Haier HDU-60CA03T3, HDU-50HT03/H, HDU-42CA03T3/H, HDU-50CA03T3/H, HDU-60CA03T3/H Service Manual

Commercial Air Conditioning
SERVICE MANUAL
Models
HDU-50HT03/H
HDU-42CA03T3/H
HDU-50CA03T3/H
HDU-60CA03T3/H
Features
High energy efficiency Fixed frequency
Long distribution pipe and high drop Flexible and easy installation
Auxiliary electric heating function (optional) Optional safety devices and much more precision control device Weekly timer (standard) Group control function(Optional) Auto restart function
Manual code: SYJS-012-08REV.0 Edition: 2008-07-23
Commercial Air Conditioner
CONTENTS
Contents………………………………………………………...2
1. Description of products & features………………………..3
2. Specification…………………………………………………5
3. Safety precaution……………………………………………7
4. Net dimension………………………………………………..9
5. Installation instructions………..……………………………10
6. Parts and functions…………………………………………15
7. Controller functions…………………………………………16
8. Electrical control functions…………………………………16
9. Electrical data……………………………………………….31
10. Troubleshooting…………………………………………...34
11. Noise curves..................................................................36
12. Performance curves.......................................................37
2
Commercial Air Conditioner
1.DESCRIPTION OF PRODUCTS & FEATURES
1.1. Products code explanation
1.2 Brief Introduction for T1 、T2、T3 working condition
Type of Air
Conditioner
Climate type
T1 T2 T3
Cooling Only
18 ~43 10~35 21~52
Heat pump
-7~43 -7~35 -7~52
Electricity Heating
~43 ~35 ~52
1.3 Operating Range of Air Conditioners(for T3 climate)
Temp. Mode Rated Maximum Minimum
Cooling
Indoor
DB
29 32 18
WB
19 23 14
Outdoor
DB
46 52 10
WB
24 31
6
Heating
Indoor
DB
20 27 15
WB
14.5 --- --
Outdoor
DB
7 24 -7
WB
6 18 ---
H D U - 42 C A 03 T3 / H
H:high ESP duct unit;M:middle ESP duct unit
T3:climate type
Power supply type: 03 stands for 200-220V, 50Hz
Design sequence
C: cooling; H: heating
Cooling capacity: 42=42000BTU/h
U: single split unit
Product type : “B” stands for cassette type, “CF” stands for
convertible type, ”D” stands for duct, ”P” stands for cabinet
system,
Haier Brand Air Conditioner
3
Commercial Air Conditioner
1.4 Product features
Flexible and easy installation
The outdoor can meet the higher request of installation. From the specifications, you will find for
each unit, how long and how high the piping will be, which will be convenient for design and installation.
High efficiency filter
The unit adopts G3 grade filter, can efficiently filter the dirt etc, and improve the room air quality, at
the same time, the filter can pull out from downside, convenient for maintenance and cleaning.
Multi-mode for installation
The indoor unit can be installed with or without an air return duct according to the installation need.
Free setting of air discharging duct
The number of the airflow outlet and its installation position can be freely selected according to the
environment of the room, sufficiently considering the load of the room and the uniform temperature of the
room to realize more perfect comfort.
High esp design
Max. external static pressure of 196 Pa brings the quick temperature adjustment to the room.
Adopts high pressure fan to provide quich speed of air blowing while keeping a low sound level and
ensuring a good air circulation of the whole indoor space.
Optional safety devices and much more precision control device
a. Ambient temperature sensor, coil temperature sensor and compressor temperature sensor
make the temperature control and defrosting control more precise.
b. High/low pressure switch can feel the discharging pipe pressure and suction pipe pressure on
time and precisely. If the pressure is too low or too high, it will stop the compressor to prevent it
being damaged for the sake of pressure.
c. 3 minutes delay protection for the compressor, the device can protect the compressor from
some damages and make the compressor have a long life.
