Haier AU142AFBEA, AU182AFBEA Schematic

0 (0)

Service Manual

Commercial Air Conditioning

14 18 Universal Outdoor Fixed Frequency Series

AC142ACBEA+AU142AFBEA

AD142AMBEA+AU142AFBEA

AB142ACBEA+AU142AFBEA

AC182ACBEA+AU182AFBEA

AD182AMBEA+AU182AFBEA

AB182ACBEA+AU182AFBEA

Features

Fixed frequency

Auto-restart function

Group control(if with a group controller)

Auto-changeover

The Outdoor unit can match with cassette \convertible\duct indoor Weekly timing(if with a weekly timer)

With new environment friendly refrigerant R407C

Haier Group

MANUAL CODE: SYJS-007 rev.0

CONTENTS

CONTENTS

Contents

1.Description of Products & Features…………...…….1

2.Specifications…………………. ………………...……3

3.Mechnical Data………………..…...………………. 7

4. Electrical Data…… …......…....

…..…

36

5.Performance Curves ………...….…………. ………..45

6. Charts …………………….........

……..…… ..………47

7. Electrical Control Functions …..........

………………56

8.Diagnostic Information (Trouble Shooting)

...............62

9. Installation Instructions and Maintenance ….......…67

10. Exploded Views and Parts lists...............

…. ……102

- 1 -

DESCRIPTION OF PRODUCTS & FEATURES

1 DESCRIPTION OF PRODUCTS & FEATURES

1.1 Products coding direction

Old code

H BU – 14 H A 03/ R1

Refers to HFC refrigerant, fixed frequency

Power: 03(230V/50Hz).04(240V/50Hz).12(115V/60Hz).13(230v/60Hz) Design series number

“H” refer to cooling and heating, ”C” refer to cooling only Nominal cooling capacity (BTU/h), 14=14000BTU/h

Indoor unit code: "B" Cassette type; "C" convertible "D" Duct type

“H” means “Haier”

New code

A B 14 2 A C B E A

Climate type: T1 (see table 1)

Design number (E stands for fixed frequency heat pump air conditioner) Product type: A stands for heat pump type, refrigerant is R22

B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407

Appearance character

Product series: one wall-mounted split type

Applicable voltage: 2 stands for 220-240V/50Hz,4 stands for 220v/60Hz N stand for 380V/50Hz

Cooling / Heating capacity,14=14000BTU/h

Product type : “B” stands for cassette type, “C” stands for convertible type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller system, "E" stands for ceiling concealed type, “U” stands for outdoor unit

Air conditioner

1.2 Brief Introduction to T1T2T3 working condition

Table 1

Type of Air Conditioner

 

 

Climate type

 

 

 

T1

 

T2

 

T3

 

 

 

 

Cool only

18

43

10

35

21

52

Heat pump

-7

43

-7

35

-7

52

Electricity heating

 

43

 

35

 

52

1.3 Operating Range of air conditioners

Normal condition

Operation

Operation Range Outside / Inside

Cooling

150C – 43oC

Drying

150C – 43oC

Heating

-7oC – 18oC

DESCRIPTION OF PRODUCTS & FEATURES

1.4 Products characteristic

The outdoor unit can match with different indoor unit

The indoor unit can be cassette type\convertible type and duct type. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish appearance of air conditioner allows it to blend right into ceiling.

Superbly efficient healthy filter

Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently.

Flexible and easy installation

Slim design with machine body, completely ceiling concealed and portable shape, all make it greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift, which allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit people's comfortable need much more.

ESP can be from 0Pa to 50Pa; in the meantime, the duct unit is equipped with a filter and air return box.

Auto-Restart function

When meeting a power failure during running, no matter how long it will be, once the power is restored, air conditioner will automatic restart with the previous status.

Safety and reliable control due to various signal controls

1.Inputting with press buttons on the panel

2.Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors)

3.Piping pressure signals 4.Compressor current signals 5.Testing signals

6.System time-shorten signal 7.Water overflowing signal

8.Communication signals between indoor unit and front plate or between indoor unit and outdoor unit.

NEW Universal convenient remote-controller

When using remote-controlling mode, it is comfortable and convenient to operate. The remote controller is used as new style; it looks like a phone, very compact. It is a universal controller and can be used for any unit such as single unit, multi free unit, MRV, etc. compatible with the old ones.

NEW New wired controller

One wired controller can control 16 indoor units without any other device such as detector.

Silent design

The use of radial outward flow turbine fan produces large airflow volume and acts to significantly decrease operating noise.

