●The total capacity of indoor unit can be more than that of outdoor unit.
●With new environment friendly refrigerant R407C
HAIER GROUP
MANUAL CODE: SYJS-023-03 REV: 2 EDITION: 2005.03
Page 2
CONTENTS
CONTENTS
Contents
1. Description of products & features
2. Specification
3. Safety precaution
4. Net dimension of indoor and outdoor
5. Installation instructions
6. Parts and functions
7. Remote controller functions
8. Refrigerant diagram
9. Electrical control functions
10. Diagnostic information (trouble shooting)
11. Electrical data
12. Exploded view and parts lists
13. Performance curves
14. Noise level charts
15. Air velocity distribution
Page 3
1.DESCRIPTION OF PRODUCTS & FEATURES
1.1. Products code explanation
A U 28 2 X H B A A
Climate type: T1 (see table 1)
Design number (A stands for design sequence,fixed frequency type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407C
M stands for cool only type, refrigerant is R22
N stands for cool only type, refrigerant is R407C
Appearance character
Product series: X stands for 1 to 2, 1 to 3, 1 to 4
Applicable voltage: 2 stands for 220-240V/50Hz,
4 stands for 220V/60Hz,N stand for 380V/50Hz
Cooling / Heating capacity,28=28000BTU/h
Product type : “B” stands for cassette type, “C” stands for convertible
type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller
system, "E" stands for ceiling concealed type, “U” stands for outdoor
unit
Air Conditioner
1.2 Brief Introduction for T1、T2、T3 working condition
Climate type
Type of Air
Conditioner
Cooling Only
Heat pump
Electricity Heating
T1 T2 T3
18 ℃~43℃ 10℃~35℃ 21℃~52℃
-7℃~43℃ -7℃~35℃ -7℃~52℃
~43℃ ~35℃ ~52℃
1.3 Operating Range of Air Conditioners
Temp. Mode Rated Maximum Minimum
Cooling
Heating
Indoor
Outdoor
Indoor
Outdoor
DB ℃
WB ℃
DB ℃
WB ℃
DB ℃
WB ℃
DB ℃
WB ℃
27 32 18
19 23 14
35 43 10
24 26 6
20 27 15
14.5 --- --
7 24 -7
6 18 ---
Page 4
1.4 Product character
1.4.1 Operating individually and operating simultaneously
The unit can realize individual operation which can control one unit running, stop, and adjusting running
mode. Also the unit can operate simultaneously which control multi indoor units at the same time.
1.4.2 Variable quantity of indoor unitIf you want to add or reduce the quantity of indoor units (of course
the match must correspond with the design), it can meet your need at any time. More convenient, more
random.
1.4.3 Universal outdoor unit, multiform indoor unit
We realize universal outdoor unit, and 6 kinds of indoor unit, choose freely according to customer’s favor
and indoor decoration, more stylish and more beautiful
1.4.4 The total capacity of indoor unit can be more than that of outdoor unit.
When all the indoor units are running at the same time, the actual capacity of every indoor unit is
proportional according to outdoor capacity.
1.4.5 Long distribution pipe and high drop
The unit can realize long distribution pipe and high drop, the detailed information please refer to the
specification, consequently, the installation can be more free, and can meet various need of the
customer.
1.4.6 Ceiling concealed type unit be equipped with high efficiency filter, and its high static pressure
can be up to 30Pa, running more silent, making room air more comfortable and more clean.
1.4.7 The ceiling concealed type can realize the “Room Card” function, and take it convenient for
hotel management.
1.4.8 Auto-check function
The unit can display the malfunction codes on the control board by using advanced auto-check
technology ,convenient for user find and dwell with the abnormal running.
1.4.9 Auto –restart function (optional );
All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will
automatically recover the previous running mode once the power supply is on.
1.4.10 Group control function
1.4.11 Weekly timer (optional)
1.4.12 Variable Control modes
Wired remote control ;
Remote control;
*Group control: a. With remote monitor function; b. Auto changeover function
Page 5
2. SPECIFICATIONS
Item ModelAU282XHBAA
Function
Capacity
Capacity
Total power input
Max. power input
EER or COP
Dehumidifying capacity
Power cable
Communication cable
Power source
Running / Max.Running current
Start current (system A / system B)
Fuse size (recommended size)
Compressor
Fan
Heat exchanger
Dimension
(L×W×H)
Drainage pipe material, diametermm
Refrigerant control method
Defrosting method
Type of 4-way valve
Material of reduce noise
Crankcase heater power
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe
Connecting method
Piping
Between I.D &O.D
Model / Manufacture——
Oil charge and type ——
Type——
Number——
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H/M/L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type / Chargeg
No need to rechargem
Rechargeg/m
Liquidmm
Gasmm
Drop between IU & OU
Drop between indoor units
Piping length
Total length
——
BTU/h
W
W
W
W/W
10‐³×m³/h
——
——
N, V, Hz
A / A15.0/17.014.0/16.0
A
A
℃
——
——
——
——
W
——
m
m
m
m
CoolingHeating
2800032000
82009300
34003400
39003900
2.402.80
//
3 × 3.0mm
2
8x(0.75~1.25mm
1, 220~230, 50
35.0 / 35.0
30
PG260X2CS-4KT1 / TOSHIBA
720 CC (RB68AF/T68/α68TF)
Rotary (Fix speed)
2
Axial × 1
50 / 840+50 / 590+50
1000+
60
4000/3000/2000
TP2M / 9.52x0.35
0.77
cooling: 43~60 / heating: 6~7
948x340x830
1050x440x979
/
Capillary tube
Automatic
DPF-6
XPE
/
58/-/-
74/89
R407C / 1900 × 2
Piping length less than 5 meters in one system
35
Φ6.35
Φ12.7
Flared
≤5 (per way)
≤5 (per way)
≤10 (per way)
≤20 (2 ways)
2
)
* Long piping length and large drop between the indoor and outdoor unit (which exceeds standard value) will obviously reduce the capacity.
Page 6
Item ModelAS072XCBAAAS092XCBAA
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
Fan
Heat exchanger
Dimension
(L×W×H)
Drainage pipe material, diametermm
Controller type
Refrigerant controlCapillary tube
Fresh air hole dimension/
Electricity Heater
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe
Piping
Connecting method
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H/M/L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A / A0.100.100.100.10
℃
——
——
mm
——
——
CoolingHeatingCoolingHeating
70008000900010000
2000230026002900
1.0/1.0/
3 × (1.0~1.5mm2 )
2x(0.75~1.25mm2 )
1, 220~230, 50
CROSS×1CROSS×1
900/800/700900/800/700
2525
400/350/300
400/350/300
TP2M / 6.35×0.7
about 0.15about 0.15
cooling: 6~7 / heating: 43~60
795×197×265795×197×265
863×304×330863×304×330
PVC, 11.4/16.4
Phone type infrared
/
37/35/3037/35/30
7.6/10.67.6/10.6
R407C
6.35
12.7
Flared
Item ModelAS122XCBAAAS142XCBAA
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
Fan
Heat exchanger
Dimension
(L×W×H)
Drainage pipe material, diametermm
Controller type
Refrigerant controlCapillary tube
Fresh air hole dimension/
Electricity Heater /
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe
Piping
Connecting method
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H-M-L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A / A0.150.150.150.15
℃
——
——
mm
——
——
CoolingHeatingCoolingHeating
12000130001400016000
3500390041004600
1.6/1.6/
3 × 0.75mm
2
2x(0.75~1.25mm2 )
1, 220~230, 50
CROSS×1CROSS×1
1100/1000/9001100/1000/900
2525
550/500/450550/500/450
TP2M / 6.35×0.7
about 0.20about 0.20
cooling: 6~7 / heating: 43~60
795×197×265795×197×265
863×304×330863×304×330
PVC, 11.4/16.4
Phone type infrared
39/37/3039/37/30
7.6/10.6
7.6/10.6
R407C
6.35
12.7
Flared
Page 7
Item ModelAF072XCBAAAF092XCBAA
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
FanCROSS × 2CROSS × 2
Heat exchanger
Dimension
(L×W×H)
Drainage pipe material, diametermm
Controller type
Refrigerant control
Fresh air hole dimension
Electricity Heater
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe6.356.35
Piping
Connecting method
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H/M/L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A0.250.250.250.25
℃
——
——
mm
——
——
CoolingHeatingCoolingHeating
70008000900010000
2000230026002900
1.0/1.0/
3 × (1.0~1.5mm2 )
2x(0.75~1.25mm2 )
1, 220~230, 50
900/800/700900/800/700
50
500/450/400500/450/400
TP2M / 7.94×0.35TP2M / 7.94×0.35
about 0.25about 0.25
50
cooling: 6~7 / heating: 43~60
720×205×630720×205×630
780×280×690780×280×690
PVC, 11.4/16.4PVC, 11.4/16.4
Phone type infrared controller
Capillary tube
//
//
38/36/3438/36/34
17/20.717/20.7
R407CR407C
12.712.7
Flared
Flared
Item ModelAF122XCBAAAF142XCBAA
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
FanCROSS × 2CROSS × 2
Heat exchangerTP2M / 7.94×0.35TP2M / 7.94×0.35
Dimension
(L×W×H)
Drainage pipe material, diametermm
Controller type
Refrigerant control
Fresh air hole dimension
Electricity Heater
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe6.356.35
Piping
Connecting method
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H/M/L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A0.250.250.250.25
℃
——
——
mm
——
——
CoolingHeatingCoolingHeating
12000130001400016000
3500390041004600
1.6/1.6/
3 × 0.75mm
2
2x(0.75~1.25mm2 )
1, 220~230, 50
1100/1000/9001100/1000/900
5050
700/650/600700/650/600
about 0.25about 0.25
cooling: 6~7 / heating: 43~60
720×205×630720×205×630
780×280×690780×280×690
PVC, 11.4/16.4PVC, 11.4/16.4
Phone type infrared controller
Capillary tube
//
//
38/36/3438/36/34
17/20.717/20.7
R407CR407C
12.712.7
FlaredFlared
Page 8
Item Model
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
FanCENTRIFUGAL × 1CENTRIFUGAL × 1
Heat exchangerTP2M / 9.52×0.8
Dimension
(L×W×H)
Drainage pipe material, diametermm
Controller type
Refrigerant control
Fresh air hole dimension
Electricity Heater
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe6.356.35
Piping
Connecting method
Dimension
(L×W×H)
Panel
WeightNet / Shipping
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H/M/L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
Externalmm
Packagemm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A0.200.200.200.20
℃
——
——
mm
——
——
kg / kg
Item Model
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
FanCENTRIFUGAL × 1
Heat exchangerTP2M / 9.52×0.8TP2M / 9.52×0.8
Dimension
(L×W×H)
Drainage pipe material, diametermm
Controller type
Refrigerant control
Fresh air hole dimension
Electricity Heater
Noise level H/M/LdB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe6.356.35
Piping
Connecting method
Dimension630×630×80630×630×80
Panel
WeightNet / Shipping
* o.d.=outer diameter; i.d.=inner diameter
Type × Number——
Speedr/min
Motor output powerW
Air-flows (H/M/L)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
Externalmm
Packagemm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A0.200.200.200.20
℃
——
——
mm
——
——
kg / kg
AB072XCBAAAB092XCBAA
CoolingHeatingCoolingHeating
70008000900010000
2000230026002900
1.0/1.0/
3 × (1.0~1.5mm2 )
2x(0.75~1.25mm2 )
1, 220~230, 50
750/610/540750/610/540
4040
650/580/550650/580/550
about 0.25about 0.25
cooling: 6~7 / heating: 43~60
700×570×276
775×715×361775×715×361
PVC, 32/26(o.d./I.d.*)PVC, 32/26(o.d./I.d.*)
Phone type infrared controller
Capillary tube
100100
//
43/40/3743/40/37
24/2624/26
R407CR407C
12.712.7
Flared
630×630×80630×630×80
680×680×155680×680×155
4.2/6.34.2/6.3
AB122XCBAAAB142XCBAA
CoolingHeatingCoolingHeating
12000130001400016000
3500390041004600
1.6/1.6/
3 × 0.75mm
2x(0.75~1.25mm2 )
1, 220~230, 50
750/610/540750/610/540
4040
650/580/550
about 0.25about 0.25
cooling: 6~7 / heating: 43~60
700×570×276
775×715×361775×715×361
PVC, 32/26(o.d./I.d.*)PVC, 32/26(o.d./I.d.*)
Phone type infrared controller
Capillary tube
100100
//
43/40/3743/40/37
26/2826/28
R407CR407C
12.7
FlaredFlared
680×680×155680×680×155
4.2/6.3
2
CENTRIFUGAL × 1
TP2M / 9.52×0.8
700×570×276
Flared
650/580/550
700×570×276
12.7
4.2/6.3
Page 9
Item ModelAE072XCBAAAE092XCBAA
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
FanAXIAL× 1
Heat exchangerTP2M / 9.52×0.8TP2M / 9.52×0.8
Dimension
(L×H×D)
Drainage holeDiametermm
Controller type
Refrigerant control
Fresh air hole dimension
Electricity Heater
Noise level SH/H/M/L*dB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe
Piping
Connecting method
Type × Number——
Speed (SH/H/M/L*)r/min
Motor output powerW
Air-flows (SH/H/M/L*)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A0.680.680.680.68
℃
——
——
mm
——
——
CoolingHeatingCoolingHeating
70008000900010000
2000230026002900
1.0/1.0/
3 × (1.0~1.5mm2 )
2x(0.75~1.25mm2 )
1, 220~230, 50
AXIAL × 1
1310/1235/1120/8851310/1235/1120/885
4040
808/754/687/543
about 0.1about 0.1
808/754/687/543
cooling: 6~7 / heating: 43~60
674*225*450
816*288*526816*288*526
O.D.=20, I.D.=18
Wired controller
Capillary tube
100100
//
43/38/35/3243/38/35/32
18/2018/20
R407CR407C
6.356.35
12.712.7
FlaredFlared
674*225*450
Item ModelAE122XCBAAAE142XCBAA
Function
Capacity
Capacity
Dehumidifying capacity
Power cable
Communication cable
Power source
Running current
FanAXIAL× 1AXIAL × 1
Heat exchangerTP2M / 9.52×0.8TP2M / 9.52×0.8
Dimension
(L×H×D)
Drainage pipe material, diametermm
Controller type
Refrigerant control
Fresh air hole dimension
Electricity Heater
Noise level SH/H/M/L*dB(A)
WeightNet / Shippingkg / kg
Refrigerant
Pipe6.356.35
Piping
Connecting method
* SH/H/M/L: Super high/High/Medium/Low, the values are measured in the condition: external static pressure is 0Pa.
