Haier HSU12VHGDB-W, HSU18VHGDB-W, HSU24VHGDB-W, HSU09VHG-W, HSU12VHG-W Installation Manual

...
Drawing for the installation of indoor and outdoor units
Necessary Tools for Installation
ƽ
Torque wrench
ƽ
(17mm,2 2mm, 26m m)
Nipper
ƽ
Reamerƽ
Pipe cutterƽ
Gas leakage detector orƽ soap-and-water solution
Hole core drillƽ
Flaring toolƽ
Spanner(17,19 and 26mm)ƽ
ƽ
Selection of Installation Place
Power Source
Preparation
The above picture is for reference only. Your product may look different.
Read this manual before installation Explain the operation of the unit to the user according to this manual
NO.0010538926
Installation Manual of Room Air Conditioner
F
A
C
E
D
Optional parts for piping
Non-adhesive tape Adhesive tape Saddle(L.S)withscrews Connecting electric cable
forindoorandoutdoor
Drain hose Insulating material
Piping hole cover
Floor fixing dimensions of the outdoor unit
Fixing of outdoor unit
Fix the unit to concrete or blockƽ
with bolts
(10mm) securely. When fitting the unit to wall
ƽ
surface, roof or rooftop, fix the unit securely in consideration of
earthquake and strong wind.
If vibration may affect the
ƽ
house, fix the unit
by attaching a
vibration-proof mat.
The marks from to
in the figure are the name of the parts. Thedistancebetween theindoorunitandthe floor should be more than 2m or 6 feet.
ThemodelsadoptHFCfreerefrigerantR410A
more than 10cm
more than 5cm
more than 10cm
more than 10cm
more than15cm
more than
60cm
A
G
ƽ
ƽ
A
F
C
E
D
G
B
Arrangement of piping directions
Rear left
Left
Rear right
Right
Below
G
Attention must be paid to
the pitch of drain hose
XYX
Z
Dimensions(mm/inches)
Model
xyz
140 500 256
140
500
256
583
319.5
113.5
633
340
HSU09VHG(DB)-W
HSU12VHG(DB)-W
HSU18VHG(DB)-W
HSU24VHG(DB)-W
Hammer
ƽ ƽ
ƽ ƽ
Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps 3 feet or approximately.
ƽ
In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent
ƽ
lamps in the room are in use.
ƽ ƽ ƽ
A distance marked
ƽ
Q
is available as illustrated in the below figure.
Indoor Unit - Select a location that is
Outdoor Unit - Select a location that is
Robust not causing vibration, where the unit can be supported s ufficiently. Not affected by heat or steam generated in the vicinity, and where the inlet and outlet of the unit are not disturbed. Possible to drain easily, and where piping can be connected with the outdoor unit. Where conditioned air can be spread in a room evenly.
Less affected by rain or direct sunlight and is sufficiently ventilated. Strong enough to bear the unit, where vibration and noise are not increased.
Not causing a nuisance to neighbors due to discharged air or noise.
(Unit:mm / inch)
(5 1/2)
(5 1/2)
(4 1/2)
(4 1/2)
113.5
(19 2/3)
(19 2/3)
(23)
(24 7/8)
(10 1/16)
(10 1/16)
(12 5/8)
(13 1/2)
(1 15/16 inches)
(3 15/16 inches)
(3 15/16 inches)
(3 15/16 inches)
more than 10cm
(3 15/16 inches)
(5 7/8 inches)
(23 5/8 inches)
All wiring to the unit must be in accordance with the National Electric code and local ordinances.
Indoor unit
Make a hole of B mm / inches
in diameter, slightly descending
to outside the wall.
ƽ
Install piping hole cover and seal it off with putty after installation
ƽ
When the mounting plate is first fixed
1. Carry out, based on the wall studs or lintels, a to be fixed against the wall, then temporarily fasten the plate with one nail.
2. Ensure
the proper level of the plate, by
hanging a thread with a
weight from the central top of the plate, then fasten the plate.
