Haier H2SM-(9+9)HRA03/R2, H2SM-(9+9)HEA03/R2, H2SM-(9+12)HEA03/R2, H2SM-(9+12)HRA03/R2, H2SM-(9+9)HEK03/R2 Installation Manual

...
Drawing for the installation of indoor and outdoor units
Necessary Tools for Installation
Driverƽ
Torque wrench
ƽ
(17mm,2 2mm, 26mm)
Nipperƽ
Reamerƽ
Gas leakage detector orƽ soap-and-water solution
Hole core drillƽ Flaring toolƽ Spanner(17,19 and 26mm)ƽ Knifeƽ
Measuring tapeƽ
Indoor Unit
Place, robust not causing vibration, where the body can be supported sufficiently.ƽ Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed.
ƽ
Place, possible to drain easily, where piping can be connected with the outdoor unit.ƽ Place,wherecoldaircanbespreadin a roomentirely.ƽ Place, nearby a power receptacle, with enough space around. (Refer to drawings).ƽ Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left.
ƽ
In the case of fixing the remote controller on a wall, place where the indoor unit can receivesignalswhenthefluorescent
ƽ
lampsintheroomarelightened.
Outdoor Unit
Place, which is less affected by rain or direct sunlight and is sufficiently ventilated.ƽ Place,possibletobeartheunit,wherevibrationandnoisearenotincreased.ƽ Place, where discharged wind and noise do not cause a nuisance to the neighbors.ƽ Place, where a distance markedƽ
is available as illustrated in the above figure.
Before inserting power plug into receptacle, check the voltage without fail. The power
sourceisthesameasthe
ƽ
correspondingnameplate.
Install an exclusive branch circuit of the power.
ƽ
Areceptacleshallbesetupin a distancewherethepowercablecanbe reached.
Donotextendthecablebycuttingit.
ƽ
Power Source
Preparation
Read this manual before installation Explain sufficiently the operating means to the user according to this manual.
NO.0010531114
Installation Manual of Room Air Conditioner
F
A
C
E
Optional parts for piping
Non-adhesive tape Adhesive tape Saddle (L.S) with screws Connecting electric cable
for indoor and outdoor
Drain hose
Heating insulating material
Piping hole cover
Floor fixing dimensions of the
outdoor unit (Unit:mm)
Fixing of outdoor unit
Fix the unit to concrete or blockƽ withbolts(10mm)andnutsfirmly and horizontally. When fitting the unit to wall
ƽ
surface, roof or rooftop, fix a supporter surely with nails or wires in consideration of earthquake and strong wind. If vibration may affect the
ƽ
house, fix the unit by attaching a vibration-proof mat.
The marks from to
in the figure are the parts numbers. Thedistancebetween the indoor unit and the floor should be more than 2m.
ThemodelsadoptHFCfreerefrigerantR410A
more than
10cm
more than 5cm
more than 10cm
more than 10cm
more than 10cm
more than15cm
more than 60cm
A
G
ƽ
ƽ
A
F
C
E
D
G
B
Arrangement of piping directions
Rear left
Left
Rear right
Right
Below
G
Please be subject to the actual product purchased , the above picture is just for your reference.
Attention must be paid to the rising up of drain hose
113.5
583
113.5
5
. 913
Selection of Installation Place
Unit A
Unit B
To unit A
To unit B
Indoor unit
Fixtosidebarandlintel a mountingbar,Whichisseparatelysold,andthen
ƽ
fasten the plate to the fixed mounting bar.
Refer to the previous article, “ When the mounting plate is
ƽ
position of wall hole.
Make a hole of 60 mm in diameter, slightly descending to outside the wall.
