Haier H2SM-14HC03/R2, H2SM-18HC03/R2 Schematic

Domestic Air Conditioner
SERVICE MANUAL
Models :
H2SM-14HC03/R2
H2SM-18HC03/R2
Features
Comfortable:wide-angle airflow Health air purifying Quiet operation Engergy efficient Wide variety of functions
Serial Number: Versio n:00.00 Edition: 2005-3-25
1
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Content
1. Description of product model coding and series introduction
2. Specifications
3. Curves of performance
4. Description,net dimensions and functions of main component s and accessories
5. Brief introduction to electrical control functions
6. Abnormity diagnose
7. Wiring diagram
8. Circuit diagram
Trouble shooting
9.
10. Refrigerating cycle diagram
11. Noise level test chart and air veloc ity distribution
12. Installation manual
2
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Description of product model coding and series introduction
3
Domestic Air Conditioner
A. Description of coding rules of unit model
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
1
2
3
4
5
6
7
8
9
Developing sequence
10
The type of power supply
C-cooling only
Function code
H-heat pump e-electric aided heating
numbers based on thousand unit
The structure code of indoor & outdoor unit
The quantity of the indoor unit is two
H-Abbreviation of Haier
Examples:
H2SM-18HB03/R2,It represents wall-mounted multi-type split type room air conditioner.The cooling capacity is 18000BTU/h,and the power supply is 220-230V/50Hz,”B” means the improvement
B.Standard Situation/Conditions
indoor air status
No.
1
2
3
Operating condition
Norminal cooling
Norminal heating
Norminal electrical heating
DBOC WBOC
27OC 19OC 35OC 24OC
20OC 15OC
--- --- --- ---
outdoor air status
DBOC WBOC
7OC 6OC
4
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
C.Series brief introduction
1.comfortable:wide-angle airflow The vertical dual-flap and horizontal wide-angle louvers ensure the cool(warm air reaches every corner of the room.
2.Health air purifying and negative ion function An air purifying filter with deodorizing and disinfecting functions keeps the air clean and users
healthy.The negative ion generator can produce the negative ion that make the air fresher and cleaner.
3.Quiet operation Fan With Random-pitched Blades. Random-pitched blades help reduce operating noise while maintaining a high airflow rate.
2.Engergy efficient The design of inner-grooved copper tube greatly increases the refrigerant contact area and the efficiency of cooling/heating functions.
5.Convenience Auto restart and washable panel: The grille can be removed easily and washed when necessary.Any series have the function then even if the power falls when the unit is operating unit will automatically return to the operating settings in use before the power failure when power is restored.
6.Wide variety of functions 24-Hour Timer: 24-hour timer allows users to select the exact time they would like the air conditioner to turn on and to turn off.Timers on previous models operation based on the number of hours of desired operation.
7.Night-set models When the air conditioner is operationg on the timer-off circuit.The preset room temperature gradually rises(going down in heating)before the unit stops as shown delow.Users can sleep comfortably without sudden change in temperature.
8.Program”dry” This function automatically reduces the level of humidity while maintaining the preset indoor temperature.
5
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Specifications
OF COMPRESSOR
8
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
CURVES OF PERFORMANCE
45
50
55
60
50
55
60
455045
55
60
60
55
50
45
9
Domestic Air Conditioner
Performance Curve
Return Gas Temperature
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
35
C
Model Power Supply Run Capacitor
2500 2330 2160 1990 1820 1650 1480 1310
Capacity (Kcal/Hr)
1140
970 800
-8-7-6-5-4-3-2-10123456789101112
900 865 830 795 760 725 690 655
Power (Watts)
620 585 550
-8-7-6-5-4-3-2-10123456789101112
4.00
3.85
3.70
3.55
3.40
3.25
3.10
2.95
Current (Amps)
2.80
2.65
2.50
-8-7-6-5-4-3-2-10123456789101112
55.0
51.5
48.0
44.5
41.0
37.5
(Kg/Hr)
34.0
30.5
Flow
27.0
23.5
20.0
-8-7-6-5-4-3-2-10123456789101112
39A173A 220-230V / 50Hz / 1PH 25 μF / 370 VAC
Subcooling
Ambient Temperature
C
8.3
C
35
Cond. Temperature
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
Evaporating Temperature( )
C
10
Performance Curve
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Return Gas Temperature
35
C
Model Power Supply Run Capacitor
3500 3300 3100 2900 2700 2500 2300 2100
Capacity(Kcal/Hr)
1900 1700 1500
-1
1150 1110 1070 1030
990 950 910 870
Power (Watts)
830 790 750
-1
5.3
5.1
4.9
4.7
4.5
4.3
4.1
3.9
Current (Amps)
3.7
3.5
3.3
-1
70.0
66.8
63.6
60.4
57.2
54.0
(Kg/Hr)
50.8
47.6
Flow
44.4
41.2
38.0
-1
44A233A
Subcooling
220-230V / 50Hz / 1PH 40 uF / 370 VAC
0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9
Ambient Temperature
C
8.3
C
35
Cond.Temperature
45
C
50
C
55
C
60
C
11 12
10
60
C
55
C
50
C
45
C
11 12
10
60
C
55
C
50
C
45
C
11 12
10
45
C
50
C
55
C
C
60
11 12
10
Evaporating Temperature( )
C
11
Domestic Air Conditioner
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
DESCRIPTION, DIMENSION
& FUNCTION OF MAIN
COMPONENTS AND ACCESSORIES
12
Domestic Air Conditioner
Description and function of main components and accessories
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
13
Domestic Air Conditioner
Net dimensions for indoor unit
Model: H2SM-14HC03/R2 H2SM-18HC03/R2
265
Net dimensions for outdoor unit
295
795
182
319.5 352
680
583 815
869
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
BRIEF INTRODUCTION TO
ELECTRICAL CONTROL FUNCTION
14
23
one. Temperature Control Function
In temperature control function, the operation frequency of outdoor unit is determined based on room temperature and the set temperature. In automatic fan speed mode, indoor fan is controlled based on the need of temperature control In heating mode, indoor fan is controlled based on the temperature of coil. 1-1-1.Specification of Indoor Ambient Temperature Sensor In case of short circuit or open circuit, indicator lamp alarms and indoor fan stops. When normal condition is resumed, fan will automatically restart and operate normally. Short Circuit: Temperature: over 126 Normal Temperature: Temperature: 25 Open Circuit: Temperature: below -31
0.15V. B Parameter = 4200 R (25 1-1-2 Specification of Indoor Coil Temperature Sensor B Constant Number = 3700 R (25 1-1-3 When heating operation starts and indoor fan stops or when within 30s of indoor fan starts after heating operation starts, the resistant of indoor ambient temperature sensor is ignored. (to avoid the impact of heat exchanger temperature over it.) When forced operation ends after start-up, temperature zone control begins. 1-3. Set Temperature Correction Set temperature is corrected according to unit model, operation mode, fan speed and whether it is in power operation. Fan speed correction is available only during low and mid heating operation.
