Haier HSU-12HEK03-R2, HSM09HEK03/R2, HSM12HEK03/R2, HSU-09HEK03-R2 User Manual

ROOM AIR CONDITIONER WALL MOUNTED TYPE
INSTALLATION MANUAL
M 09HEK03/R2(DB)
HSM 12HEK03/R2(DB)
HUM 09HA03/R2(DB) HUM 12HA03/R2(DB)
Read this manual before installation
Explain sufficiently the operating means to the user
NO.001051
according to this manual.
1.Driver
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)
5.Torque wrench(17mm,22mm,26mm)
6.Pipe cutter
7.Flaring tool
8.Knife
9.Nipper 12.Reamer
10.Gas leakage detector or soap-and-
water solution
11.Measuring tape
A
B
C
D
E
F
G
Optional parts for piping
Mark
Parts name
Non-adhesive tape
Adhesive tape
Saddle(L.S) with screws
Connecting electric cable for indoor and outdoor
Drain hose
Heating insulating material
Piping hole cover
Arrangement of piping directions
Rear left
Rear right
Left
Below
Right
The marks from to in the figure are the parts numbers.
The distance between the indoor unit and the floor should be more than 2m.
A
G
mc5nahterom
mc01nahterom
mc01nahterom
No. Accessory parts
Remote controller
R-03 dry battery
Mounting plate
Drain hose
Steel nail, cement
Screw
Plastic cap
Drain-elbow
Cover
Cushion
1
1
2
3
4
5
6
7
8
9
10
2
1
1
6
4
1
1
4
1
Number of articles
Accessory parts
4X50
4X25
Pipe supporting plate
11
Connecting cable
1
Note:Cooling only units don't have Drain-elbow
Drawing for the installation of indoor and outdoor units
Necessary Tools for Installation
mc
01nahterom
mc06nahter
om
mc51nahterom
mc01nahterom
Attention must be paid to the rising up of drain hose
A
D
Floor fixing dimensions of the outdoor unit (Unit:mm)
Fixing of outdoor unit
Indoor Unit
Place, robust not causing vibration, where the body can be supported sufficiently. Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed. Place, possible to drain easily, where piping can be connected with the outdoor unit. Place, where cold air can be spread in a room entire Place, nearby a power receptacle, with enough space around. (Refer to drawings). Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left. In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened.
Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally. When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails
or wires in consideration of earthquake and strong wind. If vibration may affect the house, fix the unit by attaching a vibration-proof mat.
Selection of Installation Place
Place, which is less affected by rain or direct sunlight and is sufficiently ventilated. Place, possible to bear the unit, where vibration and noise are not increased. Place, where discharged wind and noise do not cause a
ly.
nuisance to the neighbors. Place, where a distance marked is available as illustrated in the above figure.
Outdoor Unit
Power Source
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate. Install an exclusive branch circuit of the power. A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.
Selection of pipe
To this unit, both liquid and gas pipes shall be insulated as they become Iow temperature in operation. Use optional parts for piping set or pipes covered with equivalent insulation material.
For 09
Liquid pipe ( )
Gas pipe ( ) 9.52mm(3/8")
6.35mm(1/4")
2
For 12
6.35mm(1/4")
9.52mm(3/8")
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
B= 60mm
A=145mm
30mm
When the mounting plate is fixed side bar and lintel
Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar.
Refer to the previous article, " When the mounting plate is first fixed ", for the position of wall hole.
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 60 mm in diameter, slightly descending to outside the wall. Install piping hole cover and seal it off with putty after installation
Indoor side
Wall hole
60mm
(Section of wall hole)
G
Piping hole pipe
Outdoor side
Thickness of wall
3.Installation of the Indoor Unit Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials.
3
Indoor unit
1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials closel
y, and make sure fixing with adhesive tape
Lid for right piping
Lid for under piping
Fix with adhesive tape
Lid for left piping
Heat insulation material
Drain hose
Piping
Indoor/outdoor electric cable
Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.
[Other direction piping]
Cut awa to the position of wall hole. When bending, be careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part speciall
y, with a nipper, the lid for piping according to the piping direction and then bend the pipe according
y.
Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to side to verify its secure fixing. In order to fix the body onto the mounting plate,hold up the body aslant from the underside and then put it down perpendicularl
y.
mounting plate
Unloading of indoor unit body
When you unload the indoor unit,please use your hand to arise
the body to leave agraffe,then lift the bottom of the body outward
slightly and lift the unit aslant until it leaves the mounting plate.
4
mounting plate
agraffe
Indoor unit
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then take o
ff wiring cover by removing its screws.
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.
When connecting the cable before installing the indoor unit
Insert the cable from the back side of the unit, then pull it out on the front side. Loosen the scr Pull the ca
After the ca Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not correct, proper operation can not be carried out and will cause defect.
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar
qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the
5.
distance between its two contacts should be not less than 3mm.
ews and insert the cable ends fully into terminal block, then tighten the screws.
ble slightly to make sure the cables have been properly inserted and tightened.
ble connection, never fail to fasten the connected cable with the wiring cover.