3. Find the wall hole location A using a measuring tape
FittingoftheMountingPlateand
Positioning of the wall Hole
Lid for right piping
Lid for under piping pipe
Fix with adhesive tape
Lid for left piping
Indoor/outdoorelectriccableanddrainhosemustbeboundwithrefrigerant
ƽ
piping with adhesive.
[ Other direction piping ]
Cut away, with a nipper, the lid for piping according to the piping direction and
ƽ
then bend the pipe according to theposition of wall hole. When bending, be careful not to crush
pipes.
Make sure that the wires connecting the indoor and outdoor units are not covered by the refrigeration piping insulation and are long enough to connect to the terminal block on the indoor unit.
ƽ
proper leveling for the plate
Making a Hole on the Wall and Fitting the Piping Hole Cover
Drawing of pipe
Installation of the Indoor Unit
[Rearpiping ]
Drawpipesandthedrainhose,thenfastenthemwiththeadhesivetape
ƽ
[Left·Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping.
ƽ
In case of left-rear piping, bend the pipes according to the piping direction to
ƽ
the mark of hole for left-rear piping which is marked on insulation materials.
1. Insert the drain hose into the carity of heat insulation materials of indoor unit.
2.Inserttheindoor/outdoorelectriccablefrombackside of indoor
unit, and pull it
out on the front side, then connect them.
3.Coattheflaringsealfacewithrefrigerantoilandconnect pipes. Cover the tubing connection with insulation materials closely, and with adhesive
tape.
Fixingtheindoorunitbody
Hang the unit body onto the upper notches of the
ƽ
mounting plate. Move the body from side to side to verify
its
secure fixing.
Inordertofixthebodyontothemountingplate,holdup
ƽ
thebodyfromtheundersideandthenputitdown perpendicularly.
mounting plate
When you unload the indoor unit,please use
lift the bottom of the body outward slightly and lift the unit until it leaves the mounting plate.
agraffe
mounting plate
Unloading of indoor unit body
ƽ
your hand to raise the body , then
Remote controller (1)
AAA dry battery (2)
Mounting plate (1)
Drain hose (1)
Ø4X25 Screw
(4)
Plastic cap (4)
Drain-elbow (1)
Cushion (4)
Pipe supporting plate (1)
Accessory parts
NOTE˖The thickness of the pipe must be 0.8mm(1/16”) at least.
Selectionofpipe
2
Insu lati on material
Drain hose
Piping
Pipe supporting plate
Indoor/outdoor electric cable
Indoor side
Outdoor side
ØBmm
Wall hole
Thickness of wall
(Section of wall hole)
Piping hole pipe
G
Model Liquid pipe (Ø)
Gas pipe (Ø)
6.35mm (1/4")
6.35mm (1/4")
6.35mm (1/4")
9.52mm (3/8")
9.52mm (3/8")
9.52mm (3/8")
12.7mm (1/2")
15.88mm (5/8")
A = 145mm
30mm
A = 145mm
B =
Ø 60mm
30mm
B = Ø 60mm
B= 70mm
35mm
A=150mm
A=150mm
mm
35mm
12k
18k
24k
HSU09VHG(DB)-W HSU12VHG(DB)-W HSU18VHG(DB)-W HSU24VHG(DB)-W
09k
09k/12k : B= 60mm(2 3/8 inches) 18k/24k : B=70mm(2 3/4 inches)
(5 11/16 inches)
(1 1/6
inches
)
(1 1/6
inches
)
(5 11/16
inches
)
(1 3/8
inches
)
(5 7/8 inches)
(2 3/4
inches
)
(1 3/8
inches
)
(2 3/4
inches
)
(5 7/8 inches)
(2 3/8 inches)
(2 3/8 inches)
Pitch downward for drainage
3
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
Outdoor unit
Install according to the instructions on the 1st page of this manual
When bending the interconnect tubing, ensure the radius is at least 1 1/4" to 1 3/4", 30mm to 40mm to ensure against crushing the tubing.
