Haier HBU-14HC03 user guide manual

No.0010571987
CASSETTE AIR CONDITIONER
Operation Manual
AB142ACBBA AU142AFBBA (HBU-14HC03/R1)
Contents
Cautions
...........................................................................................
Main points of operation
..................................................................
Name of Each part
..........................................................................
Safety cautions
................................................................................
Gaide to operation
........................................................................
Maintenance
.....................................................................................
Trouble shooting
..........................................................................
When trouble happens
.....................................................................
Customer Need to know
.................................................................
Installation Tools
..............................................................................
Installation Procedures
................................................................
Installation Procedures,Check and Test Run
....................................
Air Purging Method ( To use vacuum pump) ....................................
1-2 3-4 5-6 7-8
9-14
15
16-18
19 20 21
22-31
32 33
CAUTIONS
1
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the environment.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house.
Safety Instructions and Warnings Before starting the air conditioner, read
the information given in the User's Guide carefully. The User's Guide contains very important observations relating to the assembly, operation and maintenance of the air conditioner.
The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following instruction.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Installation shall be done by professional people, don't install unit by yourself.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on the power cord. Always grip plug firmly and pull straight out from the outlet.
2
All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for the user of the air conditoiner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
Specifications
The refrigerating circuit is leak-proof.
1. Applicable ambient temperature range:
The machine is adaptive in following situation
Cooling
Heating
Indoor
Maximum: Minimum:
D.B / W.B D.B /
D.B
Outdoor
Maximum: Minimum:
D.B
D.B
Indoor
Maximum: Minimum:
D.B
Outdoor
Maximum: Minimum:
43 C/ 26 C
D.B / W.B 24 C/ 18 C
20 C
27 C
15 C
18 C/ 14 C
32 C/ 23 C
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T. 3.15A /250VAC.
CAUTIONS
4. The wiring method should be in line with the local wiring standard.
5. All the cables shall have got the European authentication certificate.
6.The waste battery shall be disposed properly .
7.The indoor unit installation height is at least
2.5m.
8.The appliance must be installation that the plug should be easily accessible after instal­ lation.
9. The power plug should be self-provided and it should have got the European authenti­ cation certificate.
D.B / W.B -7 C/ -8 C
3
Main points of Operation
Operation of Air Conditioner
When the environmental humidity is great, water maybe dripped from the air outlet in cooling or drying mode.
3-minute Protection Function
If restart the unit immediately after stopping, the compressor will start only 3 minutes later to protect the machine.
Variation of Fan Speed
If fan speed in auto mode, it will automatically lower when the room temperature close to the setting temperature in cooling mode.
In heating mode,the compressor stops when the room temperature at setting temperature and fan turns into low speed or stops.
In Dry mode,fan speed will be automatically varied.
Remote Control:
There is a telecommunication interface for remote control on the control panel of the indoor unit. After the peripheral equipment have been installed in accordance with the instruction manual of the selected remote control detector, the air conditioner will be computerized and controlled from a far­away place.
Note: Air conditioner has installed detector,in order to add group control function,Can refer to Centralized Controller installation and operation manual.
4
Main points of Operation
Prevent Cool Air Blowing Off
In heating mode,the indoor fan will not run immediately after the unit starts to prevent the cool air blowing off.
Defrosting Function
In heating mode, when frost formed on the outdoor heat exchanger, the air conditioner will automatically defrost a few minutes. During defrosting, both indoor and outdoor fan will stop running. When defrosting finished, air condi­tioner will automatically back to running.
Hints
The air conditioner absorbs heat form outside and releases inside when in heating mode, therefore the outside environmental temperature will affect heating effects.
Power Failure Compensation(to be applied for a necessary situation):
After the power failure compensation is set, if power failure suddenly occurs while the air conditioner is working,it will resume the previous working state when the power is supplied again.
Setting Method: When the remote controller is on (excluding timer mode and fan mode),press the ìsleepingî button on the remote controller 10 times within 5 seconds,and after the buzzer rings 4 times,the air conditioner will enter the state of power failure compenstation.
Cancel Method:Press the ìsleepingî button on the remote controller 10 times within 5 seconds, and after the buzzer rings 2 timer,the power failure compensation mode will be cancelled.
Note: When a power failure suddenly occurs during the air conditioner si working after the power after the power failure compensationis set,if the air conditioner will not be used for a long time, please cut off the power supply to prevent its operation from being res­ umed after the power is supplied again, or press the ì Switch On/Off î button after the power comes again.
Wait a minute
Defrosting Running
5
Indoor unit
Swing louver
(Air flow direction can be adjusted by using the SWING button on the remote controller)
Electrical Components Case
Air Inlet Grille
Air Filter
(Inside of the Inlet Grille)
Air Outlet (blow out hot air when cooling and cool air when heating)
Air Inlet (back)
Conneting pipe and electrical wiring
Name of Each Part
outdoor unit
Air Inlet (side)
6
Name of Each Part
1.ON//OFF button
2.Temperature display
3.Clock display
4.Timer ON/OFF display
5.Humidity display
6.Air filter cleaning display
When there is too much duct collected on the air inlet, the wire controller will show this display to remind the user to clean the air inlet. After cleaning and installation, just press the air filter reset button
7.Super/Soft operation display
8.Fan speed display
low
Mid
High
Auto
AUTO
9.Health state display
10.Fresh air state display
Note:
1.Cooling only type air conditioner does not have thedisplay and functions related with heating.
