Tel: 01787 272800. Sales Direct Line: 01787 475557. Fax: 01787 474588. Service Helpline: 01926 834834.
e-mail: sales@halsteadboilers.co.uk or service@halsteadboilers.co.uk Website: www.halsteadboilers.co.uk
Important Information
TESTING AND CERTIFICATION
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler, without
permission, in writing, from Halstead Boilers Ltd.
Any alteration not approved by Halstead Boilers Ltd., could invalidate the certification, boiler warranty and may also infringe the
current issue of the Statutory Requirements, see Section 1.3.
CE MARK
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is deemed
to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous
fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0086.
Product/production certified by: Notified body 0086.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed
for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
INFORMATION FOR THE INSTALLER AND SERVICE ENGINEER.
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to
health.
Ceramic fibre/Insulation Pads, Glassyarn
These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to
irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal
good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation of the eyes or severe
irritation to the skin seek medical attention.
SPARE PARTS
REMEMBER, when replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and
performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Halstead
Boilers Ltd.
MANUAL HANDLING GUIDANCE
During the appliance installation and the replacement of the heat exchanger it will be necessary to employ caution and assistance
whilst lifting as the appliance or component exceeds the recommended weight for a one man lift.
In certain situations it may be required to use a mechanical handling aid.
Take care to avoid trip hazards, slippery or wet surfaces.
CONTENTS DESCRIPTION SECTION PAGE No.
INSTRUCTIONS
FOR USE
INSTALLATION
INSTRUCTIONS
Introduction3
Lighting the Boiler4
General Data15
Water Systems27
Flue & Ventilation39
Installation410
Electrical Wiring517
Commissioning618
Instructions to User720
Please read these instructions and follow them carefully for the
safe and economical use of your boiler.
The Halstead Buckingham 4 B FF series are balanced fanned
flue boilers. They provide heating and if required, an indirect
domestic hot water supply.
The boiler is automatic in operation, having only one user
control, the boiler temperature control.
Gas Safety (Installation and Use) Regulations
In your own interests and that of safety, it is the law that ALL gas
appliances are installed by a competent person in accordance
with the current issue of the above regulations.
WARNINGS
Gas Leak or Fault
If a gas leak fault exists or is suspected the boiler must be
turned off, including the electrical supply and must not be
used until the fault has been put right. Advice/help should
be obtained from the local gas undertaking or your installation/
servicing company.
Clearances
Make sure that nothing obstructs the ventilation grills or
clearances.
Minimum clearances must be left around the boiler as
shown in diagrams 1.4, 1.5 & 1.6.
Sheet Metal Parts
This boiler contains metal parts (components) and care
should be taken when handling and cleaning, with particular
regard to edges.
Cleaning
Keep the casing clean by wiping it occasionally with a damp
soapy cloth and dry with a polishing cloth.
Do not use abrasive cleaners.
Boilers Installed in a Compartment
If the boiler is fitted in a compartment, cupboard etc., do not
obstruct the purpose built compartment vents or the grill on the
boiler.
Do not use the compartment for storage purposes.
Maintenance
To ensure the continued efficient and safe operation of the boiler
it is recommended that it is checked and serviced as necessary
at regular intervals. The frequency of servicing will depend upon
the particular installation conditions and usage, but in general
once a year should be enough.
It is the law that servicing must be carried out by a competent
person.
If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current issue
of the Gas Safety (Installation and Use) Regulations, Section
35.
To obtain service please call your installer or Halstead Boilers
Ltd. using the telephone number given on the inside of the front
panel.
Please be advised that the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and
have a registration number. Both should be recorded in your
boiler Logbook. You can check your installer is CORGI registered
by calling CORGI direct on :- 01256 372300.
Boiler Electrical Supply
THIS BOILER MUST BE EARTHED.
The boiler must only be connected to a 230V~50Hz supply
protected by a 3A fuse, maximum.
All wiring must be in accordance with the current issue of
BS7671.
Heat resistant flexible cable having a conductor size of 0.75mm
to the current issue of BS6500 Table 16 must be used.
To Connect an Electrical Plug
The standard colours of three core flexible cable are,
Brown - live, Blue - neutral, Green and Yellow - earth.
As the markings on your plug may not correspond with these
colours, continue as follows:
The Blue cable must be connected to the terminal marked “N”
or “Black”.
The Brown cable must be connected to the terminal marked “L”
or “Red”.
The Green and yellow cable must be connected to the terminal
marked “E” or “Green” or the earth symbol
.
2
,
Protection Against Freezing
If the boiler is to be out of use for any period of time during severe
weather conditions we recommend the whole system including
the boiler, be drained off to avoid the risk of freezing up. If an
immersion heater is fitted to the hot water cylinder make sure it
is switched off.
3
221992D
Instructions for Use
To Turn the Appliance On
Turn the electrical supply on to the boiler and check that all
remote controls are calling for heat.
Turn the boiler temperature control clockwise to any position
between “0” and "Max", see diagram 1.
"Max" is approximately 82°C (180°F).
The boiler lighting operation is now automatic as follows:
The fan operates and after a short period of time, the spark
ignition operates, the solenoid opens, then the burner will light
shown by the burner ON neon (green) on the control panel
lighting up.
The burner will remain alight until switched off by the control
thermostat or any remote control.
Note: If the boiler is turned OFF at the boiler temperature
control, wait at least 30 seconds before switching on again.
When the boiler switches off, the burner will go out.
The automatic lighting sequence will operate again when heat
is required.
It should be noted that this is a fanned flue appliance and fan
operation may be heard.
If the reset neon lights, turn the boiler temperature control to "0"
(off), wait 30 seconds, then repeat the lighting instructions.
BOILER
TEMPERATURE
CONTROL
10191
To Turn the Appliance Off
For short periods, turn the boiler temperature control fully anticlockwise to “0” (off).
To relight, turn the boiler temperature control to any position
between “0” and “Max”.
For longer periods, turn the boiler temperature control fully anticlockwise to “0” (off) and switch off the electrical supply to the
boiler.
To relight follow the lighting sequence given above.
"OFF"
POSITION
RESET
NEON
"BURNER ON"
NEON
Diagram 1
221992D
4
1 General Data
GAS CONNECTION
1
Rc
1
/
(
/
2
in. B.S.P.T.)
2
WATER CONNECTIONS
WATER CONNECTIONS Rc1 reduced
with DISTRIBUTOR TUBE to
3
3
/
Rc
/
(
4
4
Rc1 (1in. B.S.P.T.)
A
L
D
C
B
GENERAL DIMENSIONS - given in millimetres
in. B.S.P.T.) (pumped return)
F
K
M
G
H
E
NOTE: The boiler casing can be
set at two heights,
MAX. and MIN.
9921
J
Diagram 1.1
A B C D E F G H J K L M
387 700 558 294 364 555 442 3 Max 900/ 300 194 32
Important Notice
This boiler is for use only on G20 gas.
The boiler is delivered in one pack and the flue pack is supplied
separately.
Wherever possible, all materials, appliances and components to
be used shall comply with the requirements of applicable British
Standards.
