zNew cassette unit, with 700*700 panel and new unit body
zNew PCB for cassette indoor unit and outdoor unit, much stabler
zMutiple indoor unit types: cassette type, ceiling concealed type, and wall
mounted type
zFree combination, total indoor capacity can be 50%~130% of outdoor capacity
zMultiple control types, infrared control+wired control
zIndividual operation for every indoor uint, energy saving
zNew refrigerant control device: MP2A, MP3A
zAuto restart function
zLong piping and high drop between indoor and outdoor
zRefrigerant: R407C
Norminal condition: indoor temperature (cooling): 27 ćDB/19ćWB, indoor temperature (heating): 20 ćDB
Outdoor temperature(cooling): 35ćDB/24ćWB, outdoor temperature(heating): 7 ćDB/6ćWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter. It is a sound pressure noise level. The detailed method please refer to the following information:
Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction.
Testing method:
mounting-on-wall unit:built-in-ceiling unit: duct unit without auxiliary duct:
2m
duct
0.8m
1.4m
1.4m
1m
outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right
directions.
2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left,
right directions.
measured point:
H ( height to the ground) = (h (unit height) + 1m) /2
and, it is 1m to each side.
1m
1m
1m
h
Note: Ĵ is the real
time analyser position
1m
-13-
Page 14
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
3. Safety precaution
Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING!
CAUTION!
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
Incorrect operations may result in severe consequences of death or serious injuries.
Incorrect operations may result in injuries or machine damages; in some cases may
cause serious consequences.
WARNING!
If any abnormal phenomena is found
(e. g.smell of firing), please cut off the
power supply immediately, and contact
the dealer to find out the handling
method.
In such case, to continue using the
conditioner will damage the conditioner,
and may cause electrical shock or fire
hazard.
Don't dismantle the outlet of the
outdoor unit.
The exposed fan is very dangerous
which may harm human beings.
switch
off
After the unit being used for a long time,
the base should be checked for any
damages.
If the damaged base is not repaired, the
unit may fall down and cause accidents.
When the unit needs maintenance and
repairment, please call dealer to handle it.
Incorrect maintenance and repairment
may cause water leak, electrical shock
and fire hazard.
-14-
Page 15
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
WARNING!
Installed electrical-leaking circuit
breaker.
It easily cause electrical shock without
circuit breaker.
Air-conditioner can't be installed in
the environment with inflammable
gases because the inflammable gases
near to air-conditioner may cause fire
hazard.
Please let the dealer be responsible for
installing the conditioner.
Incorrect installation may cause water
leak, electrical shock and fire hazard.
Call the dealer to take measures to
prevent the refrigerant from leaking.
Nothing or nobody is permitted to
placed on or stand on outdoor unit.
The falling of goods and people may
cause accidents.
Don't operate the air-conditioner with
damp hands.
Otherwise will be shocked.
If conditioner is installed in a small
room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage.
When conditioner is removed or
reinstalled, dealer should be responsible
for them.
Incorrect installation may cause water
leaking, electrical shock and fire hazard.
Connect earthing wire.
Earthing wire should not be connected to the gas pipe, water pipe,
lightning rod or phone line, in-correct
earthing may cause shock.
Only use correctly-typed fuse.
May not use wire or any other materials
replacing fuse, other-wise may cause
faults or fire accidents.
Use discharge pipe correctly to ensure
efficient discharge.
Incorrect pipe use may cause water
leaking.
Earthing
-15-
Page 16
4. Net dimension
AU242FHBHA
948
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
Power wiring terminal
840
70
25
340
AU48*
184
70
580
948
55
18
184
380
Power wiring Terminal
184184
580
1250
25
18
380
18
-16-
70
55
340
Screw Hole
(4xM10)
Page 17
AB** Cassette unit:
B9
LXIQTIOM VQVM
:;9
A9
OIY VQVMRQW[QL VQVM
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
U\MXRIVML LQYZITKM JMZ]MMT ZPM KMQRQTO
ITL ZPM VITMRC ;>SS
Y[YVMTYQUT PURLMX
:>9SS
<;9SS
><>SS 7JMZ]MMT Y[YVMTYQUT VURMY8
>@9SS 7QTLUUX [TQZ LQSMTYQUT8
?>9SS 7KMQRQTO UVMTQTO LQSMTYQUT8
@99SS 7VITMR LQSMTYQUT8
GFEH D
AE** Ceiling concealed unit
100
54
240
C
>@9SS 7QTLUUX [TQZ LQSMTYQUT8
?>9SS 7KMQRQTO UVMTQTO LQSMTYQUT8
@99SS 7VITMR LQSMTYQUT8
KMQRQTO
:A9
VITMR
B>
?9SS
NXMYP IQX PURM
:=9
GFEH D
b
25
225
a
25
10
R
R
5
30
29(5
unit model
AE072FCBKA
AE092FCBKA
AE122FCBKA
AE142FCBKA
AE182FCBKA
AE242FCBKA
55
93
615
704
858
990
a
b
650
800
1020
1350
c
452
452
452
452
-17-
Page 18
AS** series
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
O
:=DAI
P
Q
FH@AE
AS072FCBHA AS092FCBHA
AS122FCBHA
AS142FCBHA AS182FCBHA
=
462
6/5
>
/32
?
.64
-18-
Page 19
Commercial Air Conditioner Model: AU242FHBIA,
Dimensions for MP2A, MP3A:
Installation on the horizontal ceiling:
horizontal ceiling
AU482FIBIA, AU48NFIBJA
-19-
Page 20
Installation on the vertical wall (adjust the installation position by fixing holder):
Dimension is the out diameter connecting to the tubing.
-21-
Page 22
FQG-B180
g
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
Refrigerant pipes between manifold pipes
Total refrigerating amount of indoor unit
Gas sideLiquid side
roup after the manifold pipe
Less than 38220Btu/h15.99.52
38220~61157Btu/h19.059.52
61157~126137Btu/h25.412.7
Note: 1. Y-shape manifold pipe can be placed in horizontal or vertical
direction
2. The manifold pipes must be welded with hard-solder
3. Pay attention to cut off the unnecessary part from its middle
parts of each joint, and to remove burr.
-22-
Page 23
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
In the file, the figure marked with "Ĝ" is permitted, and the figure marked with "h" is prohibited.
You can confirm the position according to the actual condition.
The refrigerant flow direction is always from the collective side to the divided side.
horizontal
vertical
floor surface
floor surface
floor surface
horizontal
floor surface
floor surface
floor surface
vertical
floor surface
floor surface
floor surface
-23-
Page 24
Commercial Air Conditioner Model: AU242FHBIA,
5.3 Instructions for the Electrical Expansion Valve Boxes
The E.E.V.B. general information for the C-MRV and H-MRV indoor units.
1. Installation position
AU482FIBIA, AU48NFIBJA
0°
360°
180°
Z: vertical direction
X, Y: horizontal direction
2. Installation place
The box should be installed where the place:
a. do not have vibrations;
b. easy to piping with the indoor and the outdoor unit, and the distance from the box to the indoor unit
should not exceed a certain value;
c. do not have a heat or steam source nearby;
d. should be sunless and be dry;
e. should be well ventilated and rainproof;
0°
wiring connector
liquid pipe in/out
f.do not have a strict noise restriction, because when working the box may make some noise;
-24-
Page 25
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
5.4 MP2A, MP3A Installation Requirement
1. Cautions
1.1 The place should be strong enough to support this equipment, no vibrantion;
1.2 The place where is convenient to install the indoor unit, outdoor unit and the refrigerant pipe, and
the length of the pipe is in the permitted range;
1.3 No heat source and gas source nearby;
1.4 The place has enough space for installation and maintenance;
1.5 Donpt installation in the place in the state of high temperature and high humidity for a long time;
1.6 The place with good ventilation, no direct sunshine and rain;
1.7 Donpt install the unit near the bedroom because of the refrigerant flow noise;
Please refer to the cautions and warnings in the operation manual about the other safety cautions.
2. Installation Method
2.1 MP2A, MP3A can be installed on the horizontal ceiling or the vertical wall by adjusting the fixing
holder. The maintenance plate should be installed on the place easy to maintain and near the place,
there should be checking hole with 600mm*600mm (adjust the fixing holder as below figure).
vertical wall
2.2 The equipment has been dealt with the EPS heat insulation material, so the drainage pipe needs
not any other treatments.
2.3 The pipe connected to indoor is led from the branch pipe of the equipment. The gas pipe
diameter can realize to match with different diameters by the changing pipe according to the
indoor pipe diameter request.
2.4 In installation, the equipment gradient should be in the range of 5¤, or it may cause electronic
expansion valve body in the equipment leakage or the other bad control failure.
2.5 Bolt, screw cap and gasket to fix the equipment will not be supplied by factory.
3. Wiring Connection
3.1 The wire and refrigerant pipe must be connected to the corresponding place (refer to marks on
the equipment and the terminal block as 1,2,3).
3.2 Wiring diagram is sticked on the back of cover plate, and the wiring must be performed
according to the wiring diagram, or the control will be bad or indoor and the equipment will be
damaged.
3.3 After wiring, the wires must be fixed with the wire clip firmly, in case that the electric control parts
5EJK9CC9KAFE D=K@F< AJ :=CFM- M@A;@ FECO K9B=J 671 9J 9E =N9DGC=/ 7C=9J= G9O 9KK=EKAFE K@9K K@= ?9J GAG=J
AEJK9CC9KAFE AJ 9J K@= J9D= 9J K@= ;FE<AKAFE MAK@FLK 670+671,/
AE<FFI CAHLA< GAG=
FLK<FFI CAHLA< GAG=
8.J@9G= D9EA>FC< GAG=
Piping length and drop between units
Haier
QRP
QRP
AE<FFI 2
AE<FFI 3
AE<FFI 4
AE<FFI 20
AE<FFI 30
AE<FFI 40
+
-26-
Page 27
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
1) When connected with 8 units,indoor units refer to <admissible combination examples>
2) Total length=l1+l2*2+l3*4+l4*4+l5*4<=100m
3) Max. piping length =(l1+l2+l3+l5)<=70m
4) Max. piping length between the indoor unit and the first branch pipe<=30m
5) Max. drop between outdoor unit and indoor unit: H<=30m(indoor above
outdoor);H<=20m(indoor below outdoor)
6) Max. drop between the two indoor units : h<=10m
7) Expansion valve is less than 15m to its corresponding indoor unit
8) Only wall mounted types are connected with expansion valves.
9) The expansion valves of different indoor models are different.
10)The first branch pipe must use FQG-180,the others use less than it.
Combination example:
8 by 1:
Haier
AE07
AE07
MP3A
MP3A
EEV
AE07
AE07
AE07
AE07
AB09
AS07
Note:
1.AU24 can connect with max. 5 indoor units, and AU48 can connect with max. 8 indoor units, but pay
attention that the total indoor capacity can not exceed 130% of outdoor cooling capacity.
2.