2.This model does not have the following related display and function 5 7 9 10 11 15 .
Calibration of clock
When turning on the unit for the first time, the clock should be calibrated. The method of calibration is:
1.Press ìClockî button, the Clock display ìAMî ìPMî will flash.
2.Press or to adjust time. For each press, the time will increase or decrease 1 minute. If depressing the button, the time will increase or decrease rapidly.
3.After confirming the time, press ìSetî button, ìAMî or ìPMî will stop flashing, the clock will begin to work.
11.Humidifying state display
12.Sleep state display
13.Network control display
14.Working mode display
AUTO RUN
COOL RUN
DRY RUN
HEAT RUN
FAN RUN
15.Electric heating display
16.Operation mode button
Used to set working mode: Auto,Cooling,Dry,Heating,Fan
17.Fan speed button
Used to set fan speed: Low Fan, Mid Fan, High Fan, Auto
18.Temperature Setting button
Used to set temperature,
19.Clock button
Used to calibrate the time of timer and clock
20.Setting button
Used to confirm the time of timer and clock
temperature range: 16 C~30 C
21.Sleep button
Used to confirm the time of timer and clock
22.Time Adjusting button
Used to adjust the time of timer and clock
23.Reset button
When the wire controller appears abnormal condition, use asharp­pointed article topress this button to make the wirecontroller resume normal
24.Air Filter Reset button
After cleaning the air inlet, press thisbutton, the unit can start to operate
25.Timer button
Used to set the mode of timer
26.Lock state display
2
3
5
6
7
8
9
10
11
12
13 14 15 16 17
4
AM PM
AM PM
C
AUTO
%
SET
ROOM
ON OFF
MODE
FAN SWING
TEMP
CLOCK SET
TIMER SLEEP
RESET
FILTER RESET
18 19
20 21 22 23
24 25
26
1
ON/OFF
7
Safety Cautions
Below are listed four kinds of Safety Cautions and Suggestions:
Be sure to conform with the following important Safety Cautions. The Safety Cautions should be at hand so that they can be checked at any time when needed. If the air conditoner is transferred to the new user, this manual should be as well transferred to the new user.
Incorrect operations may result in severe consequences of death or serious injures.
WARNING:
Incorrect operations may result in injures or machine damages; in some cases may cause serious consequences.
CAUTION :
: It must be strictly prohibited where marked with ì Prohibited î, otherwise may result in machine damages or endanger the userípersonal safety.
This information can ensure the correct operation of the machine.
INSTRUCTION:
Carefully read the following information in order to operate the air conditioner correctly.
WARNING
If any abnormal phenomena are found (e.g. smell of firing),please cut off the power supply immediately, and contact the dealer to find outí the handling method.
When need maintenance and repair,call dealer to handle it.
Donít put figures or any other things into the inlet/outlet and swing louver while the conditi­oner is in operation
Call the dealer to take measures to prevent the refrigerant from leaking.
Switch off
In such case,to continue using the air conditioner will damage the conditioner,and may cause electrical shock or fire hazard.
Incorrect maintenance and repair may cause water leak, electrical shock and fire hazard.
Because the high-speed fan is very dangerous and may cause injures.
The leaked refrigerant over certain density may cause oxygen deficient.If the air conditioner is installed in a small room be sure to take measure in order to prevent suffocation accident even in case of refrigerant leakage
When air conditioner is removed and reinstalled dealer should be responsible for them.
Incorrect installation may cause water leaking, electrical shock and fire hazard.
Donít dismantle the outlet of the outdoor unit.
The exposure of fan is very dangerous witch may harm human beings.
After a long time use of air conditioner the base should be checked for any damages.
If the damaged base is not repaired, the unit may fall down and cause accidents.
8
Safety Cautions
WARNING
No goods or nobody is permitted to be placed on or stand on outdoor unit.
Donít clean air conditioner with water.
The falling of goods and people may cause accidents.
Don't operate the air conditioner with damp hands.
Otherwise will be shocked.
Only use correct type fuse.
May not use wire or any other materials replacing fuse,othe­rwise may cause faults or fire accidents.
Donít place any burning unit in the airflow of air conditioner,which may cause incomplete combustion
No inflammable spray fluid should be permitted to be placed or used near to air conditioner,otherwise may cause fire accident.
Air conditioner should be cleaned only after power supply is cut off to keep from shock or hurt.
Otherwise may cause shock.
Connect earthing wire. Earthing wire should not be
connected to the gas pipe, water pipe,lightning rod or phone line,incorrect earthing may cause shock.
Use discharge pipe correctly to
ensure efficient discharge. In correct pipe usage may cause water leaking.
Air conditioner canít be be installed in the environment with inflammable gases.
The inflammable gases near to air conditioner may cause fire hazard.
Installed electrical-leaking circuit breaker.
When use the fumigating insecticide donít operate air conditioner.