Where no British Standard exists, materials and equipment
should be fit for their purpose and of suitable quality and
workmanship.
Refer to Manual Handling Operations, 1992 Regulations.
Sheet Metal Parts
WARNING. When installing or servicing this boiler, care should
be taken to avoid any possibility of personal injury when handling
the edges of sheet metal parts.
1.1 Technical Data
See diagrams 1.1 & 1.2.
All dimensions are given in millimetres (except as noted)
Approximate weight of complete boiler : 131.5kg (290lb)
Water content :5.76 litre (1.27gallons)
Gas connection :Rc
Water connection :Rc1 (1in BSPT)
Electrical supply :230V~50Hz, fused 3A
Burner :Aeromatic
1
/2 (1/2in BSPT)
.
Min 860
The Seasonal Efficiency Domestic Boilers UK (SEDBUK)
is 'D' 78.6%.
The value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data
from which it has been calculated have been certified by B.S.I.
1.2 Range Rating
See diagram 1.2.
10182
Diagram 1.2
5
221992D
1 General Data
1.3 Statutory Requirements
The installation of this appliance must be carried out by a
competent person and must be in accordance with the relevant
requirements of the current issue of:
Manufacturer’s instructions supplied.
The Gas Safety (Installation and Use) Regulations, Building
Regulations, Local Water Company Bye-laws, The Building
Standards (Scotland) Regulations, (applicable in Scotland),
Health and Safety at Work Act, Control of Substances Hazardous
to Health, Electricity at Work Regulations and any applicable
local regulations.
Detailed recommendations are contained in the current issue of
the following British Standards and Codes of Practice,
BS6891, BS5440 Part 1 and 2, BS6798, BS5449, BS5546,
BS6700, BS7478, BS7593, BS7671.
Manufacturer’s instructions must not be taken as overriding
statutory requirements.
1.4 B.S.I Certification
This boiler is certificated by B.S.I., for safety and performance.
It is, therefore, important that no alteration is made to the boiler
unless agreed, in writing, by Halstead Boilers Ltd.
Any alteration not approved by Halstead Boilers Ltd., could
invalidate the B.S.I. certification, boiler warranty and could
infringe the current issue of the Statutory Requirements.
To
floor
level
MAX.900
MIN. 860
MAX.
MIN.
FLOOR LEVEL
BOILER CASING HEIGHT(S)
WORKTOP
9922
BOILER
CASING
ALTERNATIVE
HEIGHT
POSITIONS
Diagram 1.3
9923
407 MIN.
1.5 Gas Supply
The gas installation should be fitted in accordance with the
current issue of BS6891.
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg) at
the boiler.
On completion test the gas installation using the pressure drop
method and suitable leak detection fluid, purge in accordance
with the current issue of BS6891.
1.6 Electrical
WARNING. This boiler must be earthed.
The electrical installation must be carried out by a competent
person. All external components shall be of the approved type
and shall be connected in accordance with the current issue of
BS7671 and any local regulations which apply.
Connection of the boiler and any system controls to the mains
supply through an unswitched shuttered socket outlet and 3A
fused 3 pin plug, both to the current issue of BS1363.
Alternatively, a 3A fused double pole isolating switch may be
used, having a minimum double pole contact separation of
3mm, serving only the boiler and system controls.
Heat resistant cable of at least 0.75mm
current issue of BS6500 Table 16, must be used for all
connections within the boiler casing, to the control box, pump
etc.
2
(24/0.20mm), to the
10
10
5
407 MIN.
BOILER
BOILER
CUPBOARDS
MINIMUM CLEARANCES
LEVEL WITH WORKTOP
Diagram 1.4
WORKTOP OR
FIXTURE
10
10 10
10124
221992D
CUPBOARD
MINIMUM CLEARANCES
UNDER WORKTOP, FIXTURES
6
CUPBOARD
Diagram 1.5
1 General Data
1.7 Boiler Location
This boiler is not suitable for outside installation.
The boiler casing can be fitted at two heights. Refer to
diagram 1.3.
The boiler is assembled at the factory with the control box and
heat shield fitted in the lower position.
The boiler must stand on a level floor, conforming with local
authority requirements and building regulations.
The base temperature is within the requirements of the current
issue of BS5258. The boiler may stand on a wooden floor but
a metal base plate is required to protect plastic tiles and similar
floor coverings.
Suitable installation clearance needs to be available at the
sides of the boiler to facilitate direct connection of pipework and
making good around the flue assembly. The actual clearance
required will vary with site conditions.
When the boiler is to be installed level with work surfaces and
the like, minimum clearances should be provided as shown in
diagram 1.4. Work tops which overhang the cupboard sides,
almost in contact with the casing top, require a larger minimum
air gap. Flush sided fixtures require the same overall minimum
space but can have a reduced air gap on one side.
Boilers to be installed under work tops or fixtures, should be
positioned to provide minimum clearances as shown in diagram
1.5. To facilitate minimum clearances it may be necessary to
modify kitchen units and fixtures.
A front access clearance for servicing of 700mm, should be
provided.
The boiler can be installed within a cupboard, refer to minimum
ventilation and clearances as shown in diagram 1.7.
If the boiler is to be installed in a cupboard or compartment,
make sure that nothing will obstruct the openings/vents in the
compartment.
A compartment used to enclose the boiler must be designed
and constructed specifically for this purpose. An existing
cupboard or compartment modified for the purpose may be
used. Details of essential features of cupboard or compartment
design are given in the current issue of BS6798.
The boiler may be installed in any room, although particular
attention is drawn to the requirements of BS7671 with respect
to the installation of a boiler in a room containing a bath or
shower. Any electrical switch should be so positioned that it
cannot be touched by a person using the bath or shower. The
electrical provisions of the Building Standards (Scotland)
Regulations apply to such installations in Scotland.
Where the installation of the boiler will be in an unusual location,
special procedures are necessary the current issue of BS6798
gives detailed guidance on this aspect.
1.8 Heating System Controls
The heating system should have installed: a programmer and
room thermostat controlling the boiler.
Thermostatic radiator valves may be installed, however they
must not be fitted in a room where the room thermostat is
located.
Note: For further information, see the current issue of the
Building Regulations, approved document L1, and the
references:
1) GIL 59, 2000: Central heating system specification (CheSS)
and
2) GPG 302, 2001: Controls for domestic central heating
system and hot water. BRECSU.
272cm2 FREE AREA
10mm
10mm
FOR VENTILATION
10mm
DOOR
CUPBOARDCUPBOARD
272cm2 FREE AREA
FOR VENTILATION
IMPORTANT
A CLEARANCE OF 10mm IS REQUIRED BETWEEN THE
FRONT OF THE APPLIANCE AND THE FITTED DOOR.
THE VENTILATION SLOTS ON THE FRONT
OF THE APPLIANCE MUST BE KEPT CLEAR.
THE FREE AREA FOR VENTILATION MUST
NOT BE REDUCED IF A GRILLE IS FITTED.