Type × Number——
Speed (SH/H/M/L*)r/min
Motor output powerW
Air-flows (SH/H/M/L*)m³/h
Type / Diametermm
Total aream²
Temp. scope
Externalmm
Packagemm
Type——
Liquidmm
Gasmm
——
BTU/h
W
10‐³×m³/h
——
——
N, V, Hz
A1.351.351.351.35
℃
——
——
mm
——
——
CoolingHeatingCoolingHeating
12000130001400016000
3500390041004600
1.6/1.6/
3 × 0.75mm
2
2x(0.75~1.25mm2 )
1, 220~230, 50
1384/1350/1300/12301384/1350/1300/1230
50
1051/1007/985/9301051/1007/985/930
about 0.12about 0.13
50
cooling: 6~7 / heating: 43~60
828*225*450828*225*450
976*288*526976*288*526
O.D.=20, I.D.=18
Wired controller
Capillary tube
100100
//
45/42/40/3845/42/40/38
20/2220/22
R407CR407C
12.712.7
FlaredFlared
Page 10
characteristic for sensors
modelpart numberpart namecharacteristic
1.R25=5KΩ±1%,
001A3900153ambient temp sensor
AU282XHBAA
AU422XIBAA
AF-001A3900059coil temp sensor
AE-001A3900006gas pipe temp sensor
AB-001A3900006gas pipe temp sensor
0010450243A system coil temp sensor
0010450398
0010451344
0010451343
0010450243A system coil temp sensor
0010450398
0010451344
A system discharging temp
sensor
B system discharging temp
sensor
ambient temp sensor, B
system coil temp sensor
A system discharging temp
sensor
B system discharging temp
sensor
Please read these "Safety Precautions" first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, and
those points which are related to the strong possibility of an installation done in error
CAUTION
resulting in death or serious injury are listed in the section. However, there is also a
possibility of serious consequences in relationship to the points listed in the section as well.
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please
explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's
manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.
WARNING
WARNING
CAUTION
WARNING
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior
environment such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned
countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,
and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold
concentration does occur,there is the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive
use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and
fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat
generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
- 10 -
Page 12
SAFETY PRECAUTIONS
WARNING
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (please see nameplate) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refigerant leakage.
The position of indoor unit must be above the floor 2.5m.
CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone
ground wire.
Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not
installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
- 11 -
Page 13
4. Net dimension of indoor and outdoor
4.1 Outdoor unit: AU282XHBAA
340
830
380
416
>600
185
580
950
1024
>100
>100
>150
>600
Page 14
4.2 Indoor units
Model: CONSOLE TYPE
Model: WALL MOUNTED TYPE
440
783
225
model
Haier
a
b
c
a
b
c
AS072XCBAA AS092XCBAA
AS122XCBAA AS142XCBAA
795
265
182
Page 15
Model: CASSETTE TYPE
Model: CEILING CONCEALED TYPE
UPDATED
e
d
f
g
Installation dimension: (Unit: mm)
TYPE
AE072XCBAA,
AE122XCBAA,
AE212XCBAA
AE092XCBAA
AE142XCBAA
c
b
a
abcdefgi
615
770
1064
648
804225
1099
452
452
452
225
225
55
55
55
125
225
125
225
225100
125
i
100
100
Page 16
The unit capacity and performance mode:
(A stands for A system, B stands for B system. For testing result, we will not recommend 12000BTU/h unit to you)
Must pay special attention to the match style, to see the following table:
A to 2 B to 2 A to 1 B to 1
072XCBAA*2 072XCBAA *2
142XCBAA *1 142XCBAA *1
092XCBAA*2 092XCBAA*2
Pipe connections:
AF092*2
AS092*2
AB092*2
AE092*2
B:
A:
B:
AF142*1
AS142*1
AB142*1
AE142*1
1 TO 4
Outdoor unit
A1
A2
B1
B2
A1
A2
Indoor units
B1
B2
Page 18
1 TO 3
Outdoor unit
A1
A2
B1
B2
1 TO 2
Outdoor unit
Indoor units
A1
A2
Indoor units
B1
A1B1
A1
A2
B1
B2
Admissible pipe length and drop between the units:
a. Max. single distance piping length of unit A 1、unit A2 、unit AB1、unit B2: 25m;
b. Max. drop between A1 unit and A2 unit、B1unit and B2 unit:5m;
Refrigerant recharge:
Distribute pipes for unit A1、unit A2、unit B1、 unit B2 are supplied 5m as standard, if it is longer than 5m,
recharge refrigerant as 35g/m.
Communication Wire connection:
1. The indoor unit whose liquid pipe is connected to A1 in A system is called unit A1, its communication wire
of A1(3)、 A1(4) should be connected to A1(P)、A1(Q) respectively.
2. The indoor unit whose liquid pipe is connected to A2 in A system is called unit A2, its communication wire
of A2(3) 、A2(4) should be connected to A2(P)、A2(Q) respectively.
3. The indoor unit whose liquid pipe is connected to B1 in B system is called unit B1, its communication wire
of B1(3) 、B1(4) should be connected to B1(P)、B1(Q) respectively.
4. The indoor unit whose liquid pipe is connected to B2 in B system is called unit B2, its communication wire
of B2(3) 、B2(4) should be connected to B2(P)、B2(Q) respectively.
Note: Because the customers themselves match the communication wire, and the P and Q are
nonpolar, the customers must use shielded communication wires.
Page 19
ky*r{ pnovr nxq pyxxrp}uxs pnovrg
jy{ fbbbhlmat ,cehlmat ~xu}|g
XW[QY PNOTQ
>/5GC,<62= 0-4UU
jy{ wy{r }tnx dcbbbhlmat ~xu}|g
XW[QY PNOTQ
>/5GC,<62= 1-/UU
iyxxrp}uxs *u{uxs quns{nwg
jy{ pn||r}}r nxq q~p}` pyx|yvr }+zr ~xu}|g
DJI:DDG JC?I
I;GB?C?7A 8AD9@
?C:DDG JC?I
I;GB?C?7A 8AD9@
PWVVQPZSVR PNOTQ
1
>/3GC,< 6/-54UU1\1
PWVVQPZSVR PNOTQ
1
>/3GC,< 6/-54UU1\1
AC
L8
M.=
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
0123
M.=
70718081
EFEFEFEF
M.=
0123
M.=
0123
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
0123
M.=
M.=
jy{ *nvv }+zr ~xu}|g
DJI:DDG JC?I
I;GB?C?7A 8AD9@
?C:DDG JC?I
I;GB?C?7A 8AD9@
AC
L8
M.=
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
32 10
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
M.=
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
70718081
EFEFEFEF
32 10
M.=
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
M.=
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
32 10
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
32 10
EDL;G HJEEAM6
0E>+11/,12/K^+4/>]
M.=
M.=
Page 20
5. Installation
Installation diagram of indoor & outdoor unit
Outdoor unit
Piping data.
Gas pipe mm 12.7
L1 m Suggest 10m Max. :30m
Pipe length of one way L2 m Suggest 10m Max. :25m
L3 m Suggest 10m Max. :25m
Drop between indoor Indoor unit up m Suggest 5m Max. :15m
and outdoor unit Indoor unit down m Suggest 5m Max. :10m
No need to recharge: when piping length of one way is less than 5 meters.
1
L1 means the piping length when the system only connects with one indoor unit.
2
L2, L3 means the piping length when the system connects with 2 indoor units.
3
Long piping length and large drop between indoor unit and outdoor unit will reduce the
performance capacity obviously.
A 2
L1
AS142
L2
B 1
B 2
AS072
AS092
3
3
3
3
3
L3
1
2
2
Installation tools
1. Screw
2. Steel saw
3. Drill (70mm dia.)
4. Spanner [17, 27mm dia.]
5. Spanner [14, 17, 19, 27mm]
6. Pipe cutter
7. Flarer
8. Knife
9. Pliers
10. Leakage detector or soap water
11. Tape measure
12. Scraping knife
13. Refrigerant oil
14. Vacuum pump
15. Nitrogen tank
Standard accessories
The following parts mentioned
in this instruction is optional.
The following are accessories attached with the unit,
they can be used with the need of installation
Shape, name
Rubber cushion
QuantityRemarks
4
1
1
Mark
,
Parts name
ABCDEF
Adhesive
tape
Pipe supporting
plate
Connection pipe
Drain hose
Insulation material
Powder
Page 21
5. Installation
Installation instruction
Before installing, do read this Safety precautions carefully to guarantee the proper installation.
The below attentive matters are divided into Warning andNote two parts. When the
wrong installation occur, it is very possible death and severe injury and other serious accidents will
happen. For those items are listed inWarning part. But even the items listed in Note
part can also cause serious accidents. Above all, both the two parts are very important contents
related to safety, so they must be obeyed.
After finishing the installation work, do test run to verify everything is normal. After that please
explain the using and maintenance methods to the user. Additionally, give this installation manual
and operation manual to the user and ask them to keep it properly.
!
The distributing shop, where you bought the air conditioner, or the specified shops shall do the
installation work. If you do the installation work by yourself, the improper installation will cause
water leakage, electric shock fire and other accidents.
The installation work shall be in line with what the installation manual specified. If installation
is not proper, water leakage, electric shock, fire and other accidents will occur.
Install the air conditioner to a place where can definitely stand its weight. Places not firm enough
will cause drop down of unit resulting in body hurt.
The installation work shall be preventive to typhoon and earthquake. If the installation work is
not met with the requirements, overturn of the unit will occur resulting in accidents.
The wiring work shall be done by a qualified person and referred to the technical standard of
electric equipment , indoor wiring regulation and what the manual specified. Do use
special circuit. If the capacity of the circuit is not enough or bad work, electric shock, fire and other
accidents will happen.
Using the specified cable to do wiring work and connecting firmly and properly. Fix the connecting
part of the terminals to prevent it from the external force.Improper connection and fixing will cause
heating and fire etc. accidents.
Wiring shall be kept in correct shape avoiding extrusion. After installation, the electric box cover
and the external panel shall not nip the wire. Improper installation will cause heating and fire etc.
accidents.
When setting or moving the air conditioner do not let the air and things alike get into the
refrigeration system except the specified refrigerant (R407C). If air and other things enter
abnormal high pressure will occur, which easily cause break and body injuries etc. accidents.
When installing, do use the accessories or specified parts. If not using the parts specified by our
company, water leakage, electric shock, fire and refrigerant leakage will occur.
Do not lead the drainpipe to drain where the sulfur gas may be involved. Otherwise, the poisonous
gas will enter into the indoor.
During installation, if refrigerant leakage occurs, do the ventilation work immediately. As soon as
the refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas enters into room
and meet the air blowing heater, heater or stove etc. fire source, the poisonous gas may be produced.
After installation, confirm there is no leakage of refrigerant.
Do not install the unit in a place where the combustible gas may be leaked. In any case the
combustible gas leaks and accumulated around the unit, fire accident will occur.
Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose of heat
preservation. If the heat insulation measure is not sufficient, water generated by condensing dew
will drip leading to wet the floor and indoor articles.
!
!
Warning
!
!
!
Note
Do grounding work.Do not connect the grounding wire to gas pipe,tap,lighting rod or telephone
line.Improper grounding will cause electric shock.
After electric installation,power on them to do electric leakage test.
In some places the creepage breaker shall be installed.If do not install the breaker, electric shock
may occur.
Page 22
Installation of outdoor unit
Choosing of installation position
Installation position
Do not install the air
conditioner near to a
place where flammable
gas may leak.
Explosion may be caused
(fire)
Choose a place where the
cold/heat air or noise may
not disturb the neighbors.
Install the air conditioner in a
place where good ventilation
can be guaranteed.
If there are some obstacles,
it may lower the working
power of the unit or
increase noise.
It is deadly necessary to
prevent from accumulation
of snow near the outdoor
unit to keep it away from
being blocked by
accumulated snow.
Install the air conditioner on base
that can definitely support the weight
of the unit.
Otherwise, vibration or noise may
be caused.
The following special places are not
suitable to install air conditioner,
otherwise, trouble may be caused.
When you install the air conditioner
in these places, please consult with
the distributor.
Places generate corrosive gas
(hotspring area, etc.)
Places blow salt air (seaside, etc.)
Places have heavy soot.
Places have very high humidity.
Places near an electromagnetic
wave generator.
Places with large voltage fluctuation.
Installation fixation
1. According to dimonsion shown in the following figure,
fix the installation bracket tightly in the chosen
installation area.
2. Then use screws to fix the outdoor unit on the
installation bracket.
380
190190
Installation dimension of outdoor unit (mm)
580
Over 60cm
>10cm
>10cm
Outdoor unit
>15cm
>60cm
Page 23
Installation procedureConnection of pipes
Warning
!
During installation, if refrigerant leakage
occurs, take ventilation measurement
immediately.
As soon as the leaked refrigerant gas
meets f re, poisonous gas will generate.i
After finishing installation, confirm the
refrigerant gas does not leak.
If the refrigerant gas leaks in the room,
once it meets heater, burner and gas
stove or other. fire source, the poisonous
gas will generate.
I. Connection of pipes
1 Method of pipe connection
The pipe shall be as short as possible to guarantee efficiency.
Daub the refrigerant oil on the connection and flare nut.
When bending the pipes, give the roundness as large as possible, to avoid crashing the
pipes.
To connect the pipe, fit the center and screw the nut with hand, then use spanner or
torque wrench to tighten it. The fastening torque as shown in below table. As shown in
figure.
Be careful alien matters, such as sands, water etc.shall not enter the pipes.
Forced fastening without careful
centring may damage the threads
and cause gas leakage.
Using the specified fastening torque to fasten nuts.
Pipe diameter(mm)
6.35
12.7
Installation torque(N.m)
11.8(1.2kgf.m)
49.0(5.0kgf.m)
Spanner
Spanner
Joint
Nut
Fastening torque(N.m)
13.7(1.4kgf.m)
53.9(5.5kgf.m)
Page 24
Installation procedureConnection of pipe
2.Method of cutting and flaring pipe
Cut and flare pipe
Use pipe cutter to cut the pipe, the burrs must be removed.
After inserting the flarer, perform flared nut.
Flaring pipes.
A
Flarer
Correct
Slant
When joint connecting, no gap shall
be left in the joint, the insulating
material shall be overlapped.
BreakCrack
150
Diameter of pipe
6.35mm(1/4")
12.70mm(1/2")
Uncorrect
Branch pipe
Insulating material
Partial
Dimension
(mm)
A
0.8~1.5
1.0~2.0
Too outside
Connecting pipe in site
Insulating material
Insulating material (arranged in site)
Thickness: Over 10mm
Page 25
Installation procedureConnection of pipes
4.Pipe connection of the outdoor unit.
Referring to the installation diagram in page 4, connect the indoor unit with outdoor unit, by
using the pipe connection method.
II Test of airtight quality
After connection of the refrigerant pipes, carry out airtight quality test. In this test, pressurize to the
pipes as shown in the below figure by using nitrogen tank.
Close the valves of the gas side and liquid side totally.
The nitrogen may enter the cycle system of the outdoor unit, so that, before pressurizing, the valve rods
must be fastened.(Both the gas side and liquid side)
For each of the refrigerant system, pressurize from the discharge valve of gas side in procedure.