Otherwise the poisonous chemicals may settle in air conditioner, which harm the health of chemical-allergic people.
It easily causes electrical shock without circuit breaker.
Not permitted when running
9
Guide to Operation
Fan Operation
Unit will selected the desired fan speed
ROOM
MODE
FAN SWNG
TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
1
4
2
3
ON/OFF
1.Unit start
Press ON/OFF button, unit starts. Previous operation status appears on LCD (except for TIMER ,SLEEP
, and SWING setting).
Power indicator light up.
2.Select operation mode
Press MODE button. For each press,operation mode changes as follows:
3. Adjust fan speed
Press FAN button.For each press,fan speed changes as follows:
4. Unit stop
Press ON/OFF button,unit stops.
AUTO FANHEAT
COOL
DRY
Then select FAN
LOW
MID
HIGH
The wire controller only shows the clock and room temperature.
FAN operation refers the air conditioner does not perform COOLING and HEATING operation, but air sending operation. In this mode, the air conditioner cannot perform AUOT
FAN operation, and does show the temperature value on the wire controller.
About FAN operation
AM
10
Guide to Operation
AUTO run, COOL , HEAT and DRY Operation
Then select AUTO run or select COOL operation or select DR
Y operation or select HEAT operation
Set proper temperature
T emp. setting +2 C T emp.setting
On reaching temp.setting +2 C, unit will run in mild DR
Y mode.
Ultra-low air flow
COOL operation starts when room temp.is higher than temp. setting.
About Auto operation
In Auto operation, the air conditioner will automatically choose Cooling, Heating or Fan mode according to the room temperature.
Hints:
The wire controller can memorize the working condition of each time. When start the unit for the next time, just need to press ON/OFF button, the air conditioner will work according to the previous working mode. (except for
Timer, Sleep and Swing)
SET
MODE
FAN
TEMP
CLOCK
TMER SLEEP
RESET
FLTER RESET
ON/OFF
1
5
2
4
3
Set proper fan speed
LOW
MID HIGH
AUTO
Unit runs at the speed displayed on LCD. In HEA
T mode, warm air will blow out after a short period of time due to cold-draft prevention function. In DRY mode, when room temp. becomes 2 C higher than temp. setting, unit will run intermittently at LOW speed regardless of FAN setting.
(1) Unit start
Press ON/OFF button, unit starts. Previous operation status appears on display (
except for Timer, Sleep, Swing mode). Power
indicator lights up.
(2) Select operation mode
Press MODE button. For each press, operation mode changes as follows:
AUTO COOL DRY FANHEAT
(3) Select temp. setting
Every time the button is pressed, temp. setting increases 1 C. If button is kept depressed, temp.setting will increase quickly
. Every time the button is pressed, temp. setting decreases 1 C. If button is kept depressed, temp. setting will decrease quickly.
Press TEMP button
Press ON/OFF button. Only clock and room temp remains on LCD.
(5) Unit stop
Press FAN button. For each press, fan speed changes as follows:
(4) Fan speed
AUTO
AM
11
Guide to Operation
Sleep Function
Use of SLEEP function
Before using this function, you should calibrate the clock first, otherwise, the SLEEP
function will be out of order.
Before going to bed, you can press the SLEEP button, the air conditioner will operate in comfort sleep mode to make you have a sound sleep.
After unit start,first set running mode and then press SLEEP button once.Mark the air conditioner have the previous-set sleep time(first power-on or after carrying out sleep function is 1h),the sleep symbol will appear
. Press time button / , you can choose the time in 1~8 hours.Each time the button is pressed the time increases/decreases 1 hour and ì xh î appears in the humidity setting part ,ì OFF î appears in ì TIMER OFF î display part. Press Sleep button again to cancel
Sleep function and the sleep symbol disappears.
1.In COOL, DRY mode
One hour after sleeping operation start, the temp. is 1 C higher than the setting one.
After another hour the temp. rises 1 C and then run continuously for another 6 hrs and then close. The actual temp. is higher than the setting one which is to prevent from being too cool to your sleep.
2.In HEAT mode
One hour after sleeping operation start, the temp. decreases 2 C lower than the setting one.
After another hour decreases by 2 C more. The temper­ature will automatically rise by 1 C after an other 3 hrs operation ,and then automatically close after 3 hrs continuous operation.The actual temperature is lower than the setting one which is to prevent from being too hot to your sleep.
SLEEP RUN BEGINS
SLEEP RUN STOPS
SETTING T
SHUT DOWN
about 6 hrs
1 hrs
In COOL,DRY mode
increase 1 C
increase 1 C
SLEEP RUN BEGINS
SLEEP RUN STOPS
SETTING T
SHUT DOWN
1 hrs
1 hrs
3 hrs
about 6 hrs
increase 1 C
decrease 2 C
decrease 2 C
In HEAT mode
Note:
Operation Mode
3.In AUTO mode.
The air conditioner will run in corresponding sleep operation according to the automatically selected operation mode.
In Auto mode, the air conditioner will perform relative Sleep operation according to working mode. After setting Sleep function, it is not permitted to adjust clock. The Sleep time is less than 8h, after reaching the set time, the unit will automatically stop.