CUPBOARD MINIMUM
VENTILATION & CLEARANCE
Diagram 1.6
7
221992D
2 Water Systems
2.1 Water Pressure Head
The boiler shall only be connected to a cistern water supply with
a minimum head of 1metre (3ft3in) and a maximum head of
27metres (90ft) which has an open vent in the system.
The working pressure must be within the range 0.1bar to 2.7bar
(1.3 to 39lbftin
The boiler MUST NOT be connected to a sealed water system.
2
).
2.2 Inhibitor
Attention is drawn to the current issue of BS5449 and BS7593
on the use of inhibitors in central heating systems.
If an inhibitor is to be used in the system, contact should be
made with the inhibitor manufacturers so that they can
recommend their most suitable product.
When using in an existing system take special care to drain the
entire system, including the radiators, then thoroughly clean out
before fitting the boiler whether or not adding an inhibitor.
2.3 Gravity Domestic and Pumped Heating
It is recommended that a cylinder thermostat is used to prevent
the stored water temperature becoming unnecessarily high
when the central heating pump is off.
The domestic primary flow and return must be 28mm o.d. The
installation must comply with the current issue of BS5546 and
BS6700, see diagram 2.1.
If the above conditions cannot be met, it is suggested that a fully
pumped system be used.
2.4 Pumped Heating and Hot Water
Where a single flow and return is taken from the boiler, a
minimum static head of 1metre (3ft3in) must be provided
between the water line of the feed tank and the centre of the
waterway, see diagram 2.2.
REFER TO BS 5546
27metres
Max.
BOILER
C
L
DRAIN OFF
COCK
1 metre
MIN.
27metres
MAX.
22mm VENT
15mm COLD FEED
INDIRECT
CYLINDER
(Shown with
recommended
thermostat and valve).
28mm
PUMP
Heating
Circuit
Distributor tube in
pumped return
connection
22mm VENT
15mm
COLD FEED
TO INDIRECT
CYLINDER
PUMP
0869
Diagram 2.1
0870
2.5 Circulation Pump
Normally the pump should be set to give a temperature difference
o
of 11
C (20oF) across the boiler. At the appropriate pumped flow
rate the pressure loss through the boiler can be found from the
graph, diagram 2.3.
Use a pump with integral valves or fit isolating valves as close
to the pump as possible.
2.6. Cylinder
For all systems supplying domestic hot water the cylinder must
be indirect.
2.7 Safety Valve
A safety valve need not be fitted to an open vented system.
2.8 Draining Tap
A draining tap must be provided at the lowest points of the
system which will allow the draining of the entire system,
including the boiler and hot water cylinder.
Draining taps should be to the current issue of BS2879.
2.9 Thermostatic Radiator Valves
If thermostatic radiator valves are fitted care must be taken to
ensure that there is an adequate flow rate through the boiler
when they close, refer to the current issue of BS7478 for
guidance. If fitted to all radiators ensure a bypass is fitted and
adjust to achieve a temperature difference no greater than 20oC
between flow and return with the thermostatic valves closed.
BOILER
C
L
DRAIN OFF
COCK
FULLY PUMPED SYSTEM
(DIAGRAMMATIC)
FLOW RATE (GALLON/MINUTE)
0123456789
2.00
1.75
1.50
1.25
1.00
0.75
0.50
WATER PRESSURE LOSS
(metre HEAD OF WATER)
0.25
0
6
0
FLOW RATE (LITRES/MINUTE)
12 18
Heating
Circuit
Distributor tube in
pumped return
connection
Diagram 2.2
24 30 36 42
Diagram 2.3
1074
70
60
50
40
30
20
WATER PRESSURE LOSS
10
0
(INCHES HEAD OF WATER)
221992D
8
3 Flue and Ventilation
The flue must be installed in accordance with the rules in force
in the countries of destination.
3.1 Terminal Position
The minimum acceptable siting dimensions for the terminal
from obstruction, other terminals and ventilation openings are
shown in diagram 3.1.
The terminal must be exposed to the external air, the position
allowing free passage of air across it at all times.
A
B,C
K
F
G
J
K
E
L
F
UNDER CAR PORT etc.
B,C
G
A
H,I
MINIMUM SITING DIMENSIONS FOR
FANNED FLUE TERMINALS POSITION MM
HORIZONTAL FLUES
A DIRECTLY BELOW, ABOVE OR
HORIZONTALLY TO AN OPENING, AIR BRICK,
OPENING WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING300
B BELOW GUTTER, DRAIN/SOIL PIPE25
C BELOW EAVES25
D BELOW A BALCONY OR CAR PORT25
E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES25
F FROM INTERNAL/EXTERNAL CORNERS
OR TO A BOUNDARY ALONGSIDE THE
TERMINAL25
G ABOVE ADJACENT GROUND OR
BALCONY LEVEL300
H FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL600
IFACING TERMINALS1200
J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING1200
K VERTICAL FROM A TERMINAL1500
L HORIZONTALLY FROM A TERMINAL300
C
D
F
Diagram 3.1
Car ports or similar extensions of a roof only, or a roof and one
wall, require special consideration with respect to any openings,
doors, vents or windows under the roof. Care is required to
protect the roof if it is made of plastic sheeting. If the car port
consists of a roof and two or more walls, seek advice from the
local gas company before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering or
painted soffit an aluminium shield 1500mm long should be fitted
immediately beneath the guttering or eaves. If the terminal is
fitted within 450mm below painted eaves or a painted gutter, an
aluminium shield 750mm long should be fitted immediately
beneath the guttering or eaves.
3.2 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Halstead Boilers Ltd.
3.3 Terminal Guard
A terminal guard is required if persons come into contact with
the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
be central over the terminal.
A suitable guard, reference Type “K3”, can be obtained from:
The boiler is room sealed and does not require the room or
space containing it to have permanent air vents.
3.5 Ventilation for Boilers installed in a
Cupboard
For minimum ventilation and clearances for cupboard installation
refer to section 1.7 and diagram 1.6.
3.6 Compartment Ventilation
Where the boiler is fitted in a compartment, the high and low
level permanent air vents must have effective areas, see
“Compartment Air Vent Table”.
Both the high and level air vents must communicate with the
same room or must both be on the same wall to outside air.
COMPARTMENT AIR VENT TABLE
COMPARTMENT
VENTILATION
REQUIREMENTS
VENTILATION
FROM ROOM
OR SPACE
FROM
OUTSIDE
HIGH LEVELLOW LEVEL
VENT AREAVENT AREA
272cm2 42in2 272cm2 42in
136cm
2
21in2 272cm2 42in
2
2
9
221992D
9867
4 Installation
* INCREASE TO 30mm IF A FLUE COLLAR IS ADDED
*
FLUE & AIR DUCT LENGTH = A + 15 + 3
General Installation Notes
The appliance pack contains :-
Boiler
Fan connector
Casing panels, packed seperately.
Loose items fittings pack, see list in pack.
The flue is supplied seperately.
NOTE: The rear flue option kit Part No. 425861 is available,
which consists of wall cover plates, for replacement Buckingham
balanced flue appliances.
Before installation of the boiler make sure that the location
selected is in accordance with the requirements of Section 1.7.
FLUE
PACKS
REAR STD.