ƽ
Install piping hole cover and seal it off with putty after installation
ƽ
When the mounting plate is first fixed
1. Carry out, based on the neighboring pillars or lintels, a to be fixed against the wall, then
temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by
hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
When the mounting plate is fixed side bar and lintel
Indoor side
Outdoor side
Fitting of the Mounting Plate and
Positioning of the wall Hole
Ø60mm
Wall hole
Thickness of wall
(Section of wall hole) Piping hole pipe
Lid for right piping
Lid for under piping pipe
Fixwithadhesivetape
Lid for left piping
Heat insulation material
Drain hose
Piping
Pipe supporting plate
Indoor/outdoor electric cable
Indoor/outdoor electric cable and drain hose must be bound with refrigerant
ƽ
piping by protecting tape.
[ Other direction piping ]
Cut away, with a nipper, the lid for piping according to the piping direction and
ƽ
then bend the pipe according to theposition of wall hole. When bending, be careful not to crash
pipes.
Connect beforehand the indoor/outdoor electric cable,
ƽ
andthenpulloutthe
connected to the heat insulation of connecting part specially.
proper leveling for the plate
first fixed “, for the
Making a Hole on the Wall and Fitting the Piping Hole Cover
G
Drawing of pipe
Installation of the Indoor Unit
[Rearpiping ]
Drawpipesandthedrainhose,thenfastenthemwiththeadhesivetape
ƽ
[Left・Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping.
ƽ
In case of left-rear piping, bend the pipes according to the piping direction to
ƽ
the mark of hole for left-rear piping which is marked on heat insulation materials.
1. Insert the drain hose into the dent of heat insulation
materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of
indoor unit, and pull it
out on the front side, then connect them.
3.Coattheflaringsealfacewithrefrigerantoilandconnect
pipes.
Cover the connection part with heat insulation materials closely, and make sure
fixingwithadhesivetape
Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the
ƽ
mountingplate.Movethebodyfromsidetosidetoverifyits secure fixing.
Inordertofixthebodyontothemountingplate,holdup
ƽ
thebodyaslantfromtheundersideandthenputitdown perpendicularly.
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then takeƽ
off wiring cover by removing its screws.
mounting plate
When you unload the indoor unit,please use
then lift the bottom of the body outward slightly and lift the unit aslant until it leaves the mounting plate.
agraffe
mounting plate
Unloading of indoor unit body
ƽ
your hand to arise the body to leave agraffe,
Remote controller (1)
R-03 dry battery (2)
Mounting plate (1)
Drain hose (1)
Ø4X25 Screw
(4)
Plastic cap (4)
Drain-elbow (1)
Cushion (4)
Pipe supporting plate (1)
Accessory parts
Liquid pipe (Ø) 6.35mm(1/4”)
Gaspipe(Ø)
9.52mm(3/8”)
NOTE˖The thickness of the pipe must be 0.8mm at least.
Selection of pipe
2
A=145mm
B=
60mm
mm 03
A=150mm
B=
60mm
m m
03
A=145mm
B=
60mm
Ø
30mm
CAUTION
For multi model , the indoor units A and B should be connected with corresponding valves A and B of out­door exactly. Any mixed connection is forbidden.
ƽ
3
Note
When connecting the cable, confirm the terminal number of indoor and outdoorunitscarefully.Ifwiringisnotcorrect,properoperationcannot
be carried out and will cause defect.
1.Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturerorits service agent or a similar qualified person. The type of connecting wire is H05RN-F or H07RN-F.
2. If the fuse on PC board is broken please change it with the
type of T. 3.15A/250V.
3.Thewiringmethodshouldbeinlinewiththelocalwiringstandard.
4. After installation, the power plug should be easily reached.
5. A breakershouldbeincorporatedintofixedwiring.Thebreakershouldbeall-pole switch and the distance between its two contacts should be not less than 3mm.
Outdoor unit
Install according to Drawing for the installation of indoor and
outdoor units
Tobend a pipe,givetheroundnessaslargeaspossiblenottocrushthepipe,
ƽ
andthebendingradiusshouldbe30to40
mm or longer.
Connecting the pipe of gas side first makes working easier.
