for the air/flue duct (preferably with a core-
boring tool). The hole must be horizontal and not be less than 100 mm in diameter. If the hole is not accessible from outside, its minimum diameter must be sufficient to allow insertion of the wall liner (130 mm, 5in). The wall liner is available as an optional extra and must be sealed in position with mortar (or equivalent).
e) Drill the four fixing holes using a 6mm drill and insert the wall plugs
provided.
f) Hang the wall mounting plate using two fixing screws in the top,
ensuring that it is level.
MOUNTING THE APPLIANCE
4.3
Refer to Figure 10. a) Lift the appliance into position approximately 10 mm above the top
of the wall mounting plate and use the side wings on the plate to locate the appliance in a horizontal direction. Then carefully lower the appliance, ensuring that the top locating rail is securely engaged.
b) Connect the central heating system pipes to the central heating flow
and return pipes on the boiler.
16
Pipe work may be routed from above or below the appliance as required.
9
2.5º
REAR FLUE SIDE FLUE
108
190
POSITION OF
DUCT HOLE
POSITION OF WALL
MOUNTING PLATE
127.5
101.5
190
SINGLE PAGES 20/9/10 10:00 Page 19
MOUNTING THE APPLIANCE
10
WALL MOUNTING PLATE
RAIL LOCATION EDGE
CENTRAL HEATING SERVICE
4.4
CONNECTIONS
Refer to Figure 11. a) The boiler is supplied with 22mm copper tails for both upwards and
downwards (optional) flow and return pipe routing suitable for compression or soldering connections.
USE EXTREME CARE IF SOLDERING THE JOINTS NEAR TO THE APPLIANCE. IF BOILER IS LOCATED IN TIGHT SPACE IT IS RECOMMENDED TO REMOVE THE PIPES FROM THE BOILER.
b) Connect the central heating system pipes to the central heating flow
and return pipes on the boiler. If downwards routing is required: The sealed ends must be removed before connecting to the heating system pipes. The upwards pipes must be used for connecting to a vent pipe (open system) or fitting to an automatic air vent (sealed system). The remaining pipe must be solder sealed. The flow and return sensors have to be removed from the upwards pipes and reconnected to the downward pipes (Fig 47; flow is nearest to the front).
c) Commission the central heating system as described in section 5.1,
and then proceed to section 4.5.
SERVICE CONNECTIONS
11
CH FLOW
CH RETURN
CONDENSATE CONNECTION
4.6
Refer to Figure 12.
Connect either a Ø21.5mm or Ø22mm plastic push fit or adhesive overflow pipe to the condensate outlet. It should be piped to drain, preferably within the building, maintaining a continuous 2.5° fall away from the appliance. Note; if an additional “U” trap is fitted between the appliance and the discharge point, then a visible air break is necessary between the appliance and trap, because a trap is already provided within the appliance. Ø32mm pipe should be used for external pipe work, or if the appliance is installed in a garage. If the drain is routed externally to a drain or soak away, then the external length should be kept as short as possible and not exceed 3000 mm. Protection from freezing in cold weather conditions is also advisable. Ensure that the condensate discharge system complies with any local regulations in force.
CONDENSATE CONNECTIONS
12
WASTE STACK
2.5º
CONDENSATE DRAIN
MUST BE
Ø22
CONDENSATE
DRAIN
MUST BE Ø22
SINK WASTE
2.5º
CH FLOW (OPTIONAL)
CH RETURN (OPTIONAL)
MAINS GAS INLET
CONDENSATE OUTLET
GAS CONNECTION
4.5
Refer to Figure 11.
Connect the gas supply pipe to the gas service cock. It is recommended that a minimum of 22 mm diameter OD copper pipe be used to within 1000 mm of the gas service cock.
EXTERNAL PIPE MUST BE Ø32mm
In exceptional circumstances, such as when a boiler is installed in a basement without drainage, it may be necessary to install a condensate pump to carry condensate up to ground/drain level. Such products are available from Grundfos Pumps Ltd on: 01525 850000 and Pump House on: 0115 922 2211.
AIR/FLUE DUCT INSTALLATION
4.7
For correct flue installation please refer to the installation instructions that are provided with the individual flue kit as described in sections
2.5 - 2.7. a) Measure the required flue length as shown in Figure 13. Refer to
section 2.5 to determine whether any extension kits are required. Installations using only the standard ducts or standard ducts with straight extensions are described in this section. Installation instructions for all other flue systems are included in the various flue kits.
17
SINGLE PAGES 20/9/10 10:00 Page 20
b) Ensure that all (inner and outer tube) sealing rings are provided and
assemble the air/flue ducts as shown in the flue instructions.
c) Construct the correct flue length by building the flue out from the
appliance. Ensure that the flue and air seals are correctly fitted
before assembly and that each section is fully engaged.
The flue length is measured from the centreline of the appliance flue outlet to the inside of the external wall-sealing ring. In most cases it will be possible to achieve the required flue length without cutting the ducts, however where necessary the plain ends of the extension ducts may be cut. Never cut the swaged end, and always ensure that the cut is square and free of burrs or debris.
NOTE IT IS ESSENTIAL THAT THE TERMINAL IS FITTED THE CORRECT WAY UP.
See flue kit Instructions (i.e. rain shield at the top).
MEASURING THE EXACT FLUE LENGTH
13
TOTAL FLUE LENGTH FROM OUTLET CENTRE TO OUTSIDE WALL FACE:
= LENGTH
L
L
WALL
FAN OUTLET
EXTERNAL Dia. 60mm
4.7.1
INSTALLING THE AIR/FLUE DUCT FROM INSIDE THE ROOM
Wall thickness up to 800 mm (31in) only. a) Push the terminal through the wall liner taking care to ensure that
the terminal is the correct way round and the external wall-sealing ring does not become dislodged.
b) Assemble the flue system extension ducts as necessary, referring
to Figure 14.
c) Pull the flue system towards the appliance to seat the external
sealing ring against the outside wall, ensuring that the duct joints are not disturbed.
d) Use the internal sealing ring to make good the internal hole, and
check that the terminal is correctly located on the outside wall (Where possible this should be visually checked from outside the building.) Figure 14 shows a view of the flue system, correctly installed.
e) Finally locate and secure the elbow to the appliance using the four
screws provided.
