Haier HBU-18CL03R1, HBU-36CM03R1, HBU-24CL03R1, HBU-28CM03R1, HBU-42CM03R1 Service Manual

...
HBU-14CL03/R1 (AB142ACNAC+AU142AANAC) HBU-18CL03/R1 (AB182ACNAC+AU182AANAC)
HBU-24CL03/R1 (AB242ACNAC+AU242AANAC) HBU-28CM03/R1 (AB28NACNAC+AU28NAANAC) HBU-36CM03/R1 (AB36NACNAC+AU36NAANAC) HBU-42CM03/R1 (AB42NACNAC+AU42NAANAC)
MANUAL CODE: SYJS-006 EDITION:2002.12.31.
Super low outdoor ambient cooling at -15 Auto-restart function Group control(if connect with a group controller)
Auto-changeover
Compact design of indoor unit Weekly timing(if connect with a weekly timer) With new environment friendly refrigerant R407C
Features
Service Manual
Commercial Air Conditioning
Cassette Type Low Ambient Cooling Series
CONTENTS
1. Description of Products & Features…………………...…….1
2. Specifications…………………………. ………………...……3
3. Safety precaution…………………………..………………….9
4. Net dimensions of indoor and outdoor unit………………...11
5. Installation instructions ……………………. ………………..17
6. Parts and functions …………………………..…… ..……….28
7. Remote controller functions………………………….………31
8. Refrigerant diagram…………………………..……………....43
9. Electrical control functions……………………………………44
10. Diagnostic information(trouble shooting)…………….……51
11. Electrical data.........................................…………….……56
12. Exploded views and parts lists...............……………. ……67
13. Perdormance curves……………............................... ……87
14. Noise level charts.....……………............................... ……93
15. Air velocity distribution …………............................... ……94
CONTENTS
Contents…….................................................………...…….1
- 1 -
1 DESCRIPTION OF PRODUCTS & FEATURES
1.1 Products coding direction
Old code
H BU – 42 C M 03 / R1
Refers to HFC refrigerant
Power: 03(230V/50Hz).04(240V/50Hz).12(115V/60Hz).13(230v/60Hz) Low ambient cooling “H” refer to cooling and heating, ”C” refer to cooling only Nominal cooling capacity (BTU/h), 42=42000BTU/h Indoor and outdoor unit code: "B" Cassette type; "U" Outdoor unit “H” means “Haier”
New code
A B 42 N A C N A C
Climate type: T1 (see table 1), and -15 degree cooling
Design number (A stands for fix speed type) Product type: A stands for heat pump type, refrigerant is R22 B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407 Appearance character Product series: one by one type Applicable voltage: 2 stands for 220-240V/50Hz,4 stands for 220v/60Hz N stand for 380V/50Hz Cooling / Heating capacity,42=42000BTU/h Product type : “B” stands for cassette type, “C” stands for convertible type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller
system, "E" stands for ceiling concealed type, “U” stands for outdoor unit
Air conditioner
1.2 Brief Introduction to T1 T2 T3 working condition
Table 1
Climate type
Type of Air Conditioner
T1 T2 T3
Cool only
18
43 10 35 21 52
Heat pump
-7
43 -7 35 -7 52
Electricity heating
43 35 52
1.3 Operating Range of air conditioners
Low ambient cooling
Operation Operation Range Outside / Inside
Cooling
-15
0
C – 43oC
Dehumidifying
-15
0
C – 43oC
- 2 -
DESCRIPTION OF PRODUCTS & FEATURES
1.4 Products characteristic
Completely invisible machine body
The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air
conditioner allows it to blend right into ceiling.
Superbly efficient healthy filter
Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently.
Flexible and easy installation
Slim design with machine body, completely ceiling concealing and portable shape, all make it
greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift , which
allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free"
mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit
people's comfortable need much more.
Auto-Restart function
When meeting a power failure during running, no matter how long it will be, once the power is
restored, air conditioner will automatic restart with the previous status.
Safety and reliable control due to various signal controls
1 Inputting with press buttons on the panel 2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors, outdoor ambient temperature sensors, outdoor coil pipe temperature sensors)
3 Piping pressure signals 4 Compressor current signals 5 Testing signals 6 System time-shorten signal
7 Water overflowing signal 8 Communication signals between indoor unit and front plate or between indoor unit and outdoor unit .
Precise convenient remote-controlling
When using remote-controlling mode, it is comfortable and convenient to operate.
