1.Definition of the Model........................................................................................................................................................3
2. Appearance and Parts................................................................................................................................................................3
4. Electrical parts and circuit diagram..........................................................................................................................................5
5. Spare Part List of Cooling System........................................................................................................................................... 6
6. Exploded View& Spare Part List............................................................................................................................................. 8
7. Instruction of operation.......................................................................................................................................................... 16
8.Inspection for Main part.......................................................................................................................................................... 20
2.press“sensor”or“cal cancel”to change the parameter
1P-2P-3P-4P-5P-1P
3.press“cal”choose the current parameter and display the value
Showthevalueof
parameter
4.press“sensor”or“cal cancel”to rise or decrease the value t until proper
5.press“cal”save and back
1P~5P
6.set all the parameter,press“cal” for at least 5s,or no operation for 10s save and exit.
Alarm
Code
Name
Alarm type
Troubleshooting
Sensor
error
E1
Upper sensor failed
Buzzer &light &code
Inspect upper sensor
E2
Lower sensor failed
Buzzer &light &code
Inspect lower sensor
E3
Control sensor failed
Buzzer &light &code
Inspect control sensor
E4
Defrosting sensor failed
Buzzer &light &code
Inspect defrost sensor
Door
open
N/A
Door open for 10min
Buzzer &light
Inspect door switch or close
door
High or
low
temp.
N/A
The upper or lower temp. beyond the
range
Buzzer &light
Power
failure
N/A
Power failed
Powerlight&buzzer&
alternate display temp.
Inspect power
Battery
E5
Low battery or switch is off
Buzzer &light &code
Inspect battery or switch
Remote
alarm
N/A
Above all will trigger the remote
alarm.]
-
-
E.Special considerations for installation
C.3 USB storage function
Notice: 1P to 5P means year, month , day, hour,minute.
C.4 Self-inspection for alarm function
Press “alarm test” button to simulate all alarm functions, make sure the buzzer, light and remote contacts work fine.
C.5 Anti condensation function of cabinet mouth
When humidity was too high,the condensation phenomenon may happen at the cabinet mouth. Open the cover of
the switch box on the lower right side of the machine, turn on the heater switch, this can solve the problem. Otherwise,
turn off the heater switch to save energy.
D.The alarm Code
Notice: For the low battery alarm, please check it by manual, Press “Alarm test” button, if the display panel show E5,
it means the battery is poor or damaged.
1.If the freezer includes USB board,Please adjust the system time of the USB board
2.If the freezer includes printer, Please adjust the system time of the printer
3.The blood bank freezer is Air cooling freezer, when put the goods into the freezer, not too dense, make sure the airflow
can go through the shelves
4.The freezer has 4 wheels and 2 feet, After installation, make the two feet back to the earth, keep the freezer stably
19
Page 20
8. Inspection of Main part
4 screws (M4)
4 screws (M4)
Transformer of
door heater
Control board
Power board
Remote alarm
USB support
Cabinet mouth
heater switch
Battery switch
Power switch
A.The position of Control board and power board
1)Control board, power board and USB board
a. Yellow-green wire is the earth
b.The two red wires connect with point C and point H of theAnti-high temp thermostat(Part code 0274000087A );
c. The two black wires connect with point C and point L of the Anti-low temp thermostat(Part code 0274000092B).
e. Inner fan-motor cable