Set Sleep function after setting ìTimer Offî function, the air conditioner will perform Sleep function. After setting Sleep function, the Timer function cannot be set. Set Sleep function after setting ìTimer Onî function, the Sleep function can only be set in the set time of
T
imer On.
MODE
FAN SWING
TEMP
CLOCK SET
TIMER SLEEP
R
FILTER RESET
ON/OFF
AM
SET
AM
OFF
12
Guide to Operation
Timer On/Off
Before using TIMER function, calibrate the clock first (referring to page 4). When you wake up in the morning, before going back to home after work or after going to bed, you can let your air conditioner automatically turn on or turn off.
SET
MODE
FAN SWING
TEMP
CLOCK SET
TIMER SLEEP
RESET
FILTER RESET
ON/OFF
1
2
4
AM
3
(4)Confirming your setting
After setting correct time, press SET button to confirm "ON" or "OFF" stops flashing. Time displayed: Unit starts or stops at x hour x min (ON or OFF).Timer mode indicator lights up.
To cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
Hints
Wire controller possesses memory function, when use TIMER mode next time, just press SET button after mode selecting if timer setting is the same as previous one. After power failure, the clock should be calibrated again.
At this time the will flash.
OFF
or
ON
OFF
ON
OFF
12:00 12:00 12:00 12:00
AM
PM
AM
PM
TIMER ON TIMER OFF TIMER ON-OFF
BLANK
Operation mode will be displayed on LCD. (except for Timer, Sleep, Swing)
(2)TIMER mode selection
Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows:
Select your desired TIMER mode (ON or OFF)
(1)After unit start, select your desired operation mode.
ON
(3)Timer setting
Press TIME button.
Every time the button is pressed, time increases 10min.If button is kept depressed, time will change quickly . Every time the button is pressed, time decreases 10min.If button is kept depressed, time will change quickly . Time will be shown on LCD. It can be adjusted within 24hours. AM refers to morning and PM refers to afternoon.
AM
OFF
ON
13
Guide to Operation
Timer On-Off
At this time the will flash.
ON
OFF
ON
OFF
12:00 12:00 12:00 12:00
AM
PM
AM
PM
TIMER ON TIMER OFF TIMER ON-OFF
BLANK
Operation mode will be displayed on LCD. (except for Timer, Sleep, Swing)
(2)TIMER mode selection
Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows:
Select your desired TIMER mode (ON or OFF)
(1)After unit start, select your desired operation mode.
ON
(3)Timer setting
Press TIME button.
Every time the button is pressed, time increases 10min.If button is kept depressed, time will change quickly . Every time the button is pressed, time decreases 10min.If button is kept depressed, time will change quickly . Time will be shown on LCD. It can be adjusted within 24hours. AM refers to morning and PM refers to afternoon.
(5)Time setting for TIMER OFF
Time displayed: Unit starts at X hour X min.
After time setting, press TIMER button to confirm. "ON" stops blinking, While "OFF" starts blinking.
(4) Time confirming for TIMER ON
Follow the same procedures in "Time setting for TIMER ON".
(6)Time confirming for TIMER OFF
After time setting, press SET button to confirm "OFF" stops flashing. Time displayed: Unit stops at X hour X min.
To cancel TIMER mode
According to the Time setting sequence of TIMER ON or TIMER OFF, either Start-Stop or Stop-Start can be achieved.
MODE
FAN SWING
TEMP
CLOCK SET
TIMER SLEEP
RESET
FILTER RESET
ON/OFF
1
2
PM
3
4
6
5
ROOM
Just press TIMER button several times until TIMER mode disappears.
AM
OFF
ON
14
Guide to Operation
After air conditioner operated for a period, dusts were gradually accumulated on the filter ,and the filter up/down function can be used to clean the filter.
1.Whether unit start or stop, continuously press FILTER button
3 seconds,and enter into the filter up/down waiting status
(when unit stops,the yellow TIMER indicator flashes, filter and
clock displayed on the remote controller and no others.Only the
FILTER button and the temperature button and time
button are active).
2.Press temperature button or time button in filter up/down waiting status, the up/down mechanism makes the filter to move downward and do not stop until reach the maximum limit.
3.Press temperature button or time button in filter up/down waiting status , the up/down mechanism makes the filter to move upward till near to the surface board and then automatically adjust to reset (when adjusting to reset, it will not be controlled by the remote controller till the adjustment is finished, and the remote controller can control again.
4.During moving downward ,press temperature button or time button, moving stops.
5.During moving downward ,press temperature button or time button, moving stops.
6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter backs to the original position , the remote controller backs to off status and only clock is displayed).
Note: If the filter does not thoroughly back to the original position,only need to operate several times repeatedly.
Filter Up/Down
ì î
Filter Up/Down
ì î
ì î
ì î
ì î
ì î
ì î
ì î ì î
Adjusting up/down air flow direction
Up/down direction can be adjusted by using the SWING button on the remote controller. Each time pressing this button, the mode changes in the following sequence.
SWING
No indication (louver stopped)
Change to the AIRFLOW mode.