Silent design
The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to significantly decrease operating noise.
HFC refrigerant technology
To protect the environment, we have adopted the HFC refrigerant. The HFC R407C is of aero ODP
for the purpose of environmental protection.
Low ambient temperature cooling technology
The system can run the cooling operation at the low ambient temperature -15
- 3 -
DESCRIPTION OF PRODUCTS & FEATURES
Function
Cooling Heating
Capacity BTU/h
14000 /
W
2000 /
EER or COP BTU/W
7.00 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz Running current/Starting current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm
Package mm×mm×mm Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HBU-14CL03/R1
1
1PH, 220V-230V, 50HZ
/
Indoor unit
AB142ACNAC / WHITE
CENTRIFUGAL×1
840/650/560
830
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
700×570×276
775×715×361
PVC 18/20
wireless
/
41/39/35
Weight (net / gross)
26/28
Panel
Dimension
L×W×H
630×630×95
685×685×155
Weight (net / gross)
4.2 / 6.3
Outdoor unit
AU142AANAC / WHITE
PG330X2CS-4KU1 / Guangdong TOSHIBA
scroll
Axial-flow×1
800
700/-/-
TP2M/9.52
2/2
0.225
43-60
Dimension
L×W×H
780×250×660
907×344×690
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
49/-/
Four way valve
/
Between I.U. & O.U.
MAX :5
MAX :15
Total power input
Weight (net / gross)
40/48
Piping
R407C
1.95
6.35
2 SPECIFICATIONS
9.52/48.5
/
- 4 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
18000 /
W
2000 /
EER or COP BTU/W
9.00 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz Running current/Starting current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HBU-18CL03/R1
1
1PH, 220V-230V, 50HZ
/
Indoor unit
AB182ACNAC / WHITE
CENTRIFUGAL×1
500/450/380
1050
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
750×750×280
900×900×420
PVC 18/20
wireless
/
43/42/40
Weight (net / gross)
29/39
Panel
Dimension
L×W×H
750×750×80
800×800×180
Weight (net / gross)
3.5/5.8
Outdoor unit
AU182AANAC / WHITE
PG330X2CS-4KU1 / Guangdong TOSHIBA
scroll
Axial-flow×1
800
700/-/-
TP2M/9.52
2/2
0.225
43-60
Dimension
L×W×H
810×288×680 960×406×760
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
52/-/46
Four way valve
/
Between I.U. & O.U.
MAX :5
MAX :15
Total power input
Weight (net / gross)
58/66
Piping
R407C
1.95
6.35
/
7.8/38.2
- 5 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
24000 /
W
2800 /
EER or COP BTU/W
8.57 /
Dehumidifying capacity
10³×m³/h Power source PH-V-Hz Running current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm
Package mm×mm×mm Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HBU-24CL03/R1
3
1PH,220V~230V,50Hz
/
Indoor unit
AB242ACNAC / WHITE
CENTRIFUGAL×1
700/590/470
1300
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
840×840×240 910×910×300
PVC 18/20
wireless
/
39/37/35
Weight (net / gross)
28/30
Panel
Dimension
L×W×H
950×950×80
980×980×100
Weight (net / gross)
6/9
Outdoor unit
AU242AANAC / WHITE
ZR34K3E-PFJ-522 / Copeland
scroll
Axial-flow×1
840/-/-
3240
TP2M/9.52
3/3
0.62
43-60
Dimension
L×W×H
948×830×340
1050×979×440
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
58/-/50
Four way valve
/
Between I.U. & O.U.
MAX :15
MAX : 30
Total power input
Weight (net / gross)
70/85
Piping
R407C
2.5
9.52
13.5/65 /
- 6 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
28000 /
W
2800 /
EER or COP BTU/W
10.0 /
Dehumidifying capacity
10³×m³/h Power source PH-V-Hz Running current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm
Package mm×mm×mm Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HBU-28CM03/R1
3
3N,380V~400V,50Hz
/
Indoor unit
AB28NACNAC / WHITE
CENTRIFUGAL×1
700/590/470
1300
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
840×840×240 910×910×300
PVC 18/20
wireless
/
39/37/35
Weight (net / gross)
28/30
Panel
Dimension
L×W×H
950×950×80
980×980×100
Weight (net / gross)
6/9
Outdoor unit
AU28NAANAC / WHITE
ZR34K3E-PFJ-522 / Copeland
scroll
Axial-flow×1
840/-/-
3240
TP2M/9.52
3/3
0.62
43-60
Dimension
L×W×H
948×830×340
1050×979×440
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
58/-/50
Four way valve
/
Between I.U. & O.U.
