Haier HDU-42HF03/H, HDU-42HK03, HDU-42HK03/H, HDU-42CI03/H, HDU-50HT03/H Installation Instructions Manual

...
Page 1
ROOM AIR CONDITIONER
OUTDOOR UNIT
No.0010576723 H
Before using the air conditioner,please read this manual carefully. Please keep this manual properly for future use.
CONTENTS
INSTALLATION INSTRUCTIONS
HBU-42CF03 HDU-42CF03/H HBU-42HF03 HDU-42CH03/H
HBU-28CF03
HBU-28HF03
HDU-42HF03/H HDU-42CI03/H HDU-42HK03/H HDU-50HT03/H
Page 2
Name of Parts
1
HBU-42CF03 HBU-42HF03 HDU-42CF03/H HDU-42CH03/H
HBU-28CF03
Air inlet
Air outlet
(Inside of unit)
Compressor
Air inlet
Air outlet
(Inside of unit)
Compressor
HBU-28HF03
Air inlet
Air outlet
(Inside of unit)
Compressor
Air inlet
Air outlet
(Inside of unit)
Compressor
HDU-42HF03/H HDU-42CI03/H HDU-42HK03/H
HDU-50HT03/H
Page 3
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING!
CAUTION!
Incorrect operations may result in injuries or machine damages; in some cases may cause serious consequences.
Incorrect operations may result in severe consequences of death or serious injuries.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
Safety Cautions
Carefully read the following information in order to operate the airconditioner correctly.
WARNING!
If any abnormal phenomena is found
(e. g.smell of firing), please cut off the
power supply immediately, and contact
the dealer to find out the handling
method.
Don't dismantle the outlet of the outdoor unit.
The exposure of fan is very dangerous whichmay harm human beings.
switch
off
In such case, to continue using the
conditioner will damage the conditioner,
and may cause electrical shock or fire
hazard.
Incorrect maintenance and repairment
may cause water leak, electrical shock
and fire hazard.
When need maintenance and repairment,
call dealer to handle it.
After a long time use of air-conditioner the base should be checked for any damages.
If the damaged base is not repaired, the unit may fall down and cause accidents.
2
Page 4
Air-conditioner can't be installed in the environment with inflammable gases because the inflammable gases near to air-conditioner may cause fire hazard.
Connect earthing wire.
Use discharge pipe correctly to ensure efficient discharge.
Earthing wire should not be con­nected to the gas pipe, water pipe, lightning rod or phone line, in­correct earthing may cause shock.
Incorrect pipe use may cause water leaking.
Earthing
Safety Cautions
WARNING!
Installed electrical-leaking circuit breaker.
It easily cause electrical shock without circuit breaker.
Please let the dealer be responsible for installing the conditioner.
Incorrect installation may cause water
leak, electrical shock and fire hazard.
Call the dealer to take measures to
prevent the refrigerant from leaking.
If conditioner is installed in a small
room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage.
When conditioner is deinstalled or
reinstalleddealer should be respon-
sible for them.
Incorrect installation may cause water
leaking, electrical shock and fire hazard.
No goods or nobody is permitted to placed on or stand on outdoor unit.
The falling of goods and people may cause accidents.
Don't operate the air-conditioner with damp hands.
Otherwise will be shocked.
Only use correctly-typed fuse.
May not use wire or any other materials replacing fuse, other-wise may cause faults or fire accidents.
3
Page 5
Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the
outlet air-flow hole. (3).A one meter distance should be kept from the
unit top (4).Don't block the surroundings of the unit with
sundries
Installation Procedure
2. Selection of the place of installation
1. Accessories
"Edging" for protection of electric wires from an opening edge.
Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user.
Edging
Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting.
Wind direction
NO
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.
(1) Open space requirement around the unit
L
2
L
3
L
1
500
(Servicing space)
Air outlet
Air inlet
Air inlet
Case
Distance
Unit: mm
open
open
open
500
150
150
300
300
0
L
1
L2
L3
I
II
III
Installation of outdoor unit
4
Page 6
(2) Installation sketch of outdoor unit
310
3. Installation of outdoor unit
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
(1) Installation
Installation of outdoor unit
5
Installation Procedure
635
340
Power Wiring Terminal
Power Wiring Distribution Hole
25
862
730
HBU-28CF03
(b) Foundation anchor
(a) Concrete foundation
Install the unit so that the angle of inclination must be less than 3 degrees.
Note: (1) Give enough room for the concrete foundation to fix by anchor bolts.
Note: (1) Place the concrete foundation deep enough.