4.7.2
INSTALLING THE AIR/FLUE DUCT FROM OUTSIDE THE BUILDING
(Flue hole diameter 100 mm - wall liner not necessary)
a) Secure the flue elbow with seal to the appliance using 4 screws. b) Fit external wall sealing ring over flue and then from outside the
building, push the flue system through the wall taking care to ensure that the terminal is the correct way around.
c) Loosely fit the internal wall sealing ring over the inside end of the
flue.
d) Assemble the flue system extension ducts as necessary, referring
to the flue kit instructions, and fit to the flue elbow.
e) Fit the flue terminal to the flue system, ensuring that the duct joints
are not disturbed, and that the external sealing ring is seated against the outside wall.
f) Finally use the internal sealing ring to make good the internal hole.
Check that the external wall sealing ring and the terminal is correctly located, on the outside wall from outside the building.
18
14
INSTALLING THE FLUE SYSTEM FROM INSIDE THE ROOM
FIBRE SEAL FITTED
INTERNAL WALL
SEALING RING
2 ALIGN ASSEMBLED FLUE SYSTEM ELBOW TO APPLIANCE AND SECURE
3 SLIDE INTERNAL WALL SEALING RING TO WALL TO FORM A GOOD SEAL
130mm Dia. HOLE WITH
WALL LINER
1 INSERT ASSEMBLED FLUE SYSTEM FROM INSIDE THE ROOM. EXTERNAL WALL SEALING RING OPENS
TOP
EXTERNAL WALL SEALING RING
SINGLE PAGES 20/9/10 10:00 Page 21
ELECTRICAL CONNECTIONS
4.8
Connect the electricity supply and external controls (using suitable mains cable) as follows:
Wire the cable(s) into the appropriate connections in the electrical plug provided, referring to Figure 15. Live supply to L1, Neutral and Earth as indicated. Check that L2 and L3 are linked.
To provide correct cable retention, fit the piece of tubing supplied over the cable as it passes through the clamping arrangement. The cable will be held in position as the plug cover is fitted.
If a programmer/room thermostat is to be fitted remove the red link between L2 and L3 and connect the device across these terminals. Any external controls fitted must be rated at 230V 50Hz and have volt free contacts.
15
MAINS
PUMP
L3
N
L2
L1
PROGRAMMER
16
FULLY PUMPED ‘S’ PLAN
C
A
B
1
2
Brown Blue Grey Orange Green/ yellow
Brown Blue Grey Orange Green/ yellow
L
N
E
CT200
Room thermostat
L641A
Cylinder thermostat
V4043H
Heating valve
V4043H
Hot water valve
230V mains input
Or
4
5
6
Not used
8
5 2 1 10 3
8 2 1 10 3
1
2
3
1
3
2
T6360B Room thermostat
1
3
Optional
T4360A
Frost thermostat Opens heating circuit only
910 3 2 1 9 2 3
21 EN L LN E
Boiler Pump
2= Pump live 1=Switched live L=Permanent live
6432
1
Honeywell ST6998 1002
63
L
N
(Link L-5-3)ST 799A ST6400 ST6300
34
L
N
ST6200
Programmer
4
5
2
1
5
230V 50Hz
LN
HW HTG N L
Time controller
Brown
V4043H Zone valve
Motor Motor
Blue
Green
Grey
Grey
Yellow
T6360B Room thermostat
213 1 C
Blue
Green Yellow
34567
heating
L641A Cylinder thermostat
8 9 1021
ELN
Pump
Brown
V4043H Zone valve DHW
Orange
Orange
Boiler
L3 N E L2 L1
19
SINGLE PAGES 20/9/10 10:00 Page 22
17
FULLY PUMPED ‘Y’ PLAN
CT200
Room thermostat
L641A
Cylinder thermostat
V4073A
Mid position valve
230V mains input
Optional T4360A
Frost thermostat Opens heating circuit only-use with programmers with spot switching
18
A
B
1
C
2
White Blue Grey Orange Green/ yellow
L
N
E
1
3
UPP15-50 PUMP PLAN WIRING CENTRE CONNECTIONS
Fused switched isolator
N
L
Frost thermostat
Internal heater resistor
Room thermostat
Cylinder thermostat
E
3mm air gap
Fuse 3A
N/U
Demand
N/U
Demand
Demand
N/U
Or
4
1
3
5
2
T6360B Room thermostat
6 7 6
5 2 7 8
98321 923
3
21 EN L LN E
Boiler
1
2= Pump live 1=Switched live
2
L=Permanent live
3
7643
21
1
63
L
N
L
N
1734
34
L
5
Programmer
CH on HW on
N
Programmer
Fuse 2.5A
N L
C
NO
N
N/U
N
NO
C
C
N
N/U
NO
Earth terminals for Controls,Boiler,Pumps, Electrical mains supply.
N L
4
5
2
Pump
Honeywell ST6998 1002 (Link L-5-3)ST 799A
ST6400 ST6300
ST6200
N L S/L P/L
L N L N
CH on HW on N L
N L
230V 50Hz
LN
HW Off
On
Boiler
N
L
S/L
P/L
CH/HW programmer
HW on
N
L
Basic time clock
HTGHW
Time controller
L N
L N
CH on
N/U
NL
Boiler controls or gas solenoid
Boiler pump over run
HW Pump
CW Pump
N/U
Blue
Green/yellow
T6360B Room thermostat
213
L641A Cylinder thermostat
1
C
2
34567
L2
E
Boiler
L3
N
L1
Pump live
Permament live
19
Switched live
TYPICAL PROGRAMMER
Heating
Hot water Earth
Neutral 230V fused 3 amp
White
Grey
8 9 1021
Room thermostat
Orange
Pump
ELN
Boiler Terminals
V4073A Mid position zone valve
L2 L3
E N
L1
Pump
Pump live Switched live
Permament live
20
SINGLE PAGES 20/9/10 10:00 Page 23
5
5.1
Before commissioning the appliance, the whole gas installation including the meter MUST be purged and tested for gas tightness in accordance with BS 6891: 1988.
!
Before commencing the commissioning procedure, ensure that the gas service cock is turned on, the electricity supply is isolated, and that the CH pipe-work is complete. Fill the water systems by following the procedure detailed below in steps a) and b), and referring to Figure 20.
20
COMMISSIONING & TESTING
FILLING THE WATER SYSTEM
Open all doors and windows, extinguish naked lights, and DO NOT SMOKE whilst purging the gas line.