ƽ
TheconnectionpipeisspecializedforR410A.ƽ
Installation of Outdoor Unit
Half union
Flare nut
Tor que wr enc h
Becarefulthatmatters,suchaswastesofsands,etc.shallnotenterthepipe. Thestandardpipelengthis5m.Ifitisover7m,thefunctionoftheunitwillbe affected. If the pipe has to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant must
be conducted by profes­sional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Forced fastening without careful centering may damage the threads and cause a leakage of gas.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gas side 12.7mm(1/2") 55N.m
Gas side 15.88mm(5/8") 60 N.m
Connection of pipes
charge additional refrigerant.
Use the same method on indoor unit. Loosen the screws onƽ
terminal block and
inserttheplugsfullyinto terminalblock,thentightenthescrews.
Insertthecableaccordingto terminalnumberinthesamemannerastheindoor unit.
ƽ
If wiring is not correct, proper operation can not be carried out and controller may be damaged.
ƽ
Fix the cable with a clamp.ƽ
CAUTION
Max.Elevation:
In case the elevation A is more
than 5m, oil trap shoud be installed every 5~7m Max. Length:
In case the pipe length B is
more than 7m, the refrigerant should be charged, according to 20 g/m.
Connection
If the drain-elbow is used,ƽ please attach it as figure. (Note: Onlyforheatpumpunit.)
Detach the service port’s cap of
1.
3-wayvalve,thevalverod’scapfor2-wayvalve
and 3-way’s, connect the service port into the
projection of charge hose (Iow)
for gaugemanifold.
Then connect
the projection of charge hose (center) for gau-
gemanifold
into vacuum pump.
Open the handle at Iow in
2.
gaugemanifold, operate
vacuum pump. If the scale-
moves of gause (Iow) reach vacuum condition in a moment, check 1. again.
Attaching Drain-Elbow
Purging Method:To use vacuum pump
A1max=10m
B1max=15m
A
B
Outdoor unit
Indoor unit
A1
B1
Indoor unit A2
B2
Outdoor unit
Indoor unit
Oil trap
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
A2max=10m
B2max=15m
Insert the cable from the backƽ
side of the unit, then pull it out
on the front side.
Loosen the screws and insert
ƽ
thecableendsfullyinto
terminal block, then
tighten the screws.
Pull the cable slightly to
ƽ
make sure the cables have
been properly inserted and
tightened.
After the cable connection,
ƽ
neverfailtofastentheconnectedcablewiththe
wiring cover.
When connecting the cable before installing the indoor unit
Power cable:
3G2.5mm
Outdoor unit
R
E
W
O
P
1
3
2
1
2
Indoor unit A
Indoor unit B
{
4G0.75mm
2
4G0.75mm
2
ı
ı
L
N
1
) (
2
) (
H2SM-(9+9)HEA03/R2 H2SM-(9+12)HEA03/R2
H2SM-(9+9)HRA03/R2
H2SM-(9+12)HRA03/R2
H2SM-(9+12)HEK03/R2
(C)
3
(C)
1.Insertfromoutsidetheroomcableintoleftside of thewall hole,inwhichthepipehasalreadyexisted.
2. Pull out the cable on the front side, and connect the cable
making a loop.
When connecting the cable after installing the indoor unit
H2SM-(9+9)HEK03/R2
CAUTION
For multi model , the indoor units A and B should be connected with corresponding valves A and B of out­door exactly. Any mixed connection is forbidden.
ƽ
Open
No gas leakage?5.
Detachthechargehose6.
from the service port,
open 2-way valve and 3-way. Turn
thevalverodanticlockwise until hitting lightly.
In case of gas leakage, tighten parts of pipe connection. If
leakagestops,thenproceed6.steps
If it does not stop gas leakage, discharge whole refrigerants
from the service
port.Afterflaring workagainandvacuumize,fillupprescribed
refrigerantfromthegascylinder.
