28
The combination of multiple indoor units can be controlled by wired controller or remote controller.
* Switching Mode of Line-Controlled Main Unit/ Line-Controlled Sub
Units/ Remote-Controlled Types can be used for switching over *
Socket/Code
SW08-[6]
CN23
CN30
CN21
ON
ON
OFF
Control Mode
Signal Terminals
Line-Controlled Main Unit Line-Controlled Sub Unit
Type Switching Mode of
Remote Control
A,B,C are connected
to wired controller
strapping
strapping
null
connected to receiving plank
of remote control
no strapping
strapping
null
B,C are connected to
wired controller
no strapping
no strapping
A,B,C are not connected to
wired controller
The wiring for the power line of indoor unit, the wiring between indoor and outdoor units as well
as the wiring between indoor units:
* The electrical power line and signal lines must be fastened tightly.
* Every indoor unit must have the ground connection.
* The power line should be enlarged if it exceeds the permissible length.
* Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at
the side of signal lines of outdoor units grounded at one point.
* It is not permissible if the whole length of signal line exceeds 1000m.
Signal Wiring of Wired controller
Length of Signal Line (m)
0.75mm2*3 core shielding line
0.3mm2*3 core shielding line
0.5mm2*3 core shielding line
Wiring Dimensions Length of Signal Line (m) Wiring Dimensions
2mm2*3 core shielding line
1.25mm2*3 core shielding line
*100
*100 and <200
*200 and <300
*300 <400
*400 <600
* The shielding lay of the signal line must be grounded at one end.
* The total length of the signal line shall not be more than 600m.
* The code is dialed to ìONî position with the overline at the state of strapping if the code or
overline status is ì1î; The code is dialed to ìOFFî position with the overline at the state of
disconnection if the code or overline status is ì0î.
* In the table below, the choice in the box ì*î refers to the setting of the socket/overline before
delivery.
*10 2 20 20 20 A,30 mA,0.1S or below
*10 and <15 3.5 25 30 30 A,30 mA,0.1S or below
*15 and <22 5.5 30 40 40 A,30 mA,0.1S or below
*22 and <27 10 40 50 50 A,30 mA,0.1S or below
Items
Total
Current of
Indoor Units(A)
Cross
Section
(mm2)
Length
(m)
Rated
Current of
Overflow
Breaker(A)
Rated Current of Power
Leakage Breaker (A)
Leaking Current(mA)
Operating Period (S)
Cross Sectional
Area of Signal Line
Outdoor
-indoor
(mm2)
Indoor
-indoor
(mm2)
2 cores*0.75-2.0
mm2 shielded line
Code Setting
* Indoor Units PCB
A. With the indoor units controlled by the line control in groups, the address setting of indoor units: SW01
* The setting of SW01 is performed by installation personnel during installation.
* Switch SW01 of the matching indoor unit to ì0î in one line control to one unit, double line controls
to one unit and remote controlling conditions.
0
Position of SW01 Main Unit Position of SW01 Sub Unit
1-15 (The dialing codes of sub units in the same group should be different)
Note:AS*MACHA models are set to remote- controlled type before delivery
Electrical Wiring