Haier AL24LP2VHA, AL36LP2VHA, AL48LP2VHA, AM24LP2VHA, AM36LP2VHA Installation Guide

...
Ductless Split Heat Pump
Indoor
AM24LP2VHA AM36LP2VHA AM48LP2VHA AL24LP2VHA AL36LP2VHA AL48LP2VHA
AW24LP2VHA AW36LP2VHA
Outdoor 1U24LP2VHA 1U36LP2VHA 1U48LP2VHA
Nomenclature
T
able of Cont
............................................................................................................................... 2
ents
................................................................................................................... 3
ety ........................................................................................................................................... 4
Saf
Section A - Outdoor Unit Installation ............................................................................................ 7
Section B - Indoor Unit Installation - Wall Mount ......................................................................... 13
Section C - Indoor Unit Installation - Cassette ............................................................................. 17
Section D - Indoor Unit Installation - High ESP Duct ................................................................... 23
Section E - Wir
ed Controller YR-E17 ............................................................................................ 29
Section F - Wireless Remote Controller ....................................................................................... 37
ENGLISH
1 U 24 LP 2 V H A
1 U 18 ES 2 V H A
Unit Type A = Indoor Unit 1 = Single Zone Outdoor 2 = Two Zone Outdoor 3 = Three Zone Outdoor 4 = Four Zone Outdoor
Nomenclature
Nomenclature
Product Revision
Unit Type U = Outdoor B = Casse e Type Indoor D = High ESP Duct Type Indoor
M=High Static Duct Type Indoor
W = Wall Mount Type Indoor
L = Large Cassette Type Indoor
Nominal Capacity
In Btu/hr (x 1000)
Product Family
- LP:LP=FlexFit Pro Series
System Type H = Heat Pump C = Cool Only
Compressor Speed V = Variable Speed
Voltage 1 = 115V 2 = 230V
PAGE 2
INTRODUCTION
Model
Name
Operating
Range
Power Supply
Outdoor
Unit
Indoor Unit
Refrigerant
Line
System AW24LP AW36LP AM24LP AM36LP AM48LP AL24LP AL36LP AL48LP
Outdoor
Indoor AW24LP2VH AW36LP2VH AM24LP2VH AM36LP2VH AM48LP2VH AL24LP2VH AL36LP2VH AL48LP2VH
Cooling
Heating
Voltage, Cycle,
Maximum Fuse
Minimum Circuit
Height
Width
Depth
(Ship/Net)-
°F(°C)
°F(°C)
Phase
V/Hz/-
Compressor
Size
A
Amp
A
Dimension:
in (mm)
Dimension:
in (mm)
Dimension:
in (mm)
Weight
(kg)
Dimension:
Height
in (mm)
Dimension:
Width
in (mm)
Dimension:
Depth
in (mm)
Max. External
Static Pressure
1U24LP2VH 1U36LP2VH 1U24LP2VH 1U36LP2VH 1U48LP2VH 1U24LP2VH 1U36LP2VH 1U48LP2VH
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/7
25.0 30 25.0 30 40 25.0 30 40
21.0 26.0 21.0 26.0 35.0 21.0 26.0 35.0
38 (965) 38 (965) 38 (965) 38 (965) 53 1/8 (1350) 38 (965) 38 (965) 53 1/8 (1350)
37 3/8(950) 37 3/8(950) 37 3/8(950) 37 3/8(950) 37 3/8(950) 37 3/8(950) 37 3/8(950) 37 3/8(950)
14 5/8(370) 14 5/8(370) 14 5/8(370) 14 5/8(370) 14 5/8(370) 14 5/8(370) 14 5/8(370) 14 5/8(370)
202.8/ 176.4
lbs
(92/80)
13 1/4(336) 14 3/8(365) 9 7/8 (250) 9 7/8 (250) 9 7/8 (250) 9 5/8 (246) 9 5/8 (246) 11 3/8 (288)
43 7/8(1115)
9 9/16(243) 10 7/8(275) 25 3/4 (655) 28 3/8 (720) 28 3/8 (720) 33 1/8(840) 33 1/8(840) 33 1/8(840)
NA NA 0.6(150) 0.6(150) 0.6(150) NA NA NA
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/10
207.2/180.7 (94/82)
51
13/16(1316)
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/8
202.8/ 176.4 (92/80)
37 5/8 (957) 59 (1500) 59 (1500) 33 1/8(840) 33 1/8(840) 33 1/8(840)
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/11
DC Inverter Driven Rotary
207.2/180.7 (94/82)
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/13
260.1/231.5 (118/105)
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/9
202.8/ 176.4 (92/80)
0~115
(-18~46)
-4~75
(-20~24)
208-
230/60/12
207.2/180.7 (94/82)
(-18~46)
(-20~24)
230/60/14
260.1/231.5 (118/105)
in.W.G(Pa)
Drainpipe Size
in
O.D.
Internal
Condensate
Max. Drain-Lift
height
in(mm)
Grill Model NA NA NA NA NA PB-950KB PB-950KB PB-950KB
Weight
(Ship/Net)-
lbs
(kg)
Connections Flare Flare Flare Flare Flare Flare Flare Flare
Liquid O.D.
Suction O.D.
Factory Charge
in
in
Oz
Maximum Line
Length
Ft / m
Maximum Height
Ft / m
NA NA 1 1/4 1 1/4 1 1/4 1 1 1
NA NA Standard Standard Standard Standard Standard Standard
NA NA 27 9/16(700) 27 9/16(700) 27 9/16(700) 39 3/8 (1000) 39 3/8 (1000) 39 3/8 (1000)
45.4/37.5(20. 6/17)
3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8
88.2 88.2 88.2 88.2 131 88.2 88.2 131
165 (50) 165 (50) 165/50 165/50 230/75 165/50 165/50 230/75
100/30 100/30 100/30 100/30 100/30 100/30 100/30 100/30
55.1/46.3(25. 5/21)
81.1/68.8
(36.8/31.2)
130.1/121.3 (59/55)
132.3/114.6 (60/52)
79.4/68.3 (36/31)
79.4/68.3 (36/31)
83.8/70.5
ENGLISH
0~115
-4~75
208-
(38/32)
INTRODUCTION
PAGE 3
SAFETY OVERVIEW
Read These Safety Precautions
Be sure to read the safety precautions before conducting work. The items are classified into “Warning” and “Caution.” The “Warning" items are especially important since they can lead to death or serious injury if not followed closely. Under certain
conditions, the "Caution" items can also lead to accident or injury if they are not followed. Therefore, be sure to observe all
ENGLISH
safety precautions listed here.
This symbol means be careful when doing this procedure or touching this equipment.
ᴏ This symbol indicates a prohibited action.
This symbol means that an action must be taken; the action will be listed next to the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates properly; explain the safety precautions for operating the equipment to the customer.
Warning
Disconnect the power cable from electrical supply before disassembling equipment for repair.
If the refrigerant discharges during the repair work, DO NOT touch the discharging refrigerant. The refrigerant can cause frostbite.
Before disconnecting the suction or discharge pipe of the compressor at the brazed connections, recover the refrigerant in a well-ventilated area. If refrigerant remains inside the compressor, the refrigerant or the refrigerating machine oil will discharge when the pipe is disconnected and may
cause injury.
If the refrigerant leaks during the repair work, ventilate the area. The refrigerant can generate
toxic gases when it contacts ames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Be sure to discharge the capacitor completely before conducting repair work. A charged capacitor can cause electrical shock.
Be sure to use parts listed in the service parts of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause electrical shock, excessive heat
generation, or re.
When relocating the equipment make sure that
the new installation site has sufficient strength to
withstand the weight of the equipment. If the new
installation site does not have sucient strength
and if the installation work is no
securely, the equipment can fall and cause injury.
t conducted
Be sure to install the product correctly by using the standard installation frame provided. Incorrect use of the installation frame and improper installation
can cause equipment to fall, resulting in injury.
Do not repair the electrical components with wet hands. Working on equipment with wet hands can cause electrical shock.
Do not clean the equipment by splashing water. Washing the unit with water can cause an electrical shock.
Make sure that the unit is grounded when reparing the equipment in a wet or humid place to avoid electrical shocks.
Be sure to turn o the power switch when cleaning
the equipment; the internal fan rotates at a high
speed and may cause injury.
Do not tilt the unit when removing it. Water inside
the unit can spill, wetting the oor.
Be sure to check that the refrigeration cycle section
has cooled down suciently before conducting
repair work. Working on the unit when the refrigerating cycle is hot can cause burns.
Use the brazing equipment in a well-ventilated place. Using the brazing equipment in an enclosed room can cause oxygen deficiency.
Be sure to use a dedicated power circuit for the equipment; follow appropriate technical standards for the electrical equipment, the internal wiring regulations, and the instruction manual for installation when conducting electrical work.
Insucient power circuit capacity and improper electrical work can cause an electrical shock or re.
PAGE 4
INTRODUCTION
SAFETY OVERVIEW
Read These Safety Precautions
Be sure to use the specied cable to connect
between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals.
When connecting the cable between the indoor and outdoor units make sure that the terminal cover
does not lift o or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause an electrical shock,
excessive heat generation, or re.
Do not damage or modify the power cable.
Damaged or modied power cables can cause electrical shock or re. Placing heavy items on the
power cable and heating or pulling the power cable can damage the cable.
Do not introduce air into the refrigerant system. If air enters the refrigerant system, an excessively high pressure results, causing equipment damage
and injury.