Anti countercurrent joint
Gaugemanifold(for
R410A)
2-way valve Liquid Side
3-wayvalveGasSide
Vacuum pump(for R410A)
Tube(for R410A)
Close
2-way valve
3-way valve
Open 90
O
2-way valve 3-way valve
2-way valve
3-way valve
Valve rod cap
Valve rod cap
Service port cap
To prevent the gas
leakage, turn the service
port’s cap, the valve
rod’s cap for 2-way
valve and 3-way’s a little more
than the point where the torque increases suddenly
After attaching the each
caps, check the gas
leakagearoundthecaps.
7.
8.
Step 1.
Step 2.
Step 3.
Step 7.
Step 6.
Step 4.
The power source must be exclusively used for air
ƽ
conditioner. (Over I0A)
In the case of installing an air conditioner in a moist place,
ƽ
pleaseinstallanea-
For installation in other places, use a circuit breaker as far
ƽ
as possible.
Pipe cutting is carried out with a pipe cutter and burs must
ƽ
be removed.
Afterinsertingtheflarenut,flaring workiscarriedout.
ƽ
Power Source Installation
CuttingandFlaringWorkofPiping
Flare tooling die
1.Cut pipe
2.Remove burs
FlaretoolforR410A Conventionalflaretool
Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A 0~ 0.5mm 1.0~1.5mm 1.5~2.0mm
rth leakage breaker.
Lean
Damage of flare Crack Partial Too outside
Correct Incorrect
On Drainage
It becomes
high midway.
The gap with the
ground is too small.
There is the bad smell from a ditch
It waves.
The end is imm­ersed in water.
Pleaseinstallthedrainhosesoastobedownwardslopewithoutfail. Pleasedon’tdothedrainageasshownbelow.
ƽ ƽ
Please pour water in the drain pan of the indoor unit, and
ƽ
is carried out surely to outdoor.
In case that the attached drain hose is in a room, please
ƽ
applyheatinsulationto
Less than
5cm
confirm that drainage
it without fail.
4
2-way valve
3-way valve 2-way valve
3-way valve
Iftherefrigerant of theairconditionerleaks,itisnecessarytodischargeallthe
ƽ
refrigerant. Vacuumize first, then
charge the liquid refrigerant into air conditio­neraccordingtotheamountmarkedonthenameplate. Please do not let other cooling medium, except specified one (R410A), or air
ƽ
enterintothecoolingcirculationsystem.Otherwise,therewillbeabnormal highpressureinthesystemtomakeitcrackandleadtopersonalinjuries.
CAUTION
Each indoor unit musts to be vacuumed , according to the above steps.
ƽ
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere. Refrigerant type:R410A GWP* value:1975 GWP=global warming potential Please fill in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
Refrigerant charge labelƵ
Check Items for Test Run
Put check mark
in boxes
Gasleakfrompipeconnecting? Heat insulation of pipe connecting? Are the connecting wirings of indoor and outdoor firmly
Istheconnectingwiring of indoorandoutdoorfirmlyfixed? Is drainage securely carried out? Is the earth line securely connected? Istheindoorunitsecurelyfixed? Is power source voltage abided by the code?
Is there any noise?
Isthelampnormallylighting? Arecoolingandheating(wheninheatpump)performednormally? Is the operation of room temperature regulator normal?
Please kindly explain to our customers how to operate
throughtheinstructionmanual.
Check for Installation and Test Run
Ƶ
inserted to the terminal block?
Ƶ
Vacuumize for over 15min.And check the level gauge which should read -0.1MPa
3.
(76 cm Hg) at Iow
pressure side. After the
completion of vacuumizing, close the
handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check
condition of the scale and hold it for 1-2min. If the scale-moves back in spite of
tightening, make flaring work again, the return to the beginning of 3 .
Openthevalverodforthe2-wayvalvetoanangle of4.
anticlockwise90degrees.
After 6 seconds, close the
2-wayvalveandmakethe
inspection of gas leakage.