REAR7595510
NOTE :
IF IT IS NECESSARY TO CUT THE DUCTS
TO ACHIEVE THE "FLUE LENGTH" MAKE SURE
THAT THE OVERLAPS ARE AS FOLLOWS :THE OVERLAP FOR AIR DUCT = 25mm
THE OVERLAP FOR FLUE DUCT = 50mm
MINIMUM
WALL
THICKNESS
MINIMUM
FLUE
LENGTH
MAXIMUM
FLUE
LENGTH
Diagram 4.1
4.2 Flue Position and Length
Select the boiler location, with due regard to the flue length and
terminal position, see diagrams 3.1 and 4.1.
For a wall thickness up to 300mm, provided that the optional
wall liner kit is used, the flue can be fully installed from the
inside.
For a wall thickness of over 300mm the external flue hole will
need to be made good from the outside, this also applies if you
use the flue kit without the optional wall liner kit, irrespective of
wall thickness.
387
9868
10051
4.1 Unpacking
The boiler casing panels are packed separately within the main
carton and are designed to enable gas and water connections
to be made before fitting the casing panels.
The casing brackets, flue restrictor, distributor tube and other
loose items, are in the fittings pack.
NOTE:
To make a neat finish to the flue outlet a flue collar kit, part No.
900850, with instructions, is available, see diagram 4.4.
If required an optional wall liner kit, part no. 900862, is available
complete with instructions.
All flue assemblies are designed for internal installation.
Make sure that the ductings do not slope down towards the
boiler.
221992D
115
194
BOILER
OUTLINE
700
FRONT VIEW
Diagram 4.2
10
4 Installation
4.3 Flue Hole Cutting
Mark out the flue centre, see diagram 4.2, then cut a hole for the
flue using, preferably, a 115mm minimum core drill.
4.4 Rear Flue Option Kit - 425861
Fit the wall cover plates as described in the instructions supplied
with the kit.
(if applicable)
4.5 Flue Preparation
Note: If the flue collar kit, see diagram 4.4, is to be used
increase the 15mm projection to 30mm.
Extend the telescopic flue to the required length, making sure
that the minimum overlap is no less than 25mm, and that the flue
terminal projects 15mm minimum beyond wall face, see diagram
4.1.
If it is necessary to cut the flue ensure that the overlap is as
stated in diagram 4.1.
Carefully drill though air duct pilot hole and secure with self
tapping screw provided in fittings pack, see diagram 4.3.
Seal the joint with the tape provided.
Note: Should any one of the flue sections require cutting to
obtain desired flue system length make sure that the overlaps
are as follows:-
The overlap for air duct = 25mm
The overlap for flue duct = 50mm.
Take the terminal restrictor and position the clamping bracket
making sure the clamping bracket nib protrudes in the slot of the
terminal restrictor and secure with locking screw, but do not
tighten, see diagram 4.5.
Engage the terminal restrictor on the flue terminal by hooking it
over the terminal end and engaging the clamping bracket
behind the inner ring of the terminal securing it by tightening the
locking screw, see diagram 4.5.
Fit the self adhesive foam seal provided in the flue pack around
the air duct at the position shown in diagram 4.1.
Make sure that the ductings do not slope down towards the
boiler.
Make good around the flue outside after installation of the boiler.
Important: If the wall liner kit is used, the self adhesive foam seal
included in the wall liner kit must be used in place of the one
supplied with the flue pack, see diagram 4.6 for position of self
adhesive seal.
Push the flue assembly into and through the hole such that it is
within the wall, and does not stick out into the room. Do not push
the flue assembly too far into the hole as it has to be pulled back
into the boiler and secured.
If the boiler is not to be fitted for some time cover the hole in the
wall.
7148
OPTIONAL
FLUE
COLLAR
Diagram 4.4
STANDARD 510mm REAR
FLUE
TERMINAL
CLAMPING
BRACKET
7323
SPIGOT
BAYONET
CONNECTION
GASKET
SCREW
AND TAPE
SCREW (4)
FLUE
Diagram 4.3
9869
11
RESTRICTOR
7332
TERMINAL RESTRICTOR
SHOWN FITTED
LOCKING
SCREW
CLAMPING
BRACKET NIB
Diagram 4.5
221992D
4 Installation
4.6 Water Connections - Gravity Domestic and
Pumped Heating
Fit suitable fittings into the boiler tappings, see diagram 4.7.
Make sure that all pipes are taken backwards and will clear the
casings, see diagram 1.1.
Heating flow: Any one of the four upper connections may be
used.
Domestic flow: Any one of the three remaining upper connections
may be used.
Heating return: The water distributor tube must be fitted into
either of the front lower connections on all installations, see
diagram 4.8. This tube is in the fittings pack.
Domestic return: Any one of the three remaining lower
connections may be used for the gravity domestic hot water
return.
Fit plugs into any unused boiler tappings.
4.7 Water Connections - Fully Pumped
Systems
Fit suitable fittings into the boiler tappings as required, see
diagram 4.9. Make sure that all pipes are taken backwards and
will clear the casings.
It is important that all connections are made as shown in
diagram 4.9.
Fit the water distributor tube into the return connection, see
diagram 4.8. This tube is in the fittings pack.
Fit plugs into any unused boiler tappings.
9859
GRAVITY
DOMESTIC
RETURN TO
ANY OF THE
3 REMAINING
LOWER CONNECTIONS
WATER CONNECTIONS - GRAVITY
DOMESTIC, PUMPED HEATING
UPPER MARKER
must lie between the
two outer NOTCHES
ALTERNATIVE
HEATING OR
DOMESTIC
HOT WATER
FLOW
ALTERNATIVE
HEATING
RETURN
With distributor
tube (not shown)
Diagram 4.7
1076
WITH WALL LINER KIT ONLY
WALL THICKNESSUP TO 300mm
FOAM SEAL
Q
15mm
Q-35mm
WALL THICKNESSOVER 300mm
FOAM SEAL
Q
Diagram 4.6
7102
UPPER
MARKER
DISTRIBUTOR TUBE
ALTERNATIVE
FLOW
POSITIONS
WATER CONNECTIONS FULLY
PUMPED SYSTEMS
DISTRIBUTOR
TUBE
must be in
pumped return
connection
Diagram 4.8
9859
ALTERNATIVE
RETURN
POSITIONS
With distributor
tube (not shown)
Diagram 4.9
221992D
12
4 Installation
4.8 Pipework
When the front tappings are used, it is essential that any
pipework or fittings do not project more than shown in diagram
4.10.
When using a rear tapping with Rc (1in BSP) fitting for 28mm od
pipework, it is recommended that a short nipple and an Rc
thread (BSP) to copper elbow is used. If the pipework is required
to run back to the wall, make sure that it will clear the boiler air
duct and, if working to minimum clearance, does not project too
far from the boiler, see diagram 4.11.
Do not route any pipework, water or gas, across the front of the
combustion chamber cover.
The gas pipework must be along the left hand side of the boiler.
9860
4.9 Casing Brackets
Fit the two upper and two front casing brackets shown in
diagram 4.12, using the No.8 screws provided.