When doing airtight quality test, it is absolutely forbidden to use oxygen, flammable gas and poisonous
gas.
If the hi-pressure valve of the outdoor unit is 3-way valve.
Stop valve close
Indoor side
Joint
Joint
Outdoor side
Welding part
Welding part
Fasten
Fasten
(Gas side)
Gas discharging
valve
Indoor unit
Stop valve close
(Liquid side)
When the hi-pressure valve of the outdoor unit is 2-way valve.
3-way valve close
Indoor sideOutdoor side
Welding part
Joint
(Gas side)
Fasten
Low pressure
meter
Gas discharging valve
Outdoor unit
Low pressure
meter
Gas discharging valve
High pressure
meter
VL VH
Instrument
distributor
Pressure
reducing
valve
High pressure
meter
VL VH
Instrument
distributor
Nitrogen
Indoor unit
Joint
Welding part
Fasten
Outdoor unit
2-way valve
(Liquid side)
Pressure
reducing
valve
Nitrogen
Page 26
Installation procedureConnection of pipes
III Vacuumizing of the pipes and indoor unit (using vacuum pump to vacuumize, it is strictly
forbidden to use refrigerant purging)
Choose of vacuum pump: it shall choose those that can reach a good vacuity ( Lower 200Pa ) and
have a large air discharge amount (over 40L/min).
After finishing the airtight quality test and discharging the nitrogen, connect the instrumental
diverter to the 3-way discharge valve, then connect the vacuum pump according to the below figure.
If the hi-pressure valve of the outdoor unit is 3-way valve.
Indoor side
Outdoor side
Low pressure
meter
Stop valve close
(Gas side)
VL VH
High pressure
meter
Instrument
distributor
Fasten
Fasten
Fasten
Fasten
Indoor unit
Stop valve close
(Liquid side)
When the hi-pressure valve of the outdoor unit is 2-way valve .
Indoor side
Outdoor side
Joint
Fasten
Joint
Fasten
Gas discharging valve
Gas discharging
valve
Outdoor unit
Low pressure
3-way valve close
meter
(Gas side)
Gas discharging valve
P
Vacuum pump
High pressure
meter
VL VH
Instrument
distributor
P
Indoor unit
Outdoor unit
2-way valve
(Liquid side)
When the hi-pressure valve of the outdoor unit is 2-way valve:
(1) Firstly connect indoor, outdoor power supplies, and communication lines, then set addresses
of indoor units and check their correctness.
(2) Determine running mode according to indoor temperature: Set to cooling mode when indoor
temperature Ta 23set to heating mode when Ta<23 .
(3) Keep stop valve of outdoor unit close , and start the indoor unit according to running mode
determined by indoor temperature.
Vacuum pump
Page 27
Installation procedureConnection of pipes
(4) Watch the status of outdoor unit compressor, disconnect the general power supply for the air
conditioner assembly after the compressor unit starts.
If the hi-pressure valve of the outdoor unit is 3-way valve:
Without starting the machine, simply exhaust to vacuum (vacuum degree<200Pa) directly from
hi-presser and low-pressure valves(strictly in compliance with operation steps defined in instruction
manual for outdoor unit) after machine connecting pipe is well done.
Vacuumize 2~3 hours according to the length of the pipe. When vacuumizing, confirm the gas side
and liquid side of the 2-way valve and 3-way valve shall be in full close state.
When it is not lower than 200Pa after 2 hours or more vacuumizing, vacuumize for another
1 hour. If after more than 3 hours vacuumizing it is still not lower than 200Pa, the leak part shall be
found.
When it is lower than 200Pa after more than 2 hours vacuumizing, close both the valve VL and
VH of the diverter, then close the vacuum pump. Place it there to observe if the vacuity changes.
If it changes, it indicates leakage exists, so the leak part shall be found.
After finishing the above vacuumizing work, replace the vacuum pump with refrigerant tank and
turn to the refrigerant charging procedure.
V Charging of refrigerant
1.Calculation of additional charging amount of refrigerant
After finishing vacuumizing work, replace the vacuum pump with refrigerant tank and turn to the
refrigerant additional charging procedure.
Calculation of additional charging amount of refrigerant
Quantity of filled refrigerant before the machine leaving factory does not consider supplement
for extension tubes while spot installation. After practical installation is finished, it is necessary to fill
supplement refrigerant into extension tubes provided that the length of spot liquid tube>0m.
Filling method is as the following.
Calculation method:
Quantity of supplement refrigerant is determined by specification and actual length of the spot
liquid tube.
Calculation formula:
Quantity of spot supplement refrigerant = actual length necessary supplement refrigerant
quantity per meter of the tube.
E.g.: Uuantity of spot supplement refrigerant(R407C)=(L1-5) 0.035kg/m)
L1: Actual total length of 6.35 liquid tube in one system
Uuantity of spot supplement refrigerant(R407C)=[(L2-5)+(L3-5)] 0.035kg/m)
L2, L3: Actual length of 6.35 liquid tube in the B1, B2 way.
2.Charging of refrigerant
Close all valves of outdoor unit, and charge refrigerant from air discharge valve of gas side.
When can not charge the specified amount, firstly, open all the valves, both liquid side and gas side,
of outdoor unit,then switch the valve of gas side to close state a little.Under this condition, do cooling
operation and charge refrigerant from the discharge valve of gas side. At this time, adjust the valve
of the refrigerant tank to make the refrigerant in Gas State when it is absorbed by system.
When refrigerant leakage making refrigerant lack in system occurs, all of the system shall be
recovered and recharge it according to specified amount.
3.Opening of the refrigerant pipe
Open all the valves of outdoor unit
Page 28
Installation procedureRefrigerant
The systems use regrigerangt R407C. This refrigerant itselt is innocuous, noncombustible safety
refrigerant. But then, when arranging the air conditioner equipment, it is necessary to take some
steps to take precautions against in case of the indoors refrigerant leakage. Such as, the room
size shall be taken into account to avoid making the concentration of the refrigerant not exceed the
concentration limit and other relevant steps. The concentration limit is the concentration that is not
harmful to human body and can take emergency steps to treat the concentration of Freon.
Concentration limit of R407C:0.3kg/m
3
Indoor unit
Indoor unit
If the indoor unit leaks, all the refrigerant in
the syetem will leak out
1.Sequence of refrigerant concentration affirmance
Calculate the refrigerant concentration according to the following sequence.
(1) Calculate the total refrigerant-charging amount of each of the refrigerating system(kg).
Refrigerant charging amount of outdoor system + Additional refrigerant charging amount
=Total refrigerant charging amount of the refrigerating equipment(kg).
Refrigerant charging amount of outdoor system: Refrigerant charging amount when air
conditioner leaves factory.
Additional refrigerant charging amount: Additional refrigerant charging amount according
to the site pipe length and pipe diameter.
(2) Calculate the minimum size of the room suitable for the indoor unit assembly(m ).
3
(3) Calculate the concentration of refrigerant:
Total refrigerant charging amount of refrigerating equipment/the minimum room size suitable
for indoor unit assembly(m ) Refrigerant concentration limit:0.3kg/m
3
3
2.Countermeasure when exceeding the concentration limit
(1) Set an effective opening for ventilation and fresh air.
Cut an intake respectively on the upper and lower part of the door which areas are equivalent
to 0.15% grounding area, or cut an intake in other part of the room.
(2) Reduce the total refrigerant charging amount of the refrigerating equipment
Shorten the refrigerant pipe length. Reduce the installation place distance between the
outdoor unit and the indoor unit to shorten the refrigerant pipe length, so that reduce the
total refrigerant charging amount of the refrigerating equipment.
(3) Establish ventilation and fresh air system
Establish a mechanical equipment for fresh air to keep the refrigerant concentration below
the concentration limit (normal ventilation).
When can not ventilate the normally, please set an alarm apparatus linked with the
mechanical ventilation equipment.
Page 29
Installation procedureElectric wiring
Electric wiring
Note:
The air conditioner must use special circuit (over 30A), and wiring by the qualified
electrician according to the wiring rules specified in national standard.
The grounding wire and the neutral wire shall be strictly separated. Connect the neutral
wire with grounding wire is incorrect.
The electric leakage breaker must be installed.
All the electric wire must be copper wire.When wiring,there shall keep a proper distance
between the power line and communication wire to avoid twist together.Otherwise,signal
disturbance will occur,and the air conditioner can not operate normally.
Power supply:1PH,220-230V~,50Hz.
The wiring method of power line is Y connection. If the power line is damaged,in order
to avoid risk of electric shock, it must be replaced by the manufacturer or its repair center
or other similar qualified person.
Specification of wire and short circuit protector in site wiring:
Fuse: 30A 250VAC
Type
Contents
Specificat on
i
Parameter
Power line
YZW
3x3.0mm
Short circuit
protector
2
30A
Connection signal wire
2x(0.75~1.25mm )
Note:The signal wire must be shielded .
Wiring method
1. Wiring method of orbicular terminals
For the connection wire with orbicular terminals, its wiring method
is as shown in the right figure: remove the connecting screw, put the
screw through the ring on the end of the wire, then connect to the
terminal block and fasten screw.
2. Wiring method of straight terminals
For the connection wire without orbicular terminals, its wiring
method is: loosen the connection screw, and insert the end of
the connection wire completely into the Termina l block, then
fasten the screw. Slightly pull the wire outwards to confirm it is
firmly held
3. Crimp connection method for wires without terminals
Connect the wire with
same diameter to the
two sides of the terminal
Do not connect the
wire with same diameter
to the same side
Correct Pressing
Do not connect the
wire with different
diameters
Wiring Method for
Ring Terminal Block
Wrong Pressing
Terminal
block
Pressing
Clamps
2
Crimp connection method for connection wire
After connection,the wire must be fastened by wire cover. The wire cover shall press on the
protection coat of the connection wire,as shown in right top figure.
Note:When connecting the wiring,confirm the terminal number of indoor and outdoor units
carefully. Incorrect wiring will damage the controller of air conditioner or the unit can not
operate.
Page 30
Installation procedureElectric wiring
Wiring method of outdoor unit:
Power line
Remove the repair board of the outdoor unit and loosen the wire cover A,then put the live
wire, neutral wire and grounding wire through the wire cover A,and connect them to
terminal block correspondingly. After connection, fasten wire cover A to its previous
state.
Communication wire of indoor unit
Loosen wire cover B ,put the communication wire through the wire cover B, and connect
them to terminal block correspondingly. After connection, fasten wire
cover B to its previous state.
Note: Power line and communication wire are provided by consumers themselves.
Termial
Wring clamp
B
A
Wiring method of indoor unit
Power line and communication wire of indoor unit
Loosen wire cover and connect the power line and communication wire of indoor unit to
the terminal correspondingly.
Page 31
Installation procedureElectric wiring
Note:
When connecting power line to power supply terminal, please pay attention to the following
items:
1. Do not connect the power line with different dimensions to the same connection wire end.
Improper contact will cause heat generation.
2. Do not connect the power line with different dimensions to the same grounding wire end.
Improper contact will affect protection.
3. Keep a proper distance between the communication wire and the power line. Otherwise,
abnormal communication will occur because of disturbance.
4. Do not connect the power line to the connecting end of communication wire. Incorrect
connection will cause damage of connected unit.
Wiring example diagram:
Wiring example diagram:
Outdoor unit
Terminal
To Power Supply
(1PH,220~230V,50Hz)
NL
A1 A2 B1 B2
P Q P Q P Q P Q
Outdoor unit
Terminal
1(N) 2(L)
W B Y/G R BR
To Power Supply
(1PH,220~230V,50Hz)
3 4
A2
1(N) 2(L)
W B Y/G R BR
To Power Supply
(1PH,220~230V,50Hz)
3 4
B1
1(N) 2(L)
W B Y/G R BR
To Power Supply
(1PH,220~230V,50Hz)
3 4
B2
Explanation on the communication wire connections:
1.If the communication wires are properly connected, when the indoor
units and outdoor unit power on, the communication indication LED (Red)
on the outdoor PCB will flash in sequence, also the LED (Red) on indoor
PCB will flash too.
2.If the communication indication LEDs don t flash, that shows the
communication wires are not properly connected. Please check the P and
Q connection and check the wires to see whether they have been
destroyed.
outdoor side
indoor side
Wall Mounted type
Indoor unit
Terminal
W:White B:Black
R:Red BR:Brown
Y/G:Yellow/Green
Page 32
5.2 Installation Instructions of wall mounted type
The standard accessories includes: 1) Measuring type 2) Reamer 3) Refrigerant oil 4) Gas leakage
detector or soap-and-water solution 5) Knife 6) Nipper
NO. Accessory Parts
Number of articles
1
3
4
5
1
2
1
1
1
6
6
7
air purifying filter
1
2
Page 33
Indoor Unit
1 Fitting of the Mounting plate and Positioning of the Wall Hole
When the mounting plate is first fixed
1 Carry out,based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the
wall,then temporarily fasten the plate with one steel nail.
2 Make sure once more the proper level of the plate,by hanging a thread with a weight from the central top
of the plate,then fasten securely the plate with the attachment steel nail.
3 Find the wall hole location A using a measuring tape.
A
Mounting
Plate
Weight
Holes for fixing the mounting plate
Fit the scale to a line
Thread
Fit the level line
Center of a Bmm hole
(insert a scale)
When the paper pattern is used
1 Stick a paper pattern on the wall horizontally
2 Position by using the pattern then remove the pattern.
Outline of mounting plate
Outline of indoor unit
Position of Bmm hole
Paper pattern
When the mounting plate is fixed to side bar and lintel
Fix to side bar and lintel a mounting bar, which is separately sold,and then fasten the plate to the fixed
mounting bar.
Refer to the previous article," ",for the position of wall hole.
When the mounting plate is first fixed
2 Making Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 60mm in diameter, slightly descending to outside
the wall
lnstall piping hole cover and seal off with putty after installation.
lndoor side
wall hole
B mm
(Section of wall hole) Piping hole pipe
Outdoor side
Thickness
of wall
Page 34
3 lnstallation of the lndoor Unit
Drawing of pipe
[Rear piping]
Draw pipes and the drain hose, then fasten them and connecting electric cable for indoor and outdoor with
the adhesive tape.
Drain hose should be placed under.
Heat insulation
Right piping
Under piping
B
Adhesive tape
Left piping
Drain hose
[Other direction piping]
Cut away, the left, under or right side lid with a nipper or saw, according to the wall hole
position, then bend the piping and fix it with piping support plate.
Sometimes it becomes an easy installation by preconnecting the interconnect cable,
then fasten piping and drain hose with it .
[Installation of piping support plate]
Insert the plate from top, into the piping to be fixed.
Push its buttom hard until you hear a clik.
Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the mounting
plate.Move the body from side to side to verify its secure fixing.
ln order to fix the body onto the mounting plate, hold up the body
aslant from the under side and then put it down perpendicularly.
material
Pipe supporting
plate
Pipe supporting
plate
Indoor/Outdoor
Electric cable
Click
Piping
4 Connecting the lndoor/Outdoor Electric Cable
[Cautions]
1. Make sure it is unit A or unit B, when make wiring.
2. Unit to be connected to stop valve A on outdoor unit is unit A, while
the one to be connected to stop valve B is unit B.
3. Refer to wiring diagram.
Removing the wiring cover
Open the inlet grill ,then remove one screw of the cover.
H
G
Putty
Piping hole
cover
Inlet grill
Wiring cover
Screw
Page 35
Installation Procedure
Electric wiring
! Warning
The electric wiring work shall be conducted by qualified electricians according to the installation
instructions. A separate power circuit shall be used. Insufficient power cord amperage or improper
wiring will cause danger of electric shock or fire.
During wiring connection, the power cord shall be of the specified cable and reliably fastened
so that external forces applied to the cable wouldnt transfer to the terminals. Improper connection
or fastening will cause danger of heating, fire etc.The power cord must be fitted with a grounding
wire.
Grounding shall be made as specified. Unreliable grounding will cause electric shock. The
grounding wire shall not be connected to the gas pipeline, water pipeline, thunder arrestor and
telephone wire
! Caution
A current leakage breaker shall be installed, otherwise it electric shock would happen easily.
If the power cord is damaged, it must be replaced by the manufacturer or its service center or
similar personnel to avoid risks. The power supply to the indoor unit shall be laid in complying
with the operational instruction manual.
The electric wiring shall avoid contacting with the high temperature part of the piping so as to
prevent the cable insulation melts and cause dangers.
After connected on the terminal block, the wires shall be bent to U form and then fastened with
wire clip.
The control wiring and refrigerant piping may be laid and fastened together.
Before completion of vacuum pumping of the refrigerant pipe system, do not electrify the indoor
unit.
The power cord of the indoor unit and connection wiring between indoor and outdoor units
shall be laid out according to the operational instruction manual of the indoor unit.
The connection of the power cord shall comply with the local regulations.
The power supply wiring connection should meet the local regulation.
!
!
Wiring connection method : (the wiring diagram is attached inside the machine)
1) Ring terminal connection method
If there is a ring at the end of the connection wire,
the wire connection method is as shown in the right
figure. Remove the terminal screw and insert it
through the ring at the connection wire end, then
connect to the terminal board and fasten the screw.
2) Straight terminal connection method
If there isnt a ring at the end of the connection wire,
the connection method shall be: loosen the terminal
screw, insert the connection wire end completely into the terminal board and fasten the screw.
Pull the connection wire outwards slightly to confirm it is clamped tightly.
3) Clamping method of the connection wire
After wire connection is finished, the connection wire must be pressed tightly with wire clips,
which shall apply to the outer sheath of the connection wire.
Connection method
for ring terminal
Page 36
Wire connection for built-in indoor unit
Insert from outside the connection wire and signal transmission wire through the wall hole
with pipeline already arranged.
Pull out the front ends of connection wire and signal wire and make a circle on the signal
wire.
Connect the connection wire according to the connection method and indoor and outdoor
wiring diagram.
Pull the connecting conductor outwards slightly to confirm it is clamped tightly.
Connect the plug for connecting the signal wire with the plug of the signal wire connected
from the indoor unit.
After wire connection is finished, install wire clips using the same method for connection
wire clamping.
Note: When connecting the indoor unit and the outdoor unit, please do connect the wir es
with the same color terminals.
Notes:
Before connecting the conductors between indoor unit and outdoor unit, check for the number
on the indoor and outdoor units connecting terminals. Connect the terminals with the same
color and number with a wire.
Wrong connection would damage the controller of the air conditioner or the machine couldnt
operate.
Do not connect the connection wire and signal wire with the same cable. They shall be
connected respectively to ensure system normal operation.
Page 37
5.2 Installation of indoor unit for console type
more than
Installation of indoor unit
selection of installation place
more than
more than
more than
Fig1
330
617
Fig2
Tool necessary
1. Screw driver
2. Hacksaw
3. 70mm dia.hole core drill
4. Spanner(dia. 17,27mm)
5. Spanner(14,17,27mm)
6. Pipe cutter
7. Flaring tool
8. Knife
9. Nipper
10. Gas leakage detector or soap water
11. Measuring tape
12. Reamer
13. Refrigerant oil
Standard accessories
Following parts shall be field supplied
Fig3
Place where it is easy to route drainage pipe
and outdoor piping.
Place ,away from heat source and with less
direct sunlight.
Place where cool and warm air could be
delivered evently to every corner of the room.
Place near power supply socket.Leave enough
space around the unit.
Place ,robust not causing vibration,where the
body can be supported sufficiently.
To prevent interference, place it at least 1m
away from other electric machines, such as
TV set, radio.
Installing
According to the dimension of the figure 2 shown,
nail two cement steel nails on the wall,Keep 2~3
mm out.then hang the back of the unit on them.
There must be no gap between the indoor unit
and wall.
Remove the front panel,then use two expansible
screws to fix the unit on the floor.As figure 3
shown.
Once refrigerant piping and drain piping connections
are complete,fill the gap of the throght hole with putty.
Attach the front panel and front grille in their orginal
positions once all connections are complete.
Shape and description
No.
Mark
A
B
C
D
E
F
Part name
Adhensive tape
Pipe clip
Connecting hose
Insulation material
Putty
Drain hose
Note: There isn't connecting wire with this unit.
Remote controller
Wire clip
Self-tapping screw
Wall hole cover
Dry battery #7
Cement steel nail
QTY
6
Page 38
Fixing of the unit
1.Position of the wall hole
Wall hole should be decided according to installation
place and piping direction.(refer to installation drawings).
Indoor side
Wall hole
70mm
2. Making a wall hole
Drill a hole of 120X70mm dia. with a little slope towards
outside.
3. Piping connection
(1)
Schematic diagram for unit connection
(Cross section of wall hole)
Indoor unit
Flared pipe connection
Gaseous pipe
3-way Valve
Indoor unit
Manifold tube
Outdoor uint
(2)
Connection pipe dimensions:
Liquid pipe
Flared pipe connection
2-way Valve
Apply and tighten the nut.
Pipe Value
Liquid
Gaseous
6.35mm
12.7mm
Torque
18 N.m
50 N.m
(3)
Maximum length and height difference of connecting pipe
Maximum length: 20m; Height difference: 10m
To ensure efficiency, shortest possible pipe should be used.
Cautions for pipe connection
Pipes free from twists, deformation, water, dust.
Dedicated tools for each R407C and R22
should be used and stored separately.
Optimized radii of bends
Insulation to be applied on all gaseous pipes
Flared section free from cracks
(4)
Pipe connection process
Apply refrigeration oil on the end of the pipe to be connected and on the flared section.
Align the pipes to be connected and tighten the nut. (See the figure)
Ensure that no foreign articles enter into the pipes.
Spanner
Spanner
Threads on the pipes may be damaged
when tightening if the pipes are not
well aligned.
Outdoor side
Thickness
of wall
Joint
Nut
Page 39
Piping connection of the indoor unit
1. Arrangement of piping and drainage pipe
After opening inlet grill,you will see a control box.
Remove the cover before working.
Cut away, with a hammer or a saw, the lid for piping according to piping direction.
According to the piping method, connect the piping on indoor unit with union of connection pipe.
Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping
together with polyethylene tape.
Insert the bound piping connecting electric cable and drain hoes through wall hole to connect
with outdoor unit.
Insulation material
Copper tube
Drain hose
Connecting electric cable
for indoor and outdoor unit
2. Arrangement drain hose
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down waves in drain hose.
If humidity is high, drain pipe(especially in room and indoor unit) must be covered with
installation material.
Electric wiring :
Process of wire connections
1. Loop terminal
After removing the screw, fix the wire ring on the screw, reinsert the screw into the
block terminal and then tighten the screw.
2. Straight terminal
After loosening the screw, inset the wire end into the block terminal and then tighten
the screw. Slightly pull the wire to see if it is tightly fixed.
3. Wire capping
After completion of connection, capping clips must be
applied on the external sleeve of the wires.
1(L)
Wiring of indoor unit
Remove air intake screen and take out the front wires.
Connect the wires as specified in the above
methods and diagrams for indoor unit and wire con nections.
Properly apply capping clips on the wires.
Wiring diagram of loop terminals
Block terminal
Replace the air intake screen.
Do not link the connecting and signal wire with the
same cable, a snug space must be maintained
between connecting and signal wires.
Shield of the signal wire should be spot grounded.
Capping clip
Page 40
Note:
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal
blocks. Terminals of same number and same color shall be connected by the same wire.
Incorrect wiring may damage air conditioner's control or cause operation failure.
Others
1.Power supply requirements:
Voltage: single-phase1PH,220-230V*,50Hz
Dedicated electrical cable should be installed by a qualified technician in
accordance with the state regulation for electrical engineering.
The power source must be grounded.
A circuit breaker must be installed
Electrical cables should be connected by ìYî method. Damaged or wornelectrical cable
must be replaced by authorized after sales agents.
The power plug should be connected as follows: L for live line, N for neutral line and
for grounding.
Connection parameters: H05RN-F 3G(1.0-1.5)mm
Signal parameters:
H05RN-F2X(0.75-1.5)mm
(Shieded wire)
Cables for power supply, connection and signals are prepared by the owner.
2.Piping cutting and flaring
Be sure to carry out deburring after cutting with a pipe cutter.
Insert flaring tool to make a flare.
A
CorrectIncorrect
Flare tooling die
Lean
Damage of flare CrackPartialToo outside
Liquid pipe
Gas pipe
Pipe diameterSize A (mm)
6.35mm(1/4")
12.7mm(1/2")
0.8 ~1.5
1.2 ~2.0
Page 41
5.4 Installation of ceiling concealed type
Installation of indoor unit
When installing the ceiling concealed type indoor unit, a specially designed return air
bellows shall be installed, as shown in Figure 3, Figure 4.
Figure 3
Figure 4
Ceiling
Air outlet grille
Installing building roof
*0.5m or*5m
Air supply
Air outlet duct
Unit
Detail A
A
Return air bellows
Return air
Return air bellows
Air supply
No obstacles
within 1 m
Unit
Return air
Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to
seal the interface closely. Recommend the distance between the air return duct and the wall is more than
150mm.
The distance between air duct outlet and air conditioner outlet is according to the length of actually installed
air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air
duct is showed below, when connect to short air duct, using low static terminal (terminal color is write), the
distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct,
using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet
could be within 5m at this point.
Figure 5
sling dog
drain piping
air return duct
air return shutter
transition
air duct
air outlet
duct
air diffuser
joint of air diffuser
Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover
the drain piping of condensed water to keep warmth.
As figure shown, suspend and install the unit.
Figure 6
M8 broad foundation bolt
M8 suspension screw
M8 broad lock ring
M8 nut
Unit
Figure 5
Installation for air duct of indoor unit
1. Installation for air supply duct
This type of unit uses circular air duct with its caliber of 180mm.
An additional transitive air duct is necessary for the circular air duct to connect to the air
supply inlet. It should be also connected to its respective air diffuser separately. See
Fig.1. Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so
as to meet a demand of the air conditioner in the room.
Page 42
Indoor unit
flexible joint
or static pressure box
Fig1: Duct connected
transitive air duct
circular air duct
joint of air diffuser
air diffuser
2. Installation for air return duct
Use rivets to connect the air return duct to the air return inlet of the indoor unit. The
other end connects to the air return shutter. as shown in Fig.2.
air return
shutter
air return
duct
Fig2: Duct return connected
indoor unit
rivet
3. Air duct insulation
Insulation layer is needed for air supply and return duct. First, paste a glue nail to the
air duct, and then attach the insulation cotton that has a tinfoil layer and use the glue
nail cover to fix. Finally, seal the air duct interface with tinfoil adhesive tape closely.
as shown in Fig3.
galvanized
board
insulating
fabric
glue nail
tinfoil
glue nail cover
adhesive tape
Installing the suspension screw:
Use M8 or M10 suspension screws (4, prepared in the field) (when the suspension screw
height exceeds 0.9 m, M10 size is the only choice). These screws shall be installed as
follows with space adapting to air conditioner overall dimensions according to the original
building structures.
Wooden structure
A square wood shall be supported by the beams and then set the suspension screws.
Square wood
Suspension
screw
Beam
New concrete slab
To set with embedded parts, foundation bolts etc.
Page 43
Iron reinforcement
Foundation bolt
Knife embedded part
Guide plate embedded partPipe suspension foundation bolt
Original concrete slab
Use hole hinge, hole plunger or hole bolt.
Steel reinforcement structure
Use steel angle or new support steel angle directly.
Suspension screw
Hanging bolt
Support steel angle
Hanging of the indoor unit
l Fasten the nut on the suspension screw and then hang the suspension screw in the T
slot of the suspension part of the unit.
l Aided with a level meter, adjust level of the unit within 5 mm.
Page 44
Installation of remote controller
1. Remove upper cover of wire controller
Remove upper part of wire controller
by press.
PCB is mounted on lower part of wire
controller, be careful not to damage it.
2. Install the wired remote controller
Please drill two holes on the wall according to the
back cover screw hole position of the wire remote
controller, then strike the wood block to the holes
respectively, then align the 2 screw hole of the wire
controller back cover to the wood block, fasten the
wire reote controller to the wall use wood screws.
3. Switch setting
The switchs setting as follows:1.ON 2.OFF 3.ON 4.OFF
Note
Try as far as possible a flat surface for installation.
Don't use excessive force when tightening screws,
or lower part might got deformed.
4. Connecting method as the following chart
Upper cover of wire
controller
Lower cover of wire
controller
Switch button
Screw hole
No
1
4
2
3
Symbol
A
B
C
D
colour
White or Green
Red
Yellow
contents
12V
Gnd
COM
Use shielede wires for telecommunication
between wire controller and indoor unit;
indoor unit and outdoor unit. Ground the
shield on one side.
Otherwise misoperation because of noise
may occur.
Signal wire is self-provided by user.
5. Replace the upper cover of wire controller
Be careful not to hold down the wiring.
Hint
1. Power supply switch and signal wire should be prepaired by the user.
2. Don't touch PCB with hand.
Back cover of the wire
controller
Shielded wire
ground
Page 45
In order to drain water normally, the drain pipe shall be processed as specified in
the installation manual and shall be thermal insulated to avoid dew generation.
Improper hose connection may cause indoor water leakage.
Requirements
The indoor drain pipe shall be thermal insulated.
The connection part between the drain pipe and the indoor unit shall be insulated so as to
! Caution
prevent dew generation.
The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be
of S type elbow, otherwise abnormal sound will be produced.
The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5 ñ 2m to prevent wavy form.
Central piping shall be laid out according to the following figure.