If the refrigerant leaks, be sure to locate the leak and repair it before charging the system with additional refrigerant. If the leak cannot be located and the repair work cannot be stopped, be sure to perform pump-down and close the service valve to prevent the refrigerant from leaking into the room. The refrigerant itself is harmless, but it can generate toxic gases when it contacts a heat source such as another appliance or an open flame.
When replacing the remote control battery, be sure to safely dispose of the battery.
Do not install the equipment in a place where there is a possibility of combustable gas leaks. If combustible gas leaks and remains near the unit, it
may cause a re.
Be sure to install the packing and seal on the installation frame correctly. If the packing and seal are not properly installed, water can spill out,
wetting furniture and the oor.
ENGLISH
Replace power cables and lead wires if they are scratched or deteriorated. Damaged cable and wires can cause electrical shock, excessive heat
generation, or re.
Check to see if the parts are mounted correctly, that the wires are connected correctly, and that connections at soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, electrical shock,
and re.
If the installation platform or frame has deteriorated or corroded, replace it. Corroded platform or frames
can cause the unit to fall, resulting in injury.
Check to make sure that the equipment is grounded. Repair it if it is not properly grounded. Improper grounding can cause an electrical shock.
Be sure to measure the installation resistance of the repair. Be sure that the resistance is 1 M ohm or higher. Faulty installation can cause an electric shock.
Be sure to check the drainage of the indoor unit after the repair. Faulty drainage can cause a water leak
from indoor unit and could cause property damage.
Important Safety Related
Installation Information
Indoor Clearances: If noncompliant may lead to temperature
control complaints.
Wire Sizing: If noncompliant may lead to communication errors and inverter irregular operation.
Splices in Field Wiring: Splices between the wires that connect between the outdoor and indoor unit should be avoided.
Sealing Penetrations: If penetrations at back of unit are not sealed, unconditioned air may be drawn into the back of the indoor wall mount unit. Temperature control and capacity complaints may occur.
INTRODUCTION
PAGE 5
[This page intentionally left blank.]
Section A - Outdoor Unit Installation
Step 1 - Installation of the Outdoor Unit
Attaching Drain Elbow to Outdoor Unit
(Heat Pump models only)
1.1
Step - 1.1
If attaching the supplied drain elbow to the outdoor unit, do so prior to attaching the refrigerant lines and wiring.
Extension piping to attach to this tting is eld supplied.
Electrical Connections for the Outdoor Unit
1.2
Step - 1.2
Remove the cover plate of the outdoor unit to expose the terminal block connections.
1.3
Step - 1.3
Connect the wiring for both the power source and indoor wiring. Wire the system according to applicable national / local codes. Verify that the wiring connections for the indoor unit match wire for wire. (1-1, 2-2, 3-3, Gnd-Gnd). Failure to wire the system correctly may lead to improper operation or component damage.
Step 1.1
Step 1.3
ENGLISH SECTION A
Step1.2
Step 1.4
1.4
Step - 1.4
Replace the cover plate.
Step 2 - Connecting the Indoor Unit
*See indoor section A, B, or C for electrical connections.
Piping
The standard lineset length is 25ft. If the installation length is
different, adjust the refrigerant charge by 0.5oz/ft.for the 24k,36k,42k and 48k model. (Illustration 4)
Cut the lineset to length, are and attach the piping to the
outdoor unit valves.
Torque the ttings to the specications shown in the torque
chart.
2.1
Step - 2.1
Refrigerant piping connections at the indoor unit are made utilizing flare joints. Follow standard practices for creating
pipe flares. When cutting and reaming the tubing, use caution to prevent dirt or debris from entering the tubing. Remember to place the nut on the pipe before creating the flare.
CAUTION
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
B
A
Max. Elevation: A Max.
= 100ft / 30m (24k / 36k)
In case the height of A is more than
Oil trap
B
Indoor unit
A
15ft / 5m, an oil trap should be installed every 16-23ft /5-7m
Max. Length: B Max = 165ft / 50m (24k / 36k)
B
Indoor unit
A
Illustration 4
2.2
Step - 2.2
To join the lineset piping together, directly align the piping are to the tting on the other pipe, then slide the nut onto the tting and tighten. Misalignment may result in a leaking
connection.
INSTALLATION
Step 2.2Step 2.1
PAGE 7
2.3
Step - 2.3
Two wrenches are required to join the are connections, one
standard wrench, and one torque wrench. See Table 1 for the
specic torque per piping diameter.
Forced fasteningwithout carefulcentering may
damagethe threads and cause a leakageofgas.
Pipe Diameter(ǿ)Fastening torque
Liquid side6.35mm(1/4") 18N.m/13.3Ft.lbs
Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs
Gasside12.7mm(1/2") 55N.m/40.6Ft.lbs
Gasside15.88mm(5/8") 60 N.m/44.3Ft.lbs
ENGLISHSECTION A
Half union
Spanner
Flarenut
Torque wrench
Table 1
Step 3 - Leak Test and Evacuation
Leak Test
Hazard of Explosion! Never use an open flame to detect refrigerant leaks.. Explosive conditions may occur. Use a leak
test solution or other approved methods for leak testing. Failure to follow recommended safe leak test procedures could result In death or serious injury or equipment or
property damage.
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure
testing as they may become flammable and could result in
an explosion. Refrigerant used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or
serious injury or equipment or property damage.
Step 2.3
Step 3.1 Step 3.2
3.1
Step - 3.1
Using a tank of nitrogen with attached regulator, charge the system with 150 PSIG of dry nitrogen. Use adapter AD-87
(field supplied) to connect to the service valve. Check for leaks at the flare fittings using soap bubbles or other detection methods. If a leak is detected, repair and recheck.
If no leaks are detected, proceed to evacuate the system.
System Evacuation
3.2
Step - 3.2
Attach a manifold gauge, micron gauge, and vacuum pump
to the suction line port using adapter AD-87 (eld supplied).
(Illustration 5)
Evacuate the system to 350 microns. Close the vacuum pump valve and check the micron gauge. If the gauge rises above 500 microns in 60 seconds, evacuation is incomplete or there is a leak in the system. If the gauge does not rise above 500 microns in 60 seconds, evacuation is complete.
Illustration 5
PAGE 8
INSTALLATION
3.3
Step - 3.3
Remove the adapter and hose connection from the suction line port, and replace the cap. Hoses should not be
removed and service valves should not be opened until any additional refrigerant needed for a refrigerant line longer than 25 ft. has first been added.
3.4
Step - 3.4A & 3.4B
Remove the cap from the liquid line valve. Using the hex wrench, open the valve, then replace and tighten the cap.
3.5
Step - 3.5A & 3.5B
Remove the cap from the suction line valve. Using the hex wrench, open the valve, then replace and tighten the cap.
3.6
Step - 3.6
Wrap the lineset, drain line, and wiring starting at the bottom of the bundle with an overlap type wrap, concluding at the piping hole. Use a sealant to seal the piping hole opening to prevent weather elements from entering the building. (Illustration 6)
Step 3.3 Step 3.4A
Step 3.4B
Step 3.5A
ENGLISH SECTION A
Verify the condensate drain line has a constant pitch
downward for proper water ow. There should be no kinks or rises in the tubing which may cause a trapping eect
resulting in the failure of the condensate to exit the piping.
Step 3.5B
It becomes
high midway.
Theendis imm­ersed in water.
It waves.
Thegap with the
ground is too small
Illustration 6
Step 3.6
Lessthan
5cm
Thereisthe bad smellfrom a sewer
INSTALLATION
PAGE 9
Step 4 - Charging
See Steps 5.2 - 5.5 for evacuating the system prior to charging. The standard lineset length is 25ft. If the installation length is different, adjust the refrigerant charge
by .5 oz / ft. for the 24K, 36K and 48K model. (Step 4 ­Illustration 4)
ENGLISHSECTION A
This product contains uorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type: R410A GWP* value: 1975 GWP = global warming potential
Please ll in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the eld and
• 1+2 the total refrigerant charge on the refrigerant charge
label supplied with the product.
The lled out label must be adhered in the proximity of the
product charging port (e.g. onto the inside of the stop valve cover).
A - contains uorinated greenhouse gases covered by the
Kyoto Protocol
B - factory refrigerant charge of the product: see unit name
plate
C - additional refrigerant amount charged in the eld
D - total refrigerant charge E - outdoor unit F - refrigerant cylinder and manifold for charging
Refrigerant Charge Label
System Test
Using the instruction manual, show the customer how to properly use and care for the equipment.
Check Items for Test Run
Put check mark in boxes
No refrigerant leaks from line sets or other connections?  Are the linesets insulated properly?  Are the connecting wirings of indoor and outdoor firmly
inserted to the terminal block?
Is the connecting wiring of indoor and outdoor rmly
connected?
 Is condensate draining correctly?  Is the indoor unit securely attached?
Is power source voltage correct according to local code? Is there any noise? Is the lamp normally lighting? Are cooling and heating (when in heat pump) performing
normally?
 Is the operation of room temperature sensor normal?
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
R410A
2
1=
2=
oz
oz
1
1+2=
FE
oz
A
B
C
D
PAGE 10
INSTALLATION
Section 5 - Explaining Operation to the End User
Protecti on wa lls
Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (the remote controller, removing the air lters, placing or removing the remote controller from the remote controller holder, cleaning methods, precautions for
operation, etc.)
Recommend that the user read the OPERATING INSTRUCTIONS carefully.
Section 6 - Seacoast Application
The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the installation instruction below.
Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage the outdoor unit.
ODU
ENGLISH SECTION A
Sea breeze
Sea
ODU
Sea breeze
ODU
Sea
If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the sea breeze.
A protection wall should be constructed with a solid material such as
concrete to block the sea breeze and the height and the width of the wall
ODU
should be 1.5 times larger than the size of the outdoor unit. Also, secure over 28 in (700mm) between the protection wall and the outdoor unit for
Sea
Sea breeze
ODU
exhausted air to ventilate.
Install the outdoor unit in a place where water can drain smoothly.
• If you cannot nd a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea water and the
dust on the outdoor coil.
INSTALLATION
PAGE 11
[This page intentionally left blank.]
Section B - Indoor Unit Installation - Wall Mount
Required Tools for Installation
Drill
Wire Snipper
• Hole Saw 2 3/4”
Vacuum pump
Soap-and-water solution or gas leakage
detector
Torque wrench
17mm, 22mm, 26mm
Tubing cutter
Flaring tool
Razor knife
Measuring tape
Level
Micron gauge
Nitrogen
• Mini-Split AD-87 Adapter (1/4” to 5/16”)
A - Non-adhesive Tape
B - Adhesive Tape
C - Saddle (L.S.) with screws
D - Electrical wiring
E - Drain hose (Included)
F - Insulation
G - Piping hole cover (Included)
Step 1 - Preparation
Procedure for Selecting the Location
Choose a place solid enough to bear the
weight and vibration of the unit and where
the operation noise will not be amplied.
Choose a location where the hot air
discharged from the unit or the operation noise and will not cause a nuisance to the user.
• There must be sucient space for
carrying the unit into and out of the site.
• There must be sucient space for air
passage and no obstructions around the air inlet and air outlet.
The site must be free from the possibility of ammable gas leakage in a nearby
place.
Install units, power cords and inter-unit cables at least 10ft away from television and radio sets. This is to prevent interference to images and sounds. (Noise may be heard even if they are more
than 10ft away depending on radio wave conditions.)
ENGLISH SECTION B
Clearances of Indoor and Outdoor Units
This picture is for reference only. Your product may look dierent. Read this manual before installation. Explain the operation of the unit to the user according to
this manual.
The models adopt HFC free refrigerant R410A
Attention must be paid to
more than 4in.
more than
4in.
Arrangement of piping directions
Rear left
Left
Below
The marks from to
G
in the name of the parts. The distance between the indoor unit and the
than 6 feet.
gure are the
oor should be more
Rear right
Right
A
more than 4in.
the pitch of drain hose
more than 4in.
more than 4in.
G
Floor fixing dimensions of the outdoor unit (Unit: inch)
eet t
23 5/8
he l
Z
6 7/8
ocal code.
16
A
F
C
Fixing of outdoor unit
D
E
1 2
Model
1U24/36/42/48 LP2VHA
Anchor the outdoor unit to the pad. When ins
he i
wall, t
Dimensions(inches)
1 x2
6 7/8
talling the outdoor unit on a roof or a outside
hould m
nstallation s
more than 24in.
more than 6in.
INSTALLATION
PAGE 13
Step 2 - Installation of Wall Mount Type Indoor Unit
Attaching the Mounting Plate to the Wall
2.1
Step 2.1
ENGLISHSECTION B
Using a stud sensor, locate and mark the stud positions in the wall where the indoor unit is to be mounted.
2.2
Step 2.2
Place the mounting plate on the wall in the desired location taking into account the minimum clearances necessary for proper operation.
Using a level, verify the mounting plate is horizontal and mark the screw locations.
2.3
Step 2.3
Screw the mounting plate to the wall.
Step 2.1
Step 2.2
The piping for the indoor unit may be routed to the unit from one of several directions. Left, Left Rear, Right, Right Rear, or Below (Illustration 1).
2.4
Step 2.4
Knockouts are provided on the case for Left, Right, and Right
Below.
Drilling the hole through the wall for left rear or right rear installation
2.5
Step 2.5A & 2.5B
Measure and mark the location where the piping hole is to be drilled.
2.6
Step 2.6
Drill the piping hole using a hole saw of the correct diameter. Angle the drill with a downward pitch to the outside wall so
that the outside hole will be ¼” lower than the inside hole,
giving the hole the proper angle for condensate drainage.
2.7
Step 2.7
Install the piping hole cover ange at the hole opening on the
inside wall.
NOTE: The cover ange may require modication to t
properly behind the wall unit housing.
2.8
Step 2.8A & 2.8B
Bundle the refrigerant piping, drain piping and wiring with tape and pass the bundle through the piping hole.
NOTE: When bundling the power cable, leave sucient length
available in the indoor unit to make the connections to the terminal block.
Step 2.3
Step 2.5A
Step 2.6
Step 2.8A
Piping Exit Options
Left
Step 2.4
Step 2.5B
Step 2.7
Step 2.8B
Rear left
Rear right
PAGE 14
Right
Below
Illustration 1
INSTALLATION
Outdoor unit
Mounting the Indoor Unit Onto the Wall Plate
2.9
Step 2.9
With the top of the indoor unit closer to the wall, hang the indoor unit on the upper hooks of the mounting plate. Slide the unit slightly side to side to verify proper placement of the indoor unit on the mounting plate. Rotate the lower portion of the indoor unit to the mounting plate, and lower the unit onto the lower hooks of the mounting plate. (Illustration 2) Verify the unit is secure.
2.10
Step - 2.10
Slightly raise the entire unit vertically, pull the lower portion
of the unit o the lower hooks of the mounting plate and away from the wall, then lift the upper portion of the unit o
the upper hooks of the wall plate.
Electrical Connections for the Indoor Unit
2.11
Step - 2.11A & 2.11B
To make the electrical connections for the indoor unit, two cover plates must be removed. Raise the front cover to access the screws to remove these covers.
2.13
Step - 2.13
Access the four conductor cable through the cover plate opening and make the wiring connections noting the wire color used on each terminal. The color of each wire must match the same positions on the terminal block of the outdoor unit. (Illustration 3)
Step 2.9
mounting plate
Illustration 2
Step 2.11A
ENGLISH SECTION B
Step 2.10
Step 2.11B
Failure to wire the system correctly may lead to improper operation or component damage.
2.14
Step - 2.14A & 2.14B
After the terminal block wiring is completed, replace both cover plates.
Note: Wall mount unit ships with HG remote controller. See Section F for more information.
Step 2.12
Indoor unit
Step 2.13A
3wire 14AWG
Control Wiring
Power Wiring
Step 2.13B
Illustration 3
Indoor Wall Unit Installation Complete
1
(
N ) 2 (L ) 3 (
C )
1
(
N
)
2
(
L
)
3
(
C )
INSTALLATION
PAGE 15
[This page intentionally left blank.]
Section C - Indoor Unit Installation - Cassette
Introduction - Overview
Cassette Product Information
The Cassette Indoor Air Handler ships consisting of a cassette assembly and operational louver. The Cassette Indoor Unit is operated via a factory supplied remote control. Wired controller is optional.
The Cassette unit will install between standard dropped
brackets that are located at all four corners of the cassette assembly.
The Cassette unit receives 230 volt line voltage from a connection at the outdoor condensing unit. T requirement for independent line voltage connections.
The cassette unit has a built in condensate pump and
Cassette unit. This hose connects the cassette condensate drain outlet to the building's condensate drain system.
The motorized louver is controlled via the remote control. The louver has indicator lights that communicate function and diagnostic information to the user and service technician.
here is no
Wired Controller is Optional
Built-in Condensate Pump and Float Switch
ENGLISH
Factory Supplied Remote
See Section F for more information
Outside Air
Mounting Hangers
Optional fresh air can be piped into the cassette assembly. The knockout is located on the side of the cassette assembly.
entering the cassette. A 4” galvanized pipe should be used to pipe in the fresh air.
Included with the cassette unit is factory provided insulating tape. This tape should be placed over the refrigerant piping connections at the indoor unit to prevent sweating.
Indoor AL24LP2VHA AL36LP2VHA AL48LP2VHA
Rated Cooling Capacity Btu/hr 24,000 35,000 45,000
Rated Heating Capacity Btu/hr 27,300 36,500 49,000
Voltage, Cycle, Phase V/Hz/-
Fan Speed Stages 4+Auto 4+Auto 4+Auto
Turbo/High/Med/Low/
Quiet) CFM
Motor Speed ( Turbo/High/Med/
Indoor Sound Level dB (Turbo/High/
Chassis Dimension: Height in (mm)
Chassis Dimension: Width in (mm)
Chassis Dimension: Depth in (mm)
Grill Dimension: Height in (mm)
Grill Dimension: Width in (mm)
Grill Dimension: Depth in (mm)
Weight (Ship/Net)- lbs (kg)
Drainpipe Size O.D. in 1 1/4 1 1/4 1 1/4
Internal Condensate Pump Standard Standard Standard
Max. Drain-Lift height in(mm)
Low/Quiet) RPM
Med/Low/Quiet)
Grill Model
Connections Flare Flare Flare
Liquid O.D. in 3/8 3/8 3/8
Suction O.D. in 5/8 5/8 5/8
208/230/60/1 208/230/60/1 208/230/60/1
740/630/480/400 990/900/776/700 1147/941/847/705
500/400/300/250
36/33/29/26
PB-950KB
9 5/8 (246)
33 1/8(840) 33 1/8(840) 33 1/8(840)
33 1/8(840)
2 (50)
37 3/8 (950)
37 3/8 (950)
79.4/68.3 (36/31)
39 3/8 (1000) 39 3/8 (1000) 39 3/8 (1000)
650/550/450/400 750/650/500/400
45/42/38/34
PB-950KB PB-950KB
9 5/8 (246)
33 1/8(840)
2 (50)
37 3/8 (950)
37 3/8 (950)
79.4/68.3 (36/31)
41/36/33/31
11 3/8 (288)
33 1/8(840)
2 (50)
37 3/8 (950)
37 3/8 (950)
83.8/70.5 (38/32)
SECTION C
INSTALLATION
PAGE 17
Introduction - Overview
Fresh Air Intake Option
The cassette has a marked area to cut out if outside air is desired. The piping connection should be made with a 4 inch
ENGLISHSECTION C
entry into the cassette.