1-4. Temperature Zone Control 1-4-1.Error Temperature zone error is calculated as per the following formula In Heating Mode: E = (Remote Control Set Temperature + Correction Value) – Indoor Temperature In Cooling & Dehumidification Mode: E = Indoor Temperature - (Remote Control Set Temperature +
Correction Value)
1-4-2 Compressor Shutdown E is negative and |E|>T
T TCHAHL 0.67 TCHACL 0.33 After change of T TCHAHH 0.67 TCHACH 1
T Change Condition When operation starts E ı 3.0ć,
Compressor shuts down after continuous testing for 120s, At the beginning of operation, with reference to the conditions given in above table, it operates based on the parameters after change of T until compressor shuts down for the first time. In the time period between compressor shutdown and restart, it operates based on T. (except in dehumidification mode) Compressor starts at the beginning of operation or upon switch of operation mode (except standby ends) or when E (error) > -T. When compressor is operating, remote control set temperature is changing towards the direction of compressor shutdown and when it is below –T, compressor will shut down. 2-4-3. Compressor Operation Compressor restarts when E (error) > -ƸT+0.67ć and when 3 mins standby is over.
o
C, Hexadecimal System: over F8H, Resistance: below 0.65K,Voltage: over 4.85V.
o
C, Hexadecimal System: 40H, Resistance: 23K, Voltage: 2.33V.
o
C, Hexadecimal System: below 08H, Resistance: below 620K Voltage: below
o
C) = 23K
o
C) = 10K¡
:
Heating Cooling
24
15
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
two. Indoor Fan Control
2-1. Heating 2-1-1. Warm Start
Two. Cold Air Control in Heating Mode
Heat Exchange Temperature:
THHOT3
37.0ď
THHOT2
35.2ď
THHOT1
25.2ď 4mins
THHOTR
16ď
Stop SLO LO Set LO SLO Stop
Conduct indoor fan control as per the above diagram and the heat exchange temperature.
1. Judge wind speed when heat exchange temperature is rising:
Fan is at super low level when heat exchange temperature is below 35.2ć.˄Fan will stop upon initially energized into heating mode or after defrosting, or when heat exchange temperature is lower than 25.2ć. Fan is at super low level when temperature is higher than 25.2ć but lower than 35.2
ć.˅; Fan is at low level when heat exchange temperature is between 35.2ć and 37ć; Fan will operate as per setting when heat exchange temperature is above 37ć.
2. Judge wind speed when heat exchange temperature is falling:
Fan is at low level when heat exchange temperature is below 35.2ć but above 25.2ć;
Fan is at super low level and will maintain the mode when heat exchange temperature is lower than
25.2ć˄Fan is at super low level upon initially energized into heating mode or after defrosting, or
heat exchange temperature is lower than 25.2ć but higher than 16ć; Fan will stop when heat
exchange temperature falls below 16ć.˅
3. Wind speed is at super low or low level when heat exchange temperature is rising. If heat exchange temperature fails to enter the next temperature zone after 4 mins while wind speed rises to the next stage, it is necessary to maintain the set wind speed for 4 mins before it is adjusted based on heat exchange temperature.
4. When heat exchange temperature is falling, wind speed will return to set speed if low wind level is maintained for over 4 mins.
2-1-2. 3 mins standby period when compressor shutdown.
1. When compressor shuts down˄temperature sensor is off˅, airflow is low for the initial 20s then
reduced to super low (When in silent operation, it is SSLO);
2. Wind is maintained at super low level in the standby period in heating mode˄Compressor stops during
mode switch.˅.
3. Remote control shut down and stop indoor fan.
2-1-3. Compressor Restart When warm start, airflow is at remote control set level. When in automatic airflow mode, airflow is determined based on temperature. Refers to temperature zone control functions. 2-2 Cooling Airflow is different when airflow is set at high, mid and low level. When in automatic airflow mode, airflow is determined as per temperature. Refers to temperature control functions. 2-3. Dehumidification 2-3-1. Compressor is off and is in 3 mins standby.