Take care not to apply external force onto the drain pipe connection part.
Drain pipe
1.5m~2m
Insulation
(supplied by the user)
To the largest (app. 10cm)
Down slope above 1/100
Down slope
above 1/100
VP30
Support
S type elbow
Pipe and insulation material
Pipe
Insulation
Rigid PVC pipe VP31.5mm (internal diameter)
Foamed PE with thickness above 7mm
Hose
Drain pipe size: ÿ19.05mm2 (3/4") PVC pipe
The hose is used for adjusting the off-center and angle of the rigid PVC pipe.
Directly stretch the hose to install without making any deformation.
The soft end of the hose must be fastened with a hose clamp.
Please apply the hose on horizontal part
HoseHose clamp
sulation treatment:
Wrap the hose and its clamp until to the
indoor unit without any clearance with
insulating material, as shown in the figure.
Wall
Outside
Slant
Drain pipe (supplied
by the user)
Drain confirmation
Subsidiary insulation
Insulation
Rigid PVC pipe
During trial run, check that there is no leakage at the pipe connection part during water
draining even in winter.
Page 46
Installation Procedure
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached
with the outdoor unit for details.
Pipe material and size
Refrigerant piping
Pipe material
Model
Pipe size
(mm)
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter
for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor
fault. The amount of the added refrigerant shall be as specified
in the instructions.
Connection of refrigerant pipe
Conduct flared connection work to
connect all refrigerant pipes.
Phosphorus deoxidized copper seamless pipe (TP2M) for air conditioner
AE092XCBAA
12.7
6.35
Gas side
Liquid side
AE072XCBAA
12.7
6.35
A
Pipe expander
1. Pipe cutting 2. Removing burrs
Pipe cutting and expanding
If the pipe is too long or the flare is damaged,
it needs to be cut or expanded.
3.Insertion nut 4. Pipe expansion
Pipe expansion dimensions as follows:
Pipe diameter ÿ Size A (mm)
6.35 mm (1/4") 0.8 ~ 1.5
9.52 mm (3/8") 1.0 ~ 1.8
12.7 mm (1/2") 1.2 ~ 2.0
15.88 mm (5/8") 1.4 ~2.2
Correct
Slope Damage Bur Partial Overlong
Incorrect
AE122XCBAA
12.7
6.35
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe
O.D.(mm)
6.35
9.52
12.70
15.88
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
Increased installing
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
Double-spanner
operation
Page 47
Installation Procedure
Vacuum pumping
With a vacuum pump, create vacuum from the stop valve of the outdoor unit.
l Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all valves
Open all the valves on the outdoor unit.
Gas leakage detection
Check with a leakage detector or soap water that if there is gas leakage at the pipe
connections and bonnets.
Insulation treatment
Conduct insulation treatment on both the gas side and liquid side of pipes respectively.
During cooling operation, both the liquid and gas sides are cold and thus shall be insulated
so as to avoid dew generation.
l The insulating material at gas side shall be resistant to a temperature above 120*.
l The indoor unit pipe connection part shall be insulated.
Refrigerant piping
Indoor unit
The notch upward (Attached detail view)
Field piping side
Subsidiary insulation tube
Page 48
Installation Procedure
Electric wiring
! Warning
The electric wiring work shall be conducted by qualified electricians according to the installation
instructions. A separate power circuit shall be used. Insufficient power cord amperage or improper
wiring will cause danger of electric shock or fire.
During wiring connection, the power cord shall be of the specified cable and reliably fastened
so that external forces applied to the cable wouldnt transfer to the terminals. Improper connection
or fastening will cause danger of heating, fire etc.The power cord must be fitted with a grounding
wire.
Grounding shall be made as specified. Unreliable grounding will cause electric shock. The
grounding wire shall not be connected to the gas pipeline, water pipeline, thunder arrestor and
telephone wire
! Caution
A current leakage breaker shall be installed, otherwise it electric shock would happen easily.
If the power cord is damaged, it must be replaced by the manufacturer or its service center or
similar personnel to avoid risks. The power supply to the indoor unit shall be laid in complying
with the operational instruction manual.
The electric wiring shall avoid contacting with the high temperature part of the piping so as to
prevent the cable insulation melts and cause dangers.
After connected on the terminal block, the wires shall be bent to U form and then fastened with
wire clip.
The control wiring and refrigerant piping may be laid and fastened together.
Before completion of vacuum pumping of the refrigerant pipe system, do not electrify the indoor
unit.
The power cord of the indoor unit and connection wiring between indoor and outdoor units
shall be laid out according to the operational instruction manual of the indoor unit.
The connection of the power cord shall comply with the local regulations.
The power supply wiring connection should meet the local regulation.
!
!
Wiring connection method : (the wiring diagram is attached inside the machine)
1) Ring terminal connection method
If there is a ring at the end of the connection wire,
the wire connection method is as shown in the right
figure. Remove the terminal screw and insert it
through the ring at the connection wire end, then
connect to the terminal board and fasten the screw.
2) Straight terminal connection method
If there isnt a ring at the end of the connection wire,
the connection method shall be: loosen the terminal
screw, insert the connection wire end completely into the terminal board and fasten the screw.
Pull the connection wire outwards slightly to confirm it is clamped tightly.
3) Clamping method of the connection wire
After wire connection is finished, the connection wire must be pressed tightly with wire clips,
which shall apply to the outer sheath of the connection wire.
Connection method
for ring terminal
Page 49
Wire connection for built-in indoor unit
Insert from outside the connection wire and signal transmission wire through the wall hole
with pipeline already arranged.
Pull out the front ends of connection wire and signal wire and make a circle on the signal
wire.
Connect the connection wire according to the connection method and indoor and outdoor
wiring diagram.
Pull the connecting conductor outwards slightly to confirm it is clamped tightly.
Connect the plug for connecting the signal wire with the plug of the signal wire connected
from the indoor unit.
After wire connection is finished, install wire clips using the same method for connection
wire clamping.
Note: When connecting the indoor unit and the outdoor unit, please do connect the wir es
with the same color terminals.
Notes:
Before connecting the conductors between indoor unit and outdoor unit, check for the number
on the indoor and outdoor units connecting terminals. Connect the terminals with the same
color and number with a wire.
Wrong connection would damage the controller of the air conditioner or the machine couldnt
operate.
Do not connect the connection wire and signal wire with the same cable. They shall be
connected respectively to ensure system normal operation.
Page 50
5.5 Installation of cassette type
Page 51
Page 52
Page 53
Page 54
Page 55
6. Parts and functions
6.1 Ou
tdoor unit
air outlet
air inlet
electric box
handle
valves
6.2 indoor unit
/
0
/-=A@;8@
1
0-7=<@?=; >6<8;
1-:<;8@
2
2-9:;@8? + DEFDBC ,
3-=A@;8@
3
Page 56
Cassette type Indoor unit
wall mounted type Indoor unit
Swing louver
(Air flow direction can be adjusted by using
the SWING button on the remote controller)
Electrical control box
Air Inlet Grille
Air Filter (Inside of the Inlet Grille)
signal receiver window
Fresh air conditioner
Haier
air outlet grille
ceiling concealed type Indoor unit
motor inside
electric control box
louver
fan inside
air inlet grille
air filter(inside)
air duct
evaporator
Page 57
7.Remote controller functions
Remote controller
29
30
31
32
33
34
35
36
1
2
3
4
5
6
7
8
9
SWING
RESET
M D
MODE
HEALTH
CLOCK
TIMER
FILTER
CODE
A
U
T
O
OFF
TEMP
ON
OFF
FRESH
LIGHT
SLEEP
HIGH/SO
LOCK
SET
4.Operation MODE
28
B
A
FAN
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
Used to select operation mode.
Every time you press MODE button, operation mode
changes according to following sequence:
AUTO
COOL
DRY
HEAT
FAN
5.HEALTH Button
Used to set health mode, if the unit has the negative ion function
and oxygen bar function.
6.CLOCK Button
Used to set correct time.
7.CLOCK Button
Used to select TIMER ON, TIMER OFF.
(Note: if time of TIMER ON is the same as TIMER
OFF ,TIMER ON/OFF cannot be set)
8. FILTER Button
Used to set up/down function of filter.
9. CODE Button
Used to select code A or B, for this unit, the code is A.
10
1.TEMP Setting Button
(Used to set temperature. Setting ranges:
16 C to 30 C)
In Up/Down function, for controlling up and
down filter.
2.SWING Button
If you press this button once, auto swing will
be activated.
If you press this button again, the louver will
fix in the present position.
3.Power ON/OFF Button
Used for unit start and stop
After power on, the LCD of remote controller
will display the previous operation state (except
for TIMER,SLEEP and SWING state).
10.RESET Button
Press this button by using a sharp article to resume
the correct operation of the remote controller in case
of need, i.e. for example in case of malfunctions due
to electromagnetic noise.
11.LOCK Button
Used to lock operation button and LCD display
contents: by pressing this button, other buttons comes
out of function and lock state display appears; if you press
it again, lock state will be no more active and lock state
display will disappear.
12.LIGHT Button
Used to light the control panel (only for cabinet unit)
13.Up and down Button
Used to set TIMER and CLOCK up or down.
14.HIGH/SO Button
Used to select HIGH or SOFT operation.
15.SET Button
Used to confirm TIMER and CLOCK settings.
16.FRESH Button
Used to set fresh mode, the unit will draw in fresh air.
17.SLEEP Button
(The clock must be corrected before setting sleep
function)
Used to set sleep mode.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating.
2.HIGH/SO button
This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high
functon" will be cancelled automatically after 15 minutes running.
Page 58
18.FAN Button
Used to select fan speed:LOW,MID,HIGH,AUTO.
19.TIMER OFF Display
20.CLOCK Display
21.FILTER Display
22.TEMPERATURE Display
23.AUTO SWING Display
24.HIGH/SO Display
25.SIGNAL SENDING Display
26.FRESH AIR Display
27.ELECTRICAL HEATING Display
28.Some other buttons
All these functions are not available now.
29.HEALTH Display
Displays when healthy run function is set.
30.DEHUMIDIFICATION Display
31.Operation MODE Display
AUTO RUN
COOL RUN
DRY RUN
HEAT RUN
FAN RUN
32.SLEEP State Display
33.BATTERY Energy Display
Notify the user when it is time to change
the batteries.
34.LOCK State Display
35.FAN SPEED Display
LO
MID
The distance between the remote controller and the receiver
should be max 7m and there should be no obstacle between them.
Do not throw the remote controller; prevent it from being
damaged.
When operating the remote controller in an area where
electronically controlled lights are installed or wireless handsets
are used, please move closer to the indoor unit as the function
of the remote controller might be affected by signals emitted
by the above mentioned equipments.
Battery loading
Battery loading
Batteries are fitted as follows:
Remove the battery compartment lid
Slightly press and disengage the battery compartment lid marked
with ì
section and then remove the battery compartment lid by pressing
in the direction of the arrow as shown in the figure above.
î and then hold the remote controller by the upper
Loading the battery
Ensure that batteries are correctly placed in the compartment
as required for positive and negative terminals.
Replacing the battery compartment lid
The battery compartment lid is reinstalled in the reverse
sequence.
Display review
Press the button to see if batteries are properly fitted. If
no display appears, refit the batteries.
Confirmation indicator
If no indication is displayed after press ON/OFF button,
reload the batteries.
Caution:
* *
* *
HI
AUTO
AUTO
If the remote controller does not operate as designed after
fitting new batteries of the same
type, press the Reset button (marked ) with a pointed article.
Note:
36.TIMER ON Display
Remote Controller' Operation
When in use, direct signal transmission
head to the receiver placed on the indoor
unit
It is recommended that the batteries be removed from the
compartment if the remote controller is not used for an extended
period.
The remote controller is programmed for automatic test of
operation mode after the batteries are replaced. When the test
is conducted, all icons will appear on the screen and then
disappear if the batteries are properly fitted.
Clock Set
When unit is started for the first time and after replacing batteries in remote
controller, clock should be adjusted as follows:
1.Press CLOCK button, clock indication of " AM " or " PM " flashes.
2.Press or to set correct time. Each press will increase or decrease
1 min. If the button is kept pressed, time will increase or decrease quickly.
3.After time setting is confirmed, press "SET" : AM or PM stop flashing,
while clock starts working.
Note:AM means morning and PM means afternoon.
1
RESET
HEALTH
CLOCK
TIMER
FILTER
CODE
FRESH
2
LIGHT
SLEEPMODE
SET
HIGH/SO
LOCK
3
Page 59
Fan Operation
1.Unit start
Press ON/OFF button to start your air conditioner.
Previous operation status appears on LCD (except for
TIMER, SLEEP, and SWING setting).
2.Select operating mode
Press MODE button. At each press, operation mode
changes as follows:
A
SWING
MODE
HEALTH
2
CLOCK
TIMER
FILTER
RESET
4
CODE
A
U
T
O
TEMP
ON
OFF
FRESH
1
LIGHT
FAN
SLEEP
SET
HIGH/SO
LOCK
AUTO
FANHEATCOOLDRY
Then select FAN
3. Adjust fan speed
Press FAN button. At each press, fan speed changes as
3
follows:
LOW
MID
HIGH
Air conditioner will run at the selected fan speed.
When in AUTO mode, unit will adjust fan speed
according to room temperature automatically.
4. Unit stop
Press ON/OFF button to stop unit.
About FAN mode
When the air conditioner runs in F AN mode,
it is not possible to select AUTO FAN or to
set temperature.
Page 60
AUTO, COOL , HEAT and DRY Operation
3
SWING
MODE
HEALTH
2
CLOCK
TIMER
FILTER
RESET
5
CODE
A
U
T
O
TEMP
ON
OFF
FRESH
LIGHT
1
SLEEP
HIGH/SO
LOCK
SET
A
FAN
4
1. Unit start
Press ON/OFF button,unit starts.
Previous operation status appears on LCD (except for TIMER,
SLEEP and SWING setting)
2.Select operation mode
Press MODE button. At each press, operation mode changes
as follows:
3
AUTO
FANHEATCOOLDRY
Then select AUTO run or select COOL operation or
select DRY operation or select HEAT operation
3.T emperature setting
Press TEMP button.
Every time the button is pressed, temp. setting increases
1 C; if the button is kept pressed, temp. setting will increase
quickly .
Every time the button is pressed, temp. setting decreases
1 C, if the button is kept pressed, temp. setting will decrease
quickly .
Set proper temperature
4.Adjust FAN button
Press F AN button. At each press, fan speed changes as follows:
A
U
T
O
COOL operation starts
when room temp.is
higher than temp.
setting.
Temp. setting +2 C
Temp.setting
Ultra-low air flow
On reaching temp.setting
+2 C, unit will run in mild
DRY mode.
AUTO
Air conditioner will run at the selected fan speed.
5. Unit stop
Press ON/OFF button,unit stops.
LOW
In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner
will select COOL, HEAT or F AN mode automatically according to the room temperature.