It is recommended, where possible, to flush the CH system without the appliance fitted, to avoid debris and flux blocking the waterways within the appliance.
CH FLOW
CH RETURN
MANUAL BLEED VALVE
Check the system for soundness. Drain the entire system to flush out any debris, and refill making sure
that all the air is properly vented from the system and pump. Repeat this instruction with the system hot. It is recommended that the system be cleaned with a recognised system cleaner such as Fernox or Sentinel.
Prior to lighting the appliance to check the gas rates, the central heating system should be checked for circulation by operating the appliance with the gas turned off, this is to ensure that no air locks occur. The appliance may go into ignition lockout and require resetting.
b) Sealed Systems
Fill the system until the pressure gauge registers 2.0 bar. Clear any locks and check for soundness.
Check the operation of the pressure relief valve (figure 21) by lifting the lever on the valve gently to ease the valve of its seat. Checking that water is discharged, release the lever and ensure that the valve seats correctly and does not leak. Where this is not possible a manual check should be carried out.
Release the cold water to the initial design pressure.
Do not use the pressure relief valve to drain the system, because dirt or debris could prevent the valve seating correctly. If the valve leaks or sticks closed, then replace it.
21
PRESSURE
RELIEF
LEVER
a) All Systems
A competent person in accordance with the current issue of BS6798 should carry out commissioning.
Fill the system with cold water. Vent the system via the radiator valves and system air vents in accordance with normal practice. Ensure that all system air vents are closed.
To aid venting, a manual air vent is provided on the LHS of the heat exchanger.
PRESSURE GAUGE CAPILLARY
PRESSURE GAUGE
THESE COMPONENTS ARE NOT SUPPLIED
COMMISSIONING THE APPLIANCE
5.2
Refer to Figure 22 a) Slacken the screw in the appliance inlet pressure test point and
connect a suitable manometer. Refer to Figure 23.
b) Check that the gas supply is turned ON and the gas service cock is
OPEN.
c) Switch on the electrical supply. d) Turn the CH temperature Control knob to the midpoint between the
minimum and maximum setting. The display changes from '
e) Ensure programmer and room thermostat (if fitted) are calling for
heat.
f) The display changes to '
seconds an ignition will commence.
NOTE
BY HALSTEAD BOILERS LTD.
H
'. The fan should start and after a few
o
' to ' '.
21
SINGLE PAGES 20/9/10 10:00 Page 24
g) If the burner fails to light the fan will stop. Initially this may be due
to air in the gas supply line. The boiler will automatically have five attempts at ignition. It may be necessary to turn the CH Temperature Control knob fully anti-clockwise to reset position and repeat (d). (See section 5.4).
h) When the boiler has lit the display will show '
appliance to run for at least 10 minutes and check that the gas supply pressure measured at the appliance inlet pressure test point is 20 ± 1 mbar for natural gas, and 37 ± 1 mbar for propane appliances.
FINAL CHECKS
5.3
a) Turn off the appliance and remove the manometer. Tighten the
appliance inlet pressure test point screw. Re-light the burner and test for gas tightness.
b) Fit the appliance casing as illustrated in Figure 24. Position and
secure both side panels and the decorative front cover with screws at the top and bottom.
c) Fit the appliance hinged front panel in position with two screws at
the top and bottom.
d) Set the CH Temperature Control to the required setting. Set the
room thermostat (if fitted) to the required setting. Refer to hot water cylinder instructions.
If the boiler is connected to a hot water cylinder the CH temperature has to be set to high.
H
.'. Allow the
INLET PRESSURE TEST POINT
23
GAS INLET PRESSURE TEST POINT
GAS SERVICE COCK
FROST PROTECTION
5.5
The appliance is fitted with a frost protection device. In the event of very cold conditions, the external pump may operate and the appliance light for a few minutes to protect the appliance and system from potential frost damage. This can only function if the gas and electricity supplies are maintained.
LOCKOUT / RESET INDICATION
5.4
In the event of failure during an ignition sequence, (5 attempts) the LED displays fault code ' Temperature Control anticlockwise to 'ON' within two seconds.
FASCIA PANEL AND CONTROLS
22
3
'. In order to reset the boiler turn the CH
to 'STANDBY' position and then back
7 SEGMENT DISPLAY
CH CONTROL KNOB SET TO MEDIUM
OVERHEAT PROTECTION
5.6
The appliance incorporates flow and return thermostats, which monitor the operating temperature. Abnormal temperatures such as overheating will cause the appliance to go to lockout and the LED display will show code ' Temperature Control knob fully anti-clockwise to the reset position to clear.
5.7
The following additional features are included in the appliance specification:
ANTI-CYCLE DEVICE:
When the appliance cycles on its central heating control thermostat, a slow cycle device operates. The timer (set to 5 minutes) is activated after the end of each burn cycle to prevent rapid cycling of the burner.
CH SOFT START DEVICE:
After every burner start the burner output stays at low for 3 minutes, to ensure smooth heat up of the system and maximum efficiency.
SERVICE MODE:
The appliance enters the SERVICE mode by turning the control knob fully clockwise. The LED displays a flashing ' appliance runs at the minimum CH output. This mode allows the boiler emissions to be measured.
1
'. Allow the appliance to cool and turn the CH
OTHER FEATURES
H
.'. In this mode the
22
SINGLE PAGES 20/9/10 10:00 Page 25
24
CASING
TOP HINGE
SIDE PANEL
DECORATIVE FRONT COVER
HINGED FRONT PANEL
BOTTOM HINGE
USER INSTRUCTIONS
5.8
Upon completion of commissioning and testing the system, the installer must instruct the user in how to operate the appliance by drawing the user's attention to the following.
a) Give the 'Users Instructions' to the householder and emphasise
their responsibilities under the 'Gas Safety (Installation and Use) Regulations or rules in force.
b) Explain and demonstrate the lighting and shutdown procedures. c) Advise the householder on the efficient use of the system, including
the use and adjustment of all system controls for CH.
d) Advise the user of the precautions necessary to prevent damage to
the system, and to the building, in the event of the system remaining inoperative during frost conditions.
e) Explain the function of the CH Temperature Control knob, and how
to reset the appliance. Emphasise that if cutouts persists, the appliance should be turned off and the installer or service engineer consulted.
f) Stress the importance of an annual service by a registered heating
engineer.
g) The electrical mains supply to the appliance must remain ON for the
frost protection circuit to operate.