SWING
LOUVER STOPPED
Louver moves in upward and downward directions continuously .
When the LOUVER button is pushed during SWING mode,it stops swinging at the just angle.
Avoid direct air flow to the body for many hours. Avoid downward blowing opera-tion of cooling mode for many hours. Do not touch the swing louver during swing operation.
CAUTION
MODE
FAN SWING
TEMP
CLOCK SET
TIMER SLEEP
RESET
FILTER RESET
ON/OFF
1
2
PM
3
4
6
5
ROOM
AM
OFF
ON
ì î
ì î ì î
15
Maintenance
Clean the unit
Turn off the power supply switch
Do not touch with wet hand.
Do not use hot water or volatile liquid
The 4 fixed bolts must be loosed as shown in the figure by arrow if they are bolts, the method is that: push the blots inward till to another edge. Generally the fixed blots are opened for inlet grille easily up and down as well cheaning the air filter.After open it,lower the inlet grille using remote controller, the maximum distance is 2.24m. Then turn the 1 rotated clamps 90 degree as shown in the figure, hold the air filter and nearly in the horizontal direction slightly pull it out.
Clean the air filter
Clean the air filter with water or vacuum cleaner. Use the detergent or neutral soapy water if the air filter is too dirty. Then rinse the air filter with water,and reinstall after drying.
Caution:
Do not clean the air filter with hot water over 40 C, otherwise may damage the filter.
Sweep the filter carefully.
Clean indoor (outdoor ) unit
Clean with hot wet cloth and neutral detergent, then wipe with dry cloth.Do not use too hot water (over 40 C) which may result in fading and deforming. Do not use insecticide and chemical washing agent.
Fixing nolt
Fixing nolt
Fixing nolt
Rotary fixing clamp
Outward drawable filter
ON
OFF
16
Troubleshooting
Seasonal Reserve
Operate the unit with FAN mode on a fair day for about half a day to dry the inside of the unit well.
Stop operation and turn off the power supply switch .Electric power is consumed even the air conditioner is in stop.
Clean the air filter, indoor unit and outdoor unit,and cover the unit with dustcoat.
Pre-season Care
See that there is no bostacles blocking the air inlet and air outlet of both indoor and outdoor unit to avoid reduce the working efficiency.
Be sure to install the air filter, ensure that the air filter is not dirty. Otherwise may result in machine damages or cause malfunciton due th dust inside the unit
To prevent compressor when start in HEAT mode, please cut in the power supply switch 12 hours before starting run,furthermore, always keep the power supply switch on during the using senson.
Post-season Care
17
Troubleshooting
The followings are not malfuncition
Hua
Hua
Water flowing sound is heard
When the air conditoner is started, when the compressor starts or stops during operation or when the air conditioner is stopped,it som­etimes sounds ì Bi- Bi-î or ìGodo-Godoî. It is the flowing sound of the refrigerant , not a malfunction.
Cracking sound is heard
It smells.
This is caused by heat expansion or contra­ction of plastics
Air blown out from the indoor unit sometimes smells. The smell results from smells of furniture, paint , tobacco absorbed by indoor unit.
During operation, white fog comes out of indoor unit.
When in COOL or DRY mode, a thin water fog can be seen blown out of unit ,this is the condensed fog because the suddenly cooled indoor air is blown out.
Automatically switch into FAN mode during cooling.
To prevent frost from being accumulated on the indoor unit heat exchanger, it sometimes auto­matically switched into the FAN mode,but it will soon back to the cooling mode.
The air conditioner cannot be restarted soon after it stops. Air conditioner does not start?
This is because of the self-protection function of the system, therefore,it cannot be restarted for about three minutes after it stops.
Air does not blow or the fan speed cannot be changed during drying.
In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit rill run intermittently at LO speed regardless of FAN setting
Please wait for three minutes
18
Troubleshooting
**?
ON
OFF
During heating,indoor fan is still running even unit is stopped.
To get ride of the excess heat, indoor fan will continue running for a while after unit autom­atically stops.
Water or vapor generated from the outdoor unit during heating.
This happens when the frost accumulated on the outdoor unit is removed (during defrosting operation).
Defrosting operation
Please check the following things about your air conditioner before making a service call.
Unit fails to start.
Is the power supply switch on ?
Power supply switch is not in ON position.
Is city supply power normal ?
Is the earth leakage breaker in action ?
Be sure to turn off the power supply switch immediately and contact the sales dealer.
Malfunction judgement
MALFUNCTION JUDGEMENT
When the air conditioner does not operate properly after you have checked the above mentioned items or when the following phenomenon is observed, stop the operation of the air conditioner and contact your sales dealer.
The fuse or breaker often shuts down. Water drops off during cooling operation. There is a irregularity in operation or abnormal sound is audible. When the CHECK lamp flickers, an irregularity has occurred in the air conditioner.
E0
Note:
This unit has a function of automatic restart system after recovering power stoppage. Please contact the sales dealer if it is not required.
The trouble of the drainage system
Content of defect
E1
The trouble of the room temp. sensor
E2
The trouble of the pipe temp. sensor
E5
The trouble of the overload current
E8
The trouble of the main control board communication
19
When trouble happens
Insufficient cooling or heating
The operation controller adjusted as required
Air filter too dirty ?