Fresh air knock out
Condensate Handling
The Cassette unit has a built in condensate pump and water level safety switch. There is no option for gravity drain. The condensate pump is rated to lift water up to 24” from the point of discharge on the cassette assembly.
Electrical Power
Follow all local codes and regulations when installing electrical wiring.
Route required electrical power to area where cassette is to be located. Maintain at least a 10 foot separation between TV and Radio wiring and the power to the indoor unit.
14 Gauge AWG stranded wire should be used to make the electrical connection between indoor and outdoor units. This wiring will serve to power the indoor unit and establish a communication link between indoor and outdoor units.
The wiring is connected at the indoor unit electrical terminal blocks screws 1, 2, 3 and ground. There should be no splices in the wires connected to terminals 1 or 3 as these serve as communication signal wires and electrical power
power to the indoor unit, break wire 2 only.
The cassette unit comes with a grey connection hose with clamp. This hose is connected to the cassette assembly discharge hose port. The other end of the hose is sized to accept 3/4 “ PVC piping.
here:
12 in. below
3-5 ft.
11 in. under
8.6 in.
8.6 in.
19.6 in. below
Air Delivery Clearances
Be certain to maintain proper clearances around the
Standard clearances for cassette air handlers require 5 feet of clearance in each direction. There should be 8 feet of clearance from the face of the cassette louver to the
temperature control problems.
Service and Maintenance Clearances
Make sure there are adequate clearances for future maintenance and service. Allow enough room to access the condensate pump assembly and the electrical control box.
1 ft.
5 ft.
8 ft. Over
5 ft.
PAGE 18
INSTALLATION
Step 1 - Preparation
Drill
Wire Snipper
• Hole Saw 2 3/4”
Vacuum pump
Soap-and-water solution or gas leakage
detector
Torque wrench
17mm, 22mm, 26mm
Tubing cutter
Flaring tool
Razor knife
Measuring tape
Level
Micron gauge
Nitrogen
• Mini-Split AD-87 Adapter (1/4” to 5/16”)
A - Non-adhesive Tape
B - Adhesive Tape
C - Saddle (L.S.) with screws
D - Electrical wiring
E - Drain hose (Included)
F - Insulation
G - Piping hole cover (Included)
Procedure for Selecting the LocationRequired Tools for Installation
Place above the ceiling where you have
enough space to position the unit.
Place where the drainage pipe can be
properly positioned.
Place where the inlet and outlet air of the
indoor unit will not be blocked.
Do not install the unit in a place with
heavy oil or moisture (e.g. - kitchens and workshops)
Do not install in a location with destructive
gas (such as sulfuric acid gas) or pungent gas (thinner and gasoline) are used or stored.
Choose a place solid enough to bear the
weight and vibration of the unit and where
the operation noise will not be amplied.
Install where there are no expensive items
like a television or piano below the indoor unit.
Leave enough space for maintenance.
Install at least 3 ft. away from televisions
and radios to avoid interference.
ENGLISH SECTION C
Note:
1) R-410A refrigerant is a safe, nontoxic and
nonammable refrigerant. However, if
there is a concern about a dangerous level of refrigerant concentration in the case of refrigerant leakage, add extra ventilation.
Threaded Rod Mounting Information
The Cassette unit should be mounted to the building structure using threaded rods. The threaded rods should have washers and nuts to allow the height and level of the
cassette to be adjusted.
The threaded rods and attachment brackets are eld supplied
items. The materials required for mounting to the brackets on the cassette assembly include:
4- 3/8” Threaded Rods
4- Mounting Brackets 8- Washers 8- Nuts (Double nut the assembly as shown)
INSTALLATION
PAGE 19
Step 2 - Installation of the Cassette Unit
Step By Step Guide To Cassette Installation
2.1
Step 2.1
Use cardboard template to locate center point of cassette for mounting. Use a plumb bob and string to position cassette
ENGLISHSECTION C
by referencing center hole of template. Mark the mounting positions of the threaded rods using the guides on the cardboard template.
2.2
Step 2.2
Install threaded rods to structure using appropriate fasteners.
2.3
Step 2.3
Lift the cassette and position the threaded rods into the 4 mounting clips on each corner of the cassette unit.
2.4
Step 2.4
Using a level, adjust the nuts on the threaded rods to obtain a
level reading across the bottom of the cassette unit.
2.5
Step 2.5A & 2.5B
Prior to routing the refrigerant lines to the unit, install the
supplied are nuts onto the refrigerant lines. Using a aring tool, flare the refrigerant lines. Remove the caps attached to the ends of the refrigerant line connections at the
cassette. Holding charge will be released.
Step 2.1
Step 2.2
Using a torque wrench, torque the ttings to the proper specications. (See Outdoor Unit Section for are torque
settings.)
2.6
Step 2.6
Connect the grey exible drain hose supplied with the
cassette unit to the condensate pump discharge pipe of
the cassette. Tighten the clamp securely. Using 3/4 “ PVC, connect the exible hose to the building’s condensate drain
system.
2.7
Step 2.7
Remove the electrical box cover. Remove the rubber grommet and insert a 1/2 inch electrical connector and reducing washer. Route electrical wiring into cassette unit. Connect to wire terminas as indicated in schematic drawing. (USE 14 AWG Stranded wire only.)
2.8
Step 2.8A & 2.8B ,C, D
Connect Louver assembly to cassette assembly. Connect wires from louver to the harness on the cassette assembly. There are two wire connections. (See photo for connections.) Secure louver with four screws.
Step 2.3
Step 2.4
Reinstall electrical box cover. Install return air grille into louver assembly.
Installation is now complete.
PAGE 20
INSTALLATION
Step 2 - Installation of the Cassette Unit
Step 2.5A
Step 2.5B
Step 2.8A
Step 2.8B
ENGLISH SECTION C
Step 2.6
Step 2.7
Step 2.8C
Step 2.8D
INSTALLATION
PAGE 21
Step 3 - Elec
Electrical Connections Indoor and Outdoor Units
trical Connections
14 AWG S
tranded Wire Only. (Central Controller Not Used)
Maintain 10 feet of separation between TV and any Radio wiring.
ENGLISHSECTION C
Indoor uni
Note: Cassette unit ships with remote controller. See Section F for more information.
YR-HBS01
t
3wire 14AWG
Control Wiring
Power Wiring
Outdoor unit
1
(
N ) 2 (L
) 3
(
C
)
1
(
N
)
2
(
L
)
3
(
C
)
Step 4 - Louver Installation
To mount the louver cover onto the cassette assembly. Install 2 screws at the keyhole slot positions shown in the
rst photo. Place louver onto the 2 screws and press louver onto cassette housing. Swing hang clip into position.
(White circle.) Install remaining 2 screws and tighten the 4 screws. Connect electrical plugs to socket shown below. Install the electrical cover box and then snap the return air grille into position.
Step 5 - Pull Vacuum on System
See Step 3.2 of the outdoor unit installation section for how to pull a vacuum.
Indoor Casset
PAGE 22
INSTALLATION
te Unit Installation Complete
Section D - Indoor Unit Installation - High ESP Duct
Introduction - Overview
High ESP Duct Product Information
The High ESP Duct Indoor Air Handler ships consisting of a single assembly. The High ESP Duct indoor unit is operated via a factory supplied wired remote control.
High ESP
that are located at all four corners of the High ESP Duct
The High ESP Duct unit receives 230 volt line voltage from a connection at the outdoor condensing unit. There is no requirement for independent line voltage connections. The High ESP Duct unit has a built-in condensate pump and
Duct unit. This hose connects the High ESP Duct condensate drain outlet to the building’s condensate drain system. Included with the High ESP Duct unit is factory provided insulating tape. This tape should be placed over the refrigerant piping connections at the indoor unit to prevent sweating.
g
assembly.