Group control and Central control if connected with with a group
controller or a central controller
Weekly timing function, if connected with a weekly timer YCS-A001
4
Commercial Air Conditioner
2. SPECIFICATION
Function
coolin
g
heatin
g
Capacity BTU/h
49800 56300
Capacity kW
14.6 16.5
Sensible heat ratio
0.7
W
6540 5830
W
7767 6160
EER or COP
W/W
2.2 2.8
Dehumidifying capacity
10³×m³/h
Power cable section Signal cable section Connecting cable section Wired control cable for wired control unit section Power source N, V, Hz
A / A Start Current A Class of anti electric shock
CLASS I CLASS I Circuit breaker A Max. operating pressure of heat side Mpa
2.8 2.8
Max. operating pressure of cold side Mpa
2.8 2.8
Unit model (color)
Type × Number Speed(H-M-L) r/min Fan motor output power kW Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mm
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Control type (Remote /wired /model)
dB(A)
kg / kg
Unit model (color)
Model / Manufacture Oil model Oil charging Type Protection type Starting method Type × Number Speed r/min Fan motor output power kW Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mm
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Refrigerant control method mm/mm
Noise level dB(A) crankcase heater power W
kg / kg Type / Charge g Recharge quantity g/m Liquid mm Gas mm
Connecting Method
m m
 4 x 0.33 mm2
55/52/47
40
64
840
6000
Fan
inner grooved/φ9.52
Fan
Compressor
Inner thermal protection
SCROLL
Defrosting
Automatic
Axial*2
hard startup
Capillary tube
0.06
MAX.Drop
50MAX.Pi
ping
length
Weight (Net / Shipping)
91/111
30
Refrigerant
wired
PIPING
R22/4300
65
Pipe
φ9.52
φ19.05
Flared
Between I.D &O.
Outdoor unit
HDU-50HT03/H(WHITE)
Weight (Net / Shipping)
65/80
Dimension
948*340*1250
1090*410*1350
ZR61KH-TFD-522/COPELAND
SONTEX 200 LT
1656
item Model
HDU-50HT03/H
5.0
5G×2.5mm2
Total power input Max. power input
Running /Max.Running
centrifugal
Dimension
50
15602650
1385×965×418
1197×828×355
inner grooved/φ7
 4G×1.5mm2
30
0.27
1110/880/720
3N380-400V50HZ
Indoor unit
HDU-50HT03/H(GREY)
Noise level (H-M-L)
Cooling 9.5A/11.3A Heating 9.1/10.35
5
Commercial Air Conditioner
HDU-42CA03T3/H
cooling only
Btu/h
4200012309W/10584kca/h
%
80
W
4150
W
5700
W/W
3.0
L/h
3.5
N, V, Hz
3N~,380-415V,50Hz
V
342
V
462
A / A
7.5A /10.0A
A
56
A
30
HDU-42CA03T3/H (GREY)
N, V, Hz
1PH,220-240V,50Hz
centrifugal×2
blue plug
H-L
r/min
1215-1050
red plug
H-L
r/min
1140-880
white plug
H-L
r/min
1050-880
kW
0.45
blue plug H Pa
100
red plug H Pa
80
white plug H Pa
50
0Pa m³/h
H:2950 L: 2400
100Pa m³/h
H:2250 L: 1920
0Pa m³/h
H:2460 L: 1980
80Pa m³/h
H:2250 L: 1720
0Pa m³/h
H:2400 L: 1980
50Pa m³/h
H:2250 L: 1820
mm
9.52
0.452
L×W×H mm×mm×mm 1197×830×350 L×W×H mm×mm×mm 1430×940×420
mm
PVC 26/32
hard wired / YR-E12
dB(A)
54-52
kg / kg
62/70
HDU-42CA03T3/H (WHITE)
N, V, Hz
3N~,380-415V,50Hz
ZR54KS-TFD-522/COPELAND
BLENDED WHITE MINERAL OIL
1242cm³ SCROLL
axial×2
r/min
1000±40
kW
0.23×2
m³/h
6000
mm
9.52
2/1.60
L×W×H mm×mm×mm
948×340×1250
L×W×H mm×mm×mm
1095×415×1400
capillary tubes
L
3.2
dB(A)
60
kg / kg
95/100
Hi MPa
2.85
Lo MPa
1.2
g
R22/3000
g/m
65
mm
Φ9.52
mm
Φ19.05
Flare type m30 m50
red plug
white plug
Design Pressure
Total air-flow
External
Control type (type/model)
Oil type Oil charging Type
Noise level H-L with blue plug Weight (Net / Shipping) Unit model
Model / Manufacture
Starting Current
item Model
Outdoor unit
Compressor
Fan + motor
Heat exchanger
Dimension
Tube diameter Face area
Heat exchanger
Power source Min. Spec. Voltage Max. Spec. Voltage Running /Max.Running current
Fan motor input power
Function Capacity Sensible heat ratio Total power input Max. power input EER Dehumidifying capacity
Fan motor input power
Fan + motor
Circuit breaker
Model
Type × Number
Indoor unit
Package
Drainage pipe (material , I.D./O.D.)