The ceiling concealed unit must connect with the outdoor unit through the MP2A or MP3A; the wall mounted
unit must connect with the outdoor unit through the exterior EEV box; while for the cassette unit, because it has
the built-in EEV, so it need not anything and it can connect to outdoor directly.
-27-
Page 28
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
6 by one
AU48-
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
Haier
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
EEV
AS09 (or other 9000BTU units)
-28-
Page 29
Commercial Air Conditioner Model: AU242FHBIA,
5.6 The Order of Installation Work
AU482FIBIA, AU48NFIBJA
Item
Before installationWork division -to ascertain the person responsible for installation of pipes and wiring
Work
Installation of indoor and
WorkMain points
Make installation
diagram
outdoor unit
Refrigerant pipe work-Pay attention to dry, clean and seal
Drain pipe work-Slant downward
Heat insulation work-No gaps in the joint of heat insulation material
Wiring work (control
wire, power cord)
Set every set switch-Should be complied with control wiring system diagram
Airtight test-Close all the gas, liquid valves
Vacuum drying-Should the vacuum pump that can reach 200Pa vacuity
Additional refrigerant-Write down the additional refrigerant amount on the outdoor unit body
Test run adjustment-Do test run to indoor unit one by one to verify if there is wrong pipes
Training of use and
maintenance
-to ascertain the pipe installation dimension and position of electronic
expansion valve, to make control wiring system diagram
-to prevent the ventilation from short circuit and guarantee repair space
-Choose the proper wire and cord
and record table
-Explain to user, simultaneously provide all the documents
The above work order is general knowledge, they may be changed to be complied with the
specific work site.
5.7 Attentive matters of safety
Before installing, do read this [Attentive matters of safety] carefully to guarantee the
proper installation.
The below attentive matters are divided into [warning] and [note] two parts. When the
wrong installation occur, it is very possible death and severe injury and other serious
accidents will happen. For those items are listed in [warning] part. But even the items
listed in [note] part can also cause serious accidents. Above all, both the two parts are
very important contents related to safety, so they must be obeyed.
After installation, do test run to verify everything is normal, after that please explains the
use method and maintenance method to the user according to the operation manual.
Additionally, give the installation manual together with operation manual to the user and
ask them to keep them properly.
Warning
The distributing shop, where you bought the air conditioner, or the specified shops shall
do the installation work. If you do the installation work by yourself, the improper
installation will cause water leakage, electric shock fire and other accidents.
The installation work shall be in line with what the installation manual specified. If
installation is not proper, water leakage, electric shock, fire and other accidents will
occur.
Install the air conditioner to a place where can definitely stand its weight. Places not firm
enough will cause drop down of unit resulting in body hurt.
The installation work shall be preventive to typhoon and earthquake. If the installation
-29-
Page 30
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
work is not met with the requirements, overturn of the unit will occur resulting in
accidents.
The wiring work shall be done by a qualified person and referred to the “technical
standard of electric equipment”, “indoor wiring regulation” and what the manual
specified. Do use special circuit. If the capacity of the circuit is not enough or bad work,
electric shock, fire and other accidents will happen.
Using the specified cable to do wiring work and connecting firmly and properly. Fix the
connecting part of the terminals to prevent it from the external force. Improper
connection and fixing will cause heating and fire etc. accidents.
Wiring shall be kept in correct shape avoiding extrusion. After installation, the electric
box cover and the external panel shall not nip the wire. Improper installation will cause
heating and fire etc. accidents.
When setting or moving the air conditioner do not let the air and things alike get into the
refrigeration system except the specified refrigerant. If air and other things enter,abnormal
high pressure will occur, which easily cause break and body injuries etc.
When installing, do use the accessories or specified parts. If not using the parts specified
by our company, water leakage, electric shock, fire and refrigerant leakage will occur.
Do not lead the drainpipe to drain where the sulfur gas may be involved. Otherwise, the
poisonous gas will enter into the indoor.
During installation, if refrigerant leakage occurs, do the ventilation work immediately. As
soon as the refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas
enters into room and meet the air blowing heater, heater or stove etc. fire source, the
poisonous gas may be produced. After installation, confirm there is no leakage of
refrigerant.
Do not install the unit in a place where the combustible gas may be leaked. In any case
the combustible gas leaks and accumulated around the unit, fire accident will occur.
Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose
of heat preservation. If the heat insulation measure is not sufficient, water generated by
condensing dew will drip leading to wet the floor and indoor articles.
Do not damage the power line or change it arbitrarily to avoid occurrence of fire or
electric shock.
Do not extend the power line or using other electric appliance in the same power
receptacle to avoid fire or electric shock.
Note
Do grounding work. Do not connect the grounding wire to gas pipe, tap, lighting rod or
telephone line. Improper grounding will cause electric shock.
In some places the electric leakage breaker shall be installed. If do not install the breaker,
electric shock may occur.
After installation, power on to do electric leakage detecting test.
-30-
Page 31
Commercial Air Conditioner Model: AU242FHBIA,
g
t
n
g
g
m
g
r
5.8 Special Work and Main Points in Installation
Warning
AU482FIBIA, AU48NFIBJA
Durin
leakage occurs, take ventilatio
measurement immediately.
As soon as the leaked refri
generate.
installation, if refrigeran
erant
as meets fire, poisonous gas will
After finishing installation, confir
the refrigerant gas does not leak.
If the refri
room, once it meets heater, burne
and gas stove etc. fire source, the
poisonous gas will generate.
erant gas leaks in the
A. Choosing of pipes
According to the following indoor unit and outdoor unit installation diagram to choose the
material and size of pipes and branch pipes.
B. Connection of pipes
1 Method of pipe connection
a. The pipe shall be as short as possible to guarantee efficiency.
b. Daub the refrigerant oil on the connection and flare nut.
c. When bending the pipes, give the roundness as large as possible, to avoid crashing the
pipes.
d. To connect the pipe, fit the center and screw the nut with hand, then use spanner or
torque wrench to tighten it. The fastening torque as shown in below table. As shown in
figure.
e. Be careful alien matters, such as sands,
water etc. shall not enter the pipes.
Forced fastening without
careful centering may damage
the threads and cause gas
2. Welding of pipes
a. In welding, the nitrogen shall be used to
avoid oxidation of the pipe inner part.
b. The refrigerating pipe shall use clean
new pipes. When working, it shall take steps to prevent water and dust from entering.
c. When loosening and tightening the nuts, two spanners shall be used. If using one
spanner, it can not reach the desired degree of tightness.
Using the specified fastening torque to fasten nuts.
(4) Pipe connection of the outdoor unit
Referring to the installation diagram in page 4, connect the indoor unit, outdoor unit,
branch pipe and electronic expansion valve together by using the pipe connection method and
welding method.
-32-
Page 33
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
5.9 Test of leakage after wiring work is finished
After connection of the refrigerant pipes, carry out leakage test. In this test,
pressurize to the pipes as shown in the below figure by using nitrogen tank.
Close the valves of the gas side and liquid side totally.
The nitrogen may enter the cycle system of the outdoor unit, so that, before pressurizing, the
valve rods must be fastened. (Both the gas side and liquid side).
For each of the refrigerant system, pressurize from the discharge valve of gas side in
procedure.
When doing leakage test, it is absolutely forbidden to use oxygen, flammable gas and
poisonous gas. The indoor unit expansion valve must be open.
5 vacuuming of the pipes and indoor unit (using vacuum pump to vacuums, it is strictly forbidden to use
refrigerant purging)
a. Choose of vacuum pump: it shall choose those that can reach a good vacuity (over 200Pa)and have
a large air discharge amount (over 40L/min).
b. After finishing the airtight quality test and the nitrogen discharging , connect the instrumental diverter
to the 3-way discharge valve, then connect the vacuum pump according to the below figure.
-33-
Page 34
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
c. Vacuumize 2~3 hours according to the length of the pipe. When vacuuming, confirm the
gas side and liquid side of the 2-way valve and 3-way valve shall be in full close state.
d. When it is not lower than 200Pa after 2 hours or more vacuuming, vacuums for another 1
hour. If after more than 3 hours vacuuming it is still not lower than 200Pa, the leak part
shall be found.
e. When it is lower than 200Pa after more than 2 hours vacuuming, close both the valve VL
and VH of the diverter, then close the vacuum pump. Place it there to observe if the
vacuity changes. If it changes, it indicates leakage exists, so the leak part shall be found.
f. After finishing the above vacuuming work, replace the vacuum pump with refrigerant
tank and turn to the refrigerant charging procedure.
5.10 Charging of refrigerant
1. Calculation of additional charging amount of refrigerant
After finishing vacuuming work, replace the vacuum pump with refrigerant tank and turn to
the refrigerant additional charging procedure.
Calculation of additional charging amount of refrigerant
Before the air conditioner leaving factory, the refrigerant-charging amount does not include
the refrigerant in the site pipe part. Calculate the refrigerant amount for the site pipe first, then
do the additional refrigerant charging work.
Refrigerant charging amount when air conditioner leaves factory
R407C:4200g.
Calculation method:
According to the liquid pipe dimension of site pipe and actual length to calculate the
additional refrigerant-charging amount.
Calculation formula:
Site refrigerant charging amount=Length of liquid pipe x additional refrigerant charging
amount/m
For example: additional charging amount
R (kg) = (L1x0.030kg/m)+(L2x0.065kg/m)
L1: Total length of liquid pipe diameter 6.35mm;
L2: Total length of liquid pipe diameter 9.52mm.
2. Charging of refrigerant
Close all valves of outdoor unit, and charge refrigerant from air discharge valve of gas side.
When can not charge the specified amount, firstly, open all the valves, both liquid side and
gas side, of outdoor unit, then switch the valve of gas side to close state a little. Under this
condition, do cooling operation and charge refrigerant from the discharge valve of gas side. At
this time, adjust the valve of the refrigerant tank to make the refrigerant in Gas State when it
is absorbed by system.
When refrigerant leakage making refrigerant lack in system occurs, the intrinsic refrigerant of
the system shall be recovered and recharge it according to specified amount.
Please read these "Safety Precautions" first then accurately execute the installation work.
The precautionary points indicated herein are divided under two headings:
!
WARNING and CAUTION those points which are related to the strong possibility of an
installation done in error resulting in death or serious injury are listed in the WARNING
section. However, there is also a possibility of serious consequences in relationship to the
points listed in the CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly
observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen
from the operation tests, please explain operating methods as well as maintenance methods to
the user of this equipment, based on the owner's manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.
Please entrust installation to either the company which sold you the equipment or to a
professional contractor. Defects from improper installations can be the cause of water
leakage electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again improper
installations can result in water leakage, electric shocks and fires.
Please install your air conditioner on a wall or any place which can holder the weight of the
air conditioner. And it cannot be installed on a non-professional metal structure (such as a
burglary-resisting net). Otherwise injury would occur due to a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong airs
of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent
falling over of the unit.
Wiring shall be done with the specified cable and the connection shall be firm and reliable.