High ESP
ENGLISH
YR-E17 Wired Controller
See Section E for more information
Built-in Condensate Pump and Float Switch
Indoor AM24LP2VHA AM36LP2VHA AM48LP2VHA
Rated Cooling Capacity Btu/hr 24,000 35,000 47,000
Rated Heating Capacity Btu/hr 26,500 37,500 52,000
Voltage, Cycle, Phase V/Hz/-
Fan Speed Stages 4+Auto 4+Auto 4+Auto
Airow (Turbo/High/
Med/Low/Quiet) CFM
Motor Speed (Turbo/High/
Med/Low/Quiet) RPM
Max. External Static Pressure in.W.G
Indoor Sound Level dB (Turbo/High/
Dimension: Height in (mm)
Dimension: Width in (mm)
Dimension: Depth in (mm)
Weight (Ship/Net)- lbs (kg)
Internal Condensate Pump Standard Standard Standard
Max. Drain-Lift height in(mm)
(Pa)
Med/Low)
Connections Flare Flare Flare
Liquid O.D. in 3/8 3/8 3/8
Suction O.D. in 5/8 5/8 5/8
Drainpipe Size O.D. in 1 1/4 1 1/4 1 1/4
208/230/60/1 208/230/60/1 208/230/60/1
845/670/530/470 1100/950/735/675
950/860/760/700
0.6(150) 0.6(150) 0.6(150)
38/35/32/29 32/28/25/23
9 7/8 (250) 9 7/8 (250) 9 7/8 (250)
37 5/8 (957) 59 (1500) 59 (1500)
25 3/4 (655) 28 3/8 (720) 28 3/8 (720)
81.1/68.8(36.8/31.2) 130.1/121.3 (59/55) 132.3/114.6 (60/52)
27 9/16(700) 27 9/16(700) 27 9/16 (700)
1000/920/860/810 1180/1080/1010/960
1350/1150/930/765
41/36/33/31
INSTALLATION
SECTION D
PAGE 23
Introduction - Ov
r
erview
Condensate Handling
The High ESP Duct unit has a built-in condensate pump and water level safety switch. There are also two optional ports for gravity drainage. The condensate pump is rated to lift water up to 24” from the point of discharge on the High ESP
ENGLISHSECTION D
Duct unit.
The High ESP Duct unit comes with a grey connection hose with clamp. This hose is connected to the High ESP Duct unit condensate discharge hose port. The other end of the hose is sized to accept 3/4 inch PVC piping.
Electrical Power
Follow all local codes and regulations when installing electrical wiring.
Route required electrical power to area where the High ESP Duct unit is to be located. Maintain at least a 10 foot separation between TV and Radio wiring and the power to the indoor unit.
14 Gauge AWG stranded wire should be used t electrical connection between indoor and outdoor units. This wiring will serve to power the indoor unit and establish a communication link between indoor and outdoor units.
The wiring is connected at the indoor unit electrical terminal blocks screws 1, 2, 3 and ground. There should be no splices in the wires connected to terminals 1 or 3 as these serve as communication signal wires and electrical power
connections. If a safety switch needs to be in place to shut o
power to the indoor unit, break wire 2 only.
o make the
Recommended condensate piping c
here:
12 in. below
3-5 ft.
8.6 in.
ongurations are shown
11 in. unde
8.6 in.
19.6 in. below
Air Delivery Clear
Make certain to maintain proper clearances around the High ESP Duct unit.
Inadequate clearances can cause sy temperature control problems.
Service and Maintenance Clearances
Make sure there are adequate clearances for future maintenance and service. Allow enough room to access the condensate pump assembly and the electrical control box.
ances
stem freezing and
PAGE 24
INSTALLATION
Step 1 - Preparation
Drill
Wire Snipper
• Hole Saw 2 3/4”
Vacuum pump
Soap-and-water solution or gas leakage
detector
Torque wrench
17mm, 22mm, 26mm
Tubing cutter
Flaring tool
Razor knife
Measuring tape
Level
Micron gauge
Nitrogen
• Mini-Split AD-87 Adapter (1/4” to 5/16”)
A - Non-adhesive Tape
B - Adhesive Tape
C - Saddle (L.S.) with screws
D - Electrical wiring
E - Drain hose (Included)
F - Insulation
G - Piping hole cover (Included)
Procedure for Selecting the LocationRequired Tools for Installation
• Place above the ceiling or in sot area
where you have enough space to position the unit.
Place where the drainage pipe can be
properly positioned.
Place where the inlet and outlet air of the
indoor unit will not be blocked.
Do not install the unit in a place with
heavy oil or moisture (e.g. - kitchens and workshops)
Do not install in a location with
destructive gas (such as sulfuric acid gas) or pungent gas (thinner and gasoline) are used or stored.
Choose a place solid enough to bear the
weight and vibration of the unit and where
the operation noise will not be amplied.
Install where there are no expensive
items like a television or piano below the indoor unit.
Leave enough space for maintenance.
Install at least 3 ft. away from televisions
and radios to avoid interference.
Threaded Rod Mounting Information
ENGLISH SECTION D
Note:
1) R-410A refrigerant is a safe, nontoxic
and nonammable refrigerant. However,
if there is a concern about a dangerous level of refrigerant concentration in the case of refrigerant leakage, add extra ventilation.
The High ESP Duct unit should be mounted to the building structure using threaded rods. The threaded rods should have washers and nuts to allow the height and level of the High ESP Duct unit to be adjusted.
The threaded rods and attachment brackets are eld supplied
items. The materials required for mounting to the brackets on the High ESP Duct unit include:
4- 3/8” Threaded Rods
4- Mounting Brackets Washers Nuts (Double nut the assembly as shown in step 2.3)
INSTALLATION
PAGE 25
Step 2 - Installation of the High ESP Duct Unit
Step By Step Guide To High ESP Duct Unit Installation
2.1
Step 2.1
ENGLISHSECTION D
Determine and mark the position of where the High ESP Duct unit is to be installed. Install the hardware necessary
to mount the threaded rods. Always select a location strong enough to support the indoor High ESP Duct unit.
2.2
Step 2.2
Install the threaded rods to the hardware attached to the structure.
2.3
Step 2.3
Lift the High ESP Duct unit and position the threaded rods into the 4 mounting clips, one located on each corner of the unit.
2.4
Step 2.4
Using a level, adjust the nuts on the threaded rods to obtain
level readings both side to side and front to back on the High ESP Duct unit.
2.5
Step 2.5 - 2.5A
Prior to routing the refrigerant lines to the unit, install the
supplied are nuts onto the refrigerant lines. Using a aring tool, flare the refrigerant lines. Remove the caps attached to the ends of the refrigerant line connections at the High
ESP Duct unit. Holding charge should leak out. Attach the refrigerant lines to the air handler.
Using a torque wrench, torque the ttings to the proper specications. (See Outdoor Unit Section for are torque
settings.)
Step 2.1
Step 2.2
Step 2.3
2.6
Step 2.6
Connect the grey flexible drain hose supplied with the High ESP Duct unit to the condensate pump discharge pipe of
the High ESP Duct unit. Tighten the clamp securely. Using 3/4 “ PVC, connect the flexible hose to the building’s condensate drain system.
2.7
Steps 2.7 - 2.7A - 2.7B
Route the 14AWG stranded 4 conductor power/ communication cable and the wired remote cable to the air handler. Use reducing washers and appropriate connector to attach the power/communication cable to the unit. The wired remote cable will enter the unit through a rubber grommet. The 4 conductor cable connects to the terminal block at terminals 1, 2, 3, and ground. The wired remote cable connects to the air handler main board at connector CN1. Re-install electrical box cover.
2.8
Step 2.8
The unit is now ready for connection to the ductwork.
The return air duct can be congured as either a rear side
inlet or bottom side inlet.
Step 2.4
PAGE 26
INSTALLATION
Rear side air inlet
Step 2 - Installation of the High ESP Duct Unit
Step 2.5
Step 2.5A
Step 2.7A
Step 2.7B
Re-install electrical box cover
ENGLISH SECTION D
Step 2.6
Step 2.8
Diffuser
Return Duct
Bottom side air inlet
Step 2.7
Diffuser
Return Duct
INSTALLATION
INSTALLATION IS NOW COMPLETE
PAGE 27
Step 3 - Electrical Connections
Outdoor unit
Electrical Connections Indoor and Outdoor Units
14 AWG Stranded Wire Only. (Central Controller Not Used) Maintain 10 feet of separation between TV and any Radio wiring.
ENGLISHSECTION D
Indoor unit
3wire 14AWG
Control Wiring
Power Wiring
1
(
N ) 2 (L
) 3
(
C )
1
(
N
)
2
(
L
)
3
(
C )
Note: High ESP Duct unit ships with YR-E17 wired controller. See Section E for more information.
Step 4 - Pull Vacuum on System
See Step 3.2 of the outdoor unit installation section for how to pull a vacuum.
Indoor High ESP Duct Unit Installation Complete
PAGE 28
INSTALLATION
Section E - Wired Controller YR-E17
WIRED CONTROL PANEL FUNCTIONS
Features and Interface
Clock; Parameter setting/Inquiry; Malfunction display
Timer ON/OFF; Sleep function; Parameter setting/Inquiry; Malfunction display
ROOM/SET temp. and humidity display, each step is 0.5°C (1°F). For example, if the temp is 25°C (77°F), it will display 25.°C (77°F). Humidity display function is reserved.
Energy Saving function. This icon will be dis­played only when energy saving function is set.
Filter Cleaning
Child Lock
Lock/Central
Motion Sensing (Reserved)
Left/Right Swing. This icon is displayed only when in swing function
ENGLISH SECTION E
Up/Down Swing. This icon is displayed only when in swing function
Sleep function. This icon is displayed when setting the sleep function. Remaining sleeping time is displayed in the top right corner.
Heat Reclaim Ventilation. This icon is displayed when setting the heat reclaim ventilation.
Electrical Heating. This icon is displayed when electrical heating is set on DC wired control.
Intelligent Mode--automatic cycling.
