HL8102 Series Digital Thermostat Manual
HL8102 series thermostats are used to control room temperature in industrial, commercial
and residential environment via cont rolling electric modulating valve with 0-10VDC (4-20mA)
control signal or floating control as well as damper actuator of VAV system.
Electronic control technology is adopted, with green backlit LCD display of: working mode
(cooling “
”, heating “ ”, ventilating “ ”, auto “ ” ); fan speed (low “ ”, med “ ”, high “ ”,
auto “
”); room temperature; setting temperature etc. push button: On/Off “ ”; mode
changeover “ ”; fan speed choose “ ” and temperature adjustment “ ” and “ ”.
Shell: PC + ABS retardant material.
Function :
Detect and Display room temperature
Room temperature setting
Fahrenheit or Celsius degree display
Timing sleep
Control On/Off of cooling and heating equipment
Selectable single speed or three spe ed fan control
Order Guide:
Model
Fan
(Single/3-speed)
RS485
Network
Input
Control
Remote
Sensor
Fan: thermostat with fan functions, can be selected with single speed fan or t hr ee speed fan by setting parameter .
Remote Control: input signal can be sel ected by setting parameter.
Specification :
Set temperature range: 0 - 99.5℃ adjustable
Accuracy displayed:
0.1℃
Accuracy: ±0.5℃
Rated Power: < 1 W
Sensor type:
NTC
Display: LCD
Power:
AC 24V±10%, 50Hz/60Hz
Output signal:
AC 24V×2 (0.5A resistive) ,
0 - 10VDC(5mA) / 4 - 20mA (600Ω)
Input signal: dry contact (NO)
Dimensions: 86×86×23mm (W×H×D)
Fixing screw width : 60mm (Standard)

HaiLin Controls
Beijing HaiLin Auto Controls Equipment Co., Ltd. Page 2 of 4 Tel: +86 10 8070 2235
Shahe Industrial Zone, Changping District www.hilin.com
Operations:
On/Off: Press “ ” buttons to turn on; press “ ” again to turn off.
Setpoint: With thermost at on, press “ ” to reduce the setpoint, press “ ” to increase t he set point , the se tpoint st ep is
0.5℃, the setpoint will be confirmed automatically after 5 seconds, and then return to dispay status, press “
” or “ ” to
check setpoint.
Mode: With thermostat on, press “ ” to change the workin g mode – Cooling “ ”, Heating “ ”, Vent " ", Auto “ ”
( Auto is available from HL8102E to HL8102K).
Fan Speed: With thermostat on, press “
” to select the desired speed – l ow speed “ ”, M ed speed “ ”, High speed
“ ”, auto “ ”. If single speed fan available, there’s only med speed “ ”.
Under auto speed fan, the fan speed will be changed aut omat icall y as be lo w: in low spe ed when room t emperatur e
is 1℃ difference with setpoint;in med speed when r oom te mperatur e is 2℃ difference with setpoint; in High speed when
room temperature is 3℃ difference with setpoint.
Sleep: Thermostat will get into sle ep function after programming.T he set Temperature should to be.
To set:Press “
” button for 3 seconds till “ ” display, there’s a number of count down in the center of LCD, Use “ ” or
“ ” to adjust the desired sleep time: the max. = 48 ho urs; thermostat will r eturn to the working stat us after 5
seconds, “
” is flashing to start counting down. The setpoint should be replaced by the sleep setpoint.
To quit: When thermostat get into Sleep function, “ ” will flash, press “ ” or “ ” to quit.
Keypad lock: press “ ” and “ ” for 10 seconds till to “ ” display to activate, under this function, any keypad is locked.
Press “
” and “ ” for 10 seconds till “ ” disappear to quit the function.
Set Parameters: With thermostat off, press “ ” for 10 seconds to enter menu to set the parameters.
Parameter table:
Power on status (0: Off; 1: On; 2: Hold)
2 Fan speed (0: Single Speed; 1: Three S peed) 1 0 - 1
4 Sensor selection (0: Internal; 1: Remote) 1 0 - 1
Temperature format (0: Celsius; 1: Fahrenheit)
7 Minimum setpoint 5℃/41℉ 0 - 99.5 0.5
9 Dead band (from HL8102E to HL8102K) 2 0 - 10 0.5
Heating & Auto sleep setpoint
12 Comms# (HL8102XN) 1 1 - 32 1
13
Input Signal Mode
0: Invalid
1: Changeover(from HL8102A to HL8102D)
2: thermostat will be sleep without input signal
3: thermostat will be Off without input signal
0 0 - 3
14 Heating reset time 90 sec. 10 - 300 sec. 10 sec.
16 Ports mode (0: Modulation & Floating; 1: On/Off) 0 0 - 1
Valve status as turn off (0: Close; 1:Hold; 2: Open )
Port1 Modulation direction(0:10V Open; 1:10V Close)