And the terminal connector shall be fixed firmly and reliably not to let external force exercise
on the cables. Any improper connection or fixing would cause heat, fire, and other accidents.
Wiring shall be done in a correct shape not to make any section rise upward, and accurately
install the air conditioner. The cable shall not be clamped by the lid or outer plate. Any
improper installation would lead to fire, heat, or other accidents.
When setting up or moving the location of the air conditioner, do not mix air etc, or anything
other than the designated refrigerant (R407C) within the refrigeration cycle, for such mixing
would result in rupture and injury caused by abnormal high pressure.
Always use accessory parts and authorized parts for installation construction. Using parts not
authorized by this company can result in water leakage, electric shock, fire and refrigerant
leakage.
The drain pipe must not be placed or connected into the sewage tank where harmful gas such
as sulphurous gas and etc would exist, otherwise the harmful gas would enter the room.
During installation, if the refrigerant is leaked, please immediately take measures of
ventilation, otherwise a harmful gas would be generated whenever the refrigerant meets fire.
After installation, please ensure that the refrigerant is not leaked, because the leakage of
refrigerant would produce a harmful gas if it meets fire or heating stoves.
Don't install the air conditioner where a flammable gas would be probably produced,
otherwise in case the flammable gas is leaked and exists around the unit, fire would be
caused.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and
thermally insulate it to prevent condensation. Inadequate plumbing can result in water
leakage and water damage to interior items.
The refrigerant gas pipe and liquid pipe shall all be thermally insulated to preserve the
temperature. Any improper insulation would make the unit moist and the water would drop
onto the floor or wet the indoor items.
!
!
!
WARNING
-42-
Page 43
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
PRECAUTION
Execute proper grounding. Do not connect the earth wire to a gas pipe, water pipe,
lightening rod, or a telephone ground wire.
Improper placement of earth wires can result in electric shock.
An electric leakage breaker must be installed, otherwise electric shock or other accidents
would occur.
After completion of the installation, the air conditioner shall be electrified to check for
electric leakage.
Preparation for installation
Installation Tools
1. Screw Driver (flat head, wabbler, triangle)
2. Steel Saw
3. 60mm Drill
4. Inner Hexagon Spanner
5. Shifting Spanner
6. Spanner
7. Pipe Cutter
8. Pipe Expander
9. Knives
10. Clippers
11. Leakage Checker or Soap Liquid
12. Measuring Tape
13. Scraper or File
14. Refrigeration Oil
Self-contained Accessories
No.
Name of
Parts
A
Non-adhesive
Tape
BCDEF
Adhesive
tape
Connecting
Hose
insulation
Gypsum
powder
Drain hoseHeat
material
Electrical Requirements
Power supply voltage: Single Phase 1PH, 220-230V~, 50Hz.
A specialized power supply wire, which shall be installed by a competent person as per the
rules of the national standard.
Power supply must be grounded effectively.
An electric leakage breaker shall be installed.
Layout of power supply wiring shall be Y connection. If the power supply wire is damaged, it
must be replaced by the manufacturer or its service center or professional person (the power
supply wire shall be self-contained).
For connection of the power supply plug, L shall be connected with the live wire, N shall be
connected with netural line, shall be connected with earth wire.
Power supply wire parameters:H05RN-F,3 G(1.0-1.5)mm ;
Signal wire parameters:H05RN-F,2 (0.75-1.5)mm . (User shall self-provide signal wire )
X
2
2
Note:The singnal wire and connection wire should be provided for oneself.
The singnal wire must be shielded wire
!
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION
AND/OR PROPERTY DAMAGE.
BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
-43-
Page 44
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
1.Accessories
Confirm accessories shown below are attached in the bag with this Installation manual.
Accessories Delivered with Your Air Conditioner
Please check if your unit is delivered with the following accessories.
No.
Name
1234
Remote
controller
Batteries
Mounting plate
Drain hose
5
x
4 25 screw
6
Expansion
bushing
Cement
steel nail
Piping hole
cover
Screw
and
shape
Qty
1121
66
81 2
Indoor Unit
Install the indoor unit where the weight of the unit can be supported.
Install the indoor unit where the heat source and steam source are not close and the
Unit inlet and outlet are not blocked.
Install the indoor unit where the drainage is easy and the outdoor unit can be
Easily connected.
Install the indoor unit where its cold air and hot air can be easily sent to all the comers
of the room.
Install the indoor unit where the power socket is near and there is sufficient space
around the indoor unit.
Install the indoor unit where there is no T.V set, radio set, and wireless appliance
Underneath, and the sunlight lamp is over one meter away.
If the remote controller is installed on the wall, the indoor unit shall be ensured to receive
The signal while the sunlight lamp is on.
Method for Cutting and Expanding Pipes.
When the pipe is too long or the mouth is damaged, the pipe needs to cut or expanded.
1.cutting hose
2.Removing burr
3.Put on nut4.Expand Hose
10987
Plastic
supporting
plate
1
Correct
A
Hose Expander
cracks on expanded mouth
Expansion Size
Hose dia.
6.35 mm(1/4)
12.7 mm(1/2)
Not Correct
burr
-44-
Size (mm)A
0.8-1.5
1.0-2.0
incompletetoo longTilting
Page 45
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
When the mounting plate is firstly fixed
1. Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate
to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a
weight from the central top of the plate, then fasten securely the plate with the
attachment steel nail.
3. Making a Hole on the wall and Fitting the piping Hole cover
Make a hole of 60mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation.
Indoor side
Wall hole
60mm
Outdoor side
Thickness
of wall
4. Drawing of pipe
(Section of wall hole) Piping hole pipe
Rear piping
Draw pipes and the drain hose, then fasten them with the adhesive tape.
Left Left-rear, piping
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark
of hole for left-rear piping which is marked on heat insulation materials.
a. Insert the drain hose into the dent of heat insulation materials of indoor unit.
b. Insert the indoor/outdoor electric cord from backside of indoor unit, and pull it out
on the front side, then connect them.
c. Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing
with adhesive tape.
Lid for right piping
Lid for under piping pipe
Heat insulation
material
Drain hose
Lid for left piping
Piping
Pipe supporting
plate
Indoor/Outdoor
Electric cable
Fix with adhesive tape
Indoor/outdoor electric cord and drain hose must be bound with refrigerant piping by
Protecting tape.
-45-
Page 46
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
Other direction piping
Cut away, with a nipper, the lid for piping according to the piping direction and then
bend the pipe according to the position of wall hole. When bending, be careful not
to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the
connected to the heat insulation of connecting part specially.
5.Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to verify its
secure fixing.
In order to fix the body onto the mounting plate, hold up
the body aslant from the underside and then put it down
perpendicularly.
Putty
Electric wiring
When connecting the cord before installing the indoor unit
Insert the cord from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cord ends fully into terminal block, then
tighten the screws.
Pull the cord slightly to make sure the cords have been properly inserted and
tightened.
After the cord connection, never fail to fasten the connected cord with the
wiring cover.
Note: when connecting the cord, confirm the
terminal number of indoor and outdoor units
carefully. If wiring is not correct, proper operation
can not be carried out and will cause defect.
!
CAUTION
After connecting the p iping, check the joints for gas leakage with gas leakage detector.
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)(Fig.17A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of
the exposed solid wire.
(2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal
screw using a screw driver.
B. For strand wiring (Fig.17B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of
the exposed strand wiring.
(2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 17
A. Solid
Loop
B. Strand wire
Round
terminal
Strip 25mm
Insulation
After passing the connection cord and power cable through the
insulation tube, fasten it with the cord clamp, as shown in Fig.18
Strip 10mm
-46-
Page 47
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
Fig. 18
Screw with
Insulation tube
Cord clamp
Wire
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
special washer
Round
terminal
Terminal
board
Wire
Screw with
special washer
Round
terminal
Check the Layout of the Drain Pipe and Connection Wires
The drain pipe should be placed underneath, and the connection wires should be placed upside;
and the drain pipe especially the section inside the machine and indoors must be wound up with
insulating material to preserve heat. The drain pipe shall be sloped and no concave and convex
shall occur along the whole pipe. And the cases as the right figure indicates shall not occur.
Installation check
Is power supply voltage required?
Is water completely drained to outdoors?
Are power wire and connection wires between indoor and outdoor units correctly connected?
Is any gas leaked from the pipe connectors?
Are series numbers of the terminals on the indoor and outdoor units corresponding to each
other? Is the connection section of the auxiliary pipe insulated? Is the indoor unit fixed firmly?
Is noise big?
Trial Operation
The person who has completed this installation shall be requested to conduct a test operation
for check:
Is the temperature adjuster working normally?
Does the location for installation conform to requirements?
Winding up with Protective Plastic Tape
The connection pipes, drain pipe, and the connection wires shall be wound up with PVC tape.
Notes: The connection pipes shall also be wound up with insulating material to preserve the
temperature. The airing direction shall be from bottom to top.
speed:
TC˚30ć, med speed
TC˘15ć, fan off
ƽ Current state is med
speed:
TC˚42ć, high speed
TC˘22ć, low speed
ƽ Current state is high
speed:
Fan motor
1
control
2 EEV In COOL, DRY, DEFROST state, EEV will open fully with 480 pulse.
TC ˘ 39 Current state is
med speed:
1. Startup period in heating:
High speed
2. Running state in heating:
ƽTA˚17ć
running units capacityİ
1HP, low speed will be
ON and OFF in turns.
ƽOther condition:
TE˘7ć, high speed
TE˚10ć, low speed
1. Startup period in cooling
mode: high
2. Cool, Dry mode:
ƽ Current state is Fan OFF
mode:
TC˚37ć: low speed
ƽCurrent state is low speed:
TC˚50ć, med speed
TC˘30ć, fan off
ƽCurrent state is med speed:
TC˚47ć, high speed
TC˘40ć, low speed
ƽCurrent state is high speed:
TC˘41ć, med speed
ƽIn low speed:
TC˘40ć, lower fan off
TC˚42ć, lower fan startup
1. Startup period in heating:
High speed
2. Running state in heating:ƽ
TA˚17ć
running units capacity İ
1HP, low speed will be ON
and OFF in turns.
ƽOther condition:
TE˘7ć, high speed
TE˚10ć, low speed
3. TE˚14ć, lower fan off
TE˘12, lower fan startup
1. Startup period in cooling
mode:
TA˚16
TAİ16ć, low speed
2. Cool, Dry mode:
ƽTA˚32ć, high speed
ƽ15ćİTA˘31ć:
TC˚45ć, high speed
40 ć˘TC ˘ 44 ć , med
speed
TC˘39ć, low speed
ƽTA˘15ć:
TC˘30ć, fan off
TC˚50ć, low speed
ƽIn low speed:
TC˘36ć, lower fan off
TC˚38ć, lower fan startup
ƽ 17 ć˚TA ˚ 15 ć, low
speed
ƽ 14 ć˚TA ˚
speed
ƽTA˘9ć, high speed
ć, high speed
1. Startup period in
heating:
TAı20ć, low speed
TA˘20ć, high speed
2. Running state in
heating:
ƽTA˚17ć:
running units capacityİ1
HP, low speed will be ON
and OFF in turns.
running units capacity ˚
1HP, low speed
10 ć , med
-71-
Page 72
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
control In heating mode, EEV will be adjusted due to the overheating value: SH= TS-TC
1. Adjust range: according to the compressor frequency, min open angle of EEV will be
different: high frequency, 120; med frequency, 110; low frequency, 90; the max open
angle: 470/350
2. Overheating modification: according to the discharging temperature, modify the
overheating value, when Td>100ć, overheating value will decrease 2 at the standard
overheating value; when Td İ 70 ć , overheating value will add 2 at the standard
overheating value
1. Secure operation conditions of 4-way valve:
ƽ After the outdoor receives the heating signal from indoor unit, if the 4-way valve is
not electrified before the compressor starts up, the unit will enter the 4-way valve
secure operation.