ƽ
Connecting the pipe of gas side first makes working easier.
ƽ
Ensure the interconnecting tubing is approved for R410A.ƽ
Installation of Outdoor Unit
Half union
Flare nut
Torque wrench
CAUTION
Spanner
Forced fastening without careful centering may damage the threads and cause a leakage of gas.
Connection of pipes
1.Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturerorits service agent or a similar qualified person. The type of connecting wire is H05RN-F
or H07RN-F.
2.IfthefuseonPCboardisbrokenpleasechangeitwiththe
type of
3.Thewiringmethodshouldbeinlinewiththelocalwiringstandard.
4. Use an HVACR circuit breaker or time delay fuse.
T.3.15A/250VAC (Indoor), T.25A/250VAC (Outdoor).
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then take offƽ wiringcoverbyremovingitsscrews.
1. Insert the cable from the outside into the unit through the same hole that has the interconnecting tubing.
2.Pulloutthecableonthefrontside,andconnectthecable
making a loop.
Note
When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not correct, the unit will not operate
When connecting the cable after installing the indoor unit
When connecting the cable before installing the indoor unit
Indoor unit
)C
(3
)
N
(1
)L(
2
)
C
(3
)
N
(
1)L(2
^
Outdoor unit
{
Indoor unit
Outdoor unit
1
2
N
2
) (
3
(C)
L
1
) (
Max.Elevation: Amax = 32ft / 10m (09k / 12k) = 50ft / 15m (18k / 24k)
In case the elevation A is more than 15ft / 5m, oil trap shoud be installed every 5~7m
Max. Length: Bmax = 50ft / 15m (09k / 12k) = 80ft / 25m (18k / 24k)
HSU09VHG(DB)-W HSU12VHG(DB)-W
HSU18VHG(DB)-W HSU24VHG(DB)-W
ƽ ƽ ƽ
Insert the cord from the back side of the unit, then pull it out on the front side. Fasten the unit wire harness to the conduit holder using the lock nut. Position the conduit holder to its original state using screw.
Power Wiring
4wire 18AWG
Control Wiring
Power cable:
2wire with ground 16AWG
Power cable:
2wire with ground 12AWG (4G0.75 mm )
Power Wiring
4wire 18AWG
Control Wiring
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m/13.3Ft.lbs
Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs
Gas side 12.7mm(1/2") 55N.m/40.6Ft.lbs
Gas side 15.88mm(5/8") 60 N.m/44.3Ft.lbs
properly and could cause a defect.
(4G0.75mm )
2
(4G0.75 mm )
2
(4G0.75mm )
2
2
Ensure that no dirt or debris enters the tubing. The standard tubing length is 15 ft., 5M. If a different length is required, adjust the refrigerant amount by 1/4 oz/ft, 20 g/M for the 9k, 12k and 18k models. For the 24k model, adjust by 1/2 oz/ft, 40 g/M.Before opening the service valves, evacuate the interconnecting tubing and indoor unit. Follow the instruction in section 5 on page 4.
Pipe cutting is carried out with a pipe cutter and burs must
ƽ
be removed.
After inserting the flare nut, flaring work is carried out.
ƽ
CuttingandFlaringWorkofPiping
FlaretoolforR410A Conventionalflaretool
Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A
0~0.5mm
1.0~1.5mm
1.5~2.0mm
0~1/51 inch
3/76 ~1/17 inch
1/17 ~1/8 inch
Flare tooling die
1.Cut pipe
2.Remove burs
3.Inserttheflarenut
4.Flare pipe
Lean
Damage of flare Partial Too outside
Correct Incorrect
Crack
Detach the service port’s cap of
1.
3-way valve, and the valve cap for 2-way valve
and 3-way valve. Connect the service port to the low side of the gauge manifold
Open the handle on the low side of the gauge manifold and operate vacuum pump.
2.