HaiLin Controls
Beijing HaiLin Auto Controls Equipment Co., Ltd. Page 3 of 4 Tel: +86 10 8070 2235
Shahe Industrial Zone, Changping District www.hilin.com
Port1 Modulation minimum signal
20 Port1 Modulation proportional 2 1 - 20 0.5
Port2 Modulation direction(0:10V Open;1:10V Close)
22 Port2 Modulation minimum Signal 0 Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
Port2 Modulation proportional
Port1 Floating minimum time
25 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
Port1 Floating minimum time
27 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
28
Disable / Enable bypass PID control
( 0: Disable; 1: Enable )
0 0 - 1
29
Override output value when bypass PID control
Display output value when enable PID co ntrol
0 - 255
30
Override output value when bypass PID control
Display output value when enable PID control
0 - 255
31
Input signal management:
0: Input valid
1: Override Input: open
2: Override Input: close
0 0 - 2
32
Display room temperature or set-point
0: Room temperature 1: S et-Point
0 0 - 1
33
Configuration external sensor
0: B = 3950; 1: B = 3450; 2: B = 3900
3: User define (via network. default B = 3950)
Start temperature of Low temperature protection
Stop temperature of Low temperature protection
It will confirm itself 20 seconds later after setting and return to Off state.
Switch: There is a 5 poles switch on PCB. The meaning is below:
120 ohm Resistance between AB wires
No Resistance between AB wires
2 Port 1 Modulati on 0 - 20mA Off
Port 1 Modulation 0 - 10VDC
4 Port 2 Modulati on 0 - 20mA Off
Port 3 Modulation 0 - 10VDC
Mounting:
1. Open the back panel with
screwdriver.
2. Connect the wires follow the
diagram.
3. Fix the base with screw.
4. Fix the front panel and finish
the installation.

HaiLin Controls
Beijing HaiLin Auto Controls Equipment Co., Ltd. Page 4 of 4 Tel: +86 10 8070 2235
Shahe Industrial Zone, Changping District www.hilin.com
Wiring diagram:
Note: Be sure to connect all the wires as per the wiring diagrams and keep it away from water, mud
and other material so as to prevent the unit being spoiled!
24VAC
HL8102A/AN
L
N
OPEN
CLOSE
Floating Control
Cooling/Heating
RS
┴
Input
B
A
┴
~
COM
VO
VC
TR
Modbus
A
B
Input
Remote Sensor
24VAC
HL8102B/BN
L
N
Modulating Control
Cooling/Heating
RS
┴
Input
B
A
┴
~
TR
Modbus
A
B
Input
Remote Sensor
M
0-10V
/4-20mA
V+
┴
~
24VAC
HL8102C/CN
L
N
OPEN
CLOSE
Floating Control
Cooling/Heating
RS
┴
Input
B
A
┴
~
COM
LOW
MED
HI
L
VO
VC
TR
Fan
Modbus
A
B
Input
Remote Sensor
24VAC
HL8102D/DN
L
N
Modulating Control
Cooling/Heating
RS
┴
Input
B
A
┴
~
LOW
MED
HI
L
TR
Fan
Modbus
A
B
Input
Remote Sensor
M
0-10V
/4-20mA
V+
┴
~
24VAC
HL8102E/EN
L
N
OPEN
CLOSE
Modulating Control
Heating
Floating Control
Cooling
RS
┴
Input
B
A
┴
~
COM
LOW
MED
HI
L
CO
CC
TR
Fan
Modbus
A
B
Input
Remote Sensor
M
0-10V
/4-20mA
H+
┴
24VAC
HL8102F/FN
L
N
OPEN
CLOSE
Modulating Control
Cooling
Floating Control
Heating
RS
┴
Input
B
A
┴
~
COM
LOW
MED
HI
L
HC
TR
Fan
Modbus
A
B
Input
Remote Sensor
HO
M
0-10V
/4-20mA
C+
┴
24VAC
HL8102I/IN
L
N
OPEN
CLOSE
OPEN
CLOSE
Floating Control
Heating
Floating Control
Cooling
RS
┴
Input
B
A
┴
~
COM
LOW
MED
HI
L
CO
CC
HO
HC
TR
Fan
Modbus
A
B
Input
Remote Sensor
24VAC
HL8102K/KN
L
N
Modulating Control
Heating
Modulating Control
Cooling
RS
┴
Input
B
A
┴
~
LOW
MED
HI
L
TR
Fan
Modbus
A
B
Input
Remote Sensor
M
M
0-10V
/4-20mA
C+
┴
0-10V
/4-20mA
H+
┴
~