MAX :15
MAX : 30
Total power input
Weight (net / gross)
70/85
Piping
R407C
2.5
9.52
13.5/65 /
- 7 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
36000 /
W
3900 /
EER or COP BTU/W
9.23 /
Dehumidifying capacity
10³×m³/h Power source PH-V-Hz Running current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm
Package mm×mm×mm Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HBU-36CM03/R1
5
3N, 380V-400V, 50HZ
/
Indoor unit
AB36NACNAC / WHITE
CENTRIFUGAL×1
780/710/630
950
TP2M/9.52
3/3
0.199
2-7
Dimension
L×W×H
840×1230×280 910×1320×300
PVC 18/20
wireless
/
43/41/38
Weight (net / gross)
38/55
Panel
Dimension
L×W×H
950×1340×80
995×1400×115
Weight (net / gross)
8.4/12
Outdoor unit
AU36NAANAC / WHITE
C-SBN303H8A / SANYO
scroll
Axial-flow×2
840/-/-
6000
TP2M/9.52
5/5
0.92
43-60
Dimension
L×W×H
948×1225×340
1050×1375×440
PVC,18/20
Capillary
Defrosting
Auto
19.05
FLARED
52/-/46
Four way valve
/
Between I.U. & O.U.
MAX :30
MAX : 50
Total power input
Weight (net / gross)
85/111
Piping
R407C
3.2
9.52
- 8 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
42000 /
W
4500 /
EER or COP BTU/W
9.3/
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz Running current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HBU-42CM03/R1
5
3N, 380V-400V, 50HZ
/
Indoor unit
AB42NACNAC / WHITE
CENTRIFUGAL×3
980/880/820
2040
TP2M/9.52
3/3
0.199
2-7
Dimension
L×W×H
840×1230×280 911320×300
PVC 18/20
wireless
/
43/41/39
Weight (net / gross)
46/53
Panel
Dimension
L×W×H
950×1340×80
995×1400×115
Weight (net / gross)
8.4/12
Outdoor unit
AU42NAANAC / WHITE
H73A623DBEA / Bristol
scroll
Axial-flow×2
840/-/-
6000
TP2M/9.52
5/5
0.92
43-60
Dimension
L×W×H
948×1225×340
1050×1375×440
PVC,18/20
Capillary
Defrosting
Auto
19.05
FLARED
64/-/-
Four way valve
/
Between I.U. & O.U.
MAX :30
MAX : 50
Total power input
Weight (net / gross)
85/111
Piping
R407C
3.2
9.52
/
/
- 9 -
SPECIFICATIONS
WARNING
CAUTION
WARNING
CAUTION
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior environment such as engineering shop could cause equipment malfunction. Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires. Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires. When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you purchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur,there is the danger of a resultant oxygen deficiency accident. For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit. Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit. For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires. Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire.
WARNING
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual. Moreover, ask the customer to keep this sheet together with the owner's manual.
Please read these "Safety Precautions" first then accurately execute the installation work. Though the precautionary points indicated herein are divided under two headings, and those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the section. However, there is also a possibility of serious consequences in relationship to the points listed in the section as well.
- 10 -
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (please see nameplate) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing. Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refigerant leakage. The position of indoor unit must be above the floor 2.5m.
WARNING
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone ground wire. Improper placement of ground wires can result in electric shock. The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock. Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
CAUTION
- 11 -
SAFETY PRECAUTIONS
Model: HBU-14CL03/R1 Indoor unit
4 NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Model: HBU-14CL03/R1 Outdoor unit
- 12 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
362
35
75
185
270
122
45
92
104
240
30
90
170
113
131
30
70
32
48
660
270
660
480
30
265
220
200
580
288
810
680
75
65
150
100 100
110
190
170
400
Model: HBU-18CL03/R1 Indoor unit
Model: HBU-18CL03/R1 Outdoor unit
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Model: HBU-24CL03/R1 HBU-28CM03/R1 Indoor unit
180
5555
260
160
240
180
50
30
20
135
1000
以上
安装所需位置
155
950
840
295
950
(悬挂位置)
(天花板开孔)
840
(天花板开孔)
( )
860-890
780
悬挂位置
780
860-890
以上
1500
1500
1500
以上
1500
以上
以上
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Note (1) Fix the parts with screws (2)Don't intake the strong wind directly to the outlet air-flow hole. (3)A one meter distance should be kept from the unit top (4)Don't block the surroudings of the unit with sundries.