Cooling Mode
Heating Mode
Fan Mode
Dry Mode
User Friendly: Back light; Room temperature display
Functions:
Ventilation; ECO; Filter Cleaning; Error Code display; Child Lock; Parameter Inquiry; Unit NO. Setting; Static Pressure Grade Inquiry; Temp. Compensation setting; Forced Cooling/Heating
Clock; Timer; Sleep Function; Heat Reclaim
INSTALLATION
PAGE 29
A TYPE 1, FOR AL24/36/42/48LP2VHA, AM24LP2VHA
Indoor 1
Wire controller port
Indoor 2
Wire controller port
Indoor N
Wire controller port
Indoor 15
Wire controller port
control wiring of
Wire controller
TYPE 2, FOR AM36/42/48LP2VHA
Indoor 1
Wire controller port
Indoor 2
Wire controller port
Indoor N
Wire controller port
Indoor 15
Wire controller port
Indoor16
Wire controller port
Wire controller
Indoor16
Wire controller port
(master unit)
(master unit)
The communication wiring is 189ft (4.8 meter) long; if the actual length is more than it, please distribute wiring according to below table:
B
Indoor 1
Wire controller port wire
Wire controller
C
Indoor 1
Wire controller port wire
Wire controller
Polar wire
Wire controller
control wiring of
Wire controller
Wire controller
There are three methods to connection wire controller and the indoor units:
A: One wired controller can control max.up to 16 sets of indoor units, for Flexifit Pro series indoor units, there are two connection method Type 1: for model AL24/36/42/48LP2VHA,AM24LP2VHA,the wiring connection between wired controller - the master unit (directly connected to the wired controller), master unit ­slave unit, slave unit-slave unit should be one to one match of all three lines. Type 2: for model AM36/42/48LP2VHA,The wiring connection between wired controller-the master unit (directly connected to the wired controller) should be three polar wire, and the wiring between master unit - slave unit, slave unit-slave unit should be one to one match of two polar lines.
Note: PCB DIP switches are used for setting slave units, please refer to indoor unit wiring diagram.
B. One wire controller controls one indoor unit, and the indoor unit connects with the wire controller through 3 pieces of polar wire. C. Two wired controllers control one indoor unit. The wire controller connected with indoor unit is called master one, the other is called slave one. Master wire controller and indoor unit; master and slave wire controllers are all connected through 3 pieces of polar wire.
Note: There are PCB DIP switches for slave or master units selection, please refer to the indoor unit wiring diagram to get details.
*One side of the shielded sheet of communication wire must be earthed.
Indoor PCB port. For location number ,refer to indoor unit wiring diagram.
About the wire:
The wire controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow 3­red) is connected with the terminal A, B, C of wire controller respectively.
WIRED CONTROLLER INSTALLATION
Wired Controller Wiring Instructions
Dimensions
Unit: inch (mm)
ENGLISH
Dip Switch
Dip Switch ON/OFF Function Default Setting
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
ON Set as the slave controller
OFF Set as the master controller
ON Ambient temp. display available
OFF Ambient temp. display unavailable
ON Display ambient temp. from PCB of indoor
OFF Display ambient Temp. from wired controller
ON Auto-restart invalid
OFF Auto-restart valid
ON Fahrenheit
OFF Celsius
ON Swing angle adjustment available
OFF Swing angle adjustment unavailable
ON Up/Down and Left/Right swing
OFF Up/Down swing
ON Fresh Air unit
OFF General unit
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
REMOTE CONTROLS
PAGE 31
WIRED CONTROLLER OPERATION
Settings & Functions
Initialization
The wired controller will
ENGLISHSECTION E
1
2
3
This cycle keeps repeating until initialization is complete.
The green ON/OFF LED will also ash continuously until
initialization is complete.
If the wired controller is unable to communicate with the indoor unit PCB after powering on, initialization will terminate in 4 minutes. The communication malfunction can be checked using the malfunction inquiry function. (See Malfunction Display)
momentarily display all display icons upon powering up or when resetting the system.
During the initialization process, the controller will display, in a repeating order: 88:88 (upper left corner), 88:88 (upper right corner) 88.8 (main temperature).
Mode Setting
NOTE: This function requires the ON/OFF key LED to be turned OFF and the screen backlight to be illuminated.
Press and hold the MODE key for 5 seconds, the number of the mode currently being used will display in the upper left corner of the screen. (Default is 0) Press the pq keys to
change to one the dierent modes available: 0, 1, 2, or 3. Press SET to conrm the setting.
NOTE: Corresponding modes 0 – [Intelligent] [Cooling] [Heating] [Fan] [Dry] 1 – [Cooling] [Heating] [Fan] [Dry] 2 – [Cooling] [Fan] [Dry] 3 – [Cooling] [Heating] [Fan] [Dry] (same as 1)
Error Code Display
Note: This function requires the ON/OFF key LED to be turned OFF and the screen backlight to be illuminated.
Press and hold the TIME key for 10 seconds. The unit number will display in the upper left corner of the screen. The error code/historical error code will display in the upper right corner of the screen. Press pq keys to select the unit number to view its error codes. Under Error Code display screen, press and hold the TIME key for 5 seconds to clear the fault codes of all the units.
Switching between Fahrenheit & Celsius
To switch from Celsius to Fahrenheit, select the mode you wish to operate (COOL, HEAT, DRY, INTELLIGENT/AUTO). Press and hold the p key to reach 30 °C then continue holding the p key for 15 seconds until the display reads 86 °F. Use the
pq keys to adjust to desired temperature.
To switch from Fahrenheit to Celsius, select the mode you wish to operate (COOL, HEAT, DRY, INTELLIGENT/AUTO). Press and hold the q key to reach 60 °F then continue holding the q key for 15 seconds until the display reads 16 °C. Use the
pq keys to adjust to desired temperature.
Clock Function
1. The clock is displayed in 24 Hour time A. It cannot be set for AM/PM. B. The clock function cannot be set when SLEEP function or a timer function is currently set.
When the system is rst powered up, after initialization, the
clock will default to 12:00. Within 10 seconds of the clock be­ing displayed, the time can be set. The clock icon and minutes
portion of the time display will be ashing. Press the pq keys to adjust the minutes. (Pressing and holding the pq keys will accelerate the time adjustment.) With the minutes set, press
the TIME key. The clock icon and hours portion of the time
display will now begin ashing. Press the pq keys to adjust the hours. Press the SET key to conrm the setting.
To set the clock after initial power up or reset time has ex­pired, press and hold the TIME key for 5 seconds. The clock icon and minutes portion of the time display will begin ash­ing. Press the pq keys to adjust the minutes. With the min- utes set, press the TIME key. The clock icon and hours portion
of the time display will now begin ashing. Press the pq keys to adjust the hours. Press the SET key to conrm the setting.
If neither pq key is pressed within 10 seconds, or if the MODE, FAN, or ON/OFF keys are pressed prior to pressing the SET key, the setting function is canceled and the time reverts back to the previous setting.
Screen Saving
With the system turned o, tap the TIME key to activate the
screen backlight (if not already lit).
1. Press and hold the TIME and q keys for 5 seconds to set the
backlight “on” time. The set time will be displayed in the upper
right corner of the screen.
2. Press the pq keys to adjust the time. Set times available are: 0 seconds (backlight always on), 15 seconds, 30 seconds, and 60 seconds. Initial default time is 15 seconds.
3. With time selection made, press the SET key to conrm the
setting.
Press the MODE, FAN, TIME, SET, or ON/OFF key to exit the function. If no key is pressed in 10 seconds, the function will also exit. If there are no current errors or historical error
codes, “--” will be displayed.
PAGE 32
INSTALLATION
If neither pq key is pressed within 10 seconds, or if the MODE, FAN, or ON/OFF keys are pressed prior to pressing the SET key, the setting function is canceled and reverts back to the previous setting.
WIRED CONTROLLER OPERATION
Settings & Functions
ECO Energy Saving Function
NOTE: This function requires the ON/OFF key LED to be turned ON and the screen backlight to be illuminated.
Press the SET key. The swing louver function icon will
ECO
be ashing) Press the SET key to conrm the setting. The ECO
icon will remain on.
To cancel ECO function, repeat the above steps.
NOTE: The energy saving default parameters are listed below: 74°F Lowest temperature limit of Cooling and Dry mode. 78°F Highest temperature limit of Heating mode.
74°F – 86°F Temperature adjustment range in Cooling and Dry
mode.
60°F – 78°F Temperature adjustment range in Heating mode.
be displayed. Press the pq keys to advance through the functions to select ECO function. (The icon will
ECO Parameter Setting
NOTE: This function requires the ON/OFF key LED to be turned ON and the screen backlight to be illuminated.
For Cooling
Under Cooling mode, set the temperature to 86°F. Press and hold the FAN key for 5 seconds. The Cooling ECO param-
eter (ashing) will be displayed in the upper left corner of the
screen. Default temperature is 74°F. Press the pq keys to
adjust the lowest target cooling temperature. Press the SET key to conrm the setting and exit setup.
For Heating
Under Heating mode, set the temperature to 60°F. Press and hold the FAN key for 5 seconds. The Heating ECO parameter
(ashing) will be displayed in the upper right corner of the
screen. Default temperature is 78°F. Press the pq keys to
adjust the highest target heating temperature. Press the SET key to conrm the setting and exit setup.
ENGLISH SECTION E
Timer Function Setting
NOTE: The display backlight must be illumi­nated before proceeding. To turn the back­light on, press any key (MODE, FAN, pq, TIME, or SET) located at the bottom of the display, or press the ON/OFF key located at the top of the display.
Timer ON
Press the TIMER key once, the ON timer icon will appear in the upper right corner of the screen. The ON icon and hour posi­tion are ashing. Press the pq keys to set the hour. Press the TIMER key again, the ON icon and minutes position are
now ashing. Press the pq keys to set the minutes. Press the SET key to conrm the setting.