ƽ After defrosting is over, the unit will enter the 4-way valve secure operation.
2. 4-way valve secure operation control:
ƽ In heating mode, After the outdoor receives the startup signal from indoor unit, the
compressor will start up, (fan motor shutoff, EEV close) and when the frequency rises up
to 50Hz for 10 seconds, 4-way valve will reverse (meanwhile, fan motor will enter the
target speed, EEV enters the open angle of soft startup) and the unit enters soft startup
period.
ƽ In defrosting, when the defrost condition is met, the compressor frequency will
decrease to 50Hz, 4-way valve will reverse (meanwhile, fan motor will enter the target
speed) and the unit enters soft startup period.
3. 4-way valve control in OFF state:
4-way valve will close after compressor stops for 30 minutes.
1. Enter condition:
when compressor
runs for 45 minutes
in all in heating
1. Enter condition: when compressor runs for 45 minutes in
all in heating mode, by checking TE and TA, if the below
conditions can be met for continuous 5 minutes, the unit
will enter defrosting operation: TEİChTAˉ¢, herein,
ƽC˖TA˘0ć, C=0.8; TAı0ć, C=0.6
ƽ¢˖set as 12˄L˅,10˄M˅,8˄H˅ according to the
actual condition. At the easily defrosting place, set as H; at
the not-easy-defrosting place, set as L; when out of factory,
set as M
ƽTemperature limitation: -15ćEİTEİ2ćE
mode, by checking
TE and TA, if the
below conditions can
be met for
continuous 5
minutes, the unit will
enter defrosting
operation:
ƽWhen Ta˘2ć, TA-TE
ı9ć for continuous 2
minutes; or Te ˘ -12 ć
for continuous 5 minutes;
ƽWhen Taı2ć, Te˘-5
ć for continuous 5
minutes;
3
Defrosting
4
4-way
valve
secure
operation
control
-72-
Page 73
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
2. Defrosting control:
When defrosting condition is met, compressor frequency will go down to the min.
frequency, and 4-way valve will be powered off and turn into cooling mode (fan motor off,
EEV in soft startup open angle); compressor frequency rises up to 78Hz and begins to
defrosting operation.
3. Quit condition:
ƽTE is over 7ć for 60 seconds in all or is up to 12ć, defrosting is over;
ƽDefrosting accumulative time is up to 10 minutes, defrosting is over.
5
Unloading
6
valve SV1
7
valve SV2
Pressure
8
Electric
heater
control
control
Spray
control
switch
control
1. When TAİ27ć, if the compressor stops running, electric heater will be electrified;
2. When TAı27ć, or when compressor starts up, electric heater will be off; and temp.
difference is 5ć.
1. To balance pressure: it will open 1 minute before compressor starts up, and keep open
in soft startup period after compressor starts up until the soft startup is over; in the
remaining operation and 10 minutes later after shutoff, SV1 will open;
2. Improve low pressure: in heating mode, when (TCǃTSǃTE)min. valueİ-13ć SV1
open, temp. difference is 3ć.
Adjust the SV2 according to the discharging temperature:
when TDı115ć, SV2 will open; when TDİ110ć, SV2 will close.
High pressure switch protection:
ƽWhen input level of pressure switch is 1, it shows there is no protection.
ƽWhen input level of pressure switch is 0 for a while, it shows high pressure beginning;
compressor stops and the unit alarms. The alarm can be resumable, the unit will alarm in
3 minutes when compressor is standby.
Low pressure switch protection:
ƽWhen input level of pressure switch is 1, it shows there is no protection.
ƽ When compressor is running, if low pressure switch has acted for 3 minutes
continuously, the unit will alarm. When compressor stops, if low pressure switch has acted
for 30 seconds continuously, the unit will alarm. When compressor starts up, low pressure
switch will be shielded within 3 minutes.
ƽIn defrosting and in 6 minutes after defrosting is over, low pressure switch will be
shielded.
-73-
Page 74
Compress
or capacity
9
output
control
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
In cooling mode, frequency will be calculated according to
the horse power of the running indoor units:
1. Every indoor unit will confirm 8 capacity codes
according to the difference between the set temperature
and the ambient temperature; then add all the capacity
code of the running indoor unit.
2. Divide the outdoor capacity into 13 capacity classes due
to the frequency; every capacity class is corresponding
with the different indoor capacity code; modify the relative
indoor capacity code due to the different ambient
temperature;
3. Compressor will confirm its target frequency according
to the sum of indoor capacity code;
Heating target frequency will be confirmed due to the indoor running horse power and the
In cooling mode, the adjustment by the over heating: SH= TC1(gas
pipe)-TC2˄liquid pipe˅
1. Adjust range: min. angle: 60/65, max. angle: 470/350˄data will take
EEPROM as standard˅
2. Overheat modification: according to the discharging temperature, modify
the overheat state, if Td > 100 ć, the overheat value will add 2 degree at the
base of standard degree;
3. Open modification: when EEV is at min. angle, the unit will measure the
difference between Tliquid and Ta at the interval of 5 minutes, if the
difference is within 5 degree, the valve will be back to base open angle and
modify the open angle due to the overheat state
In heating mode, adjust the open angle according to the conformity of liquid
pipe temperature.
1. Adjust range: indoor unit startup, min open angle: 100, max open angle:
470; indoor unit standby: open angle: 60.
2. The indoor EEV open angle will depend on the temperature difference
between indoor liquid pipe temp. and average liquid temp. of all running
indoor units. (if lower than average temp., the valve will open; if high than
average temp., the valve will close.
AE*FCBKA AS*FCBHA AB*FCBIA
Anti-freeze control in cooling mode:
ƔWhen liquid pipe temp. is below 7 degree for 40 minutes, or when liquid
pipe temp. is below 4 degree for 10 minute, the unit will enter anti-freeze
function. At this time, the current indoor EEV will close, and the fan motor will
turn into low speed from the current speed.
ƔAfter the anti-freeze function has worked for 10 minutes, and liquid pipe
2
Fan motor
control
temp. is over 7 degree, the unit will quit anti-freeze control (take the data in
EEPROM as standard).
Anti-cold air control in heating mode:
ƔWhen liquid pipe temp. is below 33 degree, indoor fan speed will turn into
low speed from the set speed; when liquid pipe temp. is below 25 degree,
indoor motor will stop.
ƔWhen liquid pipe temp. is over 30 degree, indoor fan speed will turn into low
speed from stop; when liquid pipe temp. is over 35 degree, indoor motor will
enter the set speed (take the data in EEPROM as standard).
-75-
Page 76
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
8.3 Temperature compensation adjustment (only for indoor unit with new PCB-AB**FCBIA):
For infrared control type unit, the temperature compensation can be adjusted. But for wired control
type unit, there is no temperature compensation.
Set the EEPROM by SWING (or SLEEP) button. For example:
Infrared control—in heating mode, press “ON/OFF” button to switch on the unit. Take the 24 degree
set temperature as the base point, press SWING (SLEEP) within 5 seconds, it will sound 2 times,
the unit will enter the heating temperature compensation mode, at this time, if you set the
temperature to 25 degree and switch off, the temperature compensation will be +1 degree; if you
set the temperature to 26 degree and switch off, the temperature compensation will be +2 degree,
and so on, the max. compensation can be +6 degree ( 30 degree); if you want to cancel the
compensation, adjust the temperature back to 24 degree.
Infrared control—in cooling mode, press “ON/OFF” button to switch on the unit. Take the 24 degree
set temperature as the base point, press SWING (SLEEP) within 5 seconds, the unit will enter the
cooling temperature compensation mode, at this time, if you set the temperature to 23 degree and
switch off, the temperature compensation will be -1 degree; if you set the temperature to 22 degree
and switch off, the temperature compensation will be -2 degree, and so on, the max. compensation
can be -8 degree ( 16 degree); if you want to cancel the compensation, adjust the temperature back
to 24 degree.
Read the temperature compensation value:
Infrared control type—change to cooling mode, the set temperature is 30 degree, in high speed.
Press SWING (SLEEP) 7 times within 5 seconds, the running LED will flash as the current temp.
compensation value.
Infrared control type—change to heating mode, the set temperature is 16 degree, in high speed.
Press SWING (SLEEP) 7 times within 5 seconds, the running LED will flash as the current temp.
compensation value.
8.4 Unit debugging:
1. Confirm indoor unit quantity
After the unit is electrified, you can check the indoor unit quantity by the outdoor dip switch or the
testing board. The display quantity must be in accordance with the actual quantity. If not, please
check if there is repeated unit No. or if the dip switch is broken, and if the communication wire is
connected correctly.
2. Confirm indoor EEV
FAQ:
2.1 The EEV communication wire is not in accordance with the indoor unit. If all the indoors are
running, the operation will be normal; when the only one indoor unit is running and it can not cool,
while the EEV of the unit not running opens.
2.2 The live wire and the neutral wire of the EEV power cable is not in accordance with those of
indoor unit power cable, E7 failure occurs.
2.3 The coil temperature sensor is not in original place or not fixed well, which cause EEV not work
properly. The efficiency will be bad or outdoor unit will be liquid return.
-76-
Page 77
Commercial Air Conditioner Model: AU242FHBIA,
y
AU482FIBIA, AU48NFIBJA
Only No.1 unit in cooling
If No.1 unit in cooling
If No. 1 unit in cooling—if yes, OK
If not
Short connect the corresponding terminal,
open the EEV compulsorily. If it can open,
check if the EEV communication wire is in
accordance with that of indoor unit and modif
Can’t open
Check if EEV is installed properly, tap the EEV body, or reset.
Switch on all the indoor units in turn
.
Still not
Replace EEV PCB
Still not
If the refrigerant of the unit not running not
flow—if yes
If the refrigerant flows, check if the EEV
communication wire is in accordance
with that of indoor unit and modify.
If yes
Replace EEV
-77-
Page 78
3. Confirm cooling operation
(
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
start
Set the unit in cooling mode and begin to run
If indoor unit blows cold air
If air circulation is OK
Make all indoor units running
If temp. drop between air outlet/indlet is normal
Once outdoor stops, the unit
must run again 2 minutes
and a half later.