25
16
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
Fan will stop if compressor stops Fan is at super low level upon the end of 3 mins standby. Compressor is on after 3 mins standby. 2-3-2. Compressor is on. When airflow is set at high, mid or low level, fan will operate as per the setting. When in automatic airflow mode, airflow is determined as per temperature.
three. Timed Operation
Time counting will start based on the difference of timer clock and current clock. In timed operation, display panel timer lamp is on. 3-0-1. Timer Off When timer off is set, panel timer lamp is on and unit will stop operation as per the timing. 3-0-2. Timer On If timer on is set, when unit is off, panel timer lamp will be on and unit will resume operation as per the timing and in set mode. Execution sequence is based on the setting.
Four . Sleep Operation
When remote control set sleep mode, timer lamp is on.
o
4ˉ1. In cooling/dehumidification mode, set temperature will rise 1
o
C after the second hour. The unit will stop after another 6 hours.
1 4ˉ2. In heating mode, set temperature will fall 2 and will rise 1
o
C after another 3 hours and the unit will stop after another 3 hours.
o
C after 1 hour and another 2 oC after the second hour
C after 1 hour operation and another
4ˉ3 If airflow of indoor fan is high before setting sleep mode, then it will turn into mid level after sleep mode is set. If airflow of indoor fan is mid before setting, it will turn into low level after setting. If airflow of indoor fan is low before setting, then it will not change after setting.
Five . Automatic Operation
4-1. Automatic Operation Mode:
On entering this mode, main control unit will decide the corresponding operation mode as per room
temperature to maintain the set temperature˄Set temperature is 23ćin heating mode and 26ć in cooling mode.˅.
Upon initial startup, the unit will enter heating mode if room inlet air temperature is equal to or lower
than 23ć or it will enter cooling mode if temperature is higher than 23ć.
When entering heating mode, the unit will operate as per heating program˄set temperature is 23ć˅
Upon reaching temperature where compressor stops operation, compressor will stop and standby for 3 mins. In case it detects that inlet air temperature is higher than 27ć 15 mins after compressor stops, the unit will enter cooling mode. Otherwise, the unit will remain in heating mode.
When entering cooling mode, the unit will operate as per cooling program˄set temperature is 26ć˅.
Temperature difference compensation is automatically cancelled. Upon reaching temperature where compressor stops operation, compressor will stop and standby for 3 mins. In case it detects that inlet air temperature is equal to or lower than 23ć 15 mins after compressor stops, the unit will enter heating mode. Otherwise, the unit will remain in cooling mode.
If the unit changes into automatic mode from any other mode and if the operation mode is changed (detect before operation), the unit will stop for 3 mins and it will operate based on inlet air temperature after 3 mins.
Six . Trial Operation
Trial operation will end after 30 mins, after which unit shuts down. In trial operation, the unit will quit trial operation mode upon reception of signal.
Compressor Stop Protection:
26
17
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
Eight . EEPROM Control
When outdoor unit is supplied with power, if there is any inconsistency between EEPROM parameter and checksum, EEPROM error. When indoor unit receives EEPROM error signal from outdoor unit, it will display outdoor unit EEPROM error. At this time, control and emergency operation are not acceptable. It can only be cancelled through power off.
Nine . Error Detect Method
9-1. Indoor Temperature Sensor Error In operation, an error occurs if the temperature is above 126
o
C or below – 31oC. Operation will resume automatically when temperature is outside the above range. 9-2. Heat Exchange Temperature Sensor Error In operation, an error occurs if the temperature is above 196
o
C or below – 53oC. Operation will resume automatically when temperature is outside the above range. In error condition, low load protection is cancelled.
9-4. Transmission Error Based on the condition of communication between indoor and outdoor unit, in case outdoor unit fails to receive signal within 20s after indoor unit sends out signal, transmission is abnormal. (except in the period of first 2 mins when power is supplied.). It is confirmed as transmission error when outdoor unit receive the error signal. Transmission error is removed by stopping operation.
Ten . Special Function
10-1. Power-Off Compensation a Entry Condition: Press sleep key 10 times in 7s and buzzer gives out 4 sounds and save the current status into indoor unit EEPROM upon the entry. b. On entering power-off compensation operation, indoor unit operates as per the following procedures: Remote control emergency signal, and operates as per condition set by remote control and emergency setting and save the current status into indoor unit EEPROM. Main unit will operate as per condition set on panel board. And save the current status into indoor unit EEPROM. c. Exit Condition: Press sleep key 10 times in 7s and buzzer gives out 2 sounds d. If timer and sleep features are set under power-off compensation condition, main unit memory is in a state of shut-off if power is off and on again.
27
18
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
Eleven . Error Presentation Mode
11.1 Three Indicator Error Code
Error Display
Error Conditions
Indoor Senistor Error ƾƵƵ * * 1. Connector loose contact or ambient
Indoor Heat Exchange Senistor Error Outdoor Senistor Error ƶƾƵ * * 1. Connector loose contact or sensor error
Indoor Fan Error Ƶƶƾ *
Note ƶOnƾBlinkƵOff * This
PS Timer Operation
Operation Heating Cooling
ƾƶƶ * * 1. Connector loose contact or coil sensor
Indoor
*
* 1. Whether control panel is damaged. EEPROM Error ƾƶƾ
function is
available.
Automatic
Outdoor
Reset
Cause
temperature sensor error.
error.
1. There is large interference source around or wiring error. Transmission Error ƵƵƾ
* 2. Wiring error or control panel error.
* 1. Whether control panel is damaged.