Timer OFF
Press the TIMER key 3 times, the OFF timer icon will appear in the upper right corner of the screen. The OFF icon and hour position are ashing. Press the pq keys to set the hour. Press the TIMER key again, the OFF icon and minutes position
are now ashing. Press the pq keys to set the minutes. Press the SET key to conrm the setting.
Timer ON/OFF
Press the TIMER key 5 times, the ON/OFF timer icon will ap­pear in the upper right corner of the screen. The ON icon and hour position are ashing. Press the pq keys to set the hour. Press the TIMER key again, the ON icon and minutes position are now ashing. Press the pq keys to set the minutes. Press the TIMER key again, the OFF icon and hour position are now
ashing. Press the pq keys to set the hour. Press the TIMER key again, the OFF icon and minutes position are now ashing.
Press the pq keys to set the minutes. Press the SET key to
conrm the setting. Based on the times set, the indoor unit will determine which event happens rst (ON-OFF or OFF­ON) and adjusts the arrow direction accordingly.
Static Pressure Grade Inquiry & Adjustment
NOTE: This function requires the ON/OFF key LED to be turned ON and the screen backlight to be illuminated.
Press and hold the SET and FAN keys for 5 seconds. The cur­rent static pressure will be displayed in the upper right corner
of the screen and the “Static Pressure” icon will begin to ash.
Press the TIME key to shift the unit no. displayed in the upper left corner of the screen. The unit numbers are from 00-15. Press the pq keys to change the static pressure grade, shown in the upper right corner of the screen.
Number range is 01-04. Press the SET key to conrm the
setting. Press the MODE, FAN, or ON/OFF key to exit the function. If no key is pressed in 10 seconds, the function will also exit.
INSTALLATION
If neither pq key is pressed within 10 seconds, or if the MODE, FAN, or ON/OFF keys are pressed prior to pressing the SET key, the setting function is canceled and reverts back to the previous setting.
Timer Cancel
Press the TIME key up to 9 times to cycle through the timer settings. When the timer icon disappears, the timer function is canceled.
Note: An active timer function will remain displayed on screen until the set time has been reached and command completed.
PAGE 33
WIRED CONTROLLER OPERATION
Settings & Functions
Left/Right/Up/Down Swing
The swing function deter-
ENGLISHSECTION E
mines air circulation.
1. Press SET key to access Swing function circulation.
2. Use pqkeys to select desired swing function.
If SW7 is on, air will circulate
UP/DOWN/LEFT/RIGHT.
3. Press SET key to conrm
swing function selection.
Parameter Inquiry
NOTE: This function requires the screen backlight to be il­luminated. The ON/OFF key LED can be either On or O.
Press and hold the SET key for 5 seconds. The unit number will be displayed in the upper left corner of the screen. The data type and current data will be displayed in the upper right corner of the screen. Press the pq keys to scroll through the data types. (See chart for data type/current data)
Press the MODE, FAN, SET, or ON/OFF key to exit the func­tion. If no key is pressed in 10 seconds, the function will also exit.
Forced Cooling/Heating
Note: This function requires the ON/OFF key LED to be turned OFF and the screen backlight to be illuminated.
Forced Cooling
When the system is turned o in cooling mode, press and hold
the ON/OFF key for 10 seconds. The system will enter forced
cooling. The temperature display will display a ashing “LL”.
Press the ON/OFF key to exit forced cooling mode.
Forced Heating
When the system is turned o in heating mode, press and hold
the ON/OFF key for 10 seconds. The system will enter forced
heating. The temperature display will display a ashing “HH”.
Press the ON/OFF key to exit forced heating mode.
NOTE: When in forced cooling or heating, all keys are disabled except for the ON/OFF key.
Child Lock Function
NOTE: This function requires the screen back­light to be illuminated. The ON/OFF key LED can
be either On or O.
Child Lock can be used to prevent unintended
operation of the control unit.
1. Press SET and the q keys together for 5 seconds to activate the Child Lock function. The child lock icon will be displayed on the left side of the screen. All normal functions of the keys will be disabled.
Unit Number Setting
NOTE: This function requires the screen backlight to be il-
luminated. The ON/OFF key LED can be either On or O.
Press and hold the SET key for 10 seconds. The wired control­ler address and communication address between the indoor and outdoor unit are displayed in the upper left corner of the screen. The central address is displayed in the upper right corner of the screen.
Press the pq keys to select the indoor unit number: 0 - 3F.
Press the SET key to conrm the setting. Press the MODE,
FAN, or ON/OFF key to exit the function. If no key is pressed in 10 seconds, the function will also exit.
PAGE 34
INSTALLATION
2. To unlock the Child Lock function, press the SET key and the q arrow together for 5 seconds. The child lock icon will disappear from the screen. All normal functions of the keys will be restored.
Temperature Compensation Setting
Note: This function requires the ON/OFF key LED to be turned OFF and the screen backlight to be illuminated.
Press and hold the FAN keys for 5 seconds, the current temperature compensation value is displayed in the upper right corner of the screen. (The default value is 00). Press the pq keys to change the temperature compensation value.
The adjustment range is -07°F to +07°F. Press the SET key to conrm the setting. Press the MODE, FAN, TIME, or ON/OFF
key to exit the function. If no key is pressed in 10 seconds, the function will also exit.
NOTE: The compensation value is used for ambient tempera­ture and is valid only for the wired controller sensor.
WIRED CONTROLLER OPERATION
Settings & Functions
Sleep Function
NOTE: This function requires the ON/OFF key LED to be turned ON and the screen backlight to be illuminated.
Press the SET key. The swing louver function icon will be displayed. Press the pq keys to advance through the functions to select the SLEEP func-
tion. The Sleep and Sleep “o” time icons will be displayed. (The Sleep icon will be ashing) Press the TIME key, the “o” icon will begin to ash. Press the pq keys to set the “o” time. (Time range is 0.5h to 72h) Press the SET key to conrm the setting. The Sleep function and “o ” time icons
will remain on.
If neither pq key is pressed within 10 seconds, or if the MODE, FAN, or ON/OFF keys are pressed prior to pressing the SET key, the setting function is canceled and reverts back to the previous setting.
To cancel the Sleep function. Press the SET key. The swing louver function icon will be displayed. Press the pq keys to advance through the functions to select the SLEEP function.
The Sleep and Sleep “o” time icons will be displayed. (The Sleep icon will be ashing) Press the SET key to cancel the
function.
Filter Cleaning
NOTE: This function requires the ON/OFF key LED to be turned ON and the screen backlight to be illuminated.
ENGLISH SECTION E
Other Functions
Note: These functions require the ON/OFF key LED to be turned OFF and the screen backlight to be illuminated.
Auto Restart
Setting DIP switch SW1-4 located on the PCB of the wired
control to the “on” position will disable the auto restart func­tion. When the switch is in the “o” position, auto-restart is enabled (default position). When the switch is in the “on” posi-
tion, auto-restart is disabled. Information retained in auto-restart are: Mode, Fan Speed, Temperature Setting, Swing State, and Heat Reclaim Ventila­tion function.
Communication Error of Wired Controller
If there is no communication between the wired controller and
indoor unit for 4 minutes, when checking error codes, “07” will
be displayed in the upper right corner of the display.
The Filter Cleaning icon will start ashing when
the indoor unit has reached 500 hours of operat­ing time.
After cleaning or replacing the lter, press the SET key to clear
the icon and reset the operating time.
Heat Reclaim Ventilation
NOTE: This function requires the ON/OFF key LED to be turned ON and the screen backlight to be illuminated.
Press the SET key. The swing louver function icon will be displayed. Press the pq keys to advance through the functions to select the Heat Reclaim
Ventilation function. (The icon will be ashing) Press the SET key to conrm the setting.
To cancel the Heat Reclaim Ventilation function, repeat the above steps.
If neither pq key is pressed within 10 seconds, or if the MODE, FAN, or ON/OFF keys are pressed prior to pressing the SET key, the setting function is canceled and reverts back to the previous setting.
This function is reserved for future models.
INSTALLATION
PAGE 35
[This page intentionally left blank.]
Display
Section F - Wireless Remote Controller
7
2
3
4
11
15
13
17
18
Functions
1
5
6
109
8
12
14
16
19
Note: TURBO/QUIET modes are only available when the unit is un­der cooling or heating mode (not for auto or fan mode).
Running the unit in QUIET mode for a long period of time may cause the room temperature to not reach the set temperature. If this occurs, cancel QUIET mode and set the fan speed to a higher setting.
3
COOL Button
In COOL mode, the unit operates in cooling. When FAN is
set to AUTO, the air conditioner automatically adjusts the
fan speed according to room temperature. The displayed during COOL mode.
4
HEAT Button
In HEAT mode, warm air will blow out after a short period of the time due to cold-air prevention function. When FAN is
set to AUTO, the air conditioner automatically adjusts the
fan speed according to room temperature. The displayed during HEAT mode.
5
DRY Button
DRY mode is used to reduce humidity. In DRY mode, when
room temperature becomes lower than temp. setting +2°F,
unit will run intermittently at LOW speed regardless of FAN
setting. The
6
Temperature +/- Buttons
Temp + Every time the button is pressed, the temperature
setting increases.
Temp - Every time the button is pressed, temperature
setting decreases.