Confirm compressor state
Confirm the louver direction
If the operation voltage is OK
230Vf10ˁ˅
If the running current is 15% of the
nominal value (at max. frequency)
If working pressure is normal
normal
Check power voltage and power
circuit.
Check indoor/outdoor temp.
Check piping length and
refrigerant charge.
Check compressor running
frequency and if there is abnormal
noise
-78-
Page 79
4. Confirm heating operation
r
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
start
Set the unit in heating mode and begin to run
If blowing warm air?
If air circulation is OK
Make all indoor unit running
If temp. drop between air outlet/indlet is normal
Once outdoor stops, the unit
can work only 2 minutes
and a half later
Confirm compressor state
Confirm the louver direction
If the operation voltage is OK
˄230Vˇ10ˁ˅
If the running current is 15% of the
nominal value (at max. frequency)
If working pressure is normal
normal
Check power voltage and powe
circuit.
Check indoor/outdoor temp.
Check piping length and
refrigerant charge.
Check compressor running
frequency and if there is
abnormal noise
-79-
Page 80
8.5 PCB information
AU242FHBIA PCB circuit diagram:
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
7654321
8
CN21
CN9
CN10
D
CP250
CN11
CP250
ZEN2
C1
FDG_1
561
CN12
CP250
+5V
R97
1K
LPRE_SW
C24
103
GND
C
B
A
12345678
ZEN1
561
L1
CT_IN
8550
T38003
C3
0.47UF
C5
C4
472
472
+5V
R38
R39
1K
1K
HPRE_SW
DQ5
CN34
9013
C36
C22
104
103
CN1
R24330
GND
R25330
R26330
R27330
R28330
R29330
+5V
R30
GND
560
LED3
RED
CN14
+5V
DQ1
R35
1K
C21103
GND
1K
R40
7(
R411K
7'
CD21
R421K
7$
4.7UF
R431K
76
CD22
R441K
7&
4.7UF
CD23
4.7UF
CD24
4.7UF
R17 20K
R21 20K
R23 20K
CD25
R20
R22
4.7UF
20K
20K
GND
R18
R11
10K
100
VD6
VD7
4148
4148
GND
C18103
R12
1
100K
2
C19
3
103
IC8
4
4011
C20103
5
6
7
GND
4
3
5
CT1
803
1
2
1
2
CT2
803
4
3
5
R98
1K
DQ6
9013
C25
104
C6
0.47UF
PTC1
RL1
JTN1AS
CN16
+5V
R50
R51
R88
10K
10K
10K
DOWN
UP
GND
CN5
SERIAL
CA1
1000PF*8
GND
AC2_IN
AC1_IN
+5V
+5V
RA2
RA-4(10KX4)
1
2
3
4
5
TX_IN
+5V
R6210K
C43
104
CX1 10MHz
14
C23
104
13
IC9
PST600D
12
GND
11
10
9
8
Ð¶ÔØ
CN35
R19
100
RL9
JQ-1A
SW07
SW06
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
C46
104
22
R34
1K
23
24
25
26
27
28
29
30
31
32
CN22
CN23
Ñõ°ÉÅçÉä ËÄͨ
R9
100
C9
103
C14
103
RL2
JQ-1A
6(5,$/29
)B83
)B'2:1
3:0B=
3:0B<
3:0B;
3:0B:
1&B*1'
3:0B9
3:0B8
+($7(5
(55
&23+($7
$&B&203
IC1
$&B,1
MB89P857
Pd(NOP)
Te
Td
Ta
7F
Ts
$9&&
$95
$966
,30
HIV
LOWV
7;B,1
V-IN
1&B*1'
,17
567
02'
02'
3(1*6(
;,1
3)&B287
;287
*1'1&
)$1B6:
7;B287
'&567
309B$
309B%
309B&
309B'
3)&B,1
CN8
CN6
CN7
CN4
¼ÓÈÈ´ø ·ç»ú
R4
R5
100
100
C8
C7
103
103
+5V
+5V
RL3
RL4
JQ-1A
RL5
JQ-1A
JQ-1A
RL8
JQ-1A
SV2
14
13
12
11
10
15
16
17
18
IC5
ULN2803
2
1
3
4
5
6
7
8
64
63
62
61
0,'
60
59
3&7
LOW
58
:$<
57
GND
56
1&
55
54
53
HPRE_SW
52
51
LPRE_SW
50
49
48
47
46
TX_OUT
45
&6
44
6.
43
',
42
'2
41
40
39
38
37
36
35
PFC_OUT
34
PFC_IN
33
GND
8
9
CD16
16V/100UF
+12V
CN15
9
GND
GND
RA-4(10KX4)
+5V
1
2
J6
R67
+5V
10K
1
2
3
4
5
6
7
IC4
ULN2003
16
15
14
13
12
11
10
SV2
+5V
RL6
R87
R86
JQ-1
2K
10K
RL7
JQ-1
J7
J8
+12V
JP1 JP2
GND
CD14
16V/100UF
+5V
C28
CD17
104
16V/100UF
GND
RA1
3
5
4
J5
J4
J3
CJ1
LED4
R99
+5V
+5V
10K
GND
RED
1
8
2
7
C27
IC7
104
3
6
93C46
4
5
R66
10K
GND
R91
10K
R77
CN25
2K
R78
GND
2K
CN24
COOL
R79
1
2K
R80
HEAT
R81
2
SS/TEST
2K
100K
3
GND
H,C
4
JP2
5
4051IN
6
+5V
7
8
C49
104
9
GND
10
11
595SI
12
595SCK
13
595RCK
14
4051S1
15
4051S2
16
GND
4051S3
17
18
CX2 16.0MHz
19
20
21
C44
104
+5V
AC1_IN
AC2_IN
CN26
IC2
42
P33
P32
41
P34
P31
40
P35
P30
39
P36
P10
38
P37
P11
37
P12
VREF
36
P13
AVDD
35
P14
AVSS
34
P40
P15
33
P41
P07
32
P06
P42
31
P05
P43
30
P44
P04
29
P45
P03
28
P46
P02
27
P47
P01
26
VSS
P00
25
XIN
P20
24
XOUT
_RST
23
TEST
P22
22
VDD
P21
TMP86FH46N
+5V
IC11
7805
+12V
7805
C48
CD18
C30
104
220UF
104
GND
+5V
VD8
4148
VD1
R48
R36
1K
4148
1K
CD13
R37
100UF
C15
1K
103
+5V
VD9
4148
JP1
TO857
FR857
FR1007
1007A
1007B
SERIAL
COM_LED
SCL
SDA
R15
180K
GND
+12V
CN30
GND
R82
CD15
R83
R72
3K
100UF
1K
10K
+5V
R92
STOP
2K
R93
2K
R94
2K
TX_OUT
R95
R84
100
2K
TX_IN
R85
100
CN19
GND
C23
104
GND
R31
10K
+5V
R1010K
R32
560
LED2
RED
R46
10K
CN3
CT_IN
SGND
GND
SW05
START
GND
+5V
IC10
PST600D
GND
R47
10K
ZD2
18V
CD3
10UF
7
8
*1'
62)7)%,6
1
2
C29
104
CD1 2.2UF
CN32
R96
100K
1
2
3
4
9&&
SW04
R3
560K/1W
IC3
C47
MM1007
101
'
2
1
&
1
16
1
&
,1
2
15
+12V
9&
,1
3
14
104
*1'
9
4
13
C45
'2B
D
1
&
5
12
GND
1
&
'2B
$
6
11
',1
%
'2B
%
7
10
',1
$
'2B
E
8
R68
10K
C26 104
24C02
IC6
R71
10
6
5
1&
IC13
'5$,1
ICE2A165
3
4
R7
2
R6
2
9
+5V
8
7
R45
R63
+5V
10K
10K
6
5
T1
VD14FR102
T28051
R2
C2
47K/2W
472
VD15
VD12
FR102
FR102
VD16
VD11
FR106
FR102
VD17
FR102
VD20HER204
SGND
IC12
TLP421
CD20
VD22
100UF
FR102
VD21
HER204
ZD1
R1
471
11V
Title
Date: 3-Sep-2005 Sheet of
File: C:\Documents and Settings \dupeng\
R8
27
+5V
A2
PFC_OUT
PFC_IN
C42
103
CD2
1UF
CN27
XP-9A
R53
5.6K
R545.6K
R56
R76
5.6K
GND
+5V
CN31
R74
10K
R73
560
R75
1K
GND
R13
100K
R14
100K
GND
R70
ZD5
4.7K
DQ3
5.6V
9013
ZD6
5.6V
R64
10K
DQ4
R65
ZD3
9013
5.6V
10K
R69
ZD4
4.7K
5.6V
GND
9
CN2
CD8
100UF
CD9
100UF
R55
CD10
5.6K
100UF
5.6K
CD11
100UF
+12V
CD12
1000UF
NumberRevisionSize
Drawn By:
Ḡ䴶\ᴼᑇথ䖛ᴹⱘ݇Ѣ80ⱘ
D
C13
104
C12104
C10104
C11
104
CN13
CD6
CD4
$
100UF
100UF
%
CD7
CD5
100UF
100UF
C
GND
B
A
-80-
Page 81
AU482FHBIA PCB circuit diagram:
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
-81-
Page 82
Commercial Air Conditioner Model: AU242FHBIA,
Æ
AU482FIBIA, AU48NFIBJA
AU48NFIBJA PCB circuit diagram:
+5V
R303
R302
R301
4.7k
4.7k
4.7k
D303
D302
D301
6 - 1N4148
+5V
+5V
SK
CN302
TXD
1
RXD
2
GND
3
4
R306
ÏÔʾ¹¤×°
5
100¦¸
XH5-5Ȯ
D
4 - 1N4148
+5V
+5V
CN303
SK
TXD
1
RXD
2
GND
3
4
R310
5
485ͨѶ
100¦¸
XH5-5˦
C310
100uF
DA
CN304
C
DB
1
2
HBS
XH2-2ºì
CN311
+5V
Tsink
1
2
XH2-2½ðÉ«
CN312
+5V
Tt
1
2
XH2-2ÂÌ
B
CN313
+5V
1
Te
2
XH2-2°×
CN314
+5V
1
Ta
2
XH2-2Ȯ
CN315
+5V
1
Ts
2
XH2-2ºÚ
CN316
+5V
1
Td
2
XH2-2˦
A
12345678
D306
D305
D304
+5V
D308
D307
D310
D309
C309
100uF
C307
100uF
C308
100uF
4 - Z_5.6V
Z302
QN301
Z303
NPN_2222A
C311204
R312
C312204
100k¦¸
+5V
R313
270¦¸
R314
10k¦¸/1%
R315
270¦¸
R316
10k¦¸/1%
R317
270¦¸
R318
10k¦¸/1%
R319
270¦¸
R320
10k¦¸/1%
R321
270¦¸
R322
10k¦¸/1%
R323
270¦¸
R324
47k¦¸/1%
C302
471
R307
4.7k
C305
471
R311100k¦¸
R304
P3.2
100¦¸
R305
TXD1
100¦¸
RXD1
C303
C304
471
471
R308
4.7k
R309
TXD0
100¦¸
RXD0
C306
471
Z304
QN302
IC309
P2.3
9
8
d_outb
Z305
NPN_2222A
P0.7
C313
472
P0.5
C314
472
P0.4
C315
472
P0.3
C316
472
P0.2
C317
472
P0.1
C318
472
D_INA
D_OUTB
D_OUTA
d_outa
Vcc
IN2
IN1
NC
MM1007
D_INB
D_OUT
P2.4
7
6
NC
5
NC
4
GND
3
+12V
Vin
2
NC
P2.2
1
10
11
12
13
+5V
14
15
16
+12V
+5V
+5VA
GND
GNDA
CN202
+5V
CN301
1
2
3
4
5
XH5-5°×
P0.0
P0.7
P0.5
P0.4
P0.3
P0.2
P0.1