Horizontal swing louver upward ? (in HEAT mode)
Any obstacle exists at the air inlet or outlet?
Door or window left opened ?
Insufficient cooling
Any other heat sources in the room?
Sunlight direct into the room ?
Too crowed in the room ?
Cooled air blown out ( when heating)
When the air conditioner does not operate properly after you have checked the above-mentioned items or when following phenomenon is observed,stop the operation of the air conditioner and contact your sales dealer. The fuse or breaker often shuts down. Water drops off during cooling or drying operation. There is an irregularity in operation or abnormal sound that is audible.
20
Customer Need-to-know
Customer Need-to-know
Please install the air conditioner according to the requirements specified in this manual to ensure the air conditioner work well.
Be careful not to scratch the surface of the case during moving the air conditioner.
Please keep the installation manual for future reference when maintenance and changing installation place.
After installation ,please use the air conditioner according to the specification in the operation manual.
Using Directions
Adjust suitable airflow direction
Avoid direct sunlight and airflow
Keep the proper indoor temperature. Too cool or hot is not good for your health. Furthermore,it will result in excessive consumption of electric power.
Optimal temper­ature
Effectively use timer. Using TIMER mode, you can make the room
temperature reach a suitable temperature when you wake up or back home.
ATTENTION: after finishing installation,confirm no refrigerant leakage.
21
A
B
C
D
E
F
Installation tools
Standard accessories
1. Screw driver
2. Hacksaw
3. Drill with a diameter of 60mm
4. Inner hexagon spanner,shifting spanner
5. Spanner (14, 17, 19,24,27mm)
6. Pipe cutter
7. Pipe expander
8. Knife
9. Pincers
10. Leakage detector or soapy water
11. Band tape
12. Scraper
13. Refrigerant oil
The installation tools listed in the following sheet can be used as required.
The following parts mentioned in this manual are the installation accessories we prepared.
Symbol Parts Name
Adhesive tape
Pipe clamp
Connecting hose
Drainage hose
Non-hydroscopic heat insulating material
Gypsum powder
Following in the list are the accessories supplied with the unit,which can be used as required
1
1
6
1
35x120mm
1
1
4
1 1
1 4
8
1
1 1
***
No.
Accessory parts
Qty.
Wire clamp
Heat insulation sheathing
Drain elbow
1 for cooling and heating mode unit
None for cooling only mode
Piping hole cover
Rubber cushion
Connecting wire
2 for cooling and heating mode unit
1 for cooling only mode
Refrigerant oil
Plastic clip
Putty
Blastic cap
4x25 Screw
Steel nail cement
Pipe supporting plate
Drain hose
Main pipes
Wire controller (signal wire)
C
ON
OFF
*
** **
** ** **
**
**
**
**
**
**
****
**/**
**
4
6
5
8
7
9
10
1 1
12
16
15
14
13
2
30x100mm
Heat insulation sheathing
3
Installation Tools
22
3.The dial code is set as:
1. ON 2.OFF 3.ON 4.OFF
1. Remove upper part of wire controller Remove upper part of wire controller by press.
2. Install wire controller
(1) For exposed installation, use 2 wood screws (accessory). (2) For recessed installation, use 2 wood screws (accessory).
Note:
Try as far as possible a flat surface for installation. Don't use excessiv force when tightening screws, or lower part might got deformed.
PCB is mounted on lower part of wire controller, be careful not to damage it.
Lower part of wire controller
Upper part of wire controller
Installation Procedures
23
Installation Procedures
4. Indoor unit wiring Connect terminals (A,B,C,D) on lower
part of wire controller to terminals (A, B,C,D) on PCB of indoor unit.
Hint When make wiring, please keep a distance between wires and power supply cord.
Hint
Tread surface of the terminal well so that shielding may not contact other part.
Cord kind
Size
Shield wire (4 core) (refer to Hint 3,4)
0.33mm
2
Wire size
5. Replace the upper part of wire controller
Hint
Be careful not to press the wiring.
1. Switch box and cord for wiring are not supplied.
2. Don't touch PCB with hand.
Use shielede wires for telecommunication between wire controller and indoor unit; indoor unit and outdoor unit. Ground the shield on one side. Otherwise misoperation because of noise may occur. Signal wire is self-provided.
Shielded wire
ground
Lower part of wire controller
A B C D
Upper part of wire controller
wiring from here
24
Installation of Outdoor Unit
Selection of installation place
Place strong enough to support unit weight, and will not cause vibration and noise. Place where discharged wind and noise do not cause nuisance to the neighbors, and is sufficiently
ventilated. Place where is less affected by rain or direct sunlight and sea breeze.
Place with enough space for smooth air flow. The unit cannot be installed on an unspecified metal frame (e.g. theft guard net).
It shall be not less than 2.5m high from the ground if the outdoor unit is installed close to a street.
Easy for maintenance.
