Haier YCZ-A001 Installation And Operating Instruction

YCZ-A001
Air conditioner central controller
Contents:
1.Safety precautions ------------------------1
2.Brief description on functions ----------2
3.System general information--------------3
4.Installation and debugging---------------4
6.Outside view and dimensions of the central controller--------------------10
7.Description and function of keys on the controller--------------------------11
8.Operational guide -------------------12-19
9.Failure diagnosis-------------------------20
10.Installation procedure -----------------21
11.Installation and debugging--------22-24
12.Model of monitor/detector----------- 25
13.Performance parameters
and spare parts--------------------------26
To ensure safe and correct operation of the central controller, please read this operational instruction manual carefully before using for thoroughly understanding the information therein. Please keep this manual appropriately.
No.
0010570688
MONI TOR
SET
UNIT
AUTO
TEMP
ROOM TEMP
CENTRAL
REMOTE
TIMER ON EVERY DAY
SELECT
ON OFF
MODE
FAN SPEED
TEMP. TIME
TIME TIMER
CENTRAL REMOTE
CONFI RM
LOCK
TIMER OFF
Total on/Total off
1
Safety Precautions
Below are four kinds of safety precautions and suggestions:
WARNING:
Improper use may result in severe consequences of death or serious injures.
Improper use may result in injures or machine damages; in some cases may cause serious consequences
CAUTION:
: It must be strictly prohibited where marked with Prohibited ,
otherwise may result in machine damages or endanger the user personal safety.
: It must be strictly followed where marked with To be followed , otherwise may result in machine damages or endanger the user personal safety.
Instructions: This information can ensure correct operation of the machine.
Be sure to follow the following important safety precautions.
These precautions should be at hand to be checked at any time when needed. If air conditioner is transferred to a new user, this manual should be as well
transferred to the new user.
WARNING
Entrusting Installation
Installation should be entrusted to after service staff; self-installation may result in electric shock, fire and the similar because of improper installation.
If any abnormal phenomena are found (e.g. smell of burning), please stop running and cut off power supply, and contact after service staff to find out treatment method.
If keep using under this situation, may result in accident of electric and fire.
Power
of f
When intend to move and reset controller, ask after service staff for responsibility.
Improper installation may result in electric shock and fire.
Absolutely not to alter without authorization. Improper alteration may result in accident
of electric shock, fire and the similar.
When repair needed, ask after service staff to handle it.
Improper maintenance and repair may result in electric shock and fire.
Not be allowed to spray flammable spraying agent directly to controller. Otherwise may result in fire. Not be allowed to operate switch with damp hands, and not to spray controller
with water. Otherwise may result in electric shock.
Not be allowed to press switch with matter having sharp tip. Otherwise may result in malfunction or electric shock.
Maintenance
When maintenance or abnormity appeared, be sure to cut off manual operation power. It will cause color change or paint-fading if wipe appearance of operation
portion with gasoline, thinner or chemical wiping cloth; be careful. If operation portion is heavily soiled, shall immerse cloth in diluted
neutral detergent, and wipe that portion after wring the cloth, and wipe cleanly with dry cloth.
2
Brief description on functions
The remote central controller (hereunder as central controller ) is a neces­sary part at the option of the user for Haier commercial air conditioner remote monitoring system group control functional network . A remote control moni­tor(or dector) is used to transform standard digital interface and realize bus co­de address communication.Connecting the air conditioner directly,it undertakes local processing and gathering of air conditioner control and operation inform­ation,transmitting control and information data to the central controller.A netw­ork air conditioner (hereunder as air conditioner ) is defined as an air conditio­ner having an indoor computer board with remote control interface, only which could combine with parts such as the monitors and central controller to form a remote monitoring system
group control network , fulfilling the function of
data exchange and monitoring .
The central controller could consult through the monitors as well as display through the LCD the main work status of the air conditioner. With it the work status of main functions of the air conditioner could be set through key input and LCD display . It can also monitor the basic working status of all air conditioners in the network . In addition, the central controller is equipped with a 24 hours real-time clock system for centrally control the clocks in the network . Brief descriptions are given as follows :
1. Communication function
Communicate with the monitors in the group control network
To communicate with the monitors through the RS-485 bus (A, B). The central controller sends commands to and receives response from the monitor; communication by address enables sending and receiving control information, work information and fault information between the monitors and the central controller.
2. LCD display function:
The LCD could display the fundamental status of air conditioning units (are the units existing? On/off? Fault? Are units group selected? Cursor and the current unit no.); The LCD can display the working status of the air conditioning unit with the current number (mode, fan speed, temperature setting, room temperature,timer, error code, central/remote control status); The working status of the central controller (monitor/set status, panel locking status, signaling status).
3. Key input function:
The keys for moving the current unit number cursor and for group selection:
, ,
, , SELECT;
The keys for setting working status of the air conditioning unit and control conditions: ON/OFF, MODE, FAN SPEED, TEMP TIME
/
, CLOCK,
TIMER, CENTRAL/REMOTE, SET; The key for locking key function of the central controller: LOCK.
4. Unit number setting function:
To enrich the control functions of Haier commercial air conditioner remote monit­oring system, multiple controllers could be set to work together for a combination of multiple functions. For this, the central controller is provided with a two-digital switch for setting controller address.
3
(Fig.2)
(Fig.1)
System general information
1. Realizing group control function with the central controller
A monitor is connected with an air conditioner through A+, A- of the 4-wire screw terminals on the interface for air conditioner, meanwhile the monitor dial switch shall be set as single unit working mode and the address unit number shall be set according to the planed scheme, see "Setting of the Dial Switch" for detailed setting and corresponding addresses. For realizing group control function through the central controller, the system still needs to connect the monitors. Each monitor shall be connected with the twin twisted shielded communicating bus through the two­wire screw terminals (A, B) on the RS-485 interface. For the communicating bus, it is required to be shield grounded and the resistances on two sides shall be matched.