NOTE: The screws will already be fitted.
Push the captive nuts, supplied loose, on to the casing brackets
as shown in diagram 4.12.
PIPEWORK CASING
CLEARANCES
REAR CONNECTION
PIPEWORK (28mm)
Diagram 4.10
FOR MINIMUM
CLEARANCE
Diagram 4.11
9861
UPPER CASING
BRACKET
No.8
SCREW
(4)
CAPTIVE
NUT
CAPTIVE
No.8
SCREW
(4)
FRONT
CASING
NUT
BRACKET
CASING BRACKETS FITTING
9858
Diagram 4.12
13
221992D
4 Installation
4.10 Side In-fill Panel (if required)
A side in-fill panel is supplied with the boiler, which can be fitted
at the rear of the left or right hand side casing but can be
discarded if the water connections are made on both sides of
the boiler or if the boiler is screened by fixtures. The in-fill panel
will usually be fitted on the side where there no pipework
connections.
Insert the push fit plastic location peg, supplied, through the infill panel and side casing holes and secure with the spring clips,
see diagram 4.13.
NOTE
The boiler is assembled at the factory with the control box and
heat shield fitted in the lower casing height position.
SIDE
CASING
(R.H.SHOWN)
SPRING
CLIP
4.11 Side Casings
Fit the side casings by locating their lugs into the appropriate
slot in the boiler plinth, see diagram 4.13, depending on the
required height, there are two options, see section 1.7.
Secure the casing sides to the front and rear upper casing
brackets with self-tapping screws supplied, see diagrams 4.13
and 4.15.
FRONT
CASING
BRACKET
MAX.
MIN.
SIDE
CASING
(R.H.)
LOCATING
SLOTS
No. 8
SCREW
(4)
9863
UPPER VIEW
SIDE
CASING
(R.H. SHOWN)
IN-FILL
PANEL
PLASTIC
PEG
SPRING
CLIP
PLASTIC
PEG
IN-FILL
PANEL
LOWER VIEW
Diagram 4.13
BOILER
PLINTH
SIDE CASINGS FITTING
SCREW
SIDE CASING
(R.H. SHOWN)
Diagram 4.14
UPPER
CASING
BRACKET
Diagram 4.15
221992D
14
4 Installation
4.12 Flue / Boiler Connection
Remove the three self-tapping screws from the lower part of the
control box support bracket, see diagram 4.16.
Undo the wing nut that secures the top of the heat shield and
carefully hinge down control box and heat shield, see diagram
4.16.
Release the two toggle latches that secure the boiler access
door and remove, see diagram 4.17.
Remove the electrical connections from the fan by pulling the
insulation boots only and disconnect the two silicone tubes from
the fan taking note of their positions, see diagram 4.18.
Remove the fan assembly from the flue hood by removing the
securing screw, pull forward and lift up to release the 3 hooked
securing lugs underneath the fan, see diagrams 4.18 & 4.19.
From the flue pack take the flue spigot,the gasket is supplied in
the fittings pack.
Connect the flue spigot and gasket to the rear flue outlet of the
boiler using the self tapping screws provided, see diagram 4.3.
IMPORTANT. With regards to the Manual Handling Operations,
1992 Regulations, the following operation, exceeds the
recommended weight for one man lift.
Place the boiler in position taking care not to damage the casing
panels.
With access to the flue system through the boiler, pull the flue
on to the spigot bayonet connection, twist anti-clockwise to lock
into position.
Take the flue duct extension from the boiler and slide on to the
fan duct until it will go no further, see diagram 4.20.
Fit fan and engage the flue duct extension into the flue duct,
secure fan, replace electrical connection and silicone tubes.
The polarity of the electrical connections is not important.
Make sure that the air pressure tubes are fitted as before, see
diagram 4.18 and that the fan duct engages fully into the flue
duct extension piece.
Replace fan access door, heat shield and control box.
Note: When replacing the fan access door make sure the lip at
the top of door fits into and behind the slotted bracket located at
the top of the boiler.
As there are two casing height options, the control box height
and the heat shield may have to be adjusted to suit your
requirements.
Complete the water connections to the boiler.
Fill, vent and flush the system.
Check for any water leaks and put right.
Make the gas connection to the service cock, at the lower left
hand side of the boiler, see diagram 1.1.
The whole of the gas installation, including the meter, should be
inspected, tested for soundness and purged in accordance with
the current issue of BS6891.
SECURING
LUGS
Diagram 4.19
4.14 Top Casing
Refer to diagram 4.21.
Fit two plastic pegs, one on each side, in the holes on the top
casing. The plastic pegs are a tight fit and are best pushed home
with a flat faced tool.
Secure front of top casing with the screws provided.
FLUE DUCT
EXTENSION PIECE
10149
FAN
Diagram 4.20
9865
221992D
TOP CASING
16
PLASTIC
PEG (2)
SCREW (2)
Diagram 4.21
5 Electrical Wiring
SECURING
SCREWS
TERMINAL
BLOCK
CONTROL
BOX
BOILER
TEMPERATURE
CONTROL
5.1 Control Box Access
Remove control box cover by undoing the four securing screws
(two on control box, two on the heat shield) and lift off, see
diagram 5.1.
CONTROL
BOX
COVER
9905
bk
TERMINAL BLOCK
CONNECTIONS
Diagram 5.1
0000
5.2 Electrical Connections
WARNING. This boiler must be earthed.
Take care not to damage any internal wiring.
Using heat resistant (85
0.2mm) and of a suitable length, route as shown in diagram 5.3.
Thread through the grommet at the bottom rear of the control
box, through the cable clamp and connect to appropriate
terminals. Tighten cable clamp screws, see diagram 5.2.
Standard colours are, brown - live (L), blue - neutral (N) and
green/yellow - earth
The mains cable outer insulation must not be cut back external
to the cable clamp.
Make sure the cable is suitably secured.
When making connections make sure that the earth conductor
is made of a greater length than the current carrying conductors,
so that if the cable is strained the earth conductor would be the
last to become disconnected.
o
C) cable of at least 0.75mm2 (24/
.
5.3 Pump Connection
The pump must be connected to the external controls.
5.4 Testing - Electrical
Checks to ensure electrical safety must be carried out by a
competent person.
After installation of the system, preliminary electrical system
checks as below should be carried out.
1. Test insulation resistance to earth.
2. Test earth continuity and short circuit of all cables.
3. Test the polarity of the mains.
The installer is requested to advise and give guidance to the
user of the controls scheme used with the boiler.
Replace the control box cover.
CABLE
CLAMP
SCREW
MAINS INLET
CONNECTOR
HEAT RESISTANT
CABLE
CABLE
CLIPS
CABLE
CLAMP
Diagram 5.2
0000
CABLE
CLIPS
Diagram 5.3
17
221992D
6 Commissioning
IMPORTANT NOTE
The WARNING NOTICE attached to the front casing
be removed by the user
Please ensure the “Benchmark” logbook is completed and left
with the user, and the magnetic lighting instruction label is
placed on the surface of the boiler casing.
must only
6.1 All Systems
Commissioning should be carried out by a competent person in
accordance with the current issue of BS6798.