APPLIANCE LOG BOOK
5.9
A logbook is supplied with this appliance to record installation and commissioning details and to make future servicing of the appliance easier. The logbook is found at the rear of this Installation and Servicing Instruction manual.
This logbook forms part of the industry's Benchmark code of practice for the installation, commissioning and servicing of central heating systems.
Please ensure that the logbook is fully completed and left with the customer for future reference, along with Users Instructions and this Installation and Servicing Instruction manual.
SIDE AND FRONT SECURING SCREWS
5.10
Appliances may be converted from one gas group to another. It is possible to convert between Propane and Natural gas by use of conversion kits. The kits comprise the following:
Propane to Natural Gas
Kit Numbers 955128 - Eden Vbx 18
Natural Gas to Propane
Kit Numbers 955129 - Eden Vbx 18
Instruction on how to convert the appliance is given in the conversion instructions supplied with these kits. However, particular attention should be given to the fitting of the gas valve and the use of the Boiler Chip Card (BCC).
For further information contact: Halstead Glen Dimplex service helpline Tel: 0844 371 1111.
GAS CONVERSION
955126 - Eden Vbx 30 Conversion Instructions Gas Control Valve Data Badge (Natural Gas) Boiler Chip Card Nat Gas Cork Gasket Polydome Badge (Natural Gas)
955127 - Eden Vbx 30 Conversion Instructions Gas Control Valve Data Badge (Propane) Boiler Chip Card Propane Cork Gasket Polydome Badge (Propane)
23
SINGLE PAGES 20/9/10 10:00 Page 26
6
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be adequate. It is the law that a competent person, such as British Gas or other CORGI registered personnel, must carry out any service work.
Service the appliance by following the full procedure detailed below:
6.1
The appliance incorporates a flue sampling point on the appliance flue elbow, or appliance vertical flue adaptor. If the service engineer has suitable equipment to analyse the flue gas, the sampling cap may be removed and an adequately sized sample tube fitted. Operate the appliance in Service mode, (see section 5.7). After ten minutes operation check the CO section 2.3. If the combustion figures are not within the limits shown in section 2.3 refer the section 9.3.1 Combustion check set-up.Do not forget to replace the sampling cap after use.
When the appliance is operating at maximum output check that the gas supply pressure is 20.0 mbar, using the inlet pressure test point, located on the gas cock.
Before commencing any service operation, ISOLATE the mains electrical supply, and TURN OFF the gas supply at the main service cock.
6.2
ROUTINE SERVICING
COMBUSTION CHECK
/CO values and compare with those figures stated in
2
GAS CONTROL, VALVE, FAN & BURNER ASSEMBLY
Refer to Figures 25, 26, 27, and 28 a) Remove the hinges and take off the hinged front panel. b) Remove the decorative front cover (4 screws). c) Remove the sealed chamber door (6 screws) d) Disconnect the igniter plug, earth lead and detection plug from the
igniter and detection electrodes.
e) Unscrew the screw holding the gas valve lead plug, and disconnect
the plug.
f) Disconnect the electrical leads from the fan (2 plugs). g) Undo the nut holding the gas valve feed pipe to the gas isolating
cock, and disconnect.
h) Remove the gas control valve, fan & burner assembly, by carefully
pulling forward the combustion chamber front and rotating the assembly anticlockwise so that the burner points forward, then disengage the gas valve feed pipe from the casing, by lifting up the assembly. Take care not to damage the insulation.
i) The assembly may then be inspected. j) Re-assemble in reverse order.
BURNER
6.3
Inspect, and if necessary clean the main burner ports using a soft brush or vacuum cleaner. Do not use a wire brush or any abrasive material.
IGNITION & DETECTION ELECTRODES
6.4
a) Inspect the ignition and detection electrodes in situ. If necessary,
clean using a soft brush. If either the electrode or the ceramic insulation shows signs of damage or wear, replace the electrode(s) and their gasket.
b) Check that the alignments of the ignition and detection electrodes
are correct. Refer to Figure 29. Adjust by carefully bending the tip of the electrode rod whilst supporting the base of the rod. Do not put any pressure on the ceramic insulation.
COMBUSTION CASE PANELS
26
24
25
CONTROL PANEL
FIXING SCREWS
FIXING SCREWS
SINGLE PAGES 20/9/10 10:00 Page 27
27
VBX
MANUAL BLEED VALVE
BURNER ASSEMBLY
IGNITION ELECTRODE
IGNITION MODULE
CONDENSATE DRAIN PIPE
GAS CONTROL VALVE
GAS VALVE LEAD AND PLUG
FAN
CH RETURN THERMISTOR CH FLOW THERMISTOR
FLUE GAS SENSOR
PRIMARY HEAT EXCHANGER
COMBUSTION CHAMBER FRONT COVER
DETECTION ELCTRODE OFFSET PRESSURE TEST POINT CONTROL DISPLAY
MAX CO
THROTTLE
2
ADJUSTMENT USER CONTROL
CONDENSATE TRAP
GAS ISOLATING COCK
CONTROL BOX
28
GAS CONTROL VALVE, FAN & BURNER ASSEMBLY
INSULATION
COMBUSTION CHAMBER
6.5
COMBUSTION CHAMBER
FRONT COVER
BURNER
FAN
& HEAT EXCHANGER
Inspect the inside of the combustion chamber for debris. If necessary, clean the inside of the tubes with a soft brush. Do not brush the insulation at the rear, check the integrity of the combustion chamber insulation panels, if damaged they will require replacement.
GAS VALVE FEED PIPE
GAS VALVE
CONDENSATE DRAIN
6.6
The condensate Drain has a removable cap, Figure 30, which allows the removal of debris that may be caught within it. Place a bowl under the cap to catch the condensate and remove the cap. Any debris inside will be expelled at this point. Replace the cap ensuring a good seal is made. Discard the condensate and debris.
25
SINGLE PAGES 20/9/10 10:00 Page 28
29A SPARK ELECTRODE
29
6mm
TO BURNER
4mm ±0.5
29B DETECTOR ELECTRODE
SEALED WATER SYSTEM
6.7
a) Check the operation of the pressure relief valve as described in
section 5.1 (b).
b) Check the correct operation of the pressure gauge by noting the
reading when cold and check that the pressure increases with temperature. Replace the gauge if readings are suspect.
c) Check that the system is at its original (cold) design pressure. If
necessary, re-pressurise the system as described in section 5.1 (b) and search for and rectify any leaks causing loss of water.
d) In case of heavy pressure fluctuations during the heat and cool down
cycle, check the pre-charge pressure of the expansion vessel. If the air pressure is less than 0.75 bar recharge vessel with an air pump.