Twelve . Emergency Switch
When shutdown, press emergency switch down for less than 5s, the unit will start emergency operation. When shutdown, press emergency switch down for more than 5s but less than 10s, the unit will start trial operation. When shutdown, press emergency switch down for more than 10s but less than 15s, it will demonstrate the previous error. When shutdown, press emergency switch down, the panel will display automatic operation. When shutdown, press emergency switch down for less than 15s, or remove hand from emergency switch, the unit will not accept remote control signal. Unit enters shutdown condition after 15s. Unit can receive remote control signal after 15s. Press emergency switch during operation, air-conditioner will shut down., During operation, if error occurs, press emergency switch to shut down the unit to clear error condition. During error presentation, press emergency switch and error presentation will end. During operation, if emergency switch is pressed continuously (press and hold) in normal or abnormal condition (such as tact switch short circuit) or in error presentation condition, the unit can also receive remote control signal. Error Record Presentation Mode: When press and hold switch for 10s it gives out 3 sounds, release switch to enter error record presentation mode. Press and hold switch for 15s, panel display is off and error record presentation mode is cancelled. Previous alarm information will be sent to display panel for status display. Error record presentation mode is cleared after 10s. (Error record presentation mode is only displayed for 10s.) During the presentation, no remote control signal except shutdown signal is accepted. There is no presentation when no error occurs, only buzzer utters sound.
28
19
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
Outdoor PCB Function Manual
1. Single-unit cooling operation
1.1When the single unit’s indoor unit gives a cooling signal, the corresponding outdoor
compressor carries out cooling operation. During the operation, the outdoor fan operates 1
second before the compressor operates.
1.2When changed from heating to cooling, the compressor stands by for 3 minutes, the
outdoor fan operates to blow off remaining heat and stops 30 seconds later.
1.3When the outdoor ambient temperature T1ı38ć, the outdoor fan runs at the high
speed. There is a return difference of 2ć for the change between high and medium
speed.
When the outdoor ambient temperature T1İ26ć, the outdoor fan runs at the low
speed. There is a return difference of 2ć for the change between low and medium
speed.
When the outdoor ambient temperature T1İ8ć, the outdoor fan is in a cycle of 1
minute stop and 3 minute run. There is a return difference of 2ć for the change
between low speed and run and stop.
1.4Once the fan operates in a mode, it must operate for more than 45 seconds.
There is a temperature cut-off protection: when the indoor coil temperature higher than
T_CPS (68ć) and maintains for 10 seconds, both the compressor and outdoor fan stop.
The compressor will not restart in 3 minutes until the coil temperature lower than T_CP
R(50ć). The indoor fan is controlled the same as the thermostat is OFF.
2. Double-unit cooling operation
2.1When the indoor unit gives out a double unit cooling signal, outdoor compressor A starts
cooling operation. During the operation, the outdoor fan runs 1 second before compressor
A operates, 20 seconds later, outdoor compressor B starts cooling operation.
2.2Once a compressor starts, the other compressor will not start in 20 seconds from the
start.
2.3 When changed from heating to cooling, the compressor stands by for 3 minutes. When
both compressors are in the strand-by status, the outdoor fan stops. Otherwise, it operates.
The status of the fan depends on the number of the compressors that operate.
29
20
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
2.4 When the outdoor ambient temperature T1ı30ć, the outdoor fan runs at the high
speed. There is a return difference for the change between high and medium speed;
When the outdoor ambient temperature T1İ23ć, the outdoor fan runs at the low
speed. There is a return difference for the change between low and medium speed;
When the outdoor ambient temperature T1İ5ć, the outdoor fan is in a cycle of 1
minute stop and 3 minute run. There is a return difference of 2ć for the change
between low speed and run and stop.
2.5Once the fan operates in a mode, it must operate for more than 45 seconds.
2.6 There is a temperature cut-off protection: when a indoor coil temperature higher than
T_CPS (68ć) and maintains for 10 seconds, the corresponding compressor stops. The
compressor will not restart in 3 minutes until the coil temperature lower than T_CP R(50ć).
The indoor fan is controlled the same as the thermostat is OFF.
2.7 In the case of double-unit cooling, one compressor stops and it changes to the
single-unit operation. The fan is controlled in the single-unit operation mode. It stops 30
after blowing off the remaining heat only if both compressors turn off at the same time.
3.Single unit heating operation:
3.1 When the single unit’s indoor unit gives a heating signal, the corresponding outdoor
compressor carries out cooling operation. During the operation, the outdoor fan and 4-way
valve operate 1 second before the outdoor fan operates.
3.2. When changed from cooling to heating, the compressor stands by for 3 minutes, the
outdoor fan stops.
3.3 When the outdoor ambient temperature T1İ3ć, the outdoor fan runs at the high
speed. There is a return difference of 2ć for the change between high and medium
speed.
When the outdoor ambient temperature T1ı13ć, the outdoor fan runs at the low speed.
There is a return difference of 2ć for the change between low and medium speed.
3.4. Once the fan operates in a mode, it must operate for more than 45 seconds.
3.5. There is a high temperature protection and a temperature cut-off protection.
High temperature protection: When the indoor coil temperature higher than T_OFS (56ć),
the outdoor fan stops; when the coil temperature falls to T_OFR (52ć), the outdoor fan
restarts. The outdoor fan stops for more than 45 seconds.
30
21
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
High temperature cut-off protection: When the indoor coil temperature higher than T_CPS
(68ć) and maintains for 10 seconds, both the compressor and outdoor fan stop, and the
indoor fan operates as the thermostat is Off. The compressor will not restart in 3 minutes
until the coil temperature lower than T_CP R(50ć).