UNDER ALL CIRCUMTANCES the case must be correctly
fitted and sealed, unless fault finding.
Make sure that the system has been thoroughly flushed out with
cold water without the pump in place.
Refit the pump, fill the system with water, ensuring that all the
air is properly vented from the system and pump.
6.2 Initial Lighting and Testing
CAUTION. This work must be carried out by a competent
person, in accordance with the current issue of BS6798.
Make sure that all naked lights and cigarettes are extinguished.
Refer to ‘Instructions for Use’ and identify the controls.
Check that the boiler is isolated from the electrical supply.
Turn the gas service cock “On” , see diagram 6.1.
Purge in accordance with the current issue of BS6891.
WARNING. The multifunctional control and fan operate on
mains voltage, terminals will become live.
If programmer control is fitted, make sure it is in the ON mode.
Make sure that any remote controls are calling for heat.
Turn the boiler temperature control clockwise to “Max”.
The ignition system will operate to light the boiler. After a pre-
set time if ignition has not taken place the boiler will shutdown.
To re-start the lighting sequence, turn the boiler temperature
control to “O”, then fully clockwise to “Max”.
"Max" is approximately 82°C (180°F).
After the burner has lit, the “Burner on” neon on the control panel
will come on.
Isolate the boiler from the electrical supply.
Loosen the burner pressure test point screw and connect a
suitable pressure gauge, see diagram 6.1.
Switch on the electrical supply to the boiler.
WARNING. The multifunctional control and fan operate on
mains voltage, terminals will become live.
6.3 Testing - Electrical
Turn the boiler temperature control fully clockwise to the
maximum setting.
The lighting sequence is automatic as follows:
The fan operates and after a short period of time, the spark
ignition operates, the solenoid opens, then the burner will light
shown by the “Burner On” neon on the control panel lighting up.
The burner will remain alight until switched off, either by the
boiler temperature control, programmer (if fitted) or any remote
system control.
To make sure that the flame supervision device is working
correctly the following should be done.
With the burner alight, turn the gas service cock “Off”, see
diagram 6.1.
0000
BOILER COMPONENTS
A
10052
A
B
G
F
E
A CONTROL BOX
B PHIAL POCKET
C
C GAS SERVICE COCK
D "BURNER ON" NEON
D
J
E RESET NEON
F TEMPERATURE CONTROL
G BURNER PRESSURE TEST POINT
H GAS PRESSURE ADJUSTMENT SCREW
J DATA LABEL
H
Diagram 6.1
221992D
18
6 Commissioning
After a short period the burner will go out.
The correct working of the flame supervision is shown by the
“Burner On” neon going out and the ignition sequence starting
up.
After a short period the boiler will shut down.
If the lighting sequence described fails, refer to fault finding
section 9.
To carry on turn the gas service cock “On”, see diagram 6.1.
To re-start the lighting sequence, turn the burner temperature
control to “0” then fully clockwise to “Max.”.
During normal operation when the boiler switches “Off”, the
burner will go out. The automatic lighting sequence will work
again when heat is required.
If the reset neon lights, turn the boiler temperature control to "0"
(off), wait 30 seconds, then repeat the lighting instructions.
6.4 Testing - Gas
With the boiler on proceed as follows:
Test for gas soundness around the boiler gas components
using a suitable leak detection fluid, in accordance with the
current issue of BS6891.
Check the burner gas pressure at least 10 minutes after boiler
has lit, refer to Data Label, see diagram 1.2.
If necessary adjust the gas pressure to obtain the required
setting turning screw clockwise, to decrease pressure, see
diagram 6.1.
Should any doubt exist about the gas rate, check it using the
gas meter test dial and stop watch at least 10 minutes after the
burner has lit, making sure that all other gas burning appliances
and pilot lights are off.
Gas rate: Buckingham 4 BFF80 : 2.8m
is for guidance only, dependent on the heat setting.
Turn the boiler temperature control fully anti-clockwise to “0”.
Isolate from the electrical supply.
Remove the pressure gauge from the test point and refit screw,
making sure a gas tight seal is made.
When the boiler temperature control is turned to the “0” position,
by hand, wait at least 30 seconds before turning On again.
There may be an initial smell given off from the boiler when new,
this is quite normal and it will disappear after a short period of
time.
3
/h (79ft3/h)
6.5 Testing - All Water Systems
Allow the system to reach maximum working temperature and
examine for water leaks.
There should be no undue noise in the system.
The boiler should then be turned off and the system drained off
as rapidly as possible,whilst still hot.
Refill system.
6.7 Adjustment - Fully Pumped Open Vented
System
When commissioning the system the boiler should first be fired
on full service, that is, central heating and domestic hot water.
Adjust the pump to the system design setting, then balance the
system, making adjustments as necessary.
6.8 Completion
Adjust the boiler temperature control and any system controls
to their required settings.
Fit the bottom plinth panel and secure with two dog point
screws, see diagram 6.2.
Finally fit the front panel by hooking under front of top panel
locating on the two studs, see diagram 6.2 and securing at the
bottom on to the bottom plinth panel with two screws, see
diagram 6.3.
SECURING SCREWS
BOTTOM PLINTH
PANEL
LOCATE
UNDER LIP
LOCATING
STUDS
FRONT
PANEL
FRONT PANEL
SECURING SCREWS
Diagram 6.2
6.6 Open Vented System
Ensure there is no pumping over of water or entry of air at the
open vent above the feed and expansion cistern.
19
Diagram 6.3
221992D
7 Instructions to the User
Instruct and demonstrate the safe and efficient operation of the boiler, heating system and domestic hot water system.
Advise the user, that to ensure the continued efficient and safe operation of the boiler, it is recommended that it is checked and
serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once
a year should be enough.
Draw attention, if applicable to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes
a duty of care on all persons who let out any property containing a gas appliance.
It is the Law that servicing is carried out by a competent person.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being
out of use during frost and freezing conditions.
Reminder - Leave these instructions and the “Benchmark” logbook with the user.
8 Servicing
REMEMBER, When replacing a part on this appliance, use only
spare parts that you can be assured conform to the safety and
performance specification that we require. Do not use
reconditioned or copy parts that have not been clearly authorised
by Halstead Boilers Ltd.
Products of Combustion Check
Note: To obtain a products of combustion reading, remove the
front panel and remove the control box as descibed in the
relevant paragraphs of section 4.12. Next, remove the cap from
the sampling point, located on the top of the left hand side of the
inner casing, see diagram 8.1.
Connect the analyser tube on to the nipple.
WARNING. The multifunctional control and fan operate on
mains voltage, terminals will become live.
Switch on the electrical supply and gas supply then operate the
boiler.
On completion of the test switch off the electrical supply and gas
supply, remove analyser tube and replace sampling point cap.
Servicing
Before servicing turn off the gas and isolate the electrical supply
to the boiler.
After completing a service always test for gas soundness, make
electrical checks and carry out functional check on controls.
Unless stated otherwise all parts are replaced in the reverse
order to removal.
8.1 Access
Remove the boiler front casing panel, refer to paragraph 6.8.