Check Items for Test Run
3.Insert the flare nut
4.Flare pipe
Manual de instalación de aparato de aire acondicionado
Preparación
Herramientas necesarias para realizar la instalación
Destornillador Llave dinamométrica (17mm, 22mm,
26mm) Alicate Sierra de tubos Sierra para metales Herramienta de conicidad Broca de tubo Cuchilla Llave (17, 19 y 26 mm) Metro Detector de fugas de gas o agua jabonosa
Avellanador
Fuente de alimentación
Antes de insertar el enchufe de alimentación en la toma, compruebe que el voltaje no falla. La fuente de alimentación es la que figura en la placa de datos nominales. Instale el aparato en un circuito dedicado de alimentación. Debe existir una toma al alcance del cable de alimentación. No prolongue el cable cortándolo.
Selección del lugar de instalación
Unidad interior
Coloque la unidad sobre una superficie que pueda soportarla correctamente y no provoque vibraciones. Asegúrese de que el lugar no se ve afectado por calor o vapor generado en las cercanías y donde las tomas de entrada y salida no estén obstruidas. Asegúrese de que el lugar permita un drenaje sencillo y en el que puedan conectarse los tubos a la unidad exterior. Asegúrese de que el aire frío pueda distribuirse uniformemente por la sala. Coloque la unidad interior cerca de una toma de suministro eléctrico con espacio suficiente alrededor. (Consulte los diagramas). Coloque la unidad interior de modo que se encuentre a más de 1m de televisiones, radios, aparatos inalámbricos y lámparas fluorescentes. En el caso de fijar el control remoto a una pared, colóquelo donde la unidad interior pueda recibir su señal mientras estén encendidas las lámparas fluorescentes de la sala.
Unidad exterior
Seleccione el lugar menos afectado por la lluvia o la luz solar directa y suficientemente ventilado. Elija un lugar que permita soportar el peso de la unidad y que no amplifique el ruido y las vibraciones. Seleccione un lugar en el que los residuos y el viento generado por la unidad no cause una molestia a los vecinos. Coloque la unidad en un lugar en el que pueda disponerse de la distancia de separación marcada
en la figura anterior.
Diagrama para la instalación de aparatos interiores y exteriores
Recuerde que la ilustración anterior podría no reflejar fielmente el producto adquirido y debe utilizarse únicamente como referencia. Lea este manual antes de la instalación Explique el uso del aparato al usuario siguiendo las instrucciones de este manual.
Los modelos cumplen la norma R410A sobre refrigerantes libres de HFC
más de 5cm
más de 10cm
Unidad A
Unidad B
Organización de la dirección de los tubos
Izquierda
Izquierda trasera
Derecha trasera
Derecha
Inferio
r
Las marcas de A a G que se muestran en la figura representan los componentes. La distancia entre la unidad interior y el suelo debe ser superior a 2m.
Debe prestarse atención a la pendientedelamanguerade drenaje
más de 10cm
más de 10cm
más de 10cm
más de
60cm
a la unidad interior A
a la unidad interior B
más de 15cm
Componentes opcionales para la instalación de los tubos
ƻ
A Cinta no adhesiva
ƻ
B Cinta adhesiva
ƻ
C Soporte (L.S) con tornillos
ƻ
D Conexión de cable
eléctrico para interior y exterior
ƻ
E Manguera de drenaje
ƻ
F Material aislante de calor
ƻ
G Cubierta de orificio de
entubación
Dimensiones de fijación al suelo de la unidad exterior (Unidad:mm)
Fijación de la unidad exterior
Fije la unidad a un bloque de cemento con pernos (10mm) y tuercas firme y horizontalmente. Si instala la unidad sobre una pared, techo o tejado, instale un soporte con clavos o cables considerando la posibilidad de terremotos o viento fuerte. Si la vibración afectase a la casa, fije la unidad instalando una alfombra de absorción de vibraciones.
5
Loading...
+ 11 hidden pages