Vacuum the tubing for at least 15 minutes. The vacuum level on the low side gauge should be 29.9 in of Hg, 76 cm of Hg, 0.1 MPa. when vacuuming is complete, close the valve on the manifold and turn off the vacuum pump. The vacuum level should hold for 1-2 minutes. If the vacuum level does not hold, check the flared connections and repeat this step.
3.
Purging Method:To use vacuum pump
Open
Open the 2-way valve 1/4 turn. After 5-6 seconds, close the valve and inspect for leaks with a leak detector or soap solution.
4.
No gas leakage? Go to step 6.
5.
Detach the charge hose6.
from the service port,
open 2-way valve and 3-way
Gauge manifold
Gaugemanifold(for
R410A)
2-way valve Liquid Side
3-wayvalveGasSide
Vacuum pump
Tube(for R410A)
Close
2-way valve
3-way valve
Open 90
O
2-way valve
3-way valve
2-way valve
3-way valve
2-way valve
3-way valve
Valve cap
Valve cap
Serviceportcap
After attaching the caps, check for leakage around the caps.
7.
8.
Step 1.
Step 2.
Step 3.
Step 7.
Step 6.
Step 4.
The power source must be exclusively used for air
ƽ
conditioner.
In the case of installing an air conditioner in a moist place,
ƽ
please install an ea-
For installation in other places, use an HVACR circuit breaker of time delay fuse.
ƽ
If the refrigerant of the air conditioner leaks, it is necessary to discharge all the
ƽ
accordingtotheamountmarkedonthenameplate.
Please do not let other cooling medium, except specified one (R410A), or air
ƽ
enter into the cooling circulation system. This could cause high pressure and
Power Source Installation
CAUTION
rth leakage breaker.(GFCI)
On Drainage
It becomes
high midway.
The gap with the
ground is too small.
There is the bad
smell from a ditch
It waves.
The end is imm­ersedinwater.
Please install the drain hose and ensure downward flow. Please don’t do the drainage as shown below.
ƽ ƽ
Please pour water in the drain pan of the indoor unit, and
ƽ
is proper.
In case that the attached drain hose is in a room, please
ƽ
apply insulation
to
Less than
5cm
confirm that drainage
to the hose to prevent condensation.
4
Check Items for Test Run
Please kindly explain to our customers how to operate throughtheinstructionmanual.
Check for Installation and Test Run
Ƶ
Ƶ
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere. Refrigerant type:R410A GWP* value:1975 GWP=global warming potential Please fill in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
Refrigerant charge labelƵ
Put check mark
in boxes
To prevent the gas
leakage,
continues, remove the refrigerant used for the leakage check and flare tubes again. Repeat vacuum and leak and if no leakage, proceed to step 6.
replace the service port and valve caps.
Gas leak from interconnecting tubing? Installation is on the interconnecting tubing? Are the connecting wirings of indoor and outdoor firmly
Is the connecting wiring of indoor and outdoor firmly fixed? Is drainage securely carried out? Is the ground wire securely connected? Is the indoor unit securely fixed? Is power source voltage the local codes?
Is there any noise?
Are the lights near the unit working normally? Are cooling and heating (when in heat pump) performing
normally?
Is the operation of room temperature control normal?
inserted to the terminal block?
Loosenthescrewson
ƽ
terminal block and
insert the wires fully into terminal
block, then tighten the screws.
If wiring is not correct, the unit will not operate properly and it could cause a
ƽ
Fix the cable with a clamp.ƽ
Connection
If the drain-elbow is used,ƽ please attach as shown in figure.
(Note:
Onlyforheatpumpunit.)
Attaching Drain-Elbow
defect in the unit.
and connect the vacuum pump to the center port of the manifold.
In case of a leak, try tightening the flare connections to fix the leak. If the leak stops, go to step 6. If the leak continues, check the flare connections and repair as needed, then go back to step 3. then proceed step 6. If leak
valve completely.
refrigerant. Repair the leak, vacuum the unit then charge the liquid refrigerant into air conditioner
could cause a leak and lead to personal injuries.
Loading...