Fan speed
Air-flows
Fan motor plugs & static pressure
blue plug
Gas
PIPING
Refrigerant
Pipe
Between I.D &O.D
Connecting Method
MAX.Drop
Recharge quantity Liquid
MAX.Piping length
Volume of Accumulator Noise level Weight(Net / Shipping)
Type / Charge
Power source
Power source
Package
Refrigerant control method
Diameter Row / Fin pitch mm
Speed
External
Type × Number
Dimension
6
Commercial Air Conditioner
HDU-50CA03T3/H
cooling only
Btu/h
5000014654W/12600kca/h
%
77
W
4590
W
6300
W/W
3.2
L/h
4.5
N, V, Hz
3N~,380-415V,50Hz
V
342
V
462
A / A
7.85A /10.5A
A
59
A
30
HDU-50CA03T3/H (GREY)
N, V, Hz
1PH,220-240V,50Hz
centrifugal×2
blue plug
H-L
r/min
1215-1050
red plug
H-L
r/min
1140-880
white plug
H-L
r/min
1050-880
kW
0.45
blue plug H Pa
100
red plug H Pa
80
white plug H Pa
50
0Pa m³/h
H:2950 L: 2400
100Pa m³/h
H:2250 L: 1920
0Pa m³/h
H:2460 L: 1980
80Pa m³/h
H:2250 L: 1720
0Pa m³/h
H:2400 L: 1980
50Pa m³/h
H:2250 L: 1820
mm
9.52
0.452
L×W×H mm×mm×mm 1197×830×350 L×W×H mm×mm×mm 1430×940×420
mm
PVC 26/32
hard wired / YR-E12
dB(A)
54-52
kg / kg
62/70
HDU-50CA03T3/H (WHITE)
N, V, Hz
3N~,380-415V,50Hz
ZR61KS-TFD-522/COPELAND
BLENDED WHITE MINERAL OIL
1242cm³
SCROLL
axial×2
r/min
1000±40
kW
0.23×2
m³/h
6000
mm
9.52
2/1.60
L×W×H mm×mm×mm
948×340×1250
L×W×H mm×mm×mm
1095×415×1400
capillary tubes
L
3.2
dB(A)
60
kg / kg
99/104
Hi MPa
2.85
Lo MPa
1.2
g
R22/3400
g/m
65
mm
Φ9.52
mm
Φ19.05
Flare type
m30 m50
Design Pressure
item Model
Function Capacity Sensible heat ratio Total power input Max. power input EER Dehumidifying capacity Power source
Fan motor plugs & static pressure
Air-flows
Min. Spec. Voltage Max. Spec. Voltage Running /Max.Running current Starting Current
blue plug
red plug
white plug
Heat exchanger
Tube diameter Face area
Circuit breaker
Indoor unit
Model
Fan + motor
Type × Number
Fan speed
Fan motor input power
Dimension
External
Package Drainage pipe (material , I.D./O.D.) Control type (type/model) Noise level H-L with blue plug Weight (Net / Shipping)
Outdoor unit
Unit model
Compressor
Model / Manufacture
Oil type
Oil charging
Type
Package
Fan + motor
Type × Number
Speed
Fan motor input power
Total air-flow
Row / Fin pitch mm
Dimension
External
Between I.D &O.D
Refrigerant control method Volume of Accumulator Noise level Weight (Net / Shipping)
MAX.Drop
MAX.Piping length
PIPING
Pipe
Liquid
Gas Connecting Method
Power source
Power source
Refrigerant
Type / Charge
Recharge quantity
Heat exchanger
Diameter
7
Commercial Air Conditioner
HDU-60CA03T3/H
cooling only
Btu/h
5700016705W/14364kca/h