Installation Servicing Space(at Least)
Unit:mm
Installation
I
300
100
0
0
150
0
500
100
0
II III
Dimension
L1
Leave space Leave space
Leave space
L2
L3
L4
185 185
55
70
70
Screw Hole
(M10)
580
Power Wiring Terminal
Power Wiring Distribution Hole
L1
L2
L3
L4
Back Air-flow Hole
Back Air­flow Hole
Outlet Air-flow Hole
Repairing Space
70
1024
840
25
Model: HBU-24CL03/R1 HBU-28CM03/R1 Outdoor unit
380
18
340
18
- 15 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
1340
950
840
30
220
20
50
280
260
315
270
135
160
300
295
1070
780
860-890
615
615
1250-1280
(ceiling hole)
over1000
mm
155
123055 55
220
over1500
over1500
over1500
over1500
(hanging position)
Model: HBU-36CM03/R1 HBU-42CM03/R1 Indoor unit
- 16 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
185 185
30 52
88
Screw Hole
(M10)
580
950
Power wiring Terminal
70
1818
340
380
1250
25
Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the outlet air-flow hole. (3).A one meter distance should be kept from the unit top (4).Don't block the surroundings of the unit with sundries
Installation Servicing Space(at Least)
Unit:mm
Installation
I
300
100
0
0
150
0
500
100
0
II III
Dimension
L1
Leave space Leave space
Leave space
L2
L3
L4
L1
L2
L3
L4
Back Air-flow Hole
Back Air­flow Hole
Outlet Air-flow Hole
Repairing Space
Model: HBU-36CM03/R1 HBU-42CM03/R1 Outdoor unit
- 17 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
5.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner, shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter
7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor
11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump 15 .Flat screwdriver
5.2 Standard accessories
Part name
QTY
Shape
Clamp
2 Piece
Washer
8 Piece
6 Piece
Clamp Paper pattern
1 Set
6321
3 Piece
Screw(M5 size)
For installation of paper pattern
Drain hose
1 Piece
Please check if your unit is delivered with following
Part name
QTY
Shape
Dry battery
Insulator Sealing pad Sealing pad Sealing pad
7
8 9
12
1 Piece 1 Piece
Insulator
2 Piece 1 Piece 1 Piece 2 Piece
Small sizeMedium sizeLarge size
For liquid pipeFor gas pipe
R03, 7#
[Other]
Operation Manual
Ornament panel
Remote controller
54
1110
5.3 Installation of indoor unit
5.3.1 Before installation
Determine the way kto carry unit to installation place. Don't remove packing until unit reaches installation place. If unpacking is unkavoidable, protect unit properly.
5.3.2 Selection of installation place
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured. No block to air flow. Water drainage is smpoth. Place strong enough to support unit weight. Place where inclination is not evident on ceiling. Enough space for mainenance. Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.) Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This is helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio wave is strong)
- 18 -
INSTALLATION INSTRUCTIONS
5 INSTALLATION INSTRUCTIONS
8
260
260
(2) Ceiling height
Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and Installation Manual of ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)
Installation space
Air inlet
Air outlet
2500 Over
Air outlet
1500 Over
1500 Over
1500 Over
1500 Over
Air outlet
Air inlet
Air inlet
5.3.3 Preparation
Ornament panel 630mm
ceiling opening 600mm
Indoor unit 570mm
Distance between
Indoor unit 570mm Ceiling opening 600mm Ornament panel 630mm
suspending bolts 460mm
210mm
335mm
35mm
Overlap between ceiling and ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
(1) Position of ceiling opening between unit and suspending bolt.
HBU-14
Unit: mm
Ceiling hole size 690
Suspension bolts pitch 620
Suspension bolts pitch 465
Suspension bolts pitch 485
H BU-18
260mm
Overlap between ceiling and ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
- 19 -
INSTALLATION INSTRUCTIONS
50~100
Roof Anchor bolt Long nut
Suspending bolt
Ceiling
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer
(3) Install a suspending bolt. (Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field. Before going on installing adjust space between ceiling.
<Installation example>
Note: All the above mentioned parts shall be prepared in field.