Remove the bottom plinth panel by unscrewing the two dog
point screws securing the panel to the boiler plinth, see diagram
8.4.
Disconnect gas valve from gas cock and unplug electrical plug
from gas valve, firstly removing electrical plug securing screw,
see diagram 8.2.
Unclip electrical wires from control box support bracket, see
diagram 8.3.
Undo the four self-tapping screws that secure the combustion
chamber front and carefully withdraw it together with the burner
and gas valve assembly, taking care not to strain the ignition
and earth wire, see diagram 8.5.
Note: When replacing burner in combustion chamber make
sure it fits correctly on the guides.
Disconnect the ignition and earth leads from the burner and
remove by drawing the leads though the grommet, see diagram
8.5.
Remove the three self-tapping screws from the lower part of the
control box support bracket, see diagram 8.6.
Undo the wing nut that secures the top of the heat shield and
carefully hinge down control box and heat shield, see diagram
8.6.
Release the two toggle latches that secure the boiler access
door and remove, see diagram 8.7.
SAMPLE POINT
Diagram 8.1
SECURING
SCREW
ELECTRICAL
PLUG
GAS
SERVICE
COCK
UNION
Diagram 8.2
0000
0000
221992D
20
8 Servicing
Note: When replacing the fan access door make sure the lip at
the top of door fits into and behind the slotted bracket located at
the top of the boiler.
Note: To ease removal of the right hand baffle from the heat
exchanger, remove both silicone tubes from the air pressure
switch.
Remove fan securing screw, electrical connections and air
pressure tubes, then remove fan by sliding back to disengage
the retaining lugs then lift up, see diagram 8.7.
Remove the flue hood.
When replacing the flue hood ensure that it rests on the guides
and that the rear of flue hood is located under the pegs at the
rear and pushed down and back fully.
IMPORTANT: When re-fitting fan check that it fits fully into the
flue duct extension piece.
0000
GROMMET
COMBUSTION
CHAMBER
COVER
IGNITION AND
EARTH LEADS
Diagram 8.5
WING NUT
0886
0000
ELECTRICAL
WIRE
RETAINING
CLIPS
CONTROL BOX
SUPPORT
BRACKET
SECURING SCREWS
Diagram 8.3
0000
SELF
TAPPING
SCREWS
(3)
Diagram 8.6
FAN
0000
TOGGLE
LATCHES
BOTTOM PLINTH
PANEL
21
FLUE HOOD
SECURING
SCREW
Diagram 8.7Diagram 8.4
221992D
8 Servicing
8.2 Boiler Flueways
Remove flueway baffles noting that there are 2 centre and 2
side flueway baffles, see diagram 8.8.
Place a sheet of paper in the combustion chamber to catch any
flue debris.
Thoroughly clean boiler flueways and fins with a suitable stiff
brush.
Replace in reverse order, after completing the relevant
instructions in sections 8.3 and 8.4.
8.3 Burner and Injector
Remove the two screws and nuts securing the burner support
bracket to the combustion chamber cover, see diagram 8.9.
Remove the graphite coated nuts on the supply feed pipe at the
rear of the burner to release the burner, see diagram 8.10.
Clean the burner. Use a vacuum cleaner or suitable stiff brush
(not wire) to clean the burner thoroughly, making sure that all
the burner ports are clear and unobstructed.
Check the burner injector for blockage or damage and replace
if necessary, see diagram 8.11.
With the burner removed the injector can be inspected and
cleaned as necessary.
For cleaning do not use a wire or sharp instrument on the hole.
If removed, use a little suitable sealant on the external thread
when refitting to make sure a gas tight seal is made.
8.4 Service Checks
Inspect the spark electrode and clean and replace as necessary,
see diagram 8.12.
Check the condition of the side and rear insulation panels in the
combustion chamber.
Check the condition of the seals on the boiler access door and
the combustion chamber cover.
Examine the flue hood and terminal to make sure they are clean
and clear of obstructions.
Refit all parts.
Light the boiler and carry out functional tests as described in
section 6.
0000
FLUEWAY
BAFFLE
HEAT
EXCHANGER
SIDE
FLUEWAY
BAFFLE
0000
0000
BURNER
SUPPORT
BRACKET
MAIN
BURNER
SUPPLY
FEED
PIPE
SCREWS &
NUTS (2)
Diagram 8.9
GRAPHITE
COATED
NUT(2)
0000
HEAT
EXCHANGER
221992D
Diagram 8.8
Diagram 8.10
22
8 Servicing
ELECTRODE
0939
SPARK GAP
+
= 3.6 1.1
-
SECURING
GRAPHITE
COATED
NUT(2)
BURNER
INJECTOR
Diagram 8.11
SCREW
Diagram 8.12
9 Fault Finding
IMPORTANT. On completion of the Fault Finding task which has required the breaking and remaking of the electrical connections,
the continuity, polarity, short circuit and resistance to earth checks must be repeated using a suitable multimeter.
WARNING. The multifunctional control and fan operate on mains voltage, the terminal will be live.
Before carrying out fault finding, ensure that gas, electricity and water are available at the boiler.
Ensure that any external controls are calling for heat and circuit water is cold.
If neon 6 is lit flame failure has occured. Reset boiler by turning temperature control to Off,
waiting 30 seconds and then on.
If fault persists continue with fault finding below.
9917
0000
Is neon 1 lit?
YES
Is neon 2 lit?
YES
Is neon 3 lit?
YES
Does sparking take place
(Listen for spark discharge.)
YES
Is neon 4 lit?
Appliance working
satisfactorily.
NO
NO
NO
YES
Is there 230V ac between
Ls and N
YES
With electrical supply isolated
disconnect the 2 way
thermistor plug from the PCB.
Check that there is a resistance
between 14k - 2.5kOhms.
With electrical supply isolated remove the fan access door as
described in the relevant parts of section 8.1, to gain access to the
air pressure switch. Switch on electrical supply Check for 230V ac
between N and normally closed contact of air pressure switch.
YES
Check for 230V ac
between N and common
contact on air
pressure switch.
NO
?
NO
Faulty PCB.
Replace.
Does burner light?
YES
Is integrity of
electrode and
ignition lead good?
NO
Replace as
necessary
Faulty
PCB.
NO
YES
NO
YES
NO
YES
NO
Check for 230V ac
between N and brown
and between N and black,
3 way connector on PCB.
Check continuity of
gas valve harness.
Faulty gas valve.
Replace.
Check power supply
Faulty PCB.
Replace.
Faulty thermistor.
Replace.
Is the fan turning?
Faulty air pressure
switch. Replace.
NO
YES
NO
YES
NO
NO
NO
Faulty PCB.
Replace.
Is there 230V ac
on fan?
YES
Faulty
PCB.
Faulty
fan.
Faulty PCB.
Replace.
Faulty harness.
Replace.
ELECTRICAL FAULT FINDING
23
Diagram 9.1
221992D
9 Fault Finding
9.1 Electrical
Gain access to the control box, refer to the relevant paragraph
in section 8.1, then remove the control box cover, refer to
section 5.1.