In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently
at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will
only run F AN operation.
In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.
MIDHIGH
Page 61
Adjusting air flow direction
AUTO SWING
Press SWING button.
Up and down airflow varies upwards
and downwards. Left and right airflow
varies left and right sides.
A
A
U
T
O
TEMP
ON
SWING
OFF
MODE
FAN
SLEEP
AUTO SWING
When the automatic swing louver moves to the proper
angle, press SWING button can fix the airflow direction.
Always use SWING button on the remote
controller to adjust flaps. Adjusting them by hand
may result in air conditioner's abnormally running.
In COOL or DRY mode, do not leave the louver in
downward position for a long time, as the water
vapor close to the grille may condense and water
may drop from the air conditioner.
Please carefully set temperature when children,
old or infirm people ues the air conditioner.
FRESH
HEALTH
LIGHT
SET
HIGH/SO
LOCK
In case of great humidity, If the vertical flaps
are completely turned towards left or right, the
louver will drop water.
Never adjust the louver directly by hand, as this
CLOCK
TIMER
FILTER
RESET
CODE
could make it work abnormally .If the louver work
abnormally , stop unit, restart and adjust the louver
by remote controller.
After unit stops:
Displays on the LCD disappear.
All indicators on the indoor unit go out.
Swing louver automatically close the air outlet.
Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful
for a better air circulation
As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for
a better air circulation.
Be careful not to catch a cold when cold air blows downward directly.
Page 62
Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make
you sleep more comfortably.
Before using this function, the clock must be set.
Use of SLEEP function
After the unit's start, set running mode and then press SLEEP button once to make the air conditioner
have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button
/ : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1
hour: "xh" and "OFF" indications appear on the display.
Operation Mode
1.In COOL, DRY mode
One hour after sleeping operation start, the temperature
is 1 C higher than the setting one. After another hour,
temperature rises 1 C: sleep run continuously for another
6 hours and then stops. The actual temperature is higher
than the setting one which is to prevent from being too
cold to your sleep.
2.In HEAT mode
One hour after sleeping operation start, the temperature
is 2 C lower than the setting one. After another hour,
temperature decreases by 2 C more. Temperature will
automatically rise by 1 C after another 3 hours'
continuous operation. The actual temperature is lower
than the setting one which is to prevent from being too
hot to your sleep.
3.In AUTO mode.
The air conditioner will run in corresponding sleep
operation according to the automatically selected
operation mode.
SLEEP RUN BEGINS
1 hrs
SETTING T
In COOL,DRY mode
SETTING T
1 hrs
1 hrs
SLEEP RUN BEGINS
In HEAT mode
SLEEP RUN STOPS
about 6 hrs
increase 1 C
increase 1 C
decrease 2 C
decrease 2 C
about 6 hrs
3 hrs
SLEEP RUN STOPS
SHUT DOWN
SHUT DOWN
increase 1 C
Notes:
After setting SLEEP function, it is not possible to set clock.
If set-sleep time does not reach 8 hours, unit will automatically stop operation
after set time is reached.
Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first,
then set SLEEP. After set SLEEP function, the TIMER function cannot be
set.
SWING
RESET
MODE
HEALTH
CLOCK
TIMER
FILTER
A
A
U
T
O
OFF
TEMP
ON
OFF
FAN
SLEEP
FRESH
SET
HIGH/SO
LOCK
LIGHT
CODE
Page 63
Timer ON/OFF Function
Set clock correctly before starting TIMER operation
1.Unit start
A
After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:
SWING
MODE
HEALTH
CLOCK
TIMER
2
FILTER
RESET
CODE
TEMP
ON
OFF
FRESH
LIGHT
1
3
FAN
SLEEP
SET
HIGH/SO
LOCK
ONOFFONOFF
AM
12:00
TIMER ON
PM
12:00
TIMER OFF
AM
12:00
TIMER ON-OFF
PM
12:00
blank
Then select TIMER mode as needed (TIMER ON or TIMER OFF).
Now or will flash.
ON
OFF
3.TIMER setting (press time adjust buttons )
Every time the button is pressed, time increases 10 minuts.
If the button is kept pressed, time changes quickly.
4
Every time the button is pressed, time decreases 10 minuts.
If the button is kept pressed, time changes quickly.
It can be adjusted within 24 hours at will.
4.Confirm setting
After setting correct time, press SET button to confirm time. Now
or stop flashing.
ON
OFF
Time displayed: unit starts or stops at X hour X min (TIMER ON
or TIMER OFF)
5.Cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
Hints:
After replacing batteries or if a power failure occurs, TIMER setting
must be reset.
Remote controller has memory function. When you use TIMER
mode next time, just press SET button after mode selection if timer
setting is the same as the previous one.
Note:
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time,
just press CLOCK button once: clock time will be displayed (if you press the button again continuously ,you
can adjust clock). 5 seconds later, the display will show TIMER time again.
Page 64
Timer ON-OFF Function
Set clock correctly before starting TIMER operation
1.Unit start
After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
SWING
2
MODE
HEALTH
CLOCK
TIMER
FILTER
4
RESET
5
CODE
OFF
TEMP
ON
OFF
FRESH
LIGHT
1
SLEEP
HIGH/SO
3
SET
LOCK
A
FAN
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:
ONOFFONOFF
AM
12:00
TIMER ON
PM
12:00
TIMER OFF
AM
12:00
Then select TIMER ON-OFF mode.
PM
12:00
TIMER ON-OFF
ON
will flash.
blank
3.Time setting for TIMER ON
Press time button
Every time the button is pressed, time increases 10 minuts.
If the button is kept pressed, time will changes quickly.
Every time the button is pressed, time decreases 10 minuts.
6
If the button is kept pressed ,time will changes quickly.
It can be adjusted within 24 hours at will.
AM refers to morning and PM refers to afternoon.
4.Timer confirming for TIMER ON
After setting correct time, press TIMER button to confirm time. Now
stops to flash, while
ON
starts flashing.
OFF
Time displayed : unit starts at X hour X min.
5.Timer setting for TIMER OFF
Press time buttons and follow the same procedures in " Time setting
for TIMER ON"
6.Time confirming for TIMER OFF
After time setting, press SET button to confirm time.
Time displayed: unit starts at X hour X min.
stops to flash.
OFF
7.Canel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
According to the time setting sequence of TIMER ON and TIMER OFF,
either start-stops or stops-start can be realized.
If the time setting of TIMER ON is the same as TIMER OFF, TIMER
ON-OFF function cannot be set.
Page 65
Filter Up/Down
(Only for 600*600panel)
A
After the air conditioner has operated for a certain period, dust has
accumulated on the filter, and the filter up/down function can be used
to clean it.
1.Whether unit starts or stops, continuously press FILTER
button for 3 seconds, and enter the filter up/down waiting
status (when unit stops, the yellow TIMER indicator flashes,
and filter and clock indication are displayed on the remote
controller . Only the FILTER button, the temperature buttons
" " " " and time buttons are active).
SWING
MODE
HEALTH
CLOCK
TIMER
FILTER
RESET
CODE
1
TEMP
ON
OFF
FRESH
LIGHT
FAN
SLEEP
SET
HIGH/SO
LOCK
2.Press temperature button or time button in filter
" "
" "
up/down waiting status: the up/down mechanism makes
the filter moving downward and does not stop until it has
reached the maximum limit.
3.Press temperature button or time button in filter
" "
" "
up/down waiting status: the up/down mechanism makes
the filter to moving upward till near the surface board and
then automatically adjusts it to reset (when adjusting to reset,
it will not be controlled by the remote controller till the adju stment is finished).
4.During moving downward, press temperature button
or time button: moving stops.
" "
5.During moving downward, press temperature button
or time button: moving stops.
" "
" "
" "
6.Continuously press FILTER button 3 seconds again to
cancel the filter up/down waiting mode (unit stops, the
yellow timer indicator stops flashing, the filter goes back to
the original position, the remote controller goes back to off
status and only clock is displayed).
Note:
If the filter does not thoroughly go back to the original position, only needs to
operate several times repeatedly.
Page 66
Auto restart function setting
A
A
U
T
O
TEMP
ON
SWING
OFF
FAN
FRESH
LIGHT
SLEEP
SET
HIGH/SO
LOCK
:
MODE
HEALTH
CLOCK
TIMER
FILTER
RESET
CODE
Setting method (to be applied for a necessary situation)
After the power failure compensation is set, if power failure suddenly occurs while the air conditioner
is working, it will resume the previous working state when the power is supplied again.
Setting Method: When the remote controller is on (excluding timer mode and fan mode),
press the "Sleeping" button on the remote controller 10 times within 5
seconds, and after the buzzer rings 4 times, the air conditioner will enter
the state of power failure compensation.
Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5
seconds, and after the buzzer rings 2 timer, the power failure compensation
mode will be cancelled.
Notes: When a power failure suddenly occurs during the air conditioner is working after the power
failure compensation is set, if the air conditioner will not be used for a long time, please cut off the
power supply to prevent its operation from being resumed after the power is supplied again, or press
the "Switch On/Off" button after the power comes again.
Page 67
Wired controller YR-E12 functions:
Buttons and functions of the wired controller
CLOCK
Used to adjust time.
TIMER
Used to set timer
mode.
CHECK
Auto-diagnostic
button.
+ -
stands for time plus/minus,
used to adjust time.
FILTER
Filter-cleaned button.
MODE
Used for select
indoor operation
mode.
FAN SPEED
Used for select indoor
air flow.
SWING
Used for setting
indoor swing mode.
HEALTH
HEALTH
C
F
SETRECOVERY
CHECK
Used for setting
indoor health
function.
TEMP + -
Used for changing
set temperature.
RECOVERY
used to switch
over airexchanging mode.
POWER ON/OFF
Used for unit start and
stop.
Cautions:
On cooling only unit, heating
mode is not available.
RESET
Reset correct
mode button.
Note:
The above information is the explanation of
the displayed information therefore varies
with those displayed in actual operation.
Page 68
Buttons function:
MODE:used for select indoor operation mode.
FAN:used for select indoor air flow.
SWING:used for setting indoor swing mode.
HEALTH:used for setting indoor health function.
TEMP + -:used for changing set temperature.
CLOCK:used to adjust time.
+、-:stands for time plus/minus, used to adjust time.
TIMER:used to set timer mode.
RECOVERY:used to switch over air-exchanging mode.
CHECK:auto-diagnostic button.
FILTER:filter-cleaned button.
RESET:reset correct mode button.
Display description:
[MODE] [AUTO]:auto operation mode
[MODE] [FAN ONLY]:air-throwing mode
[MODE] [COOL]:Cooling operation mode
[MODE] [DRY]:Dehumidification mode
[MODE] [HEAT]:Heating operation mode
[MODE] [HEAT] [TES]:In heating mode, auxiliary electric heater is running. Only when the
unit with auxiliary electric heater is in auxiliary electric heating mode, it will display.
[FAN] [AUTO]:auto fan running
Page 69
[FAN] [HIGH]:high fan speed
[FAN] [MED]: medium fan speed
[FAN] [LOW]: low fan speed
[FAN] [FIX]: fixed fan speed, it will display only when fixed fan speed is requested to main
indoor unit.
[CENTRAL]: central control mode
[OPERATION] :running mode
[STAND BY] : waiting mode
[PRE-HEAT] : pre-heating mode
[DEFROST]: defrosting mode
[FILTER] : request of filter to be cleaned
[HEALTH]:health function
[UNIT NO.]
[CEN.ADD]:central control address, the address number will display on “88”
[SYS.ADD.]:system address, the address number will display on “88”
[CHECK]:auto-diagnostic, trouble shooting
[DEMAND]:compulsory operation function, when it works, [CENTRAL] will flash
[SWING]:swing mode
[ROOM TEMP.]:indoor ambient temperature
[SET TEMP.]:set admired temperature
[TIMER][ON] :timer function is on, it will switch over in the sequence below:
[ON][OFF] → [ON][OFF][DAILY] →[ ]
[TIMER][OFF] :timer function is off
[TIMER][ON][OFF] :timer function ON-OFF
[TIMER][ON][OFF][DAILY]:timer ON-OFF will switch over in turn daily
[CLOCK]:clock display, the displaying time is the current time of the clock.
[UP]、[DOWN]:indicator of filter elevating
[VENTILATION][AUTO]:auto ventilation mode
[VENTILATION][RECOVERY]:fully heat exchanging ventilation mode
[VENTILATION][NORMAL]:normal ventilation mode
FAN ONLY OPERATION:
1)Start up operation: press the button of ON/OFF, the system will start up, and will display
[MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”.
2) Select MODE: press the MODE button, then you will see in the display section [MODE]
switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→
[FAN ONLY]. Select [FAN ONLY].
3)Select fan speed: press FAN button, then you see in the display section [FAN] switch over
in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed.
4)Power off: press ON/OFF button, indoor unit will be powered off, there are only time and
the ambient temperature in the screen.
Page 70
AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation
1) Start up operation: press the button of ON/OFF, the system will start up, and will display
[MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”.
2) Select MODE: press the MODE button, then you will see in the display section [MODE]
switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN
ONLY]. Select [FAN ONLY].
3) Change set temperature: press TEMP + or – every time, [SET] will display, and set
temperature will increase/reduce 1℃(F).
4) Select fan speed: press FAN button, then you see in the display section [FAN] switch over
in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed.
5) Select [SWING]: press [SWING] button, swing function is valid. Press again, swing
function is invalid.
6) Set [HEALTH]: used to set the indoor health function. Press it once, [HEALTH] will display
in the display section, then indoor health function is valid. Press it again, [HEALTH] will
disappear, then the health function is invalid.
This function is valid only for the unit with health function.
7) Power off: press ON/OFF button, indoor unit is powered off. There are only time and the
ambient temperature in the screen.
Set TIMER operation:
Adjust clock: when powered on, for the first time to set timer function, the clock will be
adjusted.
Press “CLOCK” button, and set the current clock. Now, “CLOCK” will flash at the frequency
of 2Hz every minute. Press the clock +/- button; the current clock can be adjusted. Until the
proper time comes, press [SET].
TIMER ON operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in
below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER]
[ON], then [TIMER] [ON] flashes, press the clock +/- button to adjust the time of TIMER ON,
press [SET] button.
TIMER OFF operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in
below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER]
[OFF], then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER
OFF, press [SET] button.
TIMER ON-OFF operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in
below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER]
[ON] [OFF]. Firstly, [TIMER][ON] flashes, press the clock +/- button to adjust the time of
Page 71
TIMER ON, press [TIMER]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes,
press the clock +/- button to adjust the time of TIMER OFF, press [SET]. The time sequence
of timer on and timer off will determine the mode is [TIMER] [ON] →[OFF] or [TIMER] [OFF]
→[ON]. If you want the current time, press [CLOCK] once, current time will display; press
again, [CLOCK] will flash, and press [+][-] to adjust the time.