RE-ASSEMBLY & RE-COMMISSIONING
6.8
a) Re-assemble all components in reverse order. b) Check that all joints and seals are correctly fitted. c) Turn on the gas and electricity supply and light the appliance, as
described in section 5.2.
d) Re-perform a combustion check, as described in section 6.1. e) Check the operation of the appliance in CH mode. f) Remove the manometer and tighten the inlet pressure test point
sealing screw.
g) Test for gas tightness.
30
CONDENSATE DRAIN
FLOW TUBE
DRAIN SUMP CAP
LOCK NUTS
6mm ±0.5
SUMP ADAPTOR
PIPE RETAINING CLIP
TRAP TUBE
CONDENSATE DRAIN
FINAL CHECKS
6.9
a) Ensure the sealed chamber door is secure with the six fixing screws. b) Re-fit all decorative casing panels. c) Return all appliance and external controls (if fitted) to their original
settings.
26
SINGLE PAGES 20/9/10 10:00 Page 29
7
31
INTERNAL WIRING DIAGRAMS
7.1 FUNCTIONAL FLOW WIRING DIAGRAM
27
SINGLE PAGES 20/9/10 10:00 Page 30
8
8.1
Before looking for a fault condition, check that:
G
The mains electrical supply is turned on.
G
The room or cylinder/tank thermostat (where fitted) are calling for heat.
G
The gas service cock is open.
G
The system is at design pressure.
Before attempting any electrical fault finding, always conduct the preliminary electrical system checks as described in the Instructions for the British Gas Multimeter, or other similar instrument.
On completion of any service or fault finding operation involving making or breaking electrical connections, always check for EARTH CONTINUITY, POLARITY and RESISTANCE TO EARTH.
Detailed procedures for replacing faulty components are described in section 9 (Parts Replacement).
For further information contact: Halstead Glen Dimplex service helpline Tel: 0844 371 1111.
8.2
FASCIA PANEL - Refer to Figure 32.
The LED shows code '3' in a lockout condition. For fault finding refer to the diagnostic chart shown below.
FAULT FINDING
GENERAL
DIAGNOSTIC LED INDICATORS
CENTRAL HEATING FAULT FINDING
8.4
Upon a demand for Central Heating, (closure of the time switch and room thermostat, where fitted), the controls should carry out a set of start up checks, followed by an ignition sequence. Refer to Section 5.2.
If the control has powered up correctly but does not respond to a CH demand. Remove plug cover and check voltage between L3 (orange) and N (blue). If 0 V ac, check external programmer / room thermostat. If 230 V ac, check control for lockout or blocking codes, (refer to section 8.3), check operation of the external pump.
Note: Whenever a CH demand is removed, an anti cycle mode is initiated which prevents the appliance from firing in CH mode for 5 minutes. Ensure that the control is not in this mode by removing power from the control and restoring it after a delay of 10 seconds.
If the Switch Live input is OK and no lockout or blocking code exists and the control is not in anti– cycle mode, then replace PCB.
FAULT FINDING CODES
8.3
In the event of the appliance failing to light, refer to the Diagnostics Chart.
32
FASCIA PANEL
7 SEGMENT DIGITAL DISPLAY
‘BURNER LIT’ INDICATOR DOT
CH CONTROL KNOB
28
SINGLE PAGES 20/9/10 10:00 Page 31
RESET LOCK-OUT CODES
LED CODE FAULT/EFFECT REASON ACTION
1
Overheated appliance Water temperature greater than 105 °C
Water flow failure or Differential check faulty/
2
Flame for a short period only
No gas or Lockout flame Low gas pressure.
3
signal/No flame, Lockout No flame signal on ignition, after 5 attempts or loss of signal during ignition
Flue gas sensor/ Flue gas temperature greater than 95 °C
4
No flame
Sensor temperature differential incorrect
G Check no air is in heat exchanger/CH system G Check external pump operation G Check PCB/X1C connector G Check flow thermistor
G Check water pressure G Check external pump/CH system blockage G Check no air is in heat exchanger/CH system G Check flow, and return sensors G Check wires to sensors not crossed
G Check gas supply G Check gas service cock G Check gas valve and lead G Check detection electrode lead G Check PCB/X2A & X2B connectors G Check spark generator/spark electrode G Check mains earth lead continuity
G Check flue sensor G Check flue system G Check no air is in heat exchanger/CH system G Check pump G Check PCB/PCB connectors
BLOCKING CODES
5
Defective sensor/No flame Defective flow, return or flue sensor
Defective gas valve/ Flame continues after
6
demand ends
7
Defective fan/No flame Missing or Erroneous RPM signal
A
PCB error/No flame Internal error G Check PCB
Activate BCC/No flame New BCC
Safety system failure/
C
No flame G Check BCC is initialised
E
BCC error/No flame Incorrect /missing BCC G Reseat or replace BCC No flame No demand/Faulty connector G Check PCB/X1A connector
Differential check faulty/
O
Flame for 15 seconds
Error in power supply/
P
No flame G Check PCB connectors
No light indication Defective power supply
NOTE: RPM SIGNAL - FAN SPEED SIGNAL IN REVOLUTIONS PER MINUTE
BCC - BOILER CHIP CARD (A SMALL MICROCHIP THAT PUSH FITS ONTO THE CONTROL PCB AND ALTERS OPERATING PARAMETERS) (ONLY FITTED TO CERTAIN MODELS)
FAULT CODES 1-4 CAN BE RESET BY FOLLOWING THE PROCEDURE IN SECTION 5.4. HOWEVER, IF ANY OTHER FAULT CODE IS SHOWING PLEASE CONTACT YOUR INSTALLER OR THE HALSTEAD GLEN DIMPLEX SERVICE HELPLINE: 0844 371 1111.
