HL116 Series Thermostat User Manual
HL116 Series thermostats are available for individual room temperature control in
residential, industrial and business premises. Suitable for 2-pipe or 4-pipe Fan Coil configuration.
HL116 adopt digital control technology with LCD display, It shows the following items: working states (cool, heat, auto or ventilation), the room temperature, set-point. There are following keys on the panel: Exchange mode (cool, heat, auto or ventilation) “ ”, set-point temperature “S” and “T”; switch: Power On/Off, and Select fan speed (high, medium or low).
BASIC FEATURES STATUS DISPLAY
Room temperature setting
Manual 3-speed changeover
Defrost (low temperature protection)
Blue Backlight
Working Status: Cool
, Heat , Auto and
Ventilation
Room temperature display
Temperature setting display
SPECIFICATIONS
Sensing element: NT C
Accuracy : ± 1
Set-point range: 5 to 35℃℃
Display range: 0~50℃
Operation environment: 0~45℃
Operating Humidity: 595%RH (non-condensing)
Power supply: AC 220V ± 10%, 50/60Hz
Switch current rating: Resistive: 2A, Inductive: 1A
Rated Power: < 2 W
Wirings: Screw-in terminals, each terminal capable of
accepting 2 x 1.5 mm
2
or 1 x 2.5 mm2 wires
Housing: ABS + PC Flame Retardant
Dimensions: 86 × 86 × 23.5 mm ( W × H × D )
Hole pitch: 60 mm ( Standard )
Protection Class: IP30
Display: LCD
OPERATION
" On/Off: Slide the switch to “LOW”, “MED” or “HIGH” turn on; Slide the switch to “OFF”, to turn off thermostat and its
output.
" Setting temperature: Press “T” to reduce set-point, press “S” to raise set-point, and 1 changed once. " Mode Selection:
HL116DA/DA2/P: When turn on, Press “
” to change system working in cooling “ ”, heating “ ” or ventilation “ ” mode, the related icon will flash, and continuous switch can be performed among three models hereinbefore while “ ” key is pressed without release.
HL116(A)FCV2: When turn on, Press “ ” to change system working in cooling “ ”, heating “ ”, Auto “
or ventilation
” mode in turn, the related icon will flash, and continuous switch can be performed among four models hereinbefore while
” key is pressed without release. Thermostat auto switch to cooling or heating mode in accordance with result set point
compared to environment temperature under AUTO “
mode (This mode is called AFCV2 mode).
" Fan speed selection: If the switch on panel is slipped to position LOW 、MED or HIGH, namely, corresponding Fan
speed of representation LOW、MED、HIGH symbol is selected.
MODEL DENOMINATIONS
HL116
DA/DA2: C ontrol Motorized Valve (DA: Control 2-wire N.C. FCU valve; DA2: Control 3-wire FCU valve) and
3-speed fan; When the temperature reaches the set-point, it will close the Motorized Valve with the fan still running.
(A)FCV2: Control 4 pipe fan coil units, Control two Motorized Valv es and 3-spee d fan, when the temperatur e
reaches the set-point, it will close the Motorized Valves with the fan still running.
P: Control 3-wire FCU valve (Floating Arithmetic) and 3-speed fan; when the temperature reaches the
set-point, it will close the Motorized Valve with the fan still running.
HaiLin Controls
Beijing HaiLin Auto Controls Equipment Co., Ltd. Page 2 of 2 Tel: +86 10 8070 2235 Shahe Industrial Zone, Changping District www.hilin.com
" Control of motorized-valve (HL116DA/DA2/P: If the difference between room temperature and set-point exceed (or under) 1, FCU valve will be open; if room temperature are equal to set-point, the FCU valve will close with the fan still running.
" Control cooling-heating FCU Valve under 4-pipe configuration (HL116FCV2): In cooling Mode, when the room temperature is higher than set-point, the cooling valve will be opened. Otherwise it will be closed. Heating valve is always closed In heating, in heating Mode When the room temperature is lower than set-point, the heating valve will be opened. Otherwise it will be closed. Cooling valve is always closed.
LOW TEMPERATURE PROTECTION
" If thermostat is at shut state, and when room temperature is lower than 5℃, thermostat will start valve for heating, HL116DA/DA2/P for electric motorized valve and HL116FCV2 for heating water valve respectively, when temperature returns to 7 or above, it will close valve.
SET LOW TEMPERATURE PROTECTION
"Turn off the thermostat, press “ ” until backlight is on and parameter setting is displayed with icon “ ” and “00”, “01”, press “S” or “T” key to adjust. “00” indicates low temperature protection is invalid, “01” indicates low temperature protection function valid. The default is “00”.
Caution: test Mode modification is prohibited while “F” is displayed in the middle of the LCD screen.
WIRING DIAGRAMS
MOUNTING
Note: Be sure to connect all the wires as per the wiring diagrams and keep it away from water, mud
and other material so as to prevent the unit being spoiled!
1. Open the front cover.
2. Connect the wires follow the diagram.
3. Fix the base with screw.
4. Fix the front panel and finish the installation.
Valve
HL116DA2
N L
FAN-H
Fan
AC 220V 50/60Hz
N L
FAN-M FAN-L
VAL-NC/HEAT
VAL-NO/COOL
N L
FAN-H
Fan
Valve
AC 220V 50/60Hz
N L
FAN-M FAN-L
VAL-NC/HEAT
VAL-NO/COOL
HL116P
AC 220V 50/60Hz
N L
HL116DA
N L
FAN-H
Fan
VAL-NO/COOL
FAN-M
FAN-L
Valve
AC 220V 50/60Hz
N L
N
L
FAN-H
Fan
VAL-NO/COOL
FAN-M FAN-L
HL116FCV2/AFCV2
VAL-NC/HEAT
Val2
VAl1
FAN-H