%
73
W
5200
W
7000
W/W
3.2
L/h
5.5
N, V, Hz
3N~,380-415V,50Hz
V
342
V
462
A / A
9.0.A /13.3A
A
74
A
30
HDU-60CA03T3/H (GREY)
N, V, Hz
1PH,220-240V,50Hz
centrifugal×2
blue plug
H-L
r/min
1210-1050
red plug
H-L
r/min
1150-880
white plug
H-L
r/min
1050-880
kW
0.45
blue plug H Pa
100
red plug H Pa
80
white plug H Pa
50
0Pa m³/h
H:2950 L: 2400
100Pa m³/h
H:2250 L: 1920
0Pa m³/h
H:2460 L: 1980
80Pa m³/h
H:2250 L: 1720
0Pa m³/h
H:2400 L: 1980
50Pa m³/h
H:2250 L: 1820
mm
9.52
0.452
L×W×H mm×mm×mm 1197×830×350 L×W×H mm×mm×mm 1430×940×420
mm
PVC 26/32
hard wired / YR-E12
dB(A)
54-52
kg / kg
62/70
HDU-60CA03T3/H (WHITE)
N, V, Hz
3N~,380-415V,50Hz
ZR68KC-TFD-522/COPELAND
BLENDED WHITE MINERAL OIL
1774cm³ SCROLL
axial×2
r/min
1000±40
kW
0.23×2
m³/h
6000
mm
9.52
2/1.60
L×W×H mm×mm×mm
948×340×1250
L×W×H mm×mm×mm
1095×415×1400
capillary tube+piston throttle (102#)
L
3.2
dB(A)
60
kg / kg
106/111
Hi MPa
2.85
Lo MPa
1.2
g
R22/4000
g/m
65
mm
Φ12.7
mm
Φ19.05
Flare type m30 m50
Norminal condition: indoor temperature (cooling): 29 DB/19WB, Outdoor temperature(cooling): 46DB/24WB, The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level. The detailed method please refer to the following information:
Design Pressure
item Model Function Capacity Sensible heat ratio Total power input Max. power input EER Dehumidifying capacity
Fan motor input power
Fan motor plugs & static pressure
Air-flows
Power source Min. Spec. Voltage Max. Spec. Voltage Running /Max.Running current
blue plug
red plug
white plug
Heat exchanger
Tube diameter Face area
Starting Current Circuit breaker
Indoor unit
Model
Fan + motor
Type × Number
Fan speed
Dimension
External
Package Drainage pipe (material , I.D./O.D.) Control type (type/model) Noise level H-L with blue plug Weight (Net / Shipping)
Outdoor unit
Unit model
Compressor
Model / Manufacture
Oil type
Oil charging
Type
Package
Fan + motor
Type × Number
Speed
Fan motor input power
Total air-flow
Row / Fin pitch mm
Dimension
External
Between I.D &O.D
Refrigerant control method Volume of Accumulator Noise level Weight (Net / Shipping)
MAX.Drop
MAX.Piping length
PIPING
Pipe
Liquid
Gas Connecting Method
Power source
Power source
Refrigerant
Type / Charge
Recharge quantity
Heat exchanger
Diameter
8
Commercial Air Conditioner
Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction. Testing method:
duct unit without auxiliary duct: duct unit with auxiliary duct:
1.4m
2m
duct
auxiliary duct
2m
1.4m
1m
auxiliary duct
outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right directions.