P0.0
+5V
R326
2.7k¦¸
R327
2.7k¦¸
P2.1
IC302
P2.7
4
5
DO
GND
C320
104
+12V
P2.5
6
3
ORG
DI
7
2
P3.4
DC
SK
8
1
VCC
CS
93C66
+5VA
+5V
+12V
C331
104
+5VA
C319
104
54
p0.6/a6/t1clk/pm.2
55
ANGND
56
Vref
57
P0.5/A5/PM.1
58
P0.4/A4/PM.0
59
P0.3/A3
60
P0.2/A2
61
P0.1/A1
62
P0.0/A0
P2.1
63
NC
64
P2.0/EPA0/PVER
65
P2.1/SCLK0/BCLK0/PALE
P2.2
66
NC
P2.3
67
NC
P2.7
68
P2.2/EPA1/PROG
69
P2.3/COMP3
70
P2.7/SCLK1/BCLK1
P2.4
71
NC
P2.5
72
NC
73
P2.4
74
P2.5
B30116MHz
C321
30pF
+5V
C301
47uF
R325
470¦¸
+5V
R328
100k¦¸
TXD0
53
52
p1.0/txd0
p0.7/a7/t1dir/pm.3
P6.7/PWM1
P2.6/COMP2/CPVER
76
75
C322
30pF
LED301
LED_GREEN
IC303E
10
11
C326
74HC14
22uF
TXD1
RXD0
RXD1
GUP
GVP
GUN
GVN
51
50
49
48
47
45
46
44
43
42
41
NC
NC
Vss
p1.1/rxd0
P6.1/WG1
P6.0/WG1
P6.2/WG2
P6.3/WG2
P6.4/WG3
P1.2/TXD1
P1.3/RXD1
N87C196MH
EXTINT
Vss
XTAL1
XTAL2
NC
NC
NC
P6.6/PWM0
P5.1/INST
P5.4
P5.6/READY
3
1
2
84
83
82
81
79
80
78
77
ALM
C323
471
9
GWN
40
4
P6.5/WG3
Vss
+5V
R329
4.7k
IC303D
RESET
8
74HC14
+5V
C325
104
R330 4. 7k
GWP
38
39
37
36
35
34
33
EA
NC
NC
Vss
Vcc
NMI
RESET
P3.0/AD00
P3.1/AD01
P3.2/AD02
P3.3/AD03
P3.4/AD04
P3.5/AD05
P3.6/AD06
P3.7/AD07
P4.0/AD08
P4.1/AD09
P4.2/AD10
P4.3/AD11
P4.4/AD12
P4.5/AD13
P4.6/AD14
P4.7/AD15
P5.2
P5.7
P5.3/RD
NC
P5.5/BHE
Vpp
P5.0/ALE
7
9
8
6
5
10
11
4148
RESET
IC301
P3.0
P3.1
32
P3.2
NC
31
P3.3
30
P3.4
29
P3.5
28
P3.6
27
P3.7 P3.7
26
25
24
23
NC
22
NC
21
20
19
18
17
+5V
16
NC
15
14
Vcc
13
12
+5V
RA303
RA302
+5V
RAA09103
RAA09103
+5V
+5V
R331
D311
P3.4
P3.0
P3.1
P3.2
P3.3
P3.4
P3.5
P3.6
C324
104
10k¦¸
R332
13
4.7k
C330
D313
D312
4148
P3.2
P3.0
+5V
RAA09103
RA301
+5V
471
4148
R335220¦¸
C327
103
+5V
R336
10k¦¸
ALM
QN303
NPN_2222A
R3378.2k¦¸
P0.0
C328
472
IC303C
6
5
74HC14
IC303B
3
4
74HC14
IC303A
2
1
74HC14
IC304A
2
1
74HC14
IC304B
4
3
+5V
74HC14
14
IC304F
13
12
74HC14
7
IC304E
11
10
74HC14
IC304D
8
9
74HC14
IC305C
5
6
74HC14
IC305B
3
4
74HC14
IC305D
9
8
74HC14
+5V
14
IC305F
13
12
74HC14
7
IC305E
11
10
74HC14
IC305A
2
1
74HC14
IC304C
6
5
74HC14
7654321
+5V
R334
14
IC303F
74HC14
7
R338
10k¦¸
R339
270¦¸
10k¦¸
Z301
12
3V
D314
4148
D315
4148
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
R333
1k¦¸
IC306D
13
14
12
LM324
IC306C
9
8
10
LM324
D316
4148
C329
105
R344
2.7k¦¸
D317
4148
D318
4148
R345
10k¦¸/1%
IC306B
6
7
5
LM324
R348
10k¦¸/1%
IC307
OUT 1
IN 1
OUT 2
IN 2
OUT 3
IN 3
OUT 4
IN 4
OUT 5
IN 5
OUT 6
IN 6
OUT 7
IN 7
OUT 8
IN 8
DIODE CLAMP
GND
C332
ULN2803A
104
IC308
OUT 1
IN 1
OUT 2
IN 2
OUT 3
IN 3
OUT 4
IN 4
OUT 5
IN 5
OUT 6
IN 6
OUT 7
IN 7
OUT 8
IN 8
DIODE CLAMP
GND
C333
ULN2803A
104
Title
A2
Date: 11-Aug-2004Sheet of
File: C:\Documents and Settings\shibin\×ÀÃæ\KR-160~2.DDBDrawn By:
QP301
PNP_3906
CN105
CN306
TRIP
1
GUP
GUP
2
GVP
GVP
3
GWP
GWP
4
GUN
GUN
5
GVN
GVN
6
GWN
GWN
7
ALM
ALM
8
GND
9
XH9-9°×
P3.6
+5V
P3.5
R340
1k¦¸/1%
R341
8.2k¦¸/1%
R342
1k¦¸/1%
P3.1
R343
P3.3
JP301
2.2k¦¸
JUMPER
1
P3.7
11
IC306A
2
LM324
1
3
R34610k¦¸/1%
+12V
R347
4
10k¦¸/1%
+5V
R349
10k¦¸/1%
18
17
16
15
14
13
12
11
+12V
10
18
17
16
15
14
13
12
11
ALM
+12V
10
P0.6
º£¶ûKR-160W/(BP)S¿ØÖ
NumberRevis ionSize
R350
4.7k
2
+12V
C334
104
8
CN317
XH2-2ÒøÉ«
CN318
XH2-2dzȮ
R351
10k¦¸
CN308
1
2
XH2-2°×
CN307
1
2
XH2-2°×
CN309
1
2
3
4
XH4-4°×
CN310
1
2
3
4
5
6
XH6-6½ðÉ«
μзЧУЕтХН·§PMV
CN305
1
2
3
4
5
6
7
8
9
10
11
12
13
XH13-13°×É«
CN203
1
2
1
2
+5V
+12V
FAN1
+12V
FAN2
SPRY
Vo
GND
+12V
+12V
+12V
A
B
C
D
GND
W_P
HEAT
SV1
SV2
4_WAY
Ox_P
F_M_R
F_L
F_H
GND
OU
Vs
OH
OP
QP302
PNP_3906
R352
330¦¸
LED302
LED_RED
+12V
V1.0A00000013
D
C
C335
104
B
A
-82-
Page 83
Commercial Air Conditioner Model: AU242FHBIA,
8.6 Dip switch and the ports on PCB functions
AU242FHBIA ports on PCB:
Ports Ports name Wiring method
CN1 IPM-OUTIPM output control line
CN2 IPM-POWERTo 4-way 15V power source
CN3 +310V ,GND
CN4Fan motor port To fan motor
CN5SERIAL857 detecting serial port
AU482FIBIA, AU48NFIBJA
To 310V DC power source
CN6
CN7 Live line of electric heaterTo live line
CN8
CN9 Live line of power sourceTo live line
CN10
CN11 Live line of power sourceTo live line
CN12Earthing line To earthing line
CN13 Communication port To communication line
CN14 Sensor port
CN15EEV port To EEV
CN16 High pressure switch portTo high pressure switch
CN19SERIAL846 detecting serial port, no used
CN22Spray valve port To spray valve
CN23 Oxygen generator port To oxygen generator (optional)
Four-way valve port To four-way valve
Neutral line of electric
heater
Neutral line of power
source
Including defrosting, discharging, ambient, air
return, evaporating temp. sensors
To neutral line
To neutral line
CN27Indicator board To exterior testing device, showing failure code
CN318 High pressure switch port To high pressure switch
Fan motor port for dispersing
heat
Mid-condenser temp. sensor
port
To fan motor for dispersing heat (be spare)
To mid-condenser temp. sensor
-84-
Page 85
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
Below we will comment for the functions of some ports and some changes of PCB
0010451530 and 0010451531:
1. Control Board 0010451530
Herein, the control board we are concerned is the board without CPU. Functions for every port are as
follows:
CN301: port for power supply, connected with CN202 of the power board.
CN302: connected to testing board.
CN303: connected to the computer serial port through the testing device.
CN304: HBUS communication port.
CN305: the driving port for relay, connected to CN203 of the power board.
CN306: the driving port for IPM, connected to CN105 of the power board.
CN307, CN308: port for the heat-emitting fan. No used at present.
CN309: port for the main relay and for testing current, connected to CN104 of the power board.
CN310: the driving port for electronic expansion valve.
CN311: testing port for the radiator temperature. No used at present.
CN312: testing port for the coil temperature Tt.
CN313: testing port for the defrosting temperature Te.
CN314: testing port for the outdoor ambient temperature Ta.
CN315: testing port for the suction temperature Ts.
CN316: testing port for the discharging temperature Td.
CN317: port for the signal of compressor overheat protection initially,but now for low pressure switch.
CN318: port for the signal of high/low pressure protection,but now only for high pressure switch.
Control board 1 Control board 2 Control board 3
Totally there are 3 types of control board, because they have different appearance, you will distinguish them
much easier.
Control board 1 is the earliest edition, because this board is rather big and it will cover the fixing screw
which supports the electric control box, also taken into consideration the convenient installation and service,
we modified and designed the Control board 2.