Unit
To fix by bolts
Anchor bolt
Concrete foundation
Unit
Concrete foundation
Anchor bolt
(a) Concrete foundation (b) Foundation anchor
Concrete foundation
Unit
Anchor bolt
Anchor bolt
Concrete foundation
Unit
To fix by bolts
Page 7
340
410
Installation of outdoor unit
6
Installation Procedure
580
380
Power Wiring Terminal
Power Wiring Distribution Hole
25
948
840
HBU-28HF03
Power Wiring Terminal
Power Wiring
Distribution Hole
646
447
2
5
1008
830
HBU-42CF03 HDU-42CF03/H HBU-42HF03 HDU-42CH03/H
Page 8
340
Outdoor unit
Gas pipe
Liquid pipe
Flare connection
Indoor unit
3-way stop valve
3-way stop valve
Installation of outdoor unit
7
Installation Procedure
Outdoor unit
Gas pipe
Liquid pipe
Flare connection
Indoor unit
3-way stop valve
2-way stop valve
4. Refrigerant piping
580
380
948
Power wiring Terminal
25
1250
HDU-42CI03/H HDU-42HK03/H HDU-42HF03/H
HBU-28HF03
HBU-28CF03 HBU-42CF03 HBU-42HF03 HDU-42CI03/H HDU-42CH03/H
HDU-42CF03/H HDU-42HF03/H¡¡ HDU-50HT03/H HDU-42HK03/H¡¡¡¡
HDU-50HT03/H
Page 9
(2) Piping size
Install the removed flare nuts to the pipes to be connected, then flare the pipes.
(3) Limitations for one way piping length and vertical height difference.
Precautions for refrigerant piping
Do not twist or crush piping. Be sure that no dust is mixed in piping. Bend piping with as wide angle as possible. Keep insulating both gas and liquid piping. Check flare-connected area for gas leakage.
Connecting method (indoor unit) Apply refrigerant oil at half union as large and flare nut. To bend a pipe, give the roundness as possible not to crush the pipe. When connecting pipe, hold the pipe centre to centre then screw nut on by hand, refer to Fig. Be careful not to let foreign matters, such as sands enter the pipe.
(4) Piping connection
Forced fastening without centering may damage the threads and cause a gas leakage.
Pipe dia Fastening torque
Liquid pipe 6.35mm
Gas pipe 15.88mm
Liquid pipe 9.52mm
Gas pipe 19.05mm
14.2-17.2N.m
61.8-75.4N.m
32.7-39.9N.m
97.2-118.6N.m
Gas pipe 12.7mm
49.5-60.3N.m
HDU-42CH03/H HDU-42CI03/H HDU-42HK03/H HDU-50HT03/H
Gas pipe
Liquid pipe
Gas pipe
9.52x0.8mm
15.88x1.0mm
9.52x0.8mm
19.05x1.0mm
Liquid pipe
Refrigerant piping
8
90+0.5
Installation Procedure
Model
One way piping length
Vertical height difference (between indoor and outdoor)
less than 40 m
HBU-42CF03 HBU-42HF03 HDU-42CF03/H HDU-42HF03/H
HBU-28CF03 HBU-28HF03
less than 50 m
less than 15 m
less than 30 m
HBU-42CF03 HBU-42HF03 HDU-42CF03/H
HBU-28CF03 HBU-28HF03
HDU-42HF03/H HDU-50HT03/H
HDU-42CH03/H HDU-42CI03/H HDU-42HK03/H
Page 10
In the first to third test steps, if the pressure drops, check the leakage in each joint use sense of hearing, feeling and soap water, etc. methods to find the leaking point. After confirming the leaking point, welding it again or tighten the nut tightly again.
Checking the leaking point
First step: 0.3MPa (3. 0kg/cm
2
g) pressurize
over 3 minutes.
Second step: 1.5Mpa (15kg/cm
2
g) pressurize over 3 minutes. Large leakage will be found.
Third step: 3.0 MPa (30kg/cm
2
g) pressurize about 24 hours. Little leakage will be found.
After finishing connection of refrigerant pipe, it shall perform air tightness test. The air tightness test adopts nitrogen tank to give pressure according to the pipe connection mode as the following figure shown. The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the circulation system of outdoor unit, tighten the valve rod before giving pressure (both gas and liquid valve rods).
Outdoor
Completely tightened
Completely tightened
Flare part
Outdoor units
Manhole
Discharging valve
3-way valve totally closed (Gas side)
Low pressure peizometer
High pressure peizometer
Meter separator
Dropping valve
2-way or 3-way valve totally closed (Liquid side)
Nitrogen tank
VL VH
Indoor units
Indoor
Flare part
9
From pressurizing to 24 hours later, eachdifference of ambient temperature will make 0.01MPa(0.1kg/cm
2
g) pressure change. It shall be corrected during test.
Check if the pressure drops
The pressure does not drop-passed The pressure drops-check the leaking point.