Indoor unit A
Power cable:
4G0.75mm
3G1.5mm
5
2
2
POWER
Outdoor unit A
1 (
N )
2(N)
3(N)
1 (
N )
2(N)
3(N)
{
Outdoor unit
1.Installation of Outdoor Unit
3.Connection
4.Atta
ching Drain-Elbow
2.Connection of pipes
Install according to
To bend a pipe, give the roundness as large as possible not to crush the pipe Connecting the pipe of gas side first makes working easier. The max vertical distance between the indoor unit and the outdoor unit is 5 m.
Use the same method on indoor unit
. Loosen the screws on terminal block and insert the plugs fully into
te
rminal block, then tighten the screws.
If wi
ring is not correct, proper operation can not be carried out and controller may be damaged.
If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.)
Drawing for the installation of indoor and outdoor units
Inse
rt the cable according to terminal number in the same manner as the indoor unit.
Fix the ca
ble with a clamp.
Half union
Spanner
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
Flare nut
Torque wrench
Forced fastening without careful centering may damage the threads and cause a leakage of gas.
Pipe Diameter ( )
Liquid side 6.35mm(1/4")
Gas side 9.52mm(3/8")
Fastening torque
18N.m
42N.m
6
Outdoor unit
5.Purging Method:
Push the air out of the indoor unit and piping as followes:
(1) Remove the valve cap on 2-way valve in outdoor unit. (2) Loosen by 1/2 turn the flare nut of gas pipe, which is
is conneted to 3-way valve.
(3) Loosen 2-way valve by 90
and after approx.10 sec tighten it up. Gas comes out
through flare nut on wide pipe. If no gas is discharged,
tighten flare nut with specified torque. (4) Open 2-way and 3-way valves using specified torque. (5)
Tighten the caps on the valves with specified torque.
Valve rod
Valve cap
When connecting pipe exceeds 5 meters, 20g refrigerant
shall be added per exceeding meter. Charge according to the following list.
Piping length
Additional amount
o
using hexagon wrench,
Tighten torque N.m
7-9
20-25
for 9k 12k
5m 7m
No need 40g
10m
100g
2-way valve
6.35mm(1/4")
3-way valve
9.52mm(3/8")
Outdoor unit
Max.Elevation:
5m
Indoor unit
Outdoor unit
for 12K : A=10m
10m
Oil trap
A
Indoor unit
CAUTION In case more than 5m Oil trap shoud be installed every 5~7m
no more gas if the length of connecting pipe is less than
The height difference between any two indoor or outdoor units can not be
more than 5m.
m7=A : K9 rof :htgneL .xaM
Note: When extending piping, air inside piping shall be removed by using external refrigerant gas, charge according to the following list.
Brand new outdoor unit is charged 50g
more refrigerant than regulated
weight. Only for first installation, this extra 50g can be used to purge air in pipes.
During this procedure, 50g refrigerant will be discharged in piping. (This must be strictly controlled within 90o and 10 sec.)
7m(
9K)
or 10m(12K).
7
1.Power Source Installation
The power source must be exclusively used for air conditioner. (Over I0A) In the case of installing an air conditioner in a moist plac
rth leakage breaker.
ea For installation in other places, use a circuit breaker as far as possible.
e, please install an
2.Cutting and Flaring
Pipe cutting is car After inse
rting the flare nut, flaring work is carried out.
A
ried out with a pipe cutter and burs must be removed.
Flare tooling die
Correct
Lean Damage of flare Crack Partial Too outside
3.On Drain
Please install the d Please don't do the d
age
rain hose so as to be downward slope without fail.
rainage as shown below.
Work of Piping
Liquid side
Gas side
Gas side 12.7mm(1/2")
Incorrect
Pipe diameter( )
6.35mm(1/4")
9.52mm(3/8")
Size A(mm)
0.8~1.5
1.0~1.8
1.2~2.0
It becomes high midway.
Please pour
ried out surely to outdoor.
car
The end is immersed
water.
in
water in the drain pan of the indoor unit, and confirm that drainage is
In case that the attached d to it without
Please kindly
fail.
ck for Installation and Test Run
Che
explain to our customers how to operate through the instruction manual.
Check Items for Test Run
Gas leak from pipe connecting? Heat insulation of pipe connecting? Are the connecting wi indoor and outdoor fi to the te
rminal block? Is the connecting wi and outdoor fi
rings of
rmly inserted
ring of indoor
rmly fixed?
Less than 5cm
It
waves. The gap with the ground
is too small
There is the bad smell from a ditch
rain hose is in a room, please apply heat insulation
Put che
ck mark in boxes
Is d
rainage securely carried out?
Is the ea
rth line securely connected? Is the indoor unit securely fi Is p
ower source voltage abided by the code? Is there a
ny noise?
xed?
Is the lamp no Are cooling and heating (when in heat pump) per Is the ope regulator no
rmally lighting?
formed normally?
ration of room temperature
rmal?
8