A
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
780
(Distance between suspending bolts)
(Distance between suspending bolts)
A
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
Suspending bolts
Refrigerant pipe
A
(160)
Suspending bracket
Ceiling
890(Ceiling opening)
(Distance between suspending bolts)
1070
515
515
(Distance between suspending bolts)
860(Ceiling opening)
780
20 Over
Note: Dimension of ceiling opening marked with * can be as large as 910mm, but the matching part of ceiling with ornament panel shall be over 20mm.
HBU-24,28
HBU-36,42
- 20 -
INSTALLATION INSTRUCTIONS
5.3.4 Installation
4
5
7
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.
(1) Install unit temporally
In the case of new ceiling
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1)) (4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem
may occur on floating switch, causing water leakage.) (5) Remove the washer mounlting , and tighten the nut above. (6) Remove the paper pattern.
(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly. (2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ). (3) Proceed with and of "In the case of new ceiling".
Level
Polythene pipe
3
4
In the case of ceiling already exists
Scrtews at the piping outlet is fixed at the corner of drain pan.
Center of ceiling hole Paper pattern
4
Paper pattern
5
Screw (accessory)
5
Screw (accessory)
[Fix the paper pattern]
5.3.5 Refrigerant piping
As for outdoor piping, please refer to installation Manual of outdoor unit.
6
9
Apple refrigerant oil
Torque spanner
spanner
Piping joing
Flare nut
Medium size seal pad 9 (accessory)
Clip 3
Gas pipe
Liquid pipe
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
7
6
(Cover the piping joint with seal pad.)
R0.4 ~ 0.8
A
Pipe size
Tighten torque
A(mm) Flare shape
9.52
3270~3990N.cm
(333~407kgf.cm)
6180~7540N.cm
(630~770kgf.cm)
15.88
19.05
9720~11860N.cm
(990~1210kgf.cm)
12.0~12.4
18.6~19.0
22.9~23.3
90
0.5
45
2
Outdoor is precharged with refrigerant. Be sure to see the Fig.1, when connecting and removing piping from unit. For the size of the flare nut, please refer to Table 1. Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it. Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage). Check piping joints for gas leakage. Insulate piping as shown in Fig. below. Cover joint of gas piping and insulator with seal .
Table 1
Diameter of Pipe Liquid Pipe 6.35mm
Gas Pipe 12.7mm
Tighten Torque
18 N. m
50N. m
- 21 -
INSTALLATION INSTRUCTIONS
5.3.6 Installation of drainage pipe
1-1.5m
Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape. Tighten the clip until head of the screw is less than 4mm from hose. Wind the drain hose to the clip using seal pad 8 . Insulate drain hose in the room.
2
<Cautions for the drain water lifting pipe>
Clip
2
Tape (White)
Self-provided stiff pipe
Clip
2
4mm below
(accessory)
(accessory)
Large size seal pad
Clip
2
10
Installation height shall be less than 280mm. There should be a right angle with unit, 300mm from unit.
Waterring can of plastic
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm) Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening. If downward slope can't be made, take other measures to lift it up. Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
Slope over 1/100
75 below
Self-provided stiff pipe
(accessory)
500 below
300mm below
1~1.5m
280 below
500 below
220
Drain hose 1
(accessory)
drain water lifting pipe
Suspending bracket
Clip
(accessory)
2
Over 100
(Note)
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Specifieations of the water hoses shall meet the requirements for the unit running.
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
Method of water charging
11
When wiring is not complete
Charge water from air outlet
Charge water from inspecting hole
Watering can of plastic pipe should be about 100 mm long
100mm
Water drainage port for maintenance
(Drain water from this hole)
Self-provided stiff pipe
Maintenance
Inspecting hole
Cover of controll box
PCB on indoor
Terminal
Terminal block
Connect with outdoor unit
1 2 3
L
N
Power
1 2 3
Indoor
Outdoor
H07RN-F 3G 4mm
2
H05RN-F 4G 0.75mm
2
1 2 3
R S T
1 2 3
N
Indoor
Power
Outdoor
H05RN-F 4G 0.75mm
2
H07RN-F 5G 2.5mm
2
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block. Note, in this operation, fan will be running. Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove short connection of "CHECK" terminal.
Check water drainage in cooling operation. See also test run.