Note: 1. If the two times are same, the timer state which is set later will flash, in this case,
timer can not be set.
2. When entering TIMER setting state, if you do not input any button in continuous 10
seconds, the unit will quit from the TIMER mode.
Cancel TIMER operation:
In the timer operation state, press [TIMER] button, the unit will quit from the current timer
operation state, and the set data will be memorized, then enter the next timer mode.
[FILTER] function
When the wired controller receives the filter-cleaned signal from indoor unit, [FILTER] will
display. After finishing clean, press [FILTER], the sign [FILTER] disappears, and the
controller will send the filter reset signal to indoor unit.
When the sign [FILTER] not display, it is invalid to press [FILTER] in short time.
FILTER ELEVATING function: (only for the unit with elevating function)
When the filter needs to be cleaned, the panel can be lowered to the admired height by the
[FILTER][UP][DOWN] function. Method is below: In power off state, press [HEALTH] for 15
seconds to enter filter elevating set state. In this state, the sign [FILTER] will flash and [UP]
[DOWN] will display simultaneously, Press TEMP [+], in timer section [UP] will display, while
press TEMP [-], in timer section [DOWN] will display. When it arrives the appropriate position,
press [UP], [UP][DOWN] will display simultaneously, filter will stop going down. Press [UP]
again, filter will go up. Press [FILTER] button to quit the mode.
DEMAND operation function:
By this function, all the indoor units can be made in nominal mode. Set the operation mode
in cooling and then shut off the unit. In the stop state, press [ON/OFF] button for 5 seconds
to enter cooling trial operation state. If it is in heating mode before shut off the unit, then
press [ON/OFF] button for 5 minutes, it will enter heating trial operation state.
In cooling, there will be “LL” in the position where the set temperature displays. In heating,
there will be “HH” in the position where the set temperature displays. The wired controller
will send the [DEMAND] signal to indoor unit. In the [DEMAND] operation, “COOL” or
“HEAT” will display at 1Hz frequency. Indoor fan motor will be fixed at “AUTO” mode. The
indoor units in the same group will quit the [DEMAND] in turn.
At this time, only the buttons of [ON/OFF] and temperature [+] [-] are valid. Press [ON/OFF]
to quit [DEMAND] mode.
Page 72
CENTRAL control function
When the central controller selects [CENTRAL] mode, the buttons in the wired controller
except for [CHECK] will be invalid.
VENTILATION mode (only for the unit with fresh air function or heat recovery
function)
Press [RECOVERY] button, then the unit will switch over the ventilation mode:
[ ]→[VENTILATION][AUTO]→[VENTILATION][RECOVERY] →
[VENTALATION][NORMAL] →[ ], please select appropriate ventilation mode.
Query indoor malfunction history:
In the state of power on or power off, press [CHECK] button, enter the malfunction-querying
mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the
actual indoor numbers will be displayed in some sequence (unit number is in decimals). At
the same time, in the time region, there will be the current malfunction and the latest time
malfunction, the displaying format is [XX:YY], in which XX stands for the current malfunction,
if normal, it will display “――”; YY stands for the latest time malfunction. The failure code of
every unit will display for 3 seconds. After the failure codes of all indoor units in the whole
group are displayed, the mode will quit automatically.
Clear abnormal state and malfunction history:
In normal state, press [CHECK] button for 5 seconds to clear abnormal states, at the same
time, wired controller will send the data of “clear abnormal state”, but the malfunction history
still retains.
In normal state, press [CHECK] button for 15 seconds, except for malfunction states, the
malfunction history in wired controller will be cleared.
Query indoor performance state:
In normal state, press both buttons of [CHECK] and [FILTER] for 5 seconds, in the set
temperature region in the screen, [XX] will display, XX is indoor number, which can be
selected by pressing [TEMP] [+] [-]. In the timer region in the screen, [YZZZ] will display, in
which Y stands for data type, ZZZ stands for the corresponding data. which can be selected
by pressing [CLOCK] [+] [-].
Y ZZZ Type
A Indoor capacity (W) Nominal cooling
capacity/10, decimal
B Request of indoor capacity(Hz)Actual value, decimal
C Temperature of indoor ambient
temp. sensor TA
d Temperature of indoor gas pipe
sensor TC1
E Temperature of indoor liquid pipe
sensor TC2
F Open degree of indoor PMV Actual value, decimal
Actual value, decimal
Actual value, decimal
Actual value, decimal
Page 73
g Preset ―――
H Outdoor total capacity Actual value, decimal
In check mode, press [CHECK] to quit the check mode, and go into normal running
mode.
How to change the function switches?
No. Type State of
Function description
switch
J01
J02
J06
J07
J03
SW01
①
SW01
②
D1
D2
Changeover of Wired
controller and central
controller
Changeover of type of
wired controller
Selection of room temp.
sensor
Auto restart after power
failure
Display of room
temperature
Changeover of master or
slave controller
℃ or ℉
Shorten time function
Compulsorily defrost
Connected Central controller
Cut off Wired controller
Connected Set as simple controller
Cut off Set as standard controller
Connected Use the sensor in the wired
controller
Cut off Use the sensor in the indoor unit
Connected Common control
Cut off Auto restart after power failure
Connected Yes
Cut off No
ON Set as slave controller
OFF Set as master controller
ON
OFF
Connected Indoor unit in shorted time
Cut off Common control
Connected Send compulsorily defrost signal
Cut off Common control
℉
℃
function
to indoor unit
Note: 1. The switches in grey can be operated after opening the cover of wired controller.
2. Switches or jumper wire must be adjusted when the wired controller is powered off. If the
wired controller is powered on, the above operations will be invalid.
3. Shorten time function
In normal operation, D1 is in short circuit, it will enter shorten time mode, and the time will be
shortened in the proportion of 60:1. In shorten time mode, LED will flash at the frequency of
0.5 second. Cut off D1, it will quit the shorten time mode and return to the normal operation
mode.
4. Compulsorily defrost
In heating mode, D2 is in short circuit, it will enter compulsorily defrost mode; cut off D2, it
will quit.
5. Lock function
There is no lock function only in the wired controller. But when it is connected with a central
Page 74
controller, if the central controller is set to “central”, the buttons in the wired controller will be
invalid, or the buttons will be valid.
Failure code:
For
remote
type,
flash
times
10 08(08H) 21D Drainage system
1 01(01H) 01D Indoor ambient temp.
2 02(02H) 02D Indoor coil temp.
3 74(4AH) 11D Outdoor ambient
4 73(49H) 12D Outdoor coil temp.
572(48H)10DOver-current
6 83(53H) 14D High pressure
7 71(47H) 22D Power supply
8 07(07H) 06D Communication
9 06(06H) 05D Communication
11 11(0BH) 30D Outside alarm signal
12 03(03H) 20D Gas pipe temp.
Failure
code on
wired
controller
For
central
control,
failure
code
Failure description Reason Remarks
Float switch broken down
abnormal
sensor failure
sensor failure
temp. sensor failure
sensor failure
(compressor
discharging temp.
sensor)
protection
abnormal
abnormal
between wired
controller and indoor
abnormal
between indoor and
outdoor abnormal
input
sensor abnormal
for more than 25m
continuously
sensor broken down or
short circuit for more than
2m continuously
sensor broken down or
short circuit for more than
2m continuously
sensor broken down or
short circuit for more than
2m continuously
Sensor broken down or
short circuit for more than
2m continuously
CT check abnormal 3 times
in 30m
High pressure switch acts 3
times in 30m
Fault phase, short of
phase, out of balance
greatly
Communication abnormal
for more than 4m
continuously
Communication abnormal
for more than 4m
continuously
Outside signal broken
down for more than 10s
Sensor broken down or
short circuit for more than
○
○
○
○
○
※
※
※
○
○
○
○
Page 75
2m continuously
13 13(0DH) 31D Solenoid valve
abnormal
14 76(4CH) 15D Discharging temp.
sensor abnormal
15 05(05H) 17D EEPROM abnormal EEPROM data missing Run as the
16 84(54H) 26D Pressure
abnormal(low
pressure)
17
18
19
20
80(50H)
12(0CH)
75(4BH)
77(4DH)
15D Compressor overheatthe discharging
23D Abnormal mode Indoor operation mode is
18D Outdoor coil
B(suction temp
sensor—for MRV II)
15D Outdoor discharging
B(oil temp
sensor—for MRV II)
Solenoid valve act
incorrectly 3 times
continuously
Sensor broken down or
short circuit for more than
2m continuously
Low pressure switch acts in
normal running
temperature is higher than
120degree
different with the running
indoor unit.
Sensor broken down or
short circuit for more than
2m continuously
Sensor broken down or
short circuit for more than
2m continuously
○
○
default
value
○
Resumable
if lower
than
100degree
○
○
○
○ shows resumable fault, ※ shows it is not resumable fault.
Setting address method:
The address setting can be realized by setting indoor PCB.
If you use the group control function, there should be a master unit and 15 sets of slave units.
For the master unit, the SW5-3 should be at “1”. For the slave units, the SW5-3 should be at
“0”.
Please refer the below table,
Indoor
unit
SW1-4 SW1-3 SW1-2 SW1-1
address
1 OFF OFF OFF OFF
2 OFF OFF OFF ON
3 OFF OFF ON OFF
4 OFF OFF ON ON
5 OFF ON OFF OFF
6 OFF ON OFF ON
7 OFF ON ON OFF
Page 76
8 OFF ON ON ON
9 ON OFF OFF OFF
10 ON OFF OFF ON
11 ON OFF ON OFF
12 ON OFF ON ON
13 ON ON OFF OFF
14 ON ON OFF ON
15 ON ON ON OFF
16 ON ON ON ON
If you use central control type, SW1, SW2 will be used simultaneously.
Wiring request in central control type: port A-B is connected with indoor port CN16(A-B)
through 2-core shield wire. Requirements:
1. Port A connects with port CN16(A)of all indoor units.
2. Port B connects with port CN16(B)of all indoor units.
Address on
central
controller
1 1 ON OFF OFF OFF OFF OFF OFF
2 2 ON OFF OFF OFF OFF OFF ON
3 3 ON OFF OFF OFF OFF ON OFF
4 4 ON OFF OFF OFF OFF ON ON
5 5 ON OFF OFF OFF ON OFF OFF
6 6 ON OFF OFF OFF ON OFF ON
7 7 ON OFF OFF OFF ON ON OFF
8 8 ON OFF OFF OFF ON ON ON
9 9 ON OFF OFF ON OFF OFF OFF
10 10 ON OFF OFF ON OFF OFF ON
11 11 ON OFF OFF ON OFF ON OFF
12 12 ON OFF OFF ON OFF ON ON
13 13 ON OFF OFF ON ON OFF OFF
14 14 ON OFF OFF ON ON OFF ON
15 15 ON OFF OFF ON ON ON OFF
16 16 ON OFF OFF ON ON ON ON
17 -------- ON OFF ON OFF OFF OFF OFF
18 -------- ON OFF ON OFF OFF OFF ON
19 -------- ON OFF ON OFF OFF ON OFF
20 -------- ON OFF ON OFF OFF ON ON
21 -------- ON OFF ON OFF ON OFF OFF
22 -------- ON OFF ON OFF ON OFF ON
23 -------- ON OFF ON OFF ON ON OFF
24 -------- ON OFF ON OFF ON ON ON
25 -------- ON OFF ON ON OFF OFF OFF
Indoor unit
address
SW2-3 SW2-2 SW2-1 SW1-4 SW1-3 SW1-2 SW1-1
Page 77
26 -------- ON OFF ON ON OFF OFF ON
27 -------- ON OFF ON ON OFF ON OFF
28 -------- ON OFF ON ON OFF ON ON
29 -------- ON OFF ON ON ON OFF OFF
30 -------- ON OFF ON ON ON OFF ON
31 -------- ON OFF ON ON ON ON OFF
32 -------- ON OFF ON ON ON ON ON
33 -------- ON ON OFF OFF OFF OFF OFF
34 -------- ON ON OFF OFF OFF OFF ON
35 -------- ON ON OFF OFF OFF ON OFF
36 -------- ON ON OFF OFF OFF ON ON
37 -------- ON ON OFF OFF ON OFF OFF
38 -------- ON ON OFF OFF ON OFF ON
39 -------- ON ON OFF OFF ON ON OFF
40 -------- ON ON OFF OFF ON ON ON
41 -------- ON ON OFF ON OFF OFF OFF
42 -------- ON ON OFF ON OFF OFF ON
43 -------- ON ON OFF ON OFF ON OFF
44 -------- ON ON OFF ON OFF ON ON
45 -------- ON ON OFF ON ON OFF OFF
46 -------- ON ON OFF ON ON OFF ON
47 -------- ON ON OFF ON ON ON OFF
48 -------- ON ON OFF ON ON ON ON
49 -------- ON ON ON OFF OFF OFF OFF
50 -------- ON ON ON OFF OFF OFF ON
51 -------- ON ON ON OFF OFF ON OFF
52 -------- ON ON ON OFF OFF ON ON
53 -------- ON ON ON OFF ON OFF OFF
54 -------- ON ON ON OFF ON OFF ON
55 -------- ON ON ON OFF ON ON OFF
56 -------- ON ON ON OFF ON ON ON
57 -------- ON ON ON ON OFF OFF OFF
58 -------- ON ON ON ON OFF OFF ON
59 -------- ON ON ON ON OFF ON OFF
60 -------- ON ON ON ON OFF ON ON
61 -------- ON ON ON ON ON OFF OFF
62 -------- ON ON ON ON ON OFF ON
63 -------- ON ON ON ON ON ON OFF
64 -------- ON ON ON ON ON ON ON
65 -------- ON OFF OFF OFF OFF OFF OFF
66 -------- ON OFF OFF OFF OFF OFF ON
67 -------- ON OFF OFF OFF OFF ON OFF
-------- ON OFF OFF OFF OFF ON ON
Page 78
-------- ON OFF OFF OFF ON OFF OFF
-------- ON OFF OFF OFF ON OFF ON
-------- ON OFF OFF OFF ON ON OFF
-------- ON OFF OFF OFF ON ON ON
-------- ON OFF OFF ON OFF OFF OFF
-------- ON OFF OFF ON OFF OFF ON
-------- ON OFF OFF ON OFF ON OFF
-------- ON OFF OFF ON OFF ON ON
-------- ON OFF OFF ON ON OFF OFF
-------- ON OFF OFF ON ON OFF ON
-------- ON OFF OFF ON ON ON OFF
-------- ON OFF OFF ON ON ON ON
-------- ON OFF ON OFF OFF OFF OFF
-------- ON OFF ON OFF OFF OFF ON
-------- ON OFF ON OFF OFF ON OFF
-------- ON OFF ON OFF OFF ON ON
-------- ON OFF ON OFF ON OFF OFF
-------- ON OFF ON OFF ON OFF ON
-------- ON OFF ON OFF ON ON OFF
-------- ON OFF ON OFF ON ON ON
-------- ON OFF ON ON OFF OFF OFF
-------- ON OFF ON ON OFF OFF ON
-------- ON OFF ON ON OFF ON OFF
-------- ON OFF ON ON OFF ON ON
-------- ON OFF ON ON ON OFF OFF
-------- ON OFF ON ON ON OFF ON
-------- ON OFF ON ON ON ON OFF
-------- ON OFF ON ON ON ON ON
-------- ON ON OFF OFF OFF OFF OFF
-------- ON ON OFF OFF OFF OFF ON
-------- ON ON OFF OFF OFF ON OFF
-------- ON ON OFF OFF OFF ON ON
-------- ON ON OFF OFF ON OFF OFF
-------- ON ON OFF OFF ON OFF ON
-------- ON ON OFF OFF ON ON OFF
-------- ON ON OFF OFF ON ON ON
-------- ON ON OFF ON OFF OFF OFF
-------- ON ON OFF ON OFF OFF ON
-------- ON ON OFF ON OFF ON OFF
-------- ON ON OFF ON OFF ON ON
-------- ON ON OFF ON ON OFF OFF
-------- ON ON OFF ON ON OFF ON
-------- ON ON OFF ON ON ON OFF
Page 79
-------- ON ON OFF ON ON ON ON
-------- ON ON ON OFF OFF OFF OFF
-------- ON ON ON OFF OFF OFF ON
-------- ON ON ON OFF OFF ON OFF
-------- ON ON ON OFF OFF ON ON
-------- ON ON ON OFF ON OFF OFF
-------- ON ON ON OFF ON OFF ON
-------- ON ON ON OFF ON ON OFF
-------- ON ON ON OFF ON ON ON
-------- ON ON ON ON OFF OFF OFF
-------- ON ON ON ON OFF OFF ON
-------- ON ON ON ON OFF ON OFF
-------- ON ON ON ON OFF ON ON
-------- ON ON ON ON ON OFF OFF
-------- ON ON ON ON ON OFF ON
-------- ON ON ON ON ON ON OFF
128 -------- ON ON ON ON ON ON ON
Page 80
Electrical functions of wired controller:
1.Function difference between master wired controller and slave one:
Contrastive items Master wired controller Slave wired controller
Function All of functions Only with below functions: ON/OFF,
MODE, FAN SPEED, SET TEMP.,
SWING
2. Wiring connections of wired controller:
A
indoor 1indoor 2
wired controller
B
indoor 1
wired controller
1
A
wired controller
2
B
wired controller
3
polar wire
C
indoor N
C
indoor 1
wired controllerwired controller
wired controller
123
ABC
wired controller
polar wire
polar wire
indoor 15
ABC
wired controller
indoor 16
(master unit)
wired controller
control wiring of wired controller, polar.