2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, right directions. measured point: H ( height to the ground) = (h (unit height) + 1m) /2 and, it is 1m to each side.
h
1m
1m
1m
1m
Note: is the real time analyser position
9
Commercial Air Conditioner
3. Safety precaution
Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING!
Incorrect operations may result in severe consequences of death or serious injuries.
CAUTION!
Incorrect operations may result in injuries or machine damages; in some cases may cause serious consequences.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
WARNING!
If any abnormal phenomena is found (e. g.smell of firing), please cut off the power supply immediately, and contact the dealer to find out the handling method.
Don't dismantle the outlet of the outdoor unit.
The exposure of fan is very dangerous whichmay harm human beings.
switch
off
In such case, to continue using the conditioner will damage the conditioner, and may cause electrical shock or fire hazard.
Incorrect maintenance and repairment may cause water leak, electrical shock and fire hazard.
When need maintenance and repairment, call dealer to handle it.
After a long time use of air-conditioner the base should be checked for any damages.
If the damaged base is not repaired, the unit may fall down and cause accidents.
10
Commercial Air Conditioner
Air-conditioner can't be installed in the environment with inflammable gases because the inflammable gases near to air-conditioner may cause fire hazard.
Connect earthing wire.
Use discharge pipe correctly to ensure efficient discharge.
Earthing wire should not be con­nected to the gas pipe, water pipe, lightning rod or phone line, in-correct earthing may cause shock.
Incorrect pipe use may cause water leaking.
Earthing
WARNING!
Installed electrical-leaking circuit breaker.
It easily cause electrical shock without circuit breaker.
Please let the dealer be responsible for installing the conditioner.
Incorrect installation may cause water
leak, electrical shock and fire hazard.
Call the dealer to take measures to
prevent the refrigerant from leaking.
If conditioner is installed in a small
room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage.
When conditioner is deinstalled or
reinstalleddealer should be responsible
for them.
Incorrect installation may cause water
leaking, electrical shock and fire hazard.
No goods or nobody is permitted to placed on or stand on outdoor unit.
The falling of goods and people may cause accidents.
Don't operate the air-conditioner with damp hands.
Otherwise will be shocked.
Only use correctly-typed fuse.
May not use wire or any other materials replacing fuse, other-wise may cause faults or fire accidents.
11
Commercial Air Conditioner
4. Net dimension
1105
1200
170 270
250
365
185
250
60
45
800
1320
830
(mm)
948
1250
25
Power wiring Terminal
184 184
55
Screw Hole
580
70
380
18
340
18
(4xM10)
12
NO
L1
500
Commercial Air Conditioner
5. Installation Instructions
5.1 Outdoor unit installation
1. Accessories
"Edging" for protection of electric wires from an
opening edge.
2. Selection of the place of installation
Edging
Select the place of installation satisfying the following conditions and, at the
same time, obtain a consent from the client or user.
Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting.
(1) Open space requirement around the unit
Air inlet
L3
(Servicing
inlet
space)
Air outlet
L2
Air
Note : (1). Fix the parts with screws
(2).Don't intake the strong wind directly to the outlet air-flow hole.
(3).A one meter distance should be kept from the unit top
(4).Don't block the surroundings of the unit with sundries
Unit: mm
Case
Distance
open
open
open
500
150
150
300
300
0
L1 L2 L3
I
II
III
Wind direction
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.
13
Commercial Air Conditioner
3. Installation of outdoor unit
(1) Installation
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
(a) Concrete foundation (b) Foundation anchor
Unit
To fix by bolts
Anchor bolt
Concrete foundation
Unit
Concrete foundation
Anchor bolt
Note: (1) Give enough room for the concrete foundation to fix by anchor bolts.
Note: (1) Place the concrete foundation deep enough.
Install the unit so that the angle of inclination must be less than 3 degrees.
(2) Installation sketch of outdoor unit
340
580
380
948
Power wiring Terminal
25
1250
4. Refrigerant piping
Flare connection
3-way stop valve
Outdoor unit
Gas pipe
Liquid pipe
Indoor unit
2-way stop valve
14