The operating temperature range is 60°F-86°F.
will be displayed during DRY mode.
will be
will be
ENGLISH SECTION A
1
Power Button
Press the ON/OFF button on the remote control to start the unit.
2
TURBO/QUIET Button
The TURBO function is used for fast heating or cooling.
Press the TURBO/QUIET
control will display the TURBO side of the remote display and switch the unit to the TURBO function.
The QUIET function may be used when silence is needed for
fast rest or reading. Press the TURBO/QUIET again to switch to QUIET mode and the remote control will
display the QUIET remote display.
Press the TURBO/QUIET TURBO/QUIET and return to normal operation.
icon on the bottom left side of the
button once and the remote
icon on the bottom right
button
button a third time to cancel
INSTALLATION
7
AUTO Button
Under the mode of auto operation, the air conditioner will automatically select Cool, Heat, or Fan operation according to set temperature. When FAN is set to AUTO the air condi-
tioner automatically adjusts the fan speed according to room
temperature. The
8
FAN Button
Fan speed selection
Press the FAN as follows:
Remote control:
MED HI
LOW
The air conditioner fan will run according to the displayed fan speed. When FAN is set to AUTO, the air conditioner automatically
adjusts the fan speed according to room temperature.
will be displayed during AUTO mode.
button. For each press, fan speed changes
circulated
AUTO
PAGE 37
WIRELESS REMOTE CONTROLLER OPERATION
9
Louver SWING Button - Vertical
Air Flow Direction Adjustment
Press the SWING UP/DOWN button to choose the position of
the vertical airow louvers.
ENGLISHSECTION A
Status display of air ow
COOL/DRY:
HEAT:
Caution:
It is advisable not to keep the vertical louver in the down-
ward position for an extended period of time in COOL or DRY mode, otherwise condensate water may form on the louver.
Note:
When turning the unit on, the remote control will automatically return the louver to the previous set swing position. When turn-
ing the unit o, the louver will rotate to the full open position
prior to closing.
10
Louver SWING Button - Horizontal
Press the SWING UP/DOWN button to choose the position of
the horizontal airow louvers.
4. Once the desired length of time is selected for the unit to turn on, press the CONFIRM/CANCEL
to conrm
this setting.
The remote control display changes as follows:
0.5h
TIMER ON TIMER OFF TIMER ON-OFF
0.5h 0.5h
0.5h
TIMER OFF-ON
BLANK
Cancel TIMER ON setting: With a TIMER ON set, press the CONFIRM/CANCEL button once to cancel the TIMER ON.
Turning the unit ON with the TIMER from it being OFF will look like this on the remote control display:
Note: Holding the TIMER ON
button down will rapidly cycle the time. After replacing batteries or a power failure occurs, the time setting will need to be reset.
According to the Time setting sequence of TIMER ON or TIMER OFF, either Start-Stop or Stop-Start can be achieved.
Status display of air ow
COOL/DRY/HEAT:
'
Caution:
When humidity levels are high, condensate water may oc- cur at the air outlet if all horizontal louvers are adjusted to
left or right.
Note:
When turning the unit on, the remote control will automatically return the louver to the previous set swing position. When turn-
ing the unit o, the louver will rotate to the full open position
prior to closing.
11
Timer ON Button
On-O Operation
1. Start the unit and select the desired operating mode.
2. Press the TIMER ON
button to enter the TIMER ON
mode. The remote control will start ashing “ON”.
3. Every time the TIMER ON button is pressed the length of time increases in 0.5 hour increments between hours 0 and 12, and 1 hour increments for times between hours 12 and
24.
12
Timer OFF Button
On-O Operation
1. Start the unit and select the desired operating mode.
2. Press the TIMER OFF
button to enter the TIMER OFF
mode. The remote control will start ashing “OFF”.
3. Every time the TIMER OFF button is pressed the length of time decreases in 0.5 hour increments between hours 0 and 12, and 1 hour increments for times between hours 12 and 24.
4. Once the desired length of time is selected for the unit to
turn o, press the CONFIRM/CANCEL
to conrm
this setting.
The remote control display changes as follows:
0.5h
TIMER ON TIMER OFF TIMER ON-OFF
0.5h 0.5h
0.5h
TIMER OFF-ON
BLANK
Cancel TIMER OFF setting: With a TIMER OFF set, press the CONFIRM/CANCEL button once to cancel the TIMER OFF.
Turning the unit OFF with the TIMER from it being ON will look like this on the remote control display:
Note: Holding the TIMER OFF
button down will rapidly cycle
PAGE 38
INSTALLATION
Healthy
Healthy
WIRELESS REMOTE CONTROLLER OPERATION
the time. After replacing batteries or a power failure occurs, the time setting will need to be reset.
According to the Time setting sequence of TIMER ON or TIMER OFF, either Start-Stop or Stop-Start can be achieved.
13
SLEEP Button
Sleep mode
Press the Extra Function
options, cycle the button to display the
icon will ash. Press the Conrm/Cancel
button to enter additional
icon, the
button to
enter the sleep function.
Sleep Operation Mode
1. SLEEP mode during COOL, DRY modes One hour after SLEEP mode starts, the temperature will
rise 2°F above set temperature, after another hour, the temperature rises an additional 2°F. The unit will run for an
additional six hours, then turns o. The nal temperature
is 4°F higher than the initial set temperature. Using this
feature will help with achieving maximum eciency and
comfort from your unit while you sleep.
SLEEP operation starts SLEEP operation stops
1 hr
Temp.setting
Approx.6hrs
O
F
Rises 2
1 hr
O
Rises 2
F
In COOL, DRY mode
Unit stop
2. SLEEP mode during HEAT mode One hour after SLEEP mode starts, the temperature will decrease 4°F below set temperature, after another hour, the temperature will decrease an additional 4°F. After an additional three hours, the temperature will rise by 2°F. The unit will run for an additional three hours, then turns
o. The nal temperature is 6°F lower than the initial set
temperature. Using this feature will help with achieving
maximum eciency and comfort from your unit while you
sleep.
Temp.setting
1 hr
SLEEP operation starts
Decreases 4OF
1 hr
Decreases 4
3 hrs
In HEAT mode
Unit stop
O
F
3 hrs
Rises 3OF
SLEEP operation stops
3. In AUTO mode The unit operates in corresponding sleep mode adapted to the automatically selected operation mode.
Note:
-When the unit is set to sleep mode, the fan speed will be set to low speed and cannot be changed.
-When the TIMER function is set, the sleeping function cannot be set. If the sleeping function has been set, and the user sets the TIMER function, the sleeping function will be canceled, and the unit will be set to the timer
function.
14
EXTRA FUNCTION Button
Function:
A) Refresh air - Feature not available on this series.
B) A-B Yard - This will allow you to control two separate units
with a single remote control. Note: this feature would be setup at the time of installation by the contractor.
C) Fan Mode - Is indicated by the
icon. Only the fan will
operate in this mode. See section 8 “FAN Button” for
changing the fan settings.
D) Intelligent upward airow, E) Intelligent downward airow, F) Reset intelligent airow position
1. Press the ON/OFF button on the remote control to turn the unit on. Select the desired operating mode.
2. Setting the intelligent airow function
Press the EXTRA FUNCTION
button to enter ad­ditional options. Press this button repeatedly to access the louver settings. The louver icon will cycle through the following three settings.
airflow upward
airflow downward
Present position
Select the desired position, then press the CONFIRM/ CANCEL
button to set the function.
3. Canceling the intelligent airow function
Press the EXTRA FUNCTION
button to enter addi­tional options. Press this button repeatedly to access the
louver settings. Cycle the button to the louver icon “pres­ent” position, then press the CONFIRM/CANCEL
button to cancel the function.
Notice: Do not reposition the horizontal louver by hand. This may cause the louver to run incorrectly and not match the icon displayed on the remote control. If the
louver is not running correctly, turn the unit o for one minute, then back on, and adjust the louver setting with
the remote control.
Note:
1. After setting the intelligent airow function, the louver position is xed.
2. In cooling, it is better to select the
3. In heating, it is better to select the
mode.
mode.
4. In cooling and dry modes, using the air conditioner for a long period of time under high humidity conditions, con­densate water may form on the grille/louver.
ENGLISH SECTION A
INSTALLATION
PAGE 39
WIRELESS REMOTE CONTROLLER OPERATION
G) Fahrenheit/Celsius mode shift on unit and remote - To switch between Fahrenheit and Celsius press the EXTRA FUNCTION is displayed. Press the CONFIRM/CANCEL apply the change.
button until either Celsius or Fahrenheit
button to
ENGLISHSECTION A
H) 50°F low temperature heating - Feature not available on this series.
I) Electrical heating - Feature not available on this series.
15
HEALTH Button
Feature not available on this series.
16
Conrm/Cancel Button
Function: Setting and canceling timer and other functions.
17
LOCK Button
Used to lock buttons and LCD display
18
LIGHT Button
Turns indoor unit display on and o
19
RESET Button
If the remote control is not functioning properly, use a pen
point or similar object to depress this button to reset the
remote.
PAGE 40
INSTALLATION
[This page intentionally left blank.]
www.Haier.com
Model #: 1U24LP2VHA, 1U36LP2VHA,
1U48LP2VHA, AM24LP2VHA, AM36LP2VHA, AM48LP2VHA, AL24LP2VHA, AL36LP2VHA, AL48LP2VHA,AW24LP2VHA,AW36LP2VHA
Issued Date: Jan 2017
Haier America,
Wayne, NJ 07470
©2017 Haier America Trading, LLC.
Loading...