ABC
wired controller
There are three methods to connection wired controller and the indoor units:
A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces
of polar wire must connect the wired controller and the master unit (the indoor
unit connected with wired controller directly), the others connect with the master
unit through 2 pieces of polar wire.
B. One wired controller controls one indoor unit, and the indoor unit connects
with the wired controller through 3 pieces of polar wire.
C. Two wired controllers control one indoor unit. The wired controller
connected with indoor unit is called master one, the other is called slave one.
Master wired controller and indoor unit; master and slave wired controllers are
all connected through 3 pieces of polar wire.
3. Communication wiring:
The wired controller is equipped with special communication wiring in the
accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the
Page 81
terminal A、B、C of wired controller respectively.
The communication wiring is 4 meter long; if the actual length is more than it,
please distribute wiring according to below table:
Communication wiring length(m)Dimensions of wiring
<100 0.3mm2X3-core shielded wire
≥100 and <200 0.5mm2X3-core shielded wire
≥200 and <3000.75mm2X3-core shielded wire
≥300 and <4001.25mm2X3-core shielded wire
≥400 and <6002mm2X3-core shielded wire
※ One side of the shielded sheet of communication wire must be earthed.
Page 82
8. Refrigerant Diagram
t
i
n
u
r
o
o
d
n
i
r
e
g
n
a
h
c
x
e
t
a
e
h
e
v
l
a
v
p
o
t
s
r
e
g
n
a
h
c
x
e
t
a
e
h
e
e
v
v
l
l
a
a
v
v
p
p
o
o
t
t
s
s
r
e
g
n
a
h
c
x
e
t
a
e
h
e
e
v
v
l
l
a
a
v
v
p
p
o
o
t
t
s
s
r
e
g
n
a
h
c
x
e
t
a
e
h
e
e
v
l
a
v
p
o
t
s
e
v
v
l
l
a
a
v
v
p
p
o
o
t
t
s
s
d
i
o
n
e
v
e
l
l
a
o
v
s
d
i
y
r
o
a
n
e
l
l
v
e
i
l
l
p
a
o
a
v
s
c
r
e
g
n
a
h
c
x
e
t
a
e
h
t
i
n
u
r
o
o
d
t
u
o
l
i
o
e
v
l
a
v
y
a
w
r
u
o
f
r
o
t
a
r
a
p
e
s
r
o
t
a
l
e
c
u
i
s
o
n
v
i
d
i
o
n
e
v
e
l
l
a
o
v
s
d
i
o
y
n
e
r
v
e
l
l
a
l
l
a
o
i
v
s
p
a
c
n
n
o
i
o
i
t
t
a
a
r
r
e
e
p
p
o
o
g
g
n
i
n
i
e
v
l
a
v
y
a
w
r
u
o
f
r
o
t
a
r
a
r
o
t
a
e
l
c
u
i
s
o
n
v
i
p
l
i
e
o
s
t
l
a
o
e
o
h
c
d
i
u
q
i
l
r
i
a
s
o
s
t
e
a
r
r
a
p
m
p
o
e
C
s
r
o
r
r
o
s
s
e
r
p
m
o
C
r
o
d
t
i
a
u
r
q
i
a
l
-
p
r
i
e
a
s
Page 83
Electrical Control Functions
NO Function Description of function
1 Auto
2 Cooling
3 Drying
4 Fan Temperature can not be adjusted
5 Emergence run
6 Test run Set force cooling
7 Fan speed adjustment Auto, high, middle, low four lever fan speeds
8 Timer switch 24hours timer on, timer off, on-off, off-on
9 Sleep run
10 Anit-freezing of indoor unit
Flow Chart for Operation
1) Turn on/off unit
Over 23
Set temperature between 16
Set temperature between 16
Over 23
Equal to 8 hours timer on, but temperature adjustment is more
comfortable
When cooling in low ambient temperature to defrost for the
outdoor unit in order to make the system have a better efficiency
cooling and set 26 less 23
and 30
and 30
cooling and set 26 less 23
begining
turn on the indoor unit
N
Y
mode judegement
autocooldryingventilate
Page 84
2) Cooling operation
does the room temp.exceed
the temp. setting
Haier
cooling operation
indoor fan runs
N
manualauto
Y
LED of power goes on
HIHI
MID
LO
MID
LO
compressor and outdoor
fans run
loide valve energized
N
frost prevent
Y
LED power goes on
LED of operation goes on
compressor and
outdoor fan stop
loide vavle is not
energized
Page 85
3) Dehumidifying operation
y op
r
A
S
Haier
Dehumidifying
No
No
Swing
Yes
wing action
If enter cooling
No
Determine if dehumidify
according to ai
temperature
Yes
Yes
Swing flap in the cooling
standard position
djust fan speed
according to temperature
Solenoid valves open,
indoor unit fan motor weak
Solenoid valves open,
indoor unit fan motor weak
Anti-defro
No
Send indoor unit Operation
State to outdoor unit
A
Yes
Electronic expansion
valve totall
en
Page 86
10. Diagnostic information (trouble shooting)
A
10.1 Failure code
Resumable failures are marked with “ ⊙ ”, the others are not resumable failures.
Resumable failure will disappear when the failure is eliminated and its failure code will
disappear automatically within 30 seconds. But the other failure code will disappear only
after the unit starts up once again.
When failure occurs, the unit only can receive “OFF” signal from the controller. And when
the unit is shut off, the failure code will disappear.
The chart (for cassette type and duct type) please refer to the information on Page 74.
For wall mounted type and the console type unit, their failure code is below:
Failure description
Room temp. sensor abnormal ⊙
Code on wired
controller
(YR-E06)
F1 Power LED flashes 1 time
Flash times of indoor receiver
board
Indoor coil temp. sensor abnormal (liquid pipe) ⊙
Refrigerant system abnormal
Indoor coil temp. sensor abnormal (gas pipe) ⊙
High pressure abnormal (outdoor)
Drainage abnormal ⊙
Communication between indoor and wired controller⊙
Indoor fan motor abnormal (up)
Indoor fan motor abnormal (down)
3 phase abnormal
Low pressure abnormal (outdoor) E2 Running LED flashes twice
Communication between indoor and outdoor abnormal⊙
Compressor overheat E4 Running LED flashes 4 times
CT current abnormal E5 Running LED flashes 5 times
Outdoor ambient temp. sensor abnormal ⊙
Outdoor coil pipe temp. sensor abnormal⊙
F2 Power LED flashes 2 times
F3 Power LED flashes 3 times
F4 Power LED flashes 4 times
F5 Power LED flashes 5 times
F6 Power LED flashes 6 times
F7 Power LED flashes 7 times
E1 Running LED flashes once
E3 Running LED flashes 3 times
E6 Running LED flashes 6 times
E7 Running LED flashes 7 times
Power LED flashes 8 times
Power LED flashes 9 times
Outdoor suction temp. sensor abnormal ⊙
bnormal modes running ⊙
Outdoor discharging temp. sensor abnormal ⊙
Indoor EEPROM abnormal EE Running LED flashes 14 times
EA Running LED flashes 10 times
EC Running LED flashes 11 times
ED Running LED flashes 12 times
Page 87
Trouble Shooting - Detailed for engineer
Malfunction flow chart: analyze and diagnose
If the air-condition fails to cooling or heating function and other functions, please check
the system as follows:
1. Cooling
begining
fails in cooling
Y
the enactment TEMP.
right or not
N
change the designed
TEMP.
condensate
flowage failure
airiness circle
improperly
the cooling load
beyond the allowable
arange
fault in solenoid vavle
N
quantity of condensate
charge is not enough
N
compressor fault
fan speed at
low-speed
Y
Y
Y
superaddition condensate
Y
Y
replacing compressor
enact fan speed of
high or middle speed
used arange is
right or not
change the
solenoid vavle
Y
redesign the TEMP.
N
air entrance filter
obstruct
heat insulation of condensate
pipeline between indoor unit
and outdoor unit is normal
Figure 7-1
Y
clear the filter
Y
insulate the two
pipeline respective
Page 88
2. Malfunction of air-conditioner units
1) Fan of indoor unit faulty on abnormal functioning
begini ng
Y
output signal of fan
motor fan-out is normal
Y
if the CMOS chip of control
panel has signal output
Y
if the relay of fan motor in
control panel is normal
N
replacing the relay
N
replacing
the fuse
if the power indi cator light of
indoor unit is illuminates
if power supply is normal
if the fuse of
PCB. i s normal
if pressure sensor
resistence throughing
replacing the
pressure sensor
resistance
N
Y
Y
Y
2) Fan of outdoor unit fault to operate
N
N
replacing the control PCB.
Figure 7-2
if CMOS chip of
control PCB.is normal
N
if capacitator of fan
motor is normal
N
if the winding of fan
motor is normal
N
replacing the
fan motor
Y
replacing the
capacit ator
begining
if the power indicator light of
indoor unit PCB.in normal state
N
if power supply is normal
Y
if the fuse of
PCB. is normal
Y
replacing the fuse
Y
output si gnal of fan
motor fan-out is normal
Y
if the CMOS chip of control
panel has signal output
Y
if the relay of fan motor in
control panel is normal
N
replacing the relay
N
N
if CMOS chip of
control PCB.i s normal
replacing the control PCB.
if capaci tance of fan
motor is normal
N
if the winding of fan
motor is normal
N
N
replaci ng the
fan motor
Y
replaci ng the
capacitance
Figure 7-3
Page 89
3) There is nothing on display of remote control organ, and the air-conditioner failure
to operate
begining
if the diode on indoor
unit is lumines
Y
check the port row of
power supply
redo the
connection work
replacing the
transformer
if there
on the primary si de
of tranaformer
Y
if power supply and
communication line are
connected correctly
N
N
if the transform of
PCB.socket is normal
if there's AC 13V on
transformer subside
of indoor unit PCB.
Y
N
if there's AC 220V
of power suplay on
PCB. of indoor unit
1.The communication terminal block to indoor cannot be connected to HT eletricity, or PCB will
be damaged.
2.Heater is optional according to different outdoor unit.
3.Oxygen pump is optional.
4.Solenoid valve A and B are not available for this model.
Page 91
console type:
BOTTOM LOUVER
MOTOR
INDOOR WIRING DIAGRAM
TOP LOUVER MOTOR
AMBIENT TEMP.
SENSOR
OPTIONAL BOARD
RECEIVING BOARD
REMOTE CONTROL
DETECTOR
TERMINAL BLOCK
PIPING TEMP.
SENS0R
BOTTOM FAN MOTOR
TOP FAN MOTOR
POWER SUPPLY
BOARD
NOTE
:PART IN DASH FRAME ARE
OPTIONAL.
SW1 is an emergency key.
SW2 is used to choose the
working satate of douwn PG
motor.
B : BLACK BL : BLUE
R : RED W : WHITE
Y/G: YELLOW/GREEN
(1PH,220-230V~,50Hz)
Connect To Outdoor UnitTo Power Supply
SW3 and SW4 are used to choose the working state of the wired controller. The detailed
information see the following:
SW3
Working state of the wire controller
SW4
If the controller power on, the indoor unit run according to the state on the
controller;If the controller power off, the indoor unit run in the auto mode
Ignore the state on the controller and power off
Ignore the state on the controller and power off
The controller is able to be controlled
Page 92
Wall mounted type:
SW1 and SW3 are used to choose the working
controller. The detailed information see the following:
Working state of the wire controller
if the controller power on, the indoor unit run according to the state on the controller;
if the controller power off, the indoor unit run in the auto mode
Ignore the state on the controller and power off
Ignore the state on the controller and power off
The controller is able to be controlled
state of thewire
NOTE:PARTS IN DASHED FRAME ARE OPTIONAL.
Explanation:
For the wall mounted indoor unit AS072/092/122/142/182XCBAA, you can select the horse power and the indoor fan
motor speed by adjusting the jumper. When out of factory, the jumper state will be as follow:
For AS072/092XCBAA PCB, jumper J27 is unconnected;
For AS122/142XCBAA PCB, jumper J26 is unconnected;
For AS182XCBAA PCB, jumper J25 is unconnected;
And jumper 24 is used to select the temperature compensation, if it is connected, the temp. compensation is available,
while if it is unconnected, the temp. compensation function is cancelled.