- 22 -
INSTALLATION INSTRUCTIONS
5.3.7 Wiring
Terminal block
Clip A
Cover of control box
1
Rubber tube A
Grounding lead
Cover of control box
2
Terminal block
Connect with outdoor unit
Out
In
Field wiring
Attach seal pad
Don't fail to seal it, or, water may come in.
Rubber tube
Note: Have it sealed, leaving no space.
Seal pad (small size)( ) (Wind around wire)
12
All supplied parts. materials and wiring operation must in appliance with local code and regulations. Use copper wire only. When make wiring, please refer to wiring diagram also. All wiring work must be done by qualified electricians. A circuit breaker must be installed, which can cut power supply to all system. See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unit Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires, tighten clamp A. Connect wires of correct pole to the terminal block inside. Wind seal (12) around wires. (Be sure to do that, or, dew may occur). Upon connecting, replace control box cover (1) and (2).
Obscrve the following when connecting power supply terminal block: Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit) Connect wires of same specifications as shown in right Fig.
Connect wires of the same specifications at two sides.
Don't connect wires of the same specifications at one side.
Don't connect wires of the different specifications.
<<WARNING>>
5.3.8 Wiring example
As for outdoor unit circuit, please see Installation Manual of outdoor unit. Note: All electric wires have their own poles, poles must match that on terminal block.
5.3.9 Installation of ornament panel
1. Prepare ornament panel Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither on an uneven object. Don' t bend carelessly the swing flap, or, problem may occur.
(1)
Remove air inlet grill from ornament panel:
Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
Lift it up for about 45 degree and remove it from ornament. Tear off adhesive tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 2)
Cautions for the installation
Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read also the Installation Manual of indoor unit. With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.
2
Accessory
Pad
Pad
1
Bar
- 23 -
INSTALLATION INSTRUCTIONS
5 _ 8mm
3
2
2
1
4
Holding ring
Piping hole position
Swing flap motor
Fig. 7
Seal
Indoor unit
Ceiling material
Ornament panel
(2)
Remove cover plate at corner
Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)
(1)
(2)
2. Install ornament panel on indoor unit.
As shown in Fig . 7, match the position of
swing flap motor with that of the indoor unit
piping hole , so that ormament panel can be
placed on to indoor unit.
Installation of ornament panel
Place the holding ring on swing flao motor
side teporarily on hooks of the indoor unit.
(2 pcs)
Put the other two holding rings on the hooks at
both side of the indoor unit. (Care should be
taken not to push wiring of swing flap motor
into seals).
Screw in all 4 screws under holding ring for
about 15mm. (Pancl will rise).
Adjust the ornament panel as per Fig. 7 to
cover opening on the ceiling.
Tighten screws to redrce the thickness of seals
between ornament and indoor unit to 5-
8mm.
1
2
3
4
5
If indoor unit is at horizontal level and water drainage is smooth, then, indoor unit height can be ad­justed throrgh holes at corners of ornament panel.
If screws are not tighten tight, problems in Fig, 8 might occur. Tighten screws properly.
If there are still space after tightening of screws, please readjust the height of indoor unit. (Refer to Fig. 9)
Leave no space.
Fig. 9
Gas leakage.
Gas leakage from roof.
Contamination
Mist exists and drop down.
Fig. 8
45
Fig. 2
Adhesive tape
Slide
Fig. 3
For indoor unit installation, please refer to Installation Manual.
Hook
Caution
1 2
Leave no space.
Fig. 6
3. Mounting on high ceiling
(1) Ornament panel can be mounted on ceiling as high as 3 m.
(2) Please install pad as accessary.
Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4) Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
Fig. 4
(3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10)
50
Cutting line
100
a
b
Place it on the frame.
Part a of the pad
Part a of the pad
Swing flap motor
Fig. 5
Side of ornament panel
Fig. 10 Wiring diagram
Side of indoor unit
If connecting is not made, error code (A7) appears on remote controller. So, make proper connecting.
- 24 -
INSTALLATION INSTRUCTIONS
1
2
4. Installation of inlet grill and cover plate
Installation of inlet grill Install in reversed order ofPrepare ornament pandl”. Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as per customers request.
(1)
When installing inlet grill, take care not to twist wiring of swing flap motor.
Install cover plate on the corner As shown in Fig. 11 tie the cover plate onto the bolt on ornament plate. Install cover plate onto ornament plate. (Refer to Fig. 12)
(2)
Slide all five hold rings
to let them drop in holes on ornament plate,
Fig. 12
Fig. 11
bolt
5.3.10 Test running
Refer to Take special care during installation, check after working
(1) (2) (3) (4) (5) (6)
Proce­dure
Operation
Open check valve on gas pipe. Open check valve on liquid pipe. Press ON/OFF button, select Cooling mode. Let it run for 3 min. Press air flow adjust button to make unit run properly Confirm unit functions according to Operation Manual.