5. Air discharging method
CYLINDER OF NITROGEN
SERVICE HOUSE
LARGE SLIP-ON CONNECTOR
SWEAT JOINT
TUBING BRING BRAZED
LINE PRESSURE GAUGE
CYLINDER PRESSURE GAUGE
Installation Procedure
Refrigerant piping
Page 11
It shall use the vacuum pump of (lower than -755mmHg)high vacuum degree and large air
discharging (over 40l/min). The vacuumizing time depends on the length of the connecting pipe, generally is 1~2 hours. When vacuumizing, it shall be confirmed both gas and liquid side valves are closed. If after 2 hours vacuumizing, it cannot reach the vacuum degree below -755mmHg, it can be vacuumized for other 1 hour. If after 3 hours vacuumizing, it still cannot reach the vacuum degree below -755mmHg, check if there is any leaking point and repair the them. If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the V
L and VH on the meter separator and stop vacuumizing. 1 hour later to confirm if the vacuum degree changes. If changes, it indicates there is leaking point in the system. Check the leaking point and repair. After finishing the above vacuumizing, change the vacuum pump into refrigerant pump to charge the refrigerant.
Use vacuum pump to perform vacuumizing. It is strictly forbidden to use the refrigerant to remove the air inside the system. After air tightness test and discharging all the nitrogen, connect the vacuum pump as the following figure shown.
Refrigerant piping
10
When the total length (L) of the two units' connecting pipe is less than 5m, it is unnecessary to charge additional refrigerant. If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter. That is: Refrigerant charging amount = (L-5) x M (g) For HBU-28CF03, HBU-28HF03, HBU-42CF03, HBU-42HF03, HDU-42CF03/H, HDU-42CH03/H, HDU-42CI03/H, HDU-42HK03/H, HDU-42HF03/H, HDU-50HT03/H M=65 Only in COOLING operation can charge the additional refrigerant. When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle. Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the additional refrigerant in liquid condition.
6. Piping and indoor unit vacuumizing
7. Charging amount of refrigerant
2-wayor 3-way valve totally closed (Liquid side)
Indoor units
Indoor
Outdoor
Completely tightened
Completely tightened
Outdoor units
Vacuum pump
Discharging valve
3-way valve totally closed (Gas side)
Low pressure peizometer
High pressure peizometer
Meter separator
V LVH
Flare part
Flare part
P
Installation Procedure
Page 12
HBU-28CF03 HBU-28HF03
5. Electric wiring
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
WARNING
30mA
Item
Model
Phase
3
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
30 20
2.5mm
2
1
40
36 4.0mm
2
Switch
breaker
Earth leakage breaker
Leak
current
30
30mA
40
11
HDU-42CF03/H
HDU-42HK03/H
Installation Procedure
Electric wiring
HBU-42HF03
HBU-42CF03
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.
For the detailed wiring connection with the indoor units, see the corresponding indoor
operation and instruction manual.
HDU-50HT03/H
HDU-42CH03/H HDU-42CI03/H
Page 13
Electric wiring
12
Installation Procedure
FIG.1
HBU-28HF03
W B
L N
Y/G
Y/G
POWER SUPPLY: 1PH,220-230V~,50Hz
To Indoor Unit
W B R BR GR
1 2 3 4 5
Y/G
Y/G
FIG.2
FIG.3
POWER SUPPLY: 3N~,380-400V,50Hz
N 1 2 3
Y/G
R S T
HBU-42CF03 HDU-42CF03/H HDU-50HT03/H HDU-42CH03/H HDU-42CI03/H HDU-42HK03/H
To Indoor Unit
Y/G
To Indoor Unit
W B R BR GR
L N 3 4 5
Y/G
R S T N
Y/G
POWER SUPPLY: 3N~,380-400V,50Hz
FIG.4
To Indoor Unit
W B R W B
1 2 3 L N
HBU-28CF03
Y/G Y/G
Y/G
POWER SUPPLY:
1PH,220-230V~,50Hz
HBU-42HF03 HDU-42HF03/H¡¡
Y/G
Page 14
13
Electric wiring
Installation Procedure
(1) Before starting test run (for Heat pump models)
6. Test run
Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hrs to energize the crankcase heater in advance of operation.
(2) Test run
Run the unit continuously for about 30 minutes, and check the following. Suction pressure at check joint of service valve for gas pipe. Discharge pressure at check joint on the compressor discharge pipe. Temperature difference between return air and supply air for indoor unit.
CAUTION
THIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION WHEN ELECTRIC POWER IS SUPPLIED.BE SURE TO EXECUTE "OFF" OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING.
This unit has a function of automatic restart system after recovering power stoppage.
WARNING
DO NOT CONNECT THE NEUTRAL WIRE TO , OR PHASE. INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG.1 FIG.2 FIG.3.FIG.4.INCORRECT WIRING CAUSE EQUIPMENT DAMAGE.
N R S
T
(3) Wiring procedure
1) Remove set screws on the side before taking off the front panel toward the direction shown in figure.
2) Connect wires to the terminal block correctly and fix the wires with a wire clamp equipped nearby the terminal block.
3) Route the wires in a proper way and penetrate the wires through the opening for electric wiring on the side panel.