5 sec flame signal after burner is switched off
Failure of internal self checking system
Water flow rate too low
Low mains voltage
G Check flow, return and flue sensors G Check wiring to sensors G Check PCB/X6 & X8 connectors
G Check gas valve and lead G Check PCB
G Check fan G Check mains fan lead & connector G Check low voltage fan lead & connector G Check PCB/X3 connector
G Turn CH control knob to reset twice
to activate
G Check PCB
G Check water pressure G Check external pump/CH system blockage G Check no air is in heat exchanger/CH system G Check flow, and return sensors G Check wires to sensors not crossed
G Check mains voltage
G Check power supply G Check PCB/X1B connector G Check PCB fuse
29
SINGLE PAGES 20/9/10 10:00 Page 32
9
Before commencing any service operation, ISOLATE the mains electrical supply and TURN OFF the gas supply at the main service cock.
Replacement of most parts first requires the removal of the sealed chamber front panels; refer to section 6.2.
There may be some slight water spillage; so electrical components should be protected.
It is the law that any service work must be carried out by a registered person.
9.1
Refer to Figure 33 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Unscrew the two screws holding the electrode, remove electrode,
and used gasket.
d) Fit the new electrode, and new gasket.
33
REPLACEMENT OF PARTS
IGNITION & DETECTION ELECTRODES
IGNITION & DETECTION ELECTRODES
ELECTRODE
PLUG
SCREW
ELECTRODE (IGNITION)
e) Check that electrode is aligned as detailed in Figures 29(a) or 29(b). f) Re-assemble in reverse order. Ensure that all joints and seals are
correctly re-fitted.
IGNITOR UNIT & IGNITION LEADS
9.2
Refer to Figure 34 a) Ensure supply voltage is isolated. b) Remove the plug and earth lead from the ignition electrode. c) Remove the electrical supply leads. d) Unscrew the two screws holding the ignitor unit, remove ignitor
unit.
e) Fit the new ignitor unit. g) Re-assemble in reverse order; ensure that the ignitor unit is
orientated as shown in Figure 34, and that the brown electric supply lead is fitted to position 1 on the igniter unit.
h) Ensure that all joints and seals are correctly re-fitted.
ELECTRODE (DETECTION)
34
IGNITOR UNIT AND IGNITION LEADS
SCREW
IGNITION MODULE
GASKET
IGNITION LEAD
EARTH LEAD
IGNITION ELECTRODE
30
SCREW
SINGLE PAGES 20/9/10 10:00 Page 33
GAS CONTROL VALVE
9.3
INCLUDING AIR INLET COWL
Refer to Figures 35, 36 & 37 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Unscrew four screws holding the gas feed pipe, and remove gas feed
pipe, refer to Figure 35.
d) Unscrew three torx screws (T-20), and remove gas control valve,
refer to Figure 36.
e) Unclip the top section of the black plastic air inlet cowl from the fan
assembly, and remove white plastic insert, clean or replace as necessary, refer to Figure 37.
f) Refit or replace the top section of the black plastic air inlet cowl,
ensuring that it is clipped into place and that the holes in the white plastic insert are aligned with the fixing holes.
g) Attach and secure the gas feed pipe to the replacement gas valve,
using a new gasket.
h) Attach and secure the replacement gas control valve to the fan
assembly.
i) Re-assemble in reverse order; ensure that all joints and seals are
correctly re-fitted.
Note: The gas control valve is factory set and sealed and is not adjustable. If the gas control valve is changed, then when the appliance is running, the flue gas CO and compared to the values stated in Performance Data, section 2.2. If the measured value does not correspond to the Performance Data, then follow section 9.3.1 below or contact: Halstead Glen Dimplex service helpline Tel: 0844 371 1111.
should be measured, refer to section 6.1,
2
GAS FEED PIPE
35
GAS CONTROL VALVE
36
4 SCREWS
9.3.1
If a new gas valve is fitted or the existing gas valve is not within the quoted CO values (see Combustion set-up table on the following page).
GAS VALVE REPLACEMENT INSTRUCTIONS
The Eden VBX 18 and 30 are category II
The appliances are supplied for use on Natural Gas (G20) at a supply pressure of 20 mbar or Propane (G31) at a supply pressure of 37 mbar but can be converted from NG to Propane or vice versa, using specific conversion kits. They are certified to comply with the requirements of EN 483 for use in GB and IE only.
!
a) The combustion values at minimum gas rate and maximum gas rate
b) Do not attempt to adjust the gas valve unless you have a suitable
COMBUSTION CHECK SET-UP
values it must be adjusted to operate within the quoted CO
2
appliances.
2H3P
It is the law that all gas appliances are installed and maintained by a competent person such as a Corgi registered installer, in accordance with the rules in force. It is in your own interest, and that of safety, to ensure that the law is complied with. Failure to do so could lead to prosecution.
The following instructions are intended for guidance and in no way override any Statutory Requirements.
must be checked using a suitably calibrated Flue Gas analyser. Compliance with BS7967-2, BS7967-3 and BS7967-4 is required.
Flue Gas analyser that is checked and within calibration. Compliance with BS7967-2, BS7967-3 and BS7967-4 is required.
2
37
3 TORX
SCREWS
AIR INLET COWL
SWIRL PLATE
AIR INLET COWL TOP
AIR INLET COWL BOTTOM
31
SINGLE PAGES 20/9/10 10:01 Page 34
RE-COMMISSIONING
Before commissioning the appliance, the whole gas installation including the meter must be purged and
!
IMPORTANT: Open all doors and windows; extinguish naked flames
a) Before switching the appliance ON ensure that the Throttle
FULLY wind out the throttle adjuster screw by rotating it counter
Using the relevant end (Nat Gas or LPG as shown in fig.38) of the
38
USE THIS END FOR NAT GAS USE THIS END FOR LPG
39
tested for gas tightness.
and do not smoke whilst purging the gas installation pipe work.
Adjuster screw (Fig. 39) is adjusted to the correct dimension as follows:-
clockwise using a conventional flat bladed screw driver.
tool provided, rotate the throttle adjuster screw clockwise until the tool bottoms out on the body of the gas valve. The dimension from the valve body to the top of the throttle adjuster screw head should then correspond with ‘Dimension X’ shown in the Combustion set­up table below.
THROTTLE ADJUSTMENT TOOL
MAX. THROTTLE ADJUSTER
Switch the appliance on and ensure that the clock and room thermostat (if fitted) are calling for heat and that all radiators are open.
c) To set the boiler into Service Mode at Minimum rate:-
Set the control knob clockwise until it stops in approximately the 5 o’clock position. Note:- the knob will turn past the horizontal maximum temperature mark. The boiler is now in ‘ with the fan speed at Minimum rate and the digital display will show a flashing ‘
Check the Minimum rate combustion readings are within the required values shown in section 2.3.
d) For service mode at Maximum rate first set the boiler to minimum
rate (see ‘c’ above) :-
Turn the CH control knob back to normal operation mode and within 3 seconds back to ‘
Maximum rate.
e. Check the Maximum
required values shown in section 2.3.