4. Double-unit heating operation
4.1 When the double-unit’s indoor unit gives out a heating signal, outdoor compressor A
starts heating operation. During the operation, outdoor compressor A and the 4-way valve
operate 1 second before the fan starts, 20 seconds later, outdoor compressor B starts
heating operation.
4.2Once an outdoor compressor starts, the other compressor will not start in 20 seconds
from the start.
4.3 When changed from cooling to heating, the compressor stands by for 3 minutes. When
both compressors are in the strand-by status, the outdoor fan stops. Otherwise, it operates.
The status of the fan depends on the number of the compressors that operate.
4.4 When the outdoor ambient temperature T1İ10ć, the outdoor fan runs at the high
speed. There is a return difference for the change between high and medium speed;
When the outdoor ambient temperature T1ı20ć, the outdoor fan runs at the low
speed. There is a return difference for the change between low and medium speed.
4.5Once a fan operates in a mode, it must operate for more than 45 seconds.
5. Cooling and heating operations take place at the same time:
5.1 When one of the indoor units gives out a cooling signal and another unit gives out a
heating signal at the same time, the outdoor fan operates at the low speed.
5.2 When the indoor unit gives the value of coil temperature, the outdoor fan runs at the low
speed if the heating outdoor unit judges high load.
5.3When outdoor ambient temperature T1ı28ć, there is no heating operation.
5.4When outdoor ambient temperature T1İ7ć, there is no cooling operation.
5.5Once a compressor starts, the other compressor will not start in 20 seconds from the start.
6.Single-unit heating operation with heat load:
6.1 In the single-unit heating operation, the indoor unit gives out the value of the coil
temperature, and the outdoor unit judges whether to start in the high load protection operation
22
31
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
based on the value of the coil temperature it has received. If the conditions for high load
protection are met, the outdoor fan stops immediately. It will restart 45 seconds later if the
signal for the outdoor heat load disappears. Otherwise, the outdoor fan will continue to stop
until the signal for the outdoor heat load disappears. The signal for heat load is as follows:
High temperature protection: When the indoor coil temperature higher than T_OFS (56ć), the
outdoor fan stops; when the coil temperature falls to T_OFR (52ć), the outdoor fan restarts.
The outdoor fan stops for more than 45 seconds.
High temperature cut-off protection: When the coil temperature higher than T_CPS (68ć) and
maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor fan
operates as the thermostat is Off. The compressor will not restart in 3 minutes until the coil
temperature lower than T_CP R(50ć).
6.2 In the single-unit heating operation, the current in the compressor is larger than 4.0 A(for
Model 14)(4.8A for Model 18), and the outdoor fan stops. 45 seconds later, the current in the
compressor is less than 3.5A(for Model 14)(4.3A for Model 18), and the outdoor fan operates
in normal condition(the compressor does not detect current within 30 seconds after its start),
the current in the compressor is larger than 3.5A(for Model 14)(4.3A for Model 18) and less
than 4.0A(for Model 14)(4.8A for Model 18), and the outdoor fan does not restore.
7.Double-unit heating operation with heat load
7.1 In the double-unit heating operation, the indoor unit gives out the value of the coil
temperature, and the outdoor unit judges whether to start in the high load protection operation
based on the value of the temperature it has received. If the conditions for high load protection
are met, the outdoor fan stops immediately. It will restart 45 seconds later if the signal for the
outdoor heat load disappears. Otherwise, the outdoor fan will continue to stop until the signal
for the outdoor heat load disappears. The signal for heat load is as follows:
High temperature protection: When the indoor coil temperature higher than T_OFS (56ć),
the outdoor fan stops; when the coil temperature falls to T_OFR (52ć), the outdoor fan
restarts. The outdoor fan stops for more than 45 seconds.
High temperature cut-off protection: When the coil temperature higher than T_CPS (68ć)
and maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor
fan operates as the thermostat is Off. The compressor will not restart in 3 minutes until the
23
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
coil temperature lower than T_CP R(50ć).
7.2 When the outdoor single-unit gives out the heat load signal, the outdoor fan stops
immediately, 45 minutes later, the heat load signal disappears, and the outdoor fan
operates.
7.3 In heating operation, any of the current in the compressor is larger than or equal to 4.0
A (for Model 14, 4.8A for Model 18), and the outdoor fan stops. The current in the
compressor is less than or equal to 3.5A (for Model 14, 4.3A for Model 18), and the
outdoor fan restores (the compressor does not detect current within 30 seconds after its
start), the current in the compressor is larger than 3.5A (for Model 14, 4.3A for Model 18)
and less than 4.0A(for Model 14, 4.8A for Model 18), and the outdoor fan does not restore.
8. Current peak protection
8.1. The current in the compressor is larger than 6.8A(for Model 14, 8.2A for Model 18) for
more than 5 seconds, The compressor which has the highest current will stop(the
compressor does not detect current within 10 seconds after its start) and 3 minutes later it
will continue to operate.
8.2. The compressor will no longer operate if overcurrent protection occurs 4 times in a row
within 30 minutes, and the output transformer signal fails. In the double-unit operation, if
one of the compressors stops due to the current too high, the other system is a single
system.
9. Single-unit defrosting operation (outdoor judgement)
Defrosting control
9.1. Conditions for starting in the defrosting operation
The heating compressor starts and operate continuously for 10 minutes. After the
compressor has been operating for 45 minutes in total, detecting the defrosting sensor TE
(detecting the frosting of the outdoor heat exchanger) and the outdoor ambient
temperature sensor TA for straight 2 minutes, provided the following conditions are met, it
will start for the defrosting operation: TEİChTAˉ¢
Where,
C: TA˘0ć
33
24
Domestic Air Conditioner
C=0.8
TAı0ć
C=0.6
¢=6
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
In the place where it tends to frost, it is preferred to choose H. In the place where it does not
intend to frost, it is preferred to choose L. It is set M at delivery.