NEW Low ambient temperature cooling function (optional)

Equipped with high/low pressure protection switch

2 SPECIFICATIONS

item

 

 

 

 

 

 

Model

 

AU142AFBEA/AB142ACBEA

Function

 

 

 

 

 

 

 

 

 

 

 

cooling

 

heating

Capacity

 

 

 

 

 

 

 

KW

 

4.10

 

4.39

Capacity

 

 

 

 

 

 

BTU/h

14000

 

15000

Total power input

 

 

 

 

 

 

 

W

 

1550

 

1450

Max. power input

 

 

 

 

 

 

 

W

 

1800

 

1800

EER or COP

 

 

 

 

 

W/W

 

2.65

 

3.03

Dehumidify capacity

 

 

 

 

 

10

 

 

 

2.95

 

 

 

 

 

 

 

³×m³/h

 

 

 

Power cable

 

 

 

 

 

 

 

 

 

 

2X2.0+2X0.75

Power source

 

 

 

 

 

 

V

 

Hz

1PH 220V-230V 50HZ

 

 

 

 

 

N

 

 

 

 

 

Running /Max.Running current

 

 

 

A / A

 

cooling:7.8/8.5

heating:6.8/8.5

Start current

 

 

 

 

 

 

 

A

 

40

 

 

 

Unit model (color)

 

 

 

 

 

 

 

 

AB142ACBEA (grey)

 

 

Fan

 

 

type×number

 

 

 

 

 

 

centrifugal×1

 

 

 

 

 

speed (H-M-L)

 

 

r/min

900±30/850±30/750±30/610/540

 

 

 

 

 

Fan motor output power

 

 

W

 

20

 

 

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

 

1100/1000/900

 

 

Heat exchanger

 

Type / Diameter

 

mm

 

9.52

 

unit

 

 

 

 

Total Area

 

 

 

 

 

653*200*65

 

 

 

 

Temp. scope

 

 

 

 

 

5-10

 

indoor

 

 

 

 

 

 

 

 

 

 

Dimension

 

 

External

 

L×W×H

mm×mm×mm

700*570*276

 

 

 

 

 

 

 

 

 

 

Package

 

L×W×H

mm×mm×mm

775*715*361

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

 

PVC 26/32

 

 

Control type

(Remote /wired)

 

 

 

 

 

 

 

remote

 

 

Fresh air hole dimension

 

 

 

mm

 

100

 

 

 

Electricity Heater

 

 

 

kW

 

0

 

 

 

Noise level

(H-M-L)

 

 

dB(A)

53.5/51.5/49.8

 

 

Weight

(Net / Shipping)

 

kg / kg

26/28

 

Panel

 

Dimension

 

 

External

 

L×W×H

mm×mm×mm

630*630*93

 

 

 

 

Package

 

L×W×H

mm×mm×mm

685*685*155

 

 

 

 

 

 

 

 

Weight

 

(Net / Shipping)

 

kg / kg

4.2/6.3

 

 

Unit model (color)

 

 

 

 

 

 

 

AU142AFBEA WHITE

 

 

Compressor

 

 

Model /

Manufacture

 

 

 

 

 

PG260X2CS-4KT1 toshiba

 

 

 

 

Type

 

 

 

 

 

 

 

rotary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type × Number

 

 

 

 

 

Axial-flow

 

 

Fan

 

 

Speed

 

 

 

r/min

820±30

 

 

 

 

Fan motor output power

 

kW

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air-flow(H-M-L)

 

m³/h

2300

 

 

 

Heat exchanger

Type / Diameter

 

mm

 

TP2M/9.52

unit

 

Total area

 

 

 

 

0.92

 

 

 

 

 

Temp. scope

 

 

 

 

 

43-60

 

Outdoor

 

 

 

 

 

 

 

 

 

 

Dimension

 

 

External

 

L×W×H

mm×mm×mm

780x650x250

 

 

 

 

 

 

 

 

 

Package

 

L×W×H

mm×mm×mm

903x714x343

 

 

 

 

 

 

 

 

Drainage pipe

 

(material ,

I.D./O.D.)

 

mm

 

 

/

 

 

 

Refrigerant control method

 

 

mm/mm

main: 1.7*400 auxiliary:2.0*140

 

 

Defrosting

 

 

 

 

 

 

 

 

 

 

auto

 

 

Volume of Accumulator

 

 

 

 

L

 

 

/

 

 

 

Noise level

 

 

 

 

 

dB(A)

58/--/50

 

 

Type of Four way

valve

 

 

 

 

 

 

 

 

/

 

 

 

material of reduce noise

 

 

 

 

 

 

 

XPE

 

 

crankcase heater power

 

 

 

 

W

 

 

/

 

 

 

Weight

 

(Net / Shipping)

 

kg / kg

41/43

 

 

 

Refrigerant

 

 

Type / Charge

 

 

 

g

 

R407C

1600

PIPING

 

 

 

Recharge quantity

 

g/m

 

50

 

 

 

 

 

 

 

 

 

Pipe

 

 

Liquid

 

 

 

mm

 

6.35

 

 

 

 

Gas

 

 

 

mm

 

12.7

 

 

 

 

 

 

 

 

 

 

 

Connecting Method

 

 

 

 

 

 

 

flared

 

 

Between I.D &O.