Fixing the unit
Fix outdoor unit bracket to the wall using anchor bolt (M10). Fasten the outdoor unit onto the installation bracket with bolt (M10) and nut ,and keep it horizontal. If installation on the wall or on top of a roof, bracket shoukd be fixed securely to resist earthquake or storms. Be sure to use rubber pad during installation against unit vibration. Install the unit in such a way that the angle of inclination is lees than 3 degrees.
Installation dimension of outdoor unit (mm)
140 500 140
256
Installation Procedures
25
1.Selection of Installation Place
(1) Place above the ceiling where have enough space to arrange the unit. (2) Place where the drainage pipe can be arranged well. (3) Place where inlet and outlet air of indoor and outdoor unit will not be blocked.
(4) Do not expose the unit to the place with heavy oil or moisture (e.g.kitchen and workshop). (5) Do not set the unit in the place where destructive gas (such as sulfuric acid gas) or pungent
gas (thinner and gasoline) concentrates and retains. (6) Place strong enough to support the unit weight.
(7) No expensive articles such as television and piano below indoor unit. (8) Enough space for maintenance.
(9) Place more than 1m away from television and radio to avoid disturbing television and radio. (10) Easy for maintenance.
1.5m
2.5m Over
1.5m
0.31m
H
Air outlet
Air outlet
Air inlet
2.Installation Preparation
(1) Position of ceiling opening between unit and suspending bolt (front view of unit).
(2) Prepare all piping (refrigerant,water drainage )and wires (connection wire of remote controller, indoor unit connection wires) to the indoor unit before installation in order to connect indoor unit immediately after installation.
Ornament panel 630mm
ceiling opening 600mm
Indoor unit 570mm
Distance between
Indoor unit 570mm
Ceiling opening 600mm
Ornament panel 630mm
suspending bolts 460mm
210mm
335mm
35mm
Overlap between ceiling and ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
Installation Procedudres
26
(3) Install a suspending bolt To support the unit weight ,anchor bolt should be used in the case of
already exists ceiling. Fow new ceiling, use flush-in type bolt, built-in type bolt or parts pretared in the field. Before going on installing, adjust space to ceiling.
Installation of indoor unit
In case of no ceiling
Install unit temporally Put suspending bracket on the suspending bolt to hang the unit up. Be sure to use nut and
washer at both end of the breaket to secure firmly.
After installation on the ceiling
(1) Adjust unit to its right position (Refer to preparation for installation-(1)) (2)Check that unit is horzontal.
Put suspending bracket on the suspending bolt to hang the unit up.Be sure to use nut and washer at both end of the bracket to secure it firmly.
Water pump and floating switch is installed inside indoor unit,check four corners of the unit for its lever using horizontal comparator or PVC tube with water.(If unit is tilting against the direction of water drainage,problem may occur on floating water leakage.)
In the case of ceiling already exists
(1)Install unit temporally
(2)Adjust the height and position of the unit. (3)Proceed with procedure (4) of ì In the case of no ceiling ì
Nut (Prepare in feild)
Washer (Prepared in feild)
Suspending bolts
Fasten (double nuts)
Insert
Washer fixing pad
(prepared in feild)
[ secure the washer firmly]
leveler
Polythene pipe
50*150mm
Ceiling
Roof
Anchor bolt
Long nut or thread
Suspending bilt M10
Note: All the above mentioned parts shall be prepared in feild, the diameter of suspending bolt is M10
<Installation Example>
Installation Procedures
27
Large size seal pad
4mm below
Clip
3.Installation of water drainage pipe
(1) Install water drainage pipe
Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size: 25mm; O.D.: 32mm )
Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming.
If downward slope of drainpipe cannot be made,lifting pipe shall be installed. Keep a distance of 1-1.5m between suspending bolts, to make water hose straight.
Use the drainage hose and clip provided with unit. Insert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose. Wind the drainage hose to the clip using seal pad for heat insulation. Insulate drainage hose in the room.
(accessory)
Cautions for the water drainage lifting pipe
Installation height of water drainage lifting pipe shall be less than 280mm There should be a right angle with unit ,300mm from unit.
< Note >
The slope of water drainage hose shall be within 75mm , make the drainage plug not to bear excessive force.
If several water hoses join together, of as per following procedures.
Specifications of the selected drainage hoses shall meet the requirements for the unit running
1-1.5m
Slope over 1/100
Tape(white)
Draingage hose
Clip
Clip
Water drainage lifting pipe
Suspending bracket
Drainage hose
280mm unter
500mm below
Drainage hose
75mm below
500mm below
220mm
Slope below 1/100
Connection drainage hose with a T-joint
100mm over
Installation Procedures
28
4. Installation of Ornament Panel
Install ornament panel on indoor unit
(1) Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the dimension of the ceiling opening is correct. Take off the lever gauge before install the ornament panel. (2)Fasten the screws to make the height difference between the two sides of indoor unit less than
5mm. (3) First fix it with screws temporally. (4) Fasten the two temporally fixing screws and other two, and tighten the four screws. (5) Connect the wires of synchro-motor. (6) Connect the wire of signal. (7) If no response of remote controller,check whether the wiring is correct,restart remote controller
10 seconds after shut off power supply.
Limits of panel board installation
(1)Install the panel board in the direction shown in the figure. (2)The incorrect direction will result in water leakage, meanwhile swing and signal receiving are displayed that cannot be connected.