During the defrosting operation, the temperature control starts -15ćİChTAˉ¢İ-2ć
9.2. Interval of defrosting
When the result of the calculation from ChTAˉ¢ falls in the range of -15ćİChTAˉ¢,
the interval between two defrosting operations is 45 minutes.
When the result of the calculation from ChTAˉ¢ falls in the range of ChTAˉ¢<-15ć, the
interval between two defrosting operations is 55 minutes.
9.3. Defrosting operation
At the beginning of defrosting, the compressor is halted for the first one minute, but the
outdoor fan operates, 50 seconds later, the 4-way valve is OFF.
9.4. Once starting to defrost, the compressor must be guaranteed at least 2 minutes of
operation before canceling defrosting. As for the conditions to cancel defrosting, it will restore
to the heating operation from the defrosting operation as long as any of the following
conditions is met.
(1) . The outdoor heat exchanger temperature is above 7 degrees for consecutive 80
seconds.
(2) . The outdoor heat exchanger temperature is above 5 degrees for consecutive 12
seconds.
(3) . The defrosting operation has lasted 9 minutes.
9.5 After the conditions for cancellation of defrosting are met, the following operations will
follow:
The compressor stops, the outdoor fan starts, 50 seconds later, the 4-way valve is engaged,
and 60 seconds later, the compressor operates.
10. Double-unit defrosting operation
After receiving the signal to stop the indoor unit during the defrosting period, the unit must not
34
25
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
be turned off until the outdoor defrosting lasts more than 2 minutes.
When the double units are activated for defrosting, the activation of compressor B is 20
minutes later than that of compressor A.
Conditions for ending defrosting: It will restore to the heating operation from the defrosting
operation as long as any of the following conditions is met.
(1) . The temperatures on both outdoor heat exchangers are above 7 degrees for consecutive
80 seconds.
(2) . The temperatures on both outdoor heat exchangers are above 5 degrees for consecutive
12 seconds.
(3) . The defrosting operation has lasted 9 minutes.
The starting conditions and control process for the double-unit are same as that for single-unit
defrosting, the only difference is that the activation of compressor B lags that of compressor A.
11. Alarming operation
1. When the whole unit is in normal operation, the alarm light is always on, but does not
flash.
2. When the outdoor temperature sensor short-circuited or disconnected, the outdoor fan
always operates at the medium speed and will restore automatically after the sensor
comes to normal.
3. When the temperature sensor short-circuited or disconnected or the current transformer
fails, the alarm light flashes in the following manner; when the current transformer fails,
the signal is sent to the indoor unit that operates abnormally, and the corresponding
indoor unit indicates trouble:
Additional codes for overcurrent
LED light flashes once outdoor Eeprom in trouble LED light flashes twice outdoor ambient temperature sensor in trouble LED light flashes 3 times communication with indoor unit A in trouble LED light flashes 5 times outdoor unit A’s coil in trouble LED light flashes 6 times outdoor unit A’s CT current too high LED light flashes 7 times communication with indoor unit B in trouble LED light flashes 9 times outdoor unit B’s coil in trouble LED light flashes 10 times outdoor unit B’s CT current too high
35
26
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
ABNORMITY DIAGNOSE
36
27
Codes and Description
H2SM-14/18C03/R2
Code indication
Description
indoor
Indoor
Malfunction
Power timer operate Operate heating cooling
★ ■ ■ ★ □ □
Room temperature sensor failure --
Heat-exchange sensor failure --
Indoor EEPROM error ---
Indoor fan motor malfunction --
■ ■ ★ Communication Error (between indoor and outdoor unit)
Outdoor
Malfunction
★      □      ■ Outdoor Senistor Error
outdoor EEPROM error 1
outdoor unit A’s coil sensor failure outdoor unit B’s coil sensor failure
explanation onflashoff
Trouble Shooting
★ ■ ■: Room temperature sensor failure CN8 ★ □ □: Heat-exchange sensor failure CN8
Pull the sensor out of the mainboard
1) Measure the value of resistance Between its two
jumpers
2) Measure the temperature at the room temperature
sensing head.
The indoor PCB is broken, replace with new indoor PCB
28
whether terminal CN8 on
indoor PCB contact wellt?
YES
Check the value of the
sensor to see whether the
sensor is dama
ged or not?
YES
NO
NO
Pull out the terminals on the indoor mainboard and
reinsert them
Sensor is broken,replace it with new sensor
Outdoor led1
blinks times
3 or 7
2
5
9
H2SM-14/18C03/R2
★ □ ★: Indoor EEPROM error: Replace the PCB of indoor unit
■ □ ★:Indoor fan motor malfunction
whether terminal CN7
and CN11 on indoor PCB
well inserted or not?
YES
Pull out and reinsert the terminals
Electrify the machine again and turn it on in the cooling
operation, Measure voltage between the positions 1 ( red
wire)
and 5( black wire) of Terminal CN1 on the indoor PCB
NO
. the voltage is about
90-200vac
NO
the indoor pcb is damaged and need replace
check whether motor
can run when turn on the unit
Yes
NO
the indoor motor is damaged and need replace
Yes
When motor is running Measure whether there is voltage pulse(0-5VDC) between the
positions 2 (middle wire) and
black wire) of Terminal CN7
3(
on the indoor PCB
NO
the indoor motor is damaged and need replace
the indoor pcb is damaged and need replace
29
H2SM-14/18C03/R2
LED1 of outdoor pcb flashes once: outdoor EEPROM error: Replace the PCB of outdoor unit,
LED1of outdoor pcb flashes twice: Outdoor ambient Sensor failure CN1,
whether terminal CN1 on
outdoor PCB contact well?