If the combustion readings are outside the values shown in section
2.3 then adjustment of the gas valve is required (See Section 6).
ADJUSTMENT OF GAS VALVE Refer to section 2.3 for the Carbon Dioxide (CO
Maximum Gas Rate.
Set the boiler into Service mode at Maximum rate (see sections ‘c’ & ‘d’ above).
Adjust the CO
39. NOTE: Only turn the throttle in small steps of no more than 1/8th of
a turn and wait for 1 minute after each adjustment for the combustion reading to stabilise.
Anti-clockwise to increase CO Clockwise to decrease CO
After setting the Carbon Dioxide (CO2) in accordance with section
2.3 put the boiler into Service mode at Minimum rate (See sections ‘c’ above)
Check the Minimum rate combustion readings are within the required values shown in section 2.3.
Once all adjustments are complete seal the throttle adjustment screw and ensure the sampling cap is replaced on the flue sample point.
COMPLETION
H
Service mode
by turning the Max Throttle Adjuster as shown in fig.
2
’. The fan speed will now increase to
rate combustion readings are within the
2
2
Service mode
) set points at
2
Combustion Set up table
Dimension ‘X’ (measured from valve body to top of screw) (nominal)
Applies to all models
b) Combustion checks
The CO (Carbon Monoxide) & CO values quoted in Section 2.3. Combustion checks must be carried out at Minimum and Maximum Gas rate.
A suitable, calibrated flue gas analyser is required. The appliance incorporates a flue sampling point on the flue socket. The cap of the sampling point should be removed and the sample tube inserted into
32
the middle of the inner flue pipe.
Nat Gas Propane
4.5mm 3.0mm
(Carbon Dioxide) must be within the
2
If CO2(Carbon Dioxide) and CO (Carbon Monoxide) are not within the range stated in Section 2.3 please call Halstead Glen Dimplex service helpline for additional information about adjustment of the gas valve. Tel: 0844 371 1111.
Finally, set the heating and hot water controls to the user’s requirements. Where fitted ensure that the clock override switch is in the timed position and check that the time clock is set at the desired time periods. Set the room thermostat and tank/cylinder thermostat, (if fitted) to the required setting(s)
If the gas control valve is changed, then it is imperative that it is commisioned as per the instructions provided with the new gas valve. The flue gas CO the values quoted in section 2.3 of this manual. If this is not the case then contact: Halstead Glen Dimplex service helpline Tel: 0844 371 1111. Always seal the gas valve adjustment screw withpaint after adjustment.
must be within
2
SINGLE PAGES 20/9/10 10:01 Page 35
FAN
9.4
Refer to Figures 37, 40 and 41. a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Remove the gas control valve; refer to section 9.3. d) Unscrew the three screws holding the gas valve mounting plate,
remove plate; refer to Figures 36 and 40.
e) Unscrew the four screws holding the fan to the burner manifold, and
remove fan; refer to Figure 41.
f) Attach and secure the replacement fan, replace the gasket. g) Re-assemble in reverse order; ensure that all joints and seals are
correctly re-fitted.
GAS VALVE MOUNTING PLATE
40
GAS VALVE MOUNTING PLATE
MANIFOLD MOUNTING SCREWS
42
WITHDRAWING BURNER
43
3 TORX SCREWS
3 SCREWS
FAN MOUNTING SCREWS
41
4 SCREWS
GASKET
BURNER
9.5
Refer to Figures 42, 43 & 44 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Unscrew the three torx screws, (T-25), holding the manifold to the
combustion chamber front cover, and remove the manifold; refer to Figure 42.
44
LOCATING TAB
BURNER GASKET
33
SINGLE PAGES 20/9/10 10:01 Page 36
d) Remove the gasket, and withdraw the burner; refer to Figure 43. e) Fit replacement burner, taking care not to damage the insulation,
and ensure burner is correctly located by lining up the locating tab.
f) Fit new gasket; refer to Figure 44. g) Re-assemble in reverse order; ensure that all joints and seals are
correctly re-fitted.
COMBUSTION CHAMBER
9.6
FRONT INSULATION
The design of the appliance is such that the combustion chamber insulation should not require replacement unless mechanically damaged. It is recommended that to prevent dust, the insulation be dampened prior to removal, and that a protective mask is worn when changing or handling the insulation material.
Refer to Figure 45 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Remove the electrodes; refer to section 9.1. d) Remove the burner: refer to section 9.5. e) Replace the combustion chamber front insulation. f) Re-assemble the burner and electrodes, using new gaskets. g) Check the position of the electrodes: refer to section 6.4. h) Re-assemble in reverse order; ensure that all joints and seals are
correctly re-fitted.
COMBUSTION CHAMBER FRONT INSULATION
45
FRONT
INSULATION
INNER
SEAL
OUTER
SEAL
COMBUSTION CHAMBER REAR INSULATION
46
SCREW
WASHER
REAR
INSULATION
HEAT EXCHANGER
9.8
Refer to Figures 14 & 47 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Disconnect the electrical leads to the flue sensor, flow sensor and
return sensor.
d) Drain down the appliance. e) Disconnect the flue system from the appliance, 4 screws, and lift up
to disengage the flue from the flue hood; refer to Figure 14.
f) Remove the retaining clip from the heat exchanger flow outlet; refer
to Figure 47.
g) Gently pull up (or down, depending on installation) to disengage the
flow pipe from the heat exchanger.
h) Remove the retaining clip from the heat exchanger return inlet. i) Rotate the return pipe clockwise and gently pull down to disengage
the return pipe from the heat exchanger.
It may be necessary to cut both flow and return pipes to disengage them from the heat exchanger.