Drain hose
Pipe
Pipe
Louver motor
Liquid inlet pipe
Gas outlet pipe
Drain hose
Installation Procedure
29
Piping Connection
(1) Dimension of connecting pipe
Fit the nut on and fasten
(2) The maximum length and drop height of connecting pipe
The maximum length is 10m The maximum drop height is 5m.
T o ensure the ef ficiency ,Pipes shall be as short as possible.
Cautions for piping connection
Do not twist or deform the connecting pipe. Do not mix dusts.
The bending radius shall be as large as possible. Both gas pipe and liquid pipe shall be heat insulation.
No leakage in the flare.
Spanner
Spanner
Joint
Nut
(3) Piping connection
Connecting method
Smear refrigerant oil on the joints of piping and flare. The bending radius shall be as large as possible. Align the pipe center when fastening, and tighten the nut, as shown in the figure. Pay attention to not mix foreign matters such as sands in.
Diameter of Pipe
Liquid Pipe 6.35mm Gas Pipe 15.88mm
Tighten Torque
18 N. m
60N. m
If not aligned ,tighten the nut by force will damage the nut that result in gas leakage
Flare connection
Gas pipe
3-way valve
Indoor Unit
Outdoor unit
Liquid pipe
2-way valve
Flare connection
90 + 0.5
15.88mm
6.35mm
Gas pipe
Liquid pipe
Installation Procedures
30
For AB142ACBBA AU142AFBBA (HBU-14HC03/R1) , the refrigerant is R407C.
Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.
6
No gas leakage?
5
4
Open the valve rod for the 2-way valve to and angle of anticlockwise 90 degree. After 6 seconds later, close the 2-way valve and male the inspection of gas leakage.
3
Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 .
2
Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.
1
Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
To use vacuum pump
CAUTION: If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.
7
8
After attaching the each caps, check the gas leakage around the caps.
To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for 2-way valve and 3-way's a lottle more than the point where the torque increases suddenly.
In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed steps.
6
Liquid pipe Gas pipe
Gaugemanifold
Vacuum pump
3-way valve
2-way valve
6.35mm(1/4'')
15.88mm(5/8'')
Service port cap
7
2-way valve
3-way valve
Valve rod cap
Valve rod cap
6
6
2-way valve
3-way valve
2
Open
3
Close
If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
90
for 6 sec.
4
Service port
90
90
3-way valve
2-way valve
7
7
Installation Procedures
31
Electrical Wiring
Cautions: Use copper wire only.Parameters of connecting line : H07RN-F 3G 2.0mm2 ,H05RN-F 2X0.75mm2 for cooling and heating type machine. Power supply :1PH,220-230V~,50Hz, connect from inside.
Wiring methods:
1.Wiring method of ring termianl
For connecting line which end is a ring,its wiring method as shown in the right figure: remove wiring screw and pass it through the end ring of connecting line,then connect it to the terminal block and tighten screw.
2. Wiring method of straight terminal
For connecting line which end is not a ring, its wiring method as follows: loosen wiring screw ans insert the end of connecting line totally into the terminal block,then tighten the screw and pull the connecting line slightly to confirm that it is clamped firmly.
Crimp connection method of connecting line
After finishing wiring.connecting line must be fastened by wire clamp,which pressed on the external sheath of the connecting line, as shown in the right figure:
Wiring of indoor unit
Open air inlet grill Take the leading end of connecting line Connect connecting line according to wiring methods
and wiring diagram of indoor and outdoor unit Fasten connecting line according to crimp connection
method of connecting line. Reinstall air inlet grill.
1.Installation fixing
Fix outdoor unit installation bracket on the wall using a M10 anchor bolt.Fix outdoor unit on the installation bracket firmly using bot(M10) and nut, and keep it on horizontal level. When installing on the wall or on the roof ,fix the bracket, firmly to prevent earthquake or storm. Be sure to use rubber-damping cushion to reduce unit vibration.
2.Installation of drain elbow
3. Connection of outdoor piping
Connect the connecting pipe according to the piping connection
method
4. Confirm the ends of wire are connected well, safe and correct.
5. After finishing wiring, press the connecting wire according to the wire crimp connection method and reinstall the cover.
Installation of drain elbow.(Only for heat pump type air conditioner, no drain elbow for single cooling type).If use drain elbow,please install as shown in the figure. Do not use drain elbow in cold place (temperature successively below 0 C)
4.Wiring connection
1.Open the wiring cover and loosen the wiring clamp.
2.Lead the connecting wire out and pass it through the wiring clamp.
3.Connect the connecting wire according to the wiring method and diagram
Drain eblow
Drain hose
Terminal
Wire clamp
Power supply
Connecting wire between inner and outer
1(L)
Wiring method of ring terminal
wiring diagram for indoor and outdoor unit of cooling-heating type machine
indoor unit casing
Terminal block of indoor unit
Terminal block of outdoor unit
1234NL
1234
Cooling and heating
1
2
3
4
Correct crimp connection of wire
Terminal block
Incorrect crimp connection of wire
Crimp connection clamp
Installation Procedures