NO
Pull out the terminals on the outdoor mainboard and
reinsert them
YES
Pull the sensor out of the mainboard
3) Measure the value of resistance Between its two
jumpers
4) Measure the temperature of
Outdoor ambient
Check the value of the
sensor to see whether the
sensor is dama
ged or not?
NO
Sensor is broken,replace it with new sensor
YES
The outdoor PCB is broken, replace a new one
30
H2SM-14/18C03/R2
■ ■ ★ :Communication fault between indoor and outdoor system
Yes
Check whether the linking cable
between the indoor and outdoor is not well connected
Reconnect the linking cable;
NO
If unit A have error , please turn
Yes
on A and B bothcheck whether B is fine
NO
YES
please check whether the connecting of L or N is reversed of the two units
NO
YES
Check whether the LED1 on the outdoor pcb is on
NO
check whether the voltage of
NO YES
CN7 in outdoor pcb is about 198-253VAC
NO
YES NO
NO
check whether the voltage of CN4 in outdoor pcb is about 12VAC
YES
the outdoor PCB is damaged
please reverse the outdoor connecting wires A(C) and B (C) between unit A and B,
reconnect the L and N wires
the outdoor PCB is damaged
check whether fuse of outdoor pcb is broken
check whether the wire from terminal block to out pcb is well connected
the transformer is bad
if A is error and B is fine, indoor unit A PCB is damaged
if A is fine and B has error,the outdoor unit main PCB is damaged
reaplace the fuse with T3.15A 250V
Reconnect the linking wire
31
H2SM-14/18C03/R2
LED1 of outdoor pcb flashes 5 or 9 times outdoor unit A or B’s coi sensor failure CN2
whether terminal CN2 on
outdoor PCB contact well?
NO
Pull out the terminals on the outdoor mainboard and
reinsert them
YES
Pull the sensor out of the mainboard
5) Measure the value of resistance Between its two
jumpers
6) Measure the temperature of
B’s coi
outdoor unit A or
Check the value of the
sensor to see whether the
sensor is dama
ged or not?
NO
Sensor is broken,replace it with new sensor
YES
The outdoor PCB is broken, replace a new one
32
Domestic Air Conditioner
WIRING DIAGRAM
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
33
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
38
349
34
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
40
35
Domestic Air Conditioner
Model: H2SM-14HC03/R2
CIRCUIT DIAGRAM
H2SM-18HC03/R2
4
36
H2SM-14/18C03/R2
CN4
CN8
1 2 3 4
+5V
SJ20-07WX
C49
R83
2.2K
LED1
IC2
SDA
6
SCL
7 8 1
24C02
RL1
CN5
GREEN
220V-N
8
1 2 3 4
61
5 6
53
7
52
51
D8
D6
45 3 2
CON1(red)
1
CON2(white)
1
C38
102/50V
C25
102/50V
C27
102/50V
C26
102/50V
1N4007
1N4007
R84
6.8K 2W
D
C
1
CON5
B
1
A
+5
R37
R36
C29 104/50v
R54 680
R43 3.3K
C5 102
10K
1K
+5V
R20 10K
CN13
SW3
R15 10k
2SC2412
+5V
R4 4.7K R38 10K R39 4.7K
5v
R91
+12
+5
R16 10k
R17 10k
Q11
2SC2412
Q4
R9
R29 10K
R5
Q8
10K
2SB1197
3.3K
R51
R52
C13
10K
104
R40
+5V
R64 10K
+5
+5
R21 10K
R73
R58 10K
10K
4.7K
C19
104
12345
89
10111213141516
R8922K
R65
10k
R18 4.7k
C36
103/50v
C12 102
R41
1K
02 IRQ
4.7K
07
PTF3/TBCH3
11
PTF5
12
PTF6
48
PTH1/KBD3
49
PTH1/KBD4
08
PTF4/TBCH0
03
RST
21
VSS GND
45 56
VSSA GND
60
PTC0
10
PTF7
57
CGMXFC
09
NC
13
PTE0/TXD
14
PTE1/RXD
15
PTE2/TACH0
25
10K
PTG2/KBD2
16
PTE3/TACH1
17
PTE4/SS
18
PTE5/MISO
23
PTG0/KBD0
24
PTG1/KBD1
R93
35
PTB1/ATD1
10K
26
PA0
27
PA1
28
PA2
29
PA3
D
30
PA4
31
C
PA5
32
B
PA6
33
A
PA7
38 PTB4
1234567
50 PTD4
IC4
2003
R25
R32 10K
10K
470UF/16V
GNDAVSS/VRE
MC68HC908AB32
E15
PTB2/ATD2 PTB3/ATD3
PTF0/TACH2 04 PTC1 PTC5 PTC3 PTC2/MCLK PTD7 PTD6/TACLK 52
OSC1
OSC2 VREFH
VDDA
PTE6/MOSI
PTE7/SPSCK
PTF2/TBCH2 PTF1/TACH3 VDDAREF 44
PTD2 PTD1 PTD0 PTB7/ATD7 PTD6/ATD6 PTB5/ATD5
PTB0/ATD0
7805
C17 104
22
VDD
36 37
61 64 63 62 53
51PTD5 59
58
55 54
19
20
06 05
47PTD3 46 43 42 41 40 39
01
PTC4
34
1N4007
IC9
R92 10K
C15 102
C35 104
100u/25v
C18 104/50V
R1 1M
R46
1K
+12+5
E9
C10 102
C41 102
13
XT1
8M
+5
R24 10K
1
2
E8
2200UF/25V
