Haier HSU24XH Installation Instruction

Installation Manual of Room Air Conditioner
Preparation
Necessary Tools for Installation
Torque wrench
Hammer Nipper Hacksaw Pipe cutter Hole core drill Flaring tool Spanner(17,19 and 26mm) Knife Gas leakage detector or soap-and-water solution
(17mm,22mm,26mm)
Measuring tape Reamer
Power Source
Before inserting power plug into receptacle, check the voltage without fail. The power
Install an exclusive branch circu
A receptacle shall be set up in a distance where the power cable can be
reached.
source is the same as the
Do not extend the cable by cutting it.
corresponding name plate.
it of the power.
Drawing for the installation of indoor and outdoor units
The models adopt HC FC free ref
more than 10cm
(3 7/8)
more than
10cm (3 7/8)
rigerant R410A
Selection of Installation Place
Indoor Unit - Select a location that is
Robust not causing vibration, where the body can be supported sufficiently.
Not affected by heat or steam generated in the vicinity, where inlet and outlet of the
unit are not disturbed. Possible to drain easily, where piping can be connected with the outdoor unit.
Where cold air can be spread in a room evenly.
Nearby a power receptacle. (Refer to drawings).
Place where the distance of more than lm from televisions, radios, wireless apparatuses
and uorescent lamps can be left. In the case of xing the remote controller on a wall, place where the indoor unit can
receive signals when the uorescent
Outdoor Unit - Select a location that is
Less affected by rain or direct sunlight and is sufficiently ventilated.
Strong enough to bear the unit, where vibration and noise are not increased.
Not causing a nuisance to neighbors due to discharged air or noise.
A distance marked
Attention must be paid to the pitch of drain hose
G
is available as illustrated in the below gure.
lamps in the room are in use.
Optional parts for piping
Non-adhesive tape
A
Adhesive tape
B
Saddle (L.S) with screws
C
Connecting electric cable
D
for indoor and outdoor
E
Drain hose
F
Heating insulating material
Piping hole cover
G
Arrangement of piping directions
Rear left
Left
Below
The marks from to
G
in the gure are the parts numbers. The distance between
the indoor unit and the oor should be more than 2m.
more than 60cm
Rear right
Right
A
(23 5/8)
more than 20cm
(7 7/8)
more than 10cm
(3 7/8)
more than 15cm
(5 7/8)
F
A
C
D
more than 25cm
(9 7/8)
Floor xing dimensions of the
outdoor unit
140 500
(5 1/2)
(Unit:mm / inch)
(19 2/3)
140
(5 1/2)
256
(10 1/16)
Fixing of outdoor unit
Fix the unit to concrete or block with bolts (10mm) and nuts rmly and horizontally. When tting the unit to wall
surface, roof or rooftop, x
E
a supporter securely with nails or wires in consideration of earthquake and strong wind. If vibration may affect the
house, x the unit by attaching a vibration-proof mat.
The above picture is for your reference only. Your product may look different.
Read this manual before installation. Explain the operation of the unit to the user according to this manual.
NO.0010536242
Accessory parts
Remote controller (1)
AAA dry battery (2)
Mounting plate (1)
Plastic cap (4)
Ø4X25 Screw
(4)
Drain hose (1)
Cushion (4)
Drain-elbow (1)
Pipe supporting plate (1)
Selection of pipe
Liquid pipe (Ø)
Gas pipe (Ø)
NOTEThe thickness of the pipe must be 0.8mm(1/16”) at least.
6.35mm(1/4”)
9.52mm(3/8”)
Indoor unit
1
Fitting of the Mounting Plate and
When the mounting plate is rst xed
1. Carry out, based on the wall studs or lintels, a to be xed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by
weight from the central top of the plate, then fasten the plate.
3. Find the wall hole location A using a measuring tape
Positioning of the wall Hole
proper leveling for the plate
hanging a thread with a
Ø
70mm
B=
(2 3/4)
[ Left·Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to
the mark of hole for left-rear piping which is marked on heat insulation materials.
1. Insert the drain hose into the carity of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor ut on the front side, then connect them.
o
3. Coat the aring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials, cover with adhesive tape.
Heat insulation
Lid for right piping
Lid for under piping pipe
Fix with adhesive tape
Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping with protecting tape.
Lid for left piping
material
Drain hose
unit, and pull it
Indoor/outdoor electric c able
Piping
Pipe supporting plate
[ Other piping direction ]
Cut away, with a nipper, the lid for piping according to the piping direction and
then bend the pipe according to the position of wall hole. When bending, be
careful not to crush
Connect beforehand the indoor/outdoor electric cable,
connected to the heat insulation of connecting part specially.
pipes.
and then pull out the
Fixing the indoor unit body
Hang the unit body securely onto the upper notches of the
mounting plate. Move the body from side to side to verify
its secure fixing. In order to x the body onto the mounting plate,hold up
the body at a slant from the underside and then put it down perpendicularly.
mounting plate
Unloading of indoor unit body
A=145mm
(5 5/7)
B=
A=145mm
(5 5/7)
2
Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 70 mm (2 3/4) in diameter, slightly descending to outside the wall.
Install piping hole cover and seal it off with putty after installation
Wall hole
Ø
70mm
(2 3/4)
(1 3/8)
35mm
30mm
B= 70mm
A=150mm
(5 7/8)
(1 1/6)
(2 3/4)
Pitch downward for drainage
Ø70mm
(2 3/4)
Indoor side
Thickness of wall
Outdoor side
35mm
(1 3/8)
When you unload the indoor unit, please use
your hand to raise the body, then lift the bottom of the body outward slightly and lift the unit until it leaves the mounting plate.
mounting plate
4
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then take
off wiring cover by removing its screws.
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable
making a loop.
When connecting the cable before installing the indoor unit
Insert the cord from the back side of the unit, then pull it out on the front side.
Fasten the unit wire harness to the conduit holder using the lock nut.
Position the conduit holder to its original state using screw.
3
Installation of the Indoor Unit
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
2
Drawing of pipe
Conduit holder
When connecting the cable, conrm the terminal number of indoor and
Note
outdoor units carefully. If wiring is not correct, improper operation may occur and cause damage to the units.
Cut the 6 slit sear