COMBUSTION CHAMBER
9.7
REAR INSULATION
Refer to Figure 46 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Use an Allen key to undo the central screw holding the rear
insulation in place.
d) Remove old insulation and fit replacement, ensuring locating
washer is in front.
e) Re-assemble in reverse order; ensure that all joints and seals are
34
correctly re-fitted.
j) Disconnect the condensate drainpipe from the condensate drainpipe
sump adaptor; refer to section 9.12.
k) Unscrew the three nuts holding the heat exchanger to the back
panel; refer to Figure 47.
l) Remove the heat exchanger. m) Disconnect the condensate drainpipe sump adaptor from the heat
exchanger.
n) Remove the flue hood from the heat exchanger, two screws, and fit
the flue hood onto the new heat exchanger, Check integrity of the flue hood seals and replace as necessary. Remove the manual air vent and vent tube from the heat exchanger and fit onto to new heat exchanger; refer to Figure 47.
o) Fit the condensate drainpipe sump adaptor to the heat exchanger
and flue hood.
p) Re-assemble in reverse order; check integrity of the flow and return
pipe 'O' rings and fibre washers and replace as necessary. Ensure that all joints and seals are correctly re-fitted.
SINGLE PAGES 20/9/10 10:01 Page 37
q) Open the isolating cocks and vent air from the system using the
manual air vent. Re-pressurise the system as necessary and check for water leaks.
Note: It is likely that the heat exchanger will still contain water.
HEAT EXCHANGER
47
MANUAL AIR VENT FLUE SENSOR
RETAINING CLIP
FIXING
POINTS
FLUE HOOD
9.9
Refer to Figures 48 a) Ensure supply voltage is isolated, and that the gas supply is isolated. b) Remove the gas control valve, fan & burner assembly; refer to
section 6.2.
c) Remove the heat exchanger: refer to section 9.8. d) Disconnect the condensate drainpipe sump adaptor from the heat
exchanger; refer to section 9.12.
e) Remove the existing flue hood from the heat exchanger, two screws,
and fit the replacement flue hood onto the heat exchanger; use new flue hood seals; refer to Figure 48.
f) Fit the condensate drainpipe sump adaptor to the heat exchanger
and flue hood.
g) Unscrew the flue sensor from the existing flue hood and fit onto the
new flue hood; refer to section 9.16.
h) Re-assemble in reverse order; check integrity of the flow and return
pipe 'O' rings and fibre washers and replace as necessary. Ensure that all joints and seals are correctly re-fitted.
i) Open the isolating cocks and vent air from the system using the
manual air vent. Re-pressurise the system as necessary and check for water leaks.
FLUE HOOD
48
FLUE SEAL
FLUE HOOD GASKET
FIXING POINTS
CONDENSATE DRAIN
9.10
Refer to Figure 49 a) Ensure supply voltage is isolated. b) Disconnect the electrical lead from the sensor to be changed. c) Unclip the sensor from the pipe and remove. d) Clip the replacement sensor onto the pipe and position as shown in
e) Reconnect the electrical lead.
WATER TEMPERATURE SENSORS
Figure 49.
49
FLOW SENSOR
TEMPERATURE SENSOR POSITION WHEN
USING STANDARD TOP OUTLET PIPEWORK
RETURN SENSOR
FLOW SENSOR
TEMPERATURE SENSOR POSITION WHEN
USING OPTIONAL BOTTOM OUTLET PIPEWORK
35
SINGLE PAGES 20/9/10 10:01 Page 38
plug).
FLUE SENSOR
FLUE SENSOR
FLUE SENSOR
9.11
Refer to Figure 50 a) Ensure supply voltage is isolated. b) Disconnect the electrical lead from the flue sensor. c) Unscrew the flue sensor and remove from the flue hood. d) Fit the replacement flue sensor and reconnect the electrical lead (blue
50
9.13
Note:- When replacing the control PCB it is important that the
instructions supplied with the new PCB are followed. Do not use any old BCC cards.
The following is only a guide. Refer to Figures 22, 27 & 30 a) Ensure supply voltage is isolated. b) Unclip the user interface from its housing (see figure 22). c) Lower the controls front. d) Unplug the electrical leads from the PCB. Refer to section 7. e) Remove the PCB plastic cover. f) Unclip the PCB and withdraw. g) Fit the new PCB and BCC if required. h) Re-assemble in reverse order. i) If the boiler requires resetting turn the CH Temperature Control
CONTROL PCB
knob anti-clockwise to 'STANDBY' position and then back to 'ON' within two seconds. Refer to section 5.4.
After fitting a new PCB always re-check the combustion of the boiler to ensure it is within the values quoted in section 2.3.
If the combustion figures are not within the values quoted then contact Halstead Glen Dimplex service helpline Tel: 0844 371 1111.
9.12
Refer to Figure 30 a) Ensure supply voltage is isolated. b) Open the drain sump cap, while holding a receptacle beneath to
c) Disconnect the condensate drainpipe from the appliance. d) Undo the two locknuts holding the system in place. e) Detach the condensate drainpipe sump adaptor, by gently pulling
f) Remove the condensate drain system, clean or replace as
g) Re-assemble in reverse order; ensure that all joints and seals are
CONDENSATE DRAIN SYSTEM
capture any condensate.
down.
necessary.
correctly re-fitted.
36
SINGLE PAGES 20/9/10 10:01 Page 39
10
Refer to Figure 51
Key G C Part No. Description No off Makers Pt No. 1 Ignition Electrode 988526
2 Detection Electrode 988527 3 Spark Generator Unit 500665 4 Gas Control Valve 988315 5 Fan Assembly 601016 6a Burner VBX 30 700602 6b Burner VBX 18 700600 7a Heat Exchanger (VBX 30) 451033 7b Heat Exchanger (VBX 18) 451034 8 Water Temperature Sensor 500661 9 Flue Sensor 500660 10 Manual Bleed Valve 300730 11 Control PCB 988491 12 User Interface 988492
SHORT PARTS LIST
Heat Exchanger Seal Kit 988489
37
SINGLE PAGES 20/9/10 10:01 Page 40
51
1
5
9
2
6
10
3
7
11
4
8
12
38
SINGLE PAGES 20/9/10 10:01 Page 41
SINGLE PAGES 20/9/10 10:01 Page 42
SINGLE PAGES 20/9/10 10:01 Page 44
Glen Dimplex Boilers, Stoney Lane, Prescot Merseyside L35 2XW.
For telephone enquiries call: 0844 371 1111.
Website: www.glendimplexboilers.com
Part of the Glen Dimplex Group
Glen Dimplex Boilers is continuously improving its products and may therefore change specifications without prior notice.
The statutory rights of the consumer are not affected.
07/10 751053 Issue 4
SALES AND SERVICE HELPLINE: 0844 371 1111
Loading...