Refer to: Boiler Fault Finding, see diagram 9.1, Fault Finding
Wiring Diagram, see diagram 9.3, Pictorial Wiring Diagram, see
diagram 9.4.
9.2 Electrical Supply Failure
Failure of the electrical supply will cause the burner to go out.
Operation will normally resume on the restoration of the electrical
supply.
If the burner does not relight after an electrical supply failure and
the red neon on the control panel is lit, turn the burner temperature
control to “0”, wait 30 seconds, then fully clockwise to “Max.”
see diagram 9.2.
REMEMBER, When replacing a part on this appliance, use only
spare parts that you can be assured conform to the safety and
performance specification that we require. Do not use
reconditioned or copy parts that have not been clearly authorised
by Halstead Boilers Ltd.
Replacement of parts must only be carried out by a competent
person.
Before removing or replacing any parts, turn off the gas supply
at the gas service cock, see diagram 8.2 and isolate the
electrical supply to the appliance.
Unless stated otherwise, all parts are replaced in the reverse
order to removal.
After replacing any parts always test for gas soundness and if
necessary carry out functional check of controls.
10.1 Electrical Thermistor
Remove front panel to gain access, see section 6.8.
Remove control box cover by undoing the four securing screws
(two on control box, two on the heat shield) and lift off, see
diagram 10.1.
Remove thermistor lead from retaining clip, located on the
control box support bracket, see diagram 8.3.
Release strain relief grommet securing thermistor lead at the
side of control box.
Disconnect the thermistor electrical plug from the control board
(P.C.B) slightly bending back the retaining latch to allow
withdrawal, see diagram 10.2.
Remove the retaining wire and withdraw the electrical thermistor
from its phial, see diagram 10.3.
Draw the thermistor lead followed by the thermistor out though
the control box case.
Re-assembly note. When fitting the thermistor make sure it is
fully inserted into the phial, see diagram 10.3. Take care when
re-threading retaining wire so as not to damage thermistor.
10.2 Control Board (P.C.B)
Remove front panel to gain access, see section 6.8.
Remove control box lid by undoing the four securing screws
(two on control box, two on the heat shield) and lift off, see
diagram 10.1.
Carefully pull the boiler temperature control knob away from the
P.C.B.
Disconnect the electrical plugs from the control board (PCB)
slightly bending back the retaining latches to allow withdrawal,
see diagram 10.2.
Disconnect ignition lead.
Carefully pull the board away from its supports bending back
slightly the retaining latches.
When refitting refer to wiring diagram 9.4.
Take care when replacing the burner temperature control knob
by supporting the potentiometer on the P.C.B.
10.3 Electrode
Refer to the relevant paragraphs of the servicing section to
remove the burner from combustion chamber.
To remove the electrode, unscrew from the retaining bracket,
see diagram 8.12.
Take the electrode out from below and remove the ignition lead.
When removing and replacing the electrode take care not to
damage it.
When refitting, check spark gap, see diagram 8.12.
10.4 Multifunctional Control
Remove front panel to gain access, see section 6.8.
Remove the securing screw and disconnect the electrical plug,
see diagram 10.4.
Disconnect the gas cock, on the left hand side.
Support the multifunctional control, remove the four screws (2
long, 2 short) from the flanged connection at the right hand side.
Remove and discard the original “O” ring from the flanged
connection and fit the new “O” ring supplied, into recess, before
fitting the replacement multifunctional control.
After assembly test for gas soundness and purge in accordance
with the current issue of BS6891.
PCB
SECURING
SCREWS
TERMINAL
BLOCK
BOILER
TEMPERATURE
CONTROL
221992D
CONTROL
BOX
COVER
CONTROL
BOX
Diagram 10.1
9905
26
PHIAL
POCKET
ELECTRICAL
PLUGS
Diagram 10.2
0000
THERMISTOR
Diagram 10.3
10 Replacement of Parts
10.5 Solenoid
Remove the electrical plug from the multifunctional control and
remove the securing screw and then the solenoid assembly,
see diagram 10.4.
10.6 Burner
Refer to the relevant paragraphs of the servicing section to
remove the burner from combustion chamber.
10.7 Injector
Refer to the relevant paragraphs of the servicing section to
remove the burner from combustion chamber.
The injector can then be unscrewed from the manifold.
When replacing use a little jointing compound on the external
thread only, to ensure a gas tight seal.
10.8 Air Pressure Switch
Remove front panel to gain access, see section 6.8.
Refer to the relevant paragraphs of the servicing section to
remove the burner from combustion chamber.
Remove the air pressure tubes and electrical connections from
the switch, release the securing screws and remove the switch,
see diagram 10.5.
When fitting the replacement make sure that the air pressure
tubes are fitted with the clear tube from the air pressure switch
to the front fan connection, as shown in diagram 10.5 and the
electrical connections are made as shown in wiring diagram
9.4.
10.9 Fan
Remove front panel to gain access, see section 6.8.
Refer to the relevant paragraphs of the servicing section to
remove the burner from combustion chamber.
Remove the electrical connections and air pressure tubes from
the fan.
Note: Remove the electrical connections by pulling insulation
boots only.
Undo the screw securing the fan to the flue hood and disengage
fan from flue hood.
When re-assembling, make sure that the air pressure tubes are
fitted as before and that the fan duct engages fully into the flue
duct extension piece.
The polarity of the electrical connections is not important.
10.10 Insulation
Refer to the relevant paragraphs of the servicing section to
remove the burner from combustion chamber.
Sides
Undo the burner support bracket nuts and remove support
bracket and insulation, see diagram 10.6.
Refit support bracket with new side insulation.
Rear
Bend forward rear insulation securing nibs, one on each side,
to release insulation.
Fit new insulation and bend back securing nibs.
FRONT AIR PRESSURE
SWITCH TUBE (CLEAR)
AIR
PRESSURE
SWITCH
ELECTRICAL
CONNECTORS
REAR AIR PRESSURE
SWITCH TUBE (RED)
Diagram 10.5
10259
ELECTRICAL
PLUG
SECURING
SCREW
GAS
SERVICE
COCK
UNION
SOLENOID ASSEMBLY
SOLENOID
SECURING SCREW
SHORT
SCREWS (2)
LONG
SCREWS
(2)
Diagram 10.4
SIDE
INSULATION
27
NUTS
SECURING
NIB
BURNER
SUPPORT
BRACKET
0000
REAR
INSULATION
PANEL
Diagram 10.6
221992D
11 Spare Parts
11.1 Part Identification
The key number in diagram 11.1 and the first column of the list
will help identify the spare part.
1
8
5
10
4
11.2 Ordering
When ordering any spare part please quote the part number
and the description from the list together with the model name
and serial number information from the data label.
The data label is positioned on the heat shield, see diagram 6.1.
2
3
6
7
9
10177
Diagram 11.1
Key No.Part No. DescriptionGC Part No.
12000461752Multifunctional control******
2227132Fan******
32000461994Air pressure switch******
42000461985Electrical thermistor******
5202635Spark electrode******
62000461714Boiler temperature control knob******
72000461924Injector******
8227098Fuse******
9227030Control board******
10205656Burner******
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
221992D
28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.