Upon installation of piping, water drainage and wiring work, make test run to ensure proper unit operation.
(1) (2) (3) (4) (5)
Procedure
Operation
Open check valve on gas pipe. Open check valve on liquid pipe. Press ON/OFF button, select Cooling mode. Let it run for 3 min. Cut main power supply after operation.
Conduct test run before installing ornament panel
Note: If unit doesn’t run due to certain problem, please see ‘‘Note to unit maintenance’’.
Conduct test run after installation of ornament panel
- 25 -
INSTALLATION INSTRUCTIONS
5.4 Installation of outdoor unit
580
380
5.4.1 Selection of installation place
Place strong enough to support the unit and will not cause vibration and noise. Place where discharged wind and noise do not cause a nuisance to the neighbors. Place where is less affected by rain or direct sunlight and is sufficiently ventilated, or to install a shield. Place with enough space for smooth air flow. The unit shall not be installed on an unspecifised metal frame (e.g. theft guard net). If the outdoor unit is installed close to a street, it shall be no less than 2.5m from the ground.
5.4.2 Fixing of the unit
Fix outdoor unit using M10 bolt to concrete floor horizontally. If installed on the wall or on top of a roof, bracket should be fixed securely to resist earthquake or storms. Use rubber pad during installation against unit vibration. Install the unit so that the angle of inclination must be less than 3 degrees.
2
Liquid (Thin)
Gas (Thick)
3way V.
2way V.
Vacuum pump
Gaugemanifold
2
Open
3
5.4.3 Air purging method: To use vacuum pump
For those models which adopt R407C refriengerant shall only use vacuum pump to purg air.
Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
1
Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.
Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 .
185
185
Installation dimension of outdoor unit (mm)
140 500 140
256
115 580 115
288
HBU-14
HBU-18 HBU-24,28,36,42
- 26 -
INSTALLATION INSTRUCTIONS
4
5
6
8
7
90°
3
3way V.
2way V.
6
6
for 6 sec.
Service port
3way V.
2way V.
90°
4
If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
Open the valve rod for the 2-way valve to and angle of anticlockwise 90 degree. After 6 seconds later, close the 2-way valve and male the inspection of gas leakage.
In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed steps.
No gas leakage?
6
Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.
After attaching the each caps, check the gas leakage around the caps.
To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for 2-way valve and 3-way's a lottle more than the point where the torque increases suddenly.
7
Valve rod cap
7
Valve rod cap
3way V.
2way V.
5
Service port cap
If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.
- 27 -
INSTALLATION INSTRUCTIONS
Item to the checked
5.5 Pay special care to the following and check after installation
Unproper installation may cause
Check
Is indor indoor unit firmly installed? Is gas leakage dheck performed? Is unit properly insulated? Is water drainage smooth? Is power voltage meet that stipulated on the nameplate? Is wiring and piping correctly arranged? Is unit safely grounded? Is wire size correct?
Are there any obstacles on air inlet and outlet grill of indoor and outdoor unit?
Is record made for piping length and refrigerant charging amount?
Unit might fall down, make vibration or noise. This may lead to gas shortage. Dew or water drop may occur. Dew or water drop may occur. Problem may occur or parts got burned. Problem may occur or parts got burned. There might be a danger of electric shock. Problem may occur or parts got burned.
This may cause poor cooling.
It is hard to control refrigerant charging amount.
- 28 -
INSTALLATION INSTRUCTIONS
PARTS AND FUNCTIONS
6.1 Drawings
6 PARTS AND FUNCTIONS
Indoor unit
Unit indication section
(Power, Timer, Run, Pump)
Remote controller signal receiver
The signal is received.
Back up switch
Swing louver
Air blows out from here. Air flow direction is adjusted.
Wireless Remote controller
Air inlet grille Takes in the indoor air.
Air filter Removes dust or dirt out of the inlet air. (In the Air inlet grille)
Swing louver (Air flow direction can be adjusted by using the SWING button on the remote controller)
Electrical Components Case
Air Inlet Grille
Air Filter (Inside of the Inlet Grille)
14 series
18 series
- 29 -