HTV8BLEEMVP*1C HTV8BLEEMVP*2C HVT8BLEEMVP*3C HTVDBLMVP*1C HTVDBLMVP*2C HTVDBLMVP*3C
OWNERS MANUAL
HTVBLEE-MVP Series Barrier-Free Water Coolers
49
41
62
56
43 53
24
34
17
23, 36, 51
64
69
54, 68 23, 36, 51
12
44
27
52
8
58
6
35
1, 47
40
22, 29
31
Fig. 1
35
35
28
45, 46
77
21, 29
33
67
30
(A) - See. Fig. 10
4, 16
15, 59, 60
13
42
55
57
63
18,
20,
26
PAGE 1 98496C (Rev. C - 7/09)
25
65
65
2, 3, 5
7
66, 70
HTV8BLEEMVP*1C HTV8BLEEMVP*2C HVT8BLEEMVP*3C HTVDBLMVP*1C HTVDBLMVP*2C HTVDBLMVP*3C
Reduzca la altura por 3” (76 mm) para
la instalación de childrens ADA más fresco.
Reduce height by 3” (76mm) for
*ADA REQUIREMENT
*REQUISITO DE A.D.A.
*EXIGENCE ADA
installation of childrens ADA cooler.
Réduire la hauteur par 3 (76 mm) pour
l’installation de childrens ADA plus frais.
NOTE: Halsey Taylor’s recommended orifice
mounting height for children 38” to 46” tall
(approx. four through seven years old) is 23”
from the finished floor.
Fig. 2
PAGE 298496C (Rev. C - 7/09)
COPPER TUBE.
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION. SHUT OFF VALVE (NOT FURNISHED) TO ACCEPT 3/8” O.D. UNPLATED
La UBICACION RECOMENDADA de ABASTECIMIENTO DE AGUA. APAGUE V ALVULA (no AMUEBLADO) ACEPTAR 3/8 O. D.
UBICACIÓN RECOMENDADA P ARA EL DRENAJE DE SALIDA DE AGUA, DE 1¼” DE DIÁMETRO.
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/4" DE SORTIE D’EAU.
El TUBO del COBRE de UNPLATED
L’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. ETEINDRE LA SOUPAPE (P AS FOURNI) ACCEPTER 3/8 O.D. LE TUBE DE
CUIVRE DE UNPLATED.
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/4” O.D. DRAIN
C = 1-1/2 TRAP NOT FURNISHED**
PURGADOR DE 1-1/2 NO PROPORCIONADO**
SIPHON 1-1/2 NON FOURNI**
CAJA RECESIV A DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6" (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA DE
VENTILACIÓN DEL MUEBLE Y LA PARED
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6" (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 5/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 5/16 POUR FIXER L’APP AREIL AU MUR
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX
E = INSURE PROPER VENTILATION BY MAINTAINING 6" (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
F = 5/16 BOLT HOLES FOR FASTENING UNIT TO WALL
HTV8BLEEMVP*1C HTV8BLEEMVP*2C HVT8BLEEMVP*3C HTVDBLMVP*1C HTVDBLMVP*2C HTVDBLMVP*3C
HANGER BRACKET & TRAP INST ALLATION
1) Remove the hanger bracket fastened to back of the
cooler by removing one (1) screw.
2) Mount the hanger bracket as shown in Fig. 2 & Fig 3.
NOTE: Hanger Bracket MUST be supported securely.
Add fixture support carrier if wall will not provide
adequate support. Anchor hanger securely to wall
using all six (6) 1/4 in. dia. mounting holes.
IMPORTANT:
7 in. (178mm) dimension from wall to centerline
of trap must be maintained for proper fit.
INSTALLATION OF COOLER
3) Hang the cooler on the hanger bracket. Be certain the
hanger bracket is engaged properly in the slots on the
cooler back as shown in Figure 3.
4) Remove the two (2) screws holding the bottom cover
at the bottom of cooler. (Shown in Fig. 16) Remove the
bottom cover by pulling straight down and set aside.
5) Connect water inlet line--See Note 4 of General Inst.
6) Install trap. Remove the slip nut and gasket from the
trap and install them on the cooler waste line making
sure that the end of the waste line fits into the trap.
Assemble the slip nut and gasket to the trap and tighten
securely.
IMPORTANT: If it is necessary to cut the wasteline, loosen
the clamp (Item 62) at the drain fitting (Item 41)
and remove. Check for leaks after re-assembly.
8) Plug in electrical power and re-install bottom cover. Unit
must have electrical power to have water flow.
HANGER BRACKET (Item 10)
COOLER BACK
Fig. 3
ST ART UP
Also See General Instructions
9) Stream height is factory set at 35 PSI. If supply pressure
varies greatly from this, adjust screw located on upper
side of frame (Item 43 or 44). See Fig. 3. CW adjustment
will raise stream and CCW adjustment will lower stream.
For best adjustment, stream should be 1-1/2” above
bubbler hood. (See Fig. 4)
NOTE: If continuous flow occurs at the end of the
compressor cycle, turn cold control (Item 16)
counterclockwise 1/4 turn.
CAUTION: PLASTIC COMPONENTS
Any service of this unit that requires use of a torch,
care should be taken not to melt any of the plastic
components. To keep flame away from plastic, the
use of a shield may be required.
CLEANING:
Warm, soapy water or mild household cleaning products
can be used to clean the exterior panels of the HTV
series coolers. Use of harsh chemicals or petroleum
based cleaners WILL VOID THE WARRANTY.
CORRECT STREAM
HEIGHT
Fig. 4
IMPORT ANT:
When installing cooler, do not solder 3/8” copper inlet tube
while inserted into union fitting as damage to o-ring and
plastic will result.
PAGE 3 98496C (Rev. C - 7/09)
HTV8BLEEMVP*1C HTV8BLEEMVP*2C HVT8BLEEMVP*3C HTVDBLMVP*1C HTVDBLMVP*2C HTVDBLMVP*3C
Top Cover Removal
Please remove bottom cover before removing top cover. To remove top cover
(Item 37), use a small screwdriver to release the snap for the top cover as shown
in Fig. 5. Then pull the small tabs on each side of the top cover outward slightly
and slide upward to remove.
FIG. 5
37
Small tabs
Cleaning the strainer
To clean the strainer, unscrew the cap of the
solenoid valve. Remove screen and rinse
thoroughly with water. Insert screen back
into solenoid valve and screw cap on. Make
sure the o-ring is placed properly.
Retén anular
Joint Torique
Cap
Tapa
Bouchon
Screen
Malla
Ecran
O-ring
FIG. 6
23
51
36
76
PAGE 498496C (Rev. C - 7/09)