Haier H2SM- - annexe 15, H2SM- 15 Installation Manual

No.0010515070
Installation Manual of Room Air Conditioner
The models adopt HFC free refrigerant R410A
The marks from to in the figure are the parts numbers. The distance between the indoor unit and the floor should be
more than 2m.
Read this manual before installation
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)
5.Torque wrench(17mm,22mm,26mm)
6.Pipe cutter
7.Flaring tool
8.Knife
9.Nipper 12.Reamer
10.Gas leakage detector or soap-and-water solution
11.Measuring tape
Explain sufficiently the operating means to the user according to this manual.
A
G
2
Pipe supporting plate
No. Accessory parts
Remote controller
R-03 dry battery
Mounting plate
Drain hose
Screw
Plastic cap
Drain-elbow
Cushion
2
1
2
3
4
5
6
7 8
4
2
2
8
1
4
Number of articles
Accessory parts
4X25
Indoor unit A
Indoor unit B
more than 10cm
more than 60cm
more than 15cm
more than 10cm
Attention must be paid to the rising up of drain hose
C
more than 10cm
Drawing for the installation of indoor and outdoor units
Necessary Tools for Installation
A B
C D E
F G
Optional parts for piping
Mark
Parts name
Non-adhesive tape
Adhesive tape
Saddle(L.S) with screws
Connecting electric cable for indoor and outdoor
Drain hose
Heating insulating material
Piping hole cover
Arrangement of piping directions
Rear left
Rear right
Left
Below
Right
more than 10cm
more than 5cm
Fixing of outdoor unit
Indoor Unit
Selection of Installation Place
Power Source
Selection of pipe
Outdoor Unit
Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally. When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails
or wires in consideration of earthquake and strong wind. If vibration may affect the house, fix the unit by attaching a vibration-proof mat.
Place, robust not causing vibration, where the body can be supported sufficiently. Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed. Place, possible to drain easily, where piping can be connected with the outdoor unit. Place, where cold air can be spread in a room entirely. Place, nearby a power receptacle, with enough space around. (Refer to drawings). Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left. In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened.
Place, which is less affected by rain or direct sunlight and is sufficiently ventilated. Place, possible to bear the unit, where vibration and noise are not increased. Place, where discharged wind and noise do not cause a nuisance to the neighbors. Place, where a distance marked is available as illustrated in the above figure.
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate. Install an exclusive branch circuit of the power. A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.
To this unit, both liquid and gas pipes shall be insulated as they become Iow temperature in operation. Use optional parts for piping set or pipes covered with equivalent insulation material. The thickness of the pipe must be 0.8 mm at least.
Floor fixing dimensions of the outdoor unit (Unit:mm)
2
Liquid pipe( )
Gas pipe( )
6.35mm(1/4")
9.52mm(3/8")
106.5
106.5
566
297
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
3
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 70 mm in diameter, slightly descending to outside the wall. Install piping hole cover and seal it off with putty after installation
When the mounting plate is fixed side bar and lintel
Refer to the previous article, " When the mounting plate is first fixed ", for the position of wall hole.
Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar.
3.Installation of the Indoor Unit Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials.
(Section of wall hole)
Piping hole pipe
Outdoor side
Thickness of wall
Indoor side
Wall hole
70mm
G
Find the level position
B= 70mm
A=145mm
35
Indoor unit
4.Connecting the indoor/outdoor Electric Cable
Fixing the indoor unit body
Removing the wiring cover
[Other direction piping]
Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.
Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according to the position of wall hole. When bending, be careful not to crash pipes. Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part specially.
Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to side to verify its secure fixing. In order to fix the body onto the mounting plate,hold up the body aslant from the underside and then put it down perpendicularly.
Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws.
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.
4
[Cautions]
1.Make sure it is unit A or unit B, when make wiring.
2.Unit to be connected to stop valve A on outdoor unit is unit A,while the one to be connected to stop valve B is unit B.
3.Refer to wiring diagram.
1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape
Lid for right piping
Lid for under piping
Lid for left piping
Fix with adhesive tape
Heat insulation material
Drain hose
Piping
Indoor/outdoor electric cable
Pipe supporting plate