2.Realizing double unit switch-over group control function with the central controller
A monitor is connected with two air conditioners with the same model through the 4-wire screw terminals on the interface for air conditioner, meanwhile the monitor dial switch shall be set as double unit switch-over working mode with the default switch-over time of 24 hours, and the address unit number shall be set according to the planed scheme, see Setting of the Dial Switch
for detailed setting and corre­sponding addresses. For realizing double unit switch-over group control function through the central controller, the system still needs to connect the monitors. Each monitor shall be connected with the twin twisted shielded communicating bus through the two-wire screw terminals (A, B) on the RS-485 interface. For the comm­unicating bus, it is required to be shield grounded and the resistances on two sides shall be matched.
RS-485 bus Upper A Lower B
Rear view of the central controller
View of the monitor interface
Power cord
Power on/off
Indoor unit
Outdoor unit
A RS-485 B
RS-485 bus Upper A Lower B
4
Installation and debugging
(Fig.3)
3. For some newly-developed models, such as A******BEA, A******BIA, A******ERA, in indoor PCB , we set the stanard connector data transforma-
tion function of the detector. They can connect the central controller directly through the RS-485 communication protocol. The detailed information refers to the operation manual with the unit.
For the above models, have no double unitswitch-over group control function.
If you want the timing function, the weekly timer YCS-A001 is necessary,
and is used together with YCZ-A001. The address seeting of weekly timer needs to be adjusted, please refer to the operation manual with the unit.
The detailed information refers to the operation manual with the unit.
RS-485 bus Upper A Lower B
Rear view of the central controller
Indoor unit
Outdoor unit
RS-485
5
(Fig.4)
Installation manual for wire controller
The communication wiring is 4 meter long; if the actual length is more than it, please distribute wiring according to below table:
2. Communication wiring:
The wired controller is equipped with special communication wiring in the accessories. 3-core terminal (Polar wire) is connected with the terminal A, B, C of wired controller respectively.
1. Wiring connections of wired controller:
There are three methods to connection wired controller and the indoor units: A.One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wired controller and the master unit (the indoor unit connected with wired controller directly), the others connect with the master unit through 2 pieces of polar wire.
B. One wired controller controls one indoor unit, and the indoor unit connects with
the wired controller through 3 pieces of polar wire.
C. Two wired controllers control one indoor unit. The wired controller connected with indoor unit is called master one, the other is called slave one. Master wired controller and indoor unit; master and slave wired controllers are all connected through 3 pieces of polar wire.
*One side of the shielded sheet of communication wire must be earthed.
Communication wiring length(m) Dimensions of wiring < 100 0.3mm2x3-core shielded wire
100 and <200 0.5mm2x3-core shielded wire
A B C
Wired controller
Control wiring of wired controller, polar.
1 2 3
1 2 3 1 2 3
1 2 3
1 2 3
Indoor 16Indoor 15Indoor NIndoor 2Indoor 1
Wired controller Wired controller Wired controller Wired controller Wired controller
(master unit)
1 2 3
Indoor 1
Wired controller
A B C
Wired controller
Polar wire
1 2 3
Indoor 1
Wired controller
A B C
Wired controller
Polar wire
A B C
Wired controller
Polar wire
A
B
C
Cut off Cut oonnected
SW0-1 Master unit Slave unit
Note
6
Installation manual for wire controller
3.Setting address method:
The dip switch of indoor unit usually marked with "SW" or "BM", you can refer the
below table to set address:
If you use central controller , the clip switch will be used simultaneously. Wiring request in central control type: port A-B is connected with indoor port refer to A-B through 2-core shield wire. Requirements:
1.Port A connects with port A of all indoor units.
2.Port B connects with port B of all indoor units. Refer to the Figure 3 to wiring.
The address setting can be realized by the dip switch, which used to set address in
indoor PCB. Please refer the indoor unit circuit diagram to find the dip switch.
If you use the group control function, there should be a master unit and 15 sets of
slave units.Refer to the operation manual with the unit to set the master unit or the slave
units.
The indoor PCB is matched with this wired controller (YR-E12)which can be set according to below table:
When the wired controller controls several indoor units, there is only one Master unit, and other can be set as Slave unit. The detailed information manual with the unit to set the master unit or the slave units.
The wired controller must be used with cooperation with indoor unit. When wired control type is selected, the function of indoor unit must be adjusted (after power cut off).
Indoor unit address
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
SW1-4
OFF OFF OFF OFF OFF OFF OFF OFF
ON ON ON ON ON ON ON ON
SW1-3
OFF OFF OFF OFF
ON ON ON
ON OFF OFF OFF OFF
ON
ON
ON
ON
SW1-2
OFF OFF
ON
ON OFF OFF
ON
ON OFF OFF
ON
ON OFF OFF
ON
ON
SW1-1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
7
Installation manual for wire controller
Address on central controller 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
Indoor unit address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
SW2-3 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
SW2-2 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON
SW2-1 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
SW1-4 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON
SW1-3 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF
SW1-2 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF
SW1-1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON
8
Installation manual for wire controller
SW2-1 OFF OFF OFF OFF OFF OFF
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON
SW1-4 ON ON ON ON ON ON
OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF
SW1-1 OFF ON OFF ON OFF ON
OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
Address on central controller 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85
Indoor unit address
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------
SW2-3 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
SW2-2 ON ON ON ON ON ON
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
SW1-3 OFF OFF ON ON ON ON
OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON
SW1-2 ON ON OFF OFF ON ON
OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF
Loading...
+ 19 hidden pages