+12
+5
E5 100u/16v
C9 102
2
R47 560 1/4W
ZJ1
D5
C42 104/50V
C4
104
C22 102
R6
10K
R97
10K
IN4007
R86
R95
R96
10K
10K
D1-D4
C28 104/50V
+5
C3 103
R85 2.2K 1/4W
10K 1/4W
R98
R33
10K
10K
5v
CN3
0-171825-3
+5
E4 100u/16v
R87
10K 1/4W
Q9 2SC2412
+5
C6
103/50V
R26 10K
5v
SW2
BEEP-PKM13EPY-4002
BUZ1
+12v
R11
10K
R49 100
Q5 2SC2412
R28 1K
+5
C1 102
4 3 2
CN6
1
+5V
R57
220
2 1
R10 10K
1 2 3
R66 27
SW1
+5
220V-L
C39
2UF 450V
R42
L1
125uH
R13 10K R12
+5
R27 10K
R30
10K
R31
10K
C2 104
R50
R14 1K
C43 103
C24
0.01u/275V120  1W
Q10
2SC2412
10K
Q1 2SC2412
R59 4.7K
Q2 2SC2412
+5V
R2
10K
R3
1K
+5V
51K
C16 102
Q3
220V-N
2SC2412
IC10
TLP3526
D
CN9
+12V
C
CN7
CN1
B
1 2 3
A
7654321
CN2
104/275V
T1
C40
RTB-1.5-2P
R45 1K
R44 1K
R34
20K 1%
R35 3.3K 1%
R69 10K R68 10K R67 10K
+5
R82
330 1/4W
+5
24
R80
2.2k 1/4W
C7
TLP421
104/50V
+5V
R7
R8
C14 104
D7
RLS4148
.
561K
Z1
E7 4.7UF/50V
E6
C47
104/50V
IC14 TLP371
+5
IC12
10K
10K
FUSE
3.15A
4.7UF/50V
R53 1K R88 560
R70 560 R71 560 R72 560
R81
330K 1/4W
+12
+5V
E13 100u/25v
1 103/50V
B2P3-VH-A
+5
JQ1A-12V
1 2 3 4 5 6 78
37
43
38
Domestic Air Conditioner
Model: H2SM-14HC03/R2
TROUBLE SHOOTING
H2SM-18HC03/R2
44
39
Domestic Air Conditioner
Domestic Air Conditioner
Domestic Air Conditioner
Model: H2SM-14HC03/R2
Model: H2SM-14HC03/R2
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
H2SM-18HC03/R2
H2SM-18HC03/R2
50
40
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
REFRIGERATING-CYCLE DIAGRAM
46
41
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
Warning and cautions :
1.1 The multi-mounted split unit adopts double separated cooling systems (A and B) that are not connected together. If the refrigerant leaks, the leaking system of them must be determined. So we can solute the abnormality. And refill the system that lacks refrigerant. It w ill influenc e the effect if the A and B syst ems are wr ongly estimated.
1.2 The maximum length of single connecting pipe is 7m. And the units c an't run normally if the pipe is over required length.
1.3 Fill refrigerant in acc ordance w ith the diagram below if the connec ting pipe is over 5m.
Length 5m 7m ----
5HIULJHUDQWFKDUJH 12 J 
9DFXXPSXPSLQJRIWKHV\VWHP 9DFXXPSXPSLQJLVWRPDLQO\GUDZRXWUHVLGXDODLUDQGZDWHULQWKHDLUFRQGLWLRQHUUHIULJHUDQWV\VW HP *HQHUDOO\YDFXXPSXPSLVFRQQHFWHGDWWKHSURFHVVLQJSRUWRIWKHZD\VWRSYDOYHLQWKHRXWGRRUXQLW 7KHV\VWHPYDFXXPGHJUHHLVUHTXLUHGWREHEHORZ3D
5HIULJHUDWLQJF\FOHGLDJUDP  
Outdoor unit
Heat exchanger
Capillary tube
Capillary tube
2- way valve
 
2- way valve
    
Capillary tube
B Compressor
Capillary tube
B indoor unit Heat exchanger
A indoor unit Heat exchanger
 
3- way valve
    
A 4-way valve
B 4-way valve
3- way valve
     
A Compressor
Cooling
Heating
42
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
NOISE LEVEL TEST CHART
& AIR VELOCITY DISTRIBUTION
48
43

G%$
Domestic Air Conditioner
LQGRRU XQLW
RXWGRRU XQLW
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
G%$







+] +] +] +] +] +] +] +]






49
44
B.Air velocity distribution
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
45
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
INSTALLATION & MAINTENANCE
46
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
47
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
48
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
49
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
50
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
3(C)
2
1
Indoor unit A
3(C)
2
1
Indoor unit B
WHT
WHT
YEL/GRN
RED
BLK
YEL/GRN
RED
BLK
BLK
BLK
WHT
WHT
RED
RED
51
YEL/GRN
YEL/GRN
POWER
{
BRN
BLU
YEL/GRN
1
2
3
1
2
3
L
N
Outdoor unit
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
52
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
53
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2
54
Domestic Air Conditioner
Model: H2SM-14HC03/R2
H2SM-18HC03/R2