Control board 2 is the second edition, because there are electric parts on both sides of this board, and
-85-
Page 86
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
hard to be installed, we designed the Control board 3.
Contro l boa rd 3: the current edition. Now the part number of control PCB is 0010451971
instead of 0010451530.
The new control board(0010451971) also can be used as 0010451530,but the connector
"OH" must be shorted.
2. Pow er board 0010451531
There are two types of power board, and they have the same dimensions, but have the different voltage
testing parts. That is easy to distinguish.
The newly power board adopts the voltage sensor to test the voltage. On the board there is a black square
type voltage sensor. The old board adopted the LM331 to test the voltage, which is an inserted part IC with
8 feet.
However both the new or old power boards can match any of the control board, but the CPU diagrams are
different.
3. Fil ter board 0010451536
Originally, the electric control box has not any filter board. In order to avoid the exterior interference and
result in the bad communication, the second edition (current edition) are all added the filter board.
-86-
Page 87
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
8.7 Testing board for AU48NFIBJA:
Press button “mode”, the display will change over in the following sequence:
State
Display
Frequency Fxx.xx
Current output A xx.x
5XQ 6WRS 'HIU &RRO +HDW
Voltage on DC side U xxx
Ambient temp 1 xx
Discharging temp 2 xx
Suction temp 3 xx
Defrosting temp 4 xx
Coil temp 5 xx
5XQ
6WRS
&RRO
+HDW
0RGH
3URJ
(QWHU
Indoor unit quantity 6 xx
Open degree of EEV7 xxx
Note: Please connect the wire on power off. Insert the testing board on the CN302 of the
outdoor PCB. The part number is 0010451601.
In addition, we set a testing port CN303 which can be connected to the computer through
another testing device (part number: 0010451800). The distributor can get the testing device
and the testing software from us.
Testing procedure:
1. After the unit powered off, connect the wire of testing board to CN302 port, and then pull
down the communication wire between outdoor and indoor unit.
2. Check if the wiring is right. If yes, power on the outdoor unit.
3. On the operation panel of the testing board, the relative data can be modified.
4. Press “Prog.”, enter data editing mode.
5. Set data “Pr-00” as “0”ˈthen data can be edited. Press “Enter” to confirm.
6. The other data can be set according to the requirement like this way.
7. After all the data be modified, set “Pr-00” as “1”.
8. Press “Prog.”, quit out of data editing mode.
9. Note: Data of the chip is very important, the improper modification will cause the main
parts damaged such as compressor. So before modification, please contact with us.
10. After quitting from data editing mode, operation board will display “P r.E” which will
flash. After 3 minutes, it will display “b.P.160”. At this time, pressing the
to reset
the program.
11. After reset, power off the outdoor. For 1~2 minutes, the outdoor release all the electricity,
plug the communication wire between outdoor and indoor to the original position, the
modification is over.
-87-
Page 88
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
8.8 AU482FIBHA: function specification of SW01, SW02, SW04, SW05, SW06, SW07
Table 1
SW01 SW02 Display of 7 segments LED (LD1,LD2,LD3)
0
0 FFF shows capability overloading (if capability overloading function is chose)
Outdoor diagnosis code when without diagnosis code, display: - 1 Outdoor running mode cooling: C heating: H defrosting:J
2 Defrosting area set: display 1------shows that L is set at “12”
display 2------shows that L is set at “10”
display 3------shows that L is set at “8”
When the following condition is available, the unit enters into defrosting running:
(TE: defrosting temp., TA: ambient temp.)
TEİChTAˉ¢
Note˖C˖TA˘0ćˈC=0.8
TAı0ćˈC=0.6
The value of ¢ can be set according to the selection of jump wiring:
selection of jump wiring L MH
¢(ć)
4
5
6
7 Back up running: TS sensor: 1 , TE sensor: 1
INV command frequency˄decimalism˅ e.g.120 stands for 120HZ
INV receiving frequency˄decimalism˅ e.g. 84 stands for 84HZ
Quantity of indoor units connected˄decimalism˅ e.g. 6 stands for 6 indoor units
This function is preset and not available.
12e 10e 8e
8 Back up running: TA sensor: 1 , mid-section temp. sensor: 1
This function is preset and not available.
9 Back up running: PD sensor: 1 , PS sensor: 1
This function is preset and not available.
13 Display compensation of capacity class: 4------class 4, 6-----class 6
After the start-up of system is over, the frequency of compressor has gotten the
target frequency confirmed by the request of indoor unit capacity for 5 minutes,
and then the unit will modulate the capacity.
(Note: class 4 and class 6 can be selected. Class 4 is that the capacity class
whose range is from 4 classes higher to 3 classes lower than the target frequency.
Class 6 is that the capacity class whose range is from 6 classes higher to 4
classes lower than the target frequency. For the unit without pressure sensors,
there is no this function.)
14 Display “U” shows that indefinite capacity is chose
Display “d” shows that definite capacity is chose (indoor total capacity can’t be
over 130%˅
15 Display o1-----stands for HP
Display o2-----stands for HP
Display H1-----shows that can be connected with central communication
1
0
1
2
3
4 Mid-section of coil pipe sensor data (decimalism)
new code:0 stands for 0.8HP, 1 stands for 1HP, 2 stands for 1.2HP,
3 stands for 1.5HP, 4 stands for 2HP, 5 stands for 2.5HP, 6 stands for 3HP, 7
stands for 4HP
Old code: 1 stands for 1HP,7 stands for 7HP
Indoor saturation temperature (decimalism) -26.0—67.0˄account according to
outdoor suction pressure PS˅
Indoor sensor TA temperature˄decimalism˅-26.0—67.0
Indoor sensor TC2 temperature˄indoor gas pipe˅˄decimalism˅-26.0—100.0
Indoor sensor TC1 temperature˄indoor liquid pipe˅˄decimalism˅-26.0—100.0
C --this function is preset
1Four-way valve not switched on: OFF˖_ _
C, heating: H
CC --this function is preset
HH--this function is preset
run: 11/stop: 00˄display -- after 3 minutes
1ˈOFF˖--
1 receiving abnormal:
Combination control with outdoor switches
Table 2
function summary Method of set, cancel
Cool trial run Indoor trial run in cooling
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max. temp., and
send it to outdoor, the other
control is similar with normal.
Heat trial run Indoor trial run in heating
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max.
[set]
SW01“2”, SW02“03”, press SW04 for more
than 2 seconds, after set of trial run success, LD
will always display –C until the function is
cancelled.
[cancel]
in trial run state, SW01“02”, SW02“03”, press
SW05
[set]
SW01“2”, SW02“04”, press SW04 for more than
4 seconds, after set of trial run success, LD will
always display –H until the function is cancelled.
[cancel]
in trial run state, SW01“02”, SW02“03”,
ress
-89-
Page 90
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
temperature, and send it to
outdoor, the other control is
similar with normal.
Swing trial run Indoor trial run in swing
mode,the control is the same
as swing trial run with remote
controller.
Uniform running Indoor is uniform running
The indoor running mode is
corresponding with the setting
or memory of remote
controller.
Uniform stop Indoor uniform stops [set]
Indoor PMV
fully open
compelled
Rated running Set the unit rated running [set]
Outdoor PMV1
fully open,
closed function
Indoor PMV fully open
compelled in 2 minutes
Outdoor PMV1 compelled fully
open or close in 2 minutes
SW05
[set]
SW01“02”, SW02“05”, press SW04 for more than
2 seconds, after set of trial run success, LD will
always display –F until the function is cancelled.
[cancel]
in trial run state, SW01“02”, SW02“05”, press
SW05
[set]
SW01“02”, SW02“05”, press SW04 for more than
2 seconds, after set of trial run success, LD will
display FF for 5 seconds.
[cancel]
cancel according to operation of remote
controller
SW01“02”, SW02“06”, press SW05 for 2
seconds, after set success, LD will display FF for
5 seconds.
[cancel]
cancel according to operation of remote
controller
[set]
SW01“2”, SW02“10”, press SW04 for more than
2 seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display “FF” all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes ˄ after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.˅
SW01“02”, SW02“11”, press SW05 for more than
2 seconds, after setting success, LD will display
–F, shows that the unit may enter rated running
mode, afterwards you can set SW06,
SW07.SW06 is used for increasing frequency,
while SW07 is used for decreasing frequency.
[cancel]
cancel according to operation of remote
controller
[set]
SW01“3”, SW02“9”, press SW04 for more than 2
seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display “FF” all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes ˄ after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.˅
-90-
Page 91
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
Outdoor PMV2
fully open,
closed function
Outdoor PMV2 compelled fully
open or close in 2 minutes
[set]
SW01“3”, SW02“10”, press SW04 for more than
2 seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display “FF” all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes ˄ after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.˅
2. Specification for SW03
The two switches of SW03 should be ON or OFF at the same time.
1. CN302 ǃ CN303 areports for
controllers,and will be used in maintenance.
2. Parts in dashed frame are optional.
Symbols meaning
part name
symbol
CM
compressor
FM
fan motor
OX-P
oxygen bar function
4-WAY
4-way valve
SV
solenoid valve
HEAT
crankcase heater
W-P
water pump
TSINK
radiator temp. sensor
mid-condenser temp. sensor
Tt
Color symbol:
symbol symbol
black
B
blue
BL
red
R
C1 C2
W
Y
G
Y/G
white
yellow
green
yellow/green
0010577105
symbol
part name
defrosing temp. sensor
Te
ambient temp. sensor
Ta
suction temp. sensor
Ts
Td
discharging temp. sensor
Low pressure switch
0H
0P
High pressure switch
EEV
Electronic expansion valve
CT
current transducer
4-WAY
OX-P
321 321123321321213
RY209
5
4
1
5
4
3
2
1
3
2
CN212
RY208
CN204
FAN1
CF1
CN211
1
2
CN3
3
1
2
3
CN2
4
5
SV2SV1
CN210 CN210 CN208 CN207 CN206 CN205
RY206 RY205 RY204 RY203
Power Supply Board
RY207
T3.15A/250VAC
123
L
N
UVW
AB**2FCBIA wiring diagram:
gas pipe temp. sensor
liquid pipe temp. sensor
Room temp. sensor
LED3
LED4
10
TIMCOMP
B:Black
BL:Blue
BR:Brown
R:Red
W:White
Y/G:Yellow/Green
float switch
5
146
97823
OPER
Remote receiver
Remote control type
Wired controller
A
Wired control type
electronic
expansion valve
Builtin EEV type
emergency
LED1LED2
switch
POW
sw01
BEEP1
B
CD
outdoor
communication
CN5
243
1
2
CN9
1
23
CN11
1
2
CN
1
10
9
8
7
6
CN13
5
4
3
2
1
CN14
3214
ac
b
d
W
indoor power
1PH.220-230V~.50Hz
sw03
BR
M
423156
CN6
CN1
1
2
R
Indoor unit wiring diagram
fan capacitor
serial
CN16
M
swing motor
32145
CN3
sw02
2
1
Indoor control board
sw01
unit code setti ng
1
Outside EEV type
CN7
1
23
M
pump motor
CN4
R
32
negative ion generator or high
voltage accumulator
<*
electronic
expansion valve
box power supply
and communication
Must connect electronic expansion valve box
NOTE
˖
power and communication from corresponding
indoor,wiring sequence must correspond with
the label respectively,other wise, will cause
PCB of indoor and electronic expansion valve
box not work and damaged.
T3.15A/250VAC
FUSE
CN19
M
5
4
CN8
123
CN20
fan motor
CN25
CN18
CN22
0010577029
About the PCB setting
In the diagram,gas pipe temp. sensor,liquid pipe temp.
sensor,room temp.sensor ,indoor fan motor,float switch,
pump motor,swing motor are
controller,remote receiver,electronic
Wired
valve
are parts matched with
negative ion generator or
are optional parts for health
Wired controller and remote receiver
one of type at will.
The setting of SW01,SW02 and SW03 :
1.The former three bits of SW01 are used to set unit
number,which are operated by the installer on field .
2.The fourth bit of SW01 is used to choose different
indoor fan speed in heating mode."ON"means that fan
speed can be set as middle and low level,"OFF"means
that fan speed can be set as high,middle and low level.
3.The first bit of SW02 and SW03 is used to choose
wired control type or remote control type.
"ON"means that the unit with wired controller(other parts
are as the same as remote control unit). And "OFF"is
remote controller.
The unit with wired controller
on wired controller with remote controller such
4.The second bit of SW02 is used to choose built-in or
outside electronic expansion valve setting .
"ON"means built-in type :
expansion valve
"OFF"means outside type:
electronic expansion valve communication,and the
expansion valve box(MP3A) control indoor
Attentions:
The CN9 is
is must be set "ON",And CN19,CN22 is not available.
CN16 is a serial communication port for service.
The dip switch setting when out of factory
necessary parts;
the model(combined usage);
high voltage accumulator
and comfort
CN6 is connected with
and indoor unit control
CN25 is connected with
So the second bit
not available .
expansion
combined
˄
only can be chosen
can make remote operation
as YR-H71 .
electronic
refrigerant flow itself.
electronic
refrigerant flow.
of SW03
usage).
-96-
Page 97
AE**2FCBKA wiring diagram:
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
electronic
M
gas pipe temp. sensor
liquid pipe temp. sensor
ambient temp.
sensor
receive display PCB
choice of remote
controller type
negative ion generator or
high voltage accumulator
electronic
expansion valve
box power supply
and communication
Must connect electronic ex pansion valve box
NOTE˖
power and communication from c orresponding
indoor,wiring sequence mus t correspond with
the label respectively,ot her wise, will cause
PCB of indoor and electroni c expansion valve
box not work and damaged.
AS**2FCBHA wiring diagram:
Indoor unit wiring diagram
TRANSFORMER
Display Bar
CN11
R
W
XB1
XB2
CN10
CN1
Control Board
SW01
ON
OFF
water
CN9
sensor
2
1
unit code setting
RL4
1
2
connector
earthing
CN6
temperate
RL3RL2
CN7CN12
23132
MM
CN2
CN13
CN12
CN14
CN7
CN8
CN5
CN17
1
2
CN23
SW2
1
2
swing motorpump motor
BL BL
1
CN8
FUSE
T3.15A/250VAC
RL1
CN19
CN20
1
resumable heat
protector
80 10A/250VACćˈ
FUSE
T15A/250VAC
one-off heat protector
105ćˈ10A/250VAC
only applicable for unit with
auxiliary electric heater
FAN MOTOR
EMERGENCY SWITCH
LIQUID PIPE TEMP.
SENSOR
ROOM TEMP. SENSOR
GAS PIPE TEMP.
SENSOR
STEPPING MOTOR
32
transformer
CN25
BR
CN18
W
CN22
CN3
21
RRB
auxiliary heater
M
TO
ELECTROMAGNETIC
VALVE BOX
M
0010573324
NOTE:The dashed "
PCB inner wiring.
About control board outer connector:
In the diagram,gas pipe temp. sensor,liquid pipe
temp. sensor,indoor fan motor,transformer are
necessary parts
display,electronic expansion val ve,float
switch,pump motor,swing motor are parts matched
with the model(combin ed usage˅˗
electric heater,negative ion generator,high voltage
accumulator are optional parts for health and
comfort
controller and receive display only can choose one
at will.
The unit with remote controller is matched with
receive display:
1.Ceiling concealed type:CN11 must be short
2.Duct type˖connected with float switch and
3.Cassette type:connected with float switch
4.Cabinet type:CN11 must be short connected
The unit with wired controller(equipped with wired
controllerˈ
controller with remote controller such as YR-H39)
Short connect CN15
wireˈ
Setting method with electronic expansion valve outside:
CN23 is disconnected,CN25 is connected with electronic
expansion valve communication,and the electronic
expansion valve box(MP3 or MP2) control indoor
refrigerant flow.
Setting method with built-in electronic expansion valve:
connected with electronic expansion valve
indoor unit control refrigerant flow itself.
Attentions: The water temp sensor (CN9) and indoor
temp sensor (CN24) are unus eful now. The fourth bit
of 4 position dial switch is used to choose the
different speed of indoor fan under heating mode.
"ON" means that the speed of indo or can be choosed
from middle and low."OFF" means that the speed of
indoor fan can be choosed from high,middle and low.
CN23
CN15
CN17
CN16
CN11
LED3
LED2
LED1RL1
ˉˉˉ"in indoor controll board is
˗Wired controller,receive
combination usage arbitrarily).Wired
˄
connected with a jump wire
pump motor
pump motor and swing motor˗
with a jump wireˈ
can make remote operation on wired
other parts are the same as remote control unit
CN23 is short connected with a jump wire, CN6 is
short connector for built-in
electronic expansion valve
short connector for wired
controller
serial communication port
connector for float switch
indicator˄runningˉred˅
indicator
˄timerˉyellow˅
indicator˄powerˉgreen˅
˗
˗
connected with swing motor
CN17 together with jump
ǃ
emergency switch(ON/OFF)
SW1
indoor fan motor low-speed relay
RL7
indoor fan motor Mid-speed relay
RL6
RL5
indoor fan motor High-speed relay
health function module relay
RL4
pump motor relay
RL3
swing motor relay
RL2
auxiliary eletric heater relay
Auxiliary
˖
and
ˈ
0010573625
VIEW A
1
R
W
B
Y/G
ǃ
24
VIEW A
˗
˖
3
R: RED
B: BLACK
W: WHITE
BL: BLUE
BR: BROWN
Y/G: YELLOW/GREEN
Note:
1.SW01 is the dip switch to set
unit number.
2CN6 is a serial port for some
device.
W
N
Power Supply
1PH,220-230v~,50Hz
-97-
B
Earthing
Wire
EARTHING
C2C1Y/G
RRL
Communication
Wire
Page 98
MP3A wiring diagram:
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
electronic
expansion
valve3
M
electronic
expansion
valve2
M
electronic
expansion
valve1
M
6
5
4
3
2
1
6
5
4
3
2
1
MP3A wiring diagram
FUSE T3.15A/250VAC
CN1
CN2
CN3
CN15
CN14
CN13
4
65
3
1
2
Control board
CN4
CN5
CN6
CN7
CN8
CN9
1
2
CN6
0010577068
SERIAL
CN10
CN11
CN12
indoor 1
B:Black
BR:Brown
W:White
Y/G:Yellow/ Green
BWBRBWBRBW
L1 N1C1L2 N2C2L3 N3
BR
C3
Y/G
indoor 3
indoor 2
NOTE: Power supply and communicat ion wire must be connected with the corresponding indo or units.Wiring sequence must be
correspondent respectively,L and N must not be conn ected reversely,otherwise, it will cause the unit not work and demaged.
On running, "indoor 1" must be electrified alwa ys, or air conditioner does not work normally.When the system is equipped with MP2A,
the installer should use the corresponding two-way el ectronic expansion valve communication wiring and its driver port
.
-98-
Page 99
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
10. Failure code and troubleshooting
10.1 Outdoor failure code:
AU242FHBIA, AU482FIBIA: check indoor mainboard LED1 or outdoor mainboard LED1.
Failure code Failure description
01Outdoor defrosting temperature sensor TE circuit failure
02Ambient temperature sensor TA circuit failure
03Suction temperature sensor TS circuit failure
04Discharging temperature sensor TD circuit failure
05Outdoor mid-condenser temperature sensor failure
06Over current abnormal
07
09 IPM protection
10EEPROM on PCB incorrect
11 Discharging temperature protection action
13Pressure switch circuit abnormal
14Pressure switch circuit abnormal
Current
mutual inductor failure
19Discharging temperature protection action when in low frequency
20Communication abnormal when chip 857 receives signal from chip 846
21Compressor over current failure
22Communication abnormal when chip 846 receives signal from indoor unit
23Chip 846 EEPROM/chip 857 EEPROM failure
-99-
Page 100
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
AU48NFIBJA malfunction code:
LED display on
Malfunction description Code
Normal 0 Normal Yes
Defrosting temperature
sensor abnormal
Ambient temperature sensor
abnormal
Suction temperature sensor
abnormal
Discharging temperature
sensor abnormal
Coil temperature sensor
abnormal
Over current protection 6
Current sensor abnormal 7 C.T.
Overload protection 8
IPM protection 9
Read EEPROM value
wrongly
Discharging temperature
over high abnormal
High pressure switch
abnormal
Voltage over low protection 13
Voltage over high protection 14
Compressor overheat
protection
Recover the parameter set
when out of factory
Clear the malfunction
memory
Need reset 18 P r.E. noNeed reset and restart
Radiator temperature sensor
abnormal
1 E.4.
2 E.1.
3 E.3.
4 E.2.
5 E.5.
10 P E.E.
11
12 O.P.
15 O.H.
16 P I.A.
17 P C.T.
-- --
the regulating
board
O.C.
P O.C. no
O.L. Yes
P O.L. no
E.P. Yes
P E.P. no
O.D. Yes
P O.D. no
L.U.
P L.U.
O.U.
P O.U.
If sent to
indoor unit?
Yes
Yes Resumable
Yes Resumable
Yes Resumable
Yes Resumable
Yes
Yes After trouble shooting, need powered off
no
Yes
Yes
Yes
Yes
no
noNeed reset and restart
No use
temporarily
Remarks
Resumable
After there are current malfunction for 3
times in 1 hour, the testing board will
display the last abnormal reason P X.X.
Need powered off and restart
and restart
After there are current malfunction for 3
times in 1 hour, the testing board will
display the last abnormal reason P X.X.
Need powered off and restart
Need reset and restart
After there are current malfunction for 3
times in half an hour, the testing board
will display the last abnormal reason P
X.X. Need powered off and restart
Resumable
After there are voltage malfunction for 3
times in 1 hour, the testing board will
display the last abnormal reason P X.X.
Need powered off and restart
Resumable
Need reset and restart
-100-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.