MAX.Drop

 

 

 

m

 

20

 

 

 

 

 

 

 

 

 

 

 

 

MAX.Piping length

 

 

m

 

30

 

 

 

 

 

 

 

 

 

 

item

 

 

 

 

 

Model

AU142AFBEA/AC142ACBEA

Function

 

 

 

 

 

 

 

cooling

 

heating

Capacity

 

 

 

 

 

KW

4.10

 

4.39

Capacity

 

 

 

 

 

BTU/h

14000

 

15000

Total power input

 

 

 

 

 

W

1550

 

1450

Max. power input

 

 

 

 

 

W

1800

 

1800

EER or COP

 

 

 

 

 

W/W

2.65

 

3.03

Dehumidify capacity

 

 

 

 

 

10 ³×m³/h

2.95

 

Power cable

 

 

 

 

 

 

2X2.0+2X0.75

Power source

 

 

 

 

 

N V Hz

1PH 220V-230V 50HZ

Running /Max.Running current

 

 

 

A / A

cooling:7.8/8.5

heating:6.8/8.5

Start current

 

 

 

 

 

A

40

 

 

 

Unit model (color)

 

 

 

 

 

AC142ACBEA (white)

 

 

Fan

 

type×number

 

 

 

 

centrifugal×2

 

 

 

 

speed (H-M-L)

 

 

r/min

1350±30/1280±30/1210±30

 

 

 

 

Fan motor output power

 

W

20W

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

1100/1000/900

 

 

Heat exchanger

Type / Diameter

 

 

mm

9.52

 

unit

 

 

 

Total Area

 

 

 

653*200*65

 

 

 

Temp. scope

 

 

 

5-10

indoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

830*450*225

 

 

 

Package

 

L×W×H

 

mm×mm×mm

976*526*288

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

PVC 26/32

 

 

Control type

(Remote /wired)

 

 

 

remote

 

 

Fresh air hole dimension

 

 

 

mm

 

/

 

 

 

Electricity Heater

 

 

 

 

kW

 

/

 

 

 

Noise level

(H-M-L)

 

 

dB(A)

53.5/51.5/49.8

 

 

Weight

(Net / Shipping)

 

 

kg / kg

20/22

Panel

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

 

/

 

 

 

Package

 

L×W×H

 

mm×mm×mm

 

/

 

 

 

 

 

 

 

 

 

Weight

(Net / Shipping)

 

 

kg / kg

 

/

 

 

 

 

 

 

 

 

 

Unit model (color)

 

 

 

 

 

AU142AFBEA WHITE

 

 

Compressor

 

Model / Manufacture

 

 

PG260X2CS-4KT1 toshiba

 

 

 

Type

 

 

 

 

rotary

 

 

 

 

 

 

 

 

 

 

 

 

Type × Number

 

 

 

Axial-flow

 

 

Fan

 

Speed

 

 

 

r/min

820±30

 

 

 

Fan motor output power

 

kW

35

 

 

 

 

 

 

 

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

2300

 

 

Heat exchanger

Type / Diameter

 

 

mm

TP2M/9.52

unit

 

Total area

 

 

 

0.92

 

 

 

 

Temp. scope

 

 

 

43-60

Outdoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

780x650x250

 

 

Package

 

L×W×H

 

mm×mm×mm

903x714x343

 

 

 

 

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

 

/

 

 

 

 

 

 

 

 

 

Refrigerant control method

 

 

 

mm/mm

main: 1.7*400 auxiliary:2.0*140

 

 

Defrosting

 

 

 

 

 

 

auto

 

 

Volume of Accumulator

 

 

 

L

 

/

 

 

 

Noise level

 

 

 

 

 

dB(A)

58/--/50

 

 

Type of Four way

valve

 

 

 

 

 

/

 

 

 

material of reduce noise

 

 

 

 

XPE

 

 

crankcase heater power

 

 

 

W

 

/

 

 

 

Weight

(Net / Shipping)

 

 

 

kg / kg

41/43

 

 

Refrigerant

 

Type / Charge

 

 

g

R407C

1600

PIPING

 

 

Recharge quantity

 

g/m

50

 

 

 

 

 

 

 

Pipe

 

Liquid

 

 

 

mm

6.35

 

 

 

Gas

 

 

 

mm

12.7

 

 

 

 

 

 

 

 

 

Connecting Method

 

 

 

 

 

flared

 

 

Between I.D &O.D

MAX.Drop

 

 

 

m

20

 

 

 

MAX.Piping length

 

m

30

 

 

 

 

 

 

 

Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB

item

 

 

 

 

 

Model

AU142AFBEA/AD142AMBEA

Function

 

 

 

 

 

 

 

cooling

 

heating

Capacity

 

 

 

 

 

KW

4.10

 

4.39

Capacity

 

 

 

 

 

BTU/h

14000

 

15000

Total power input

 

 

 

 

 

W

1550

 

1450

Max. power input

 

 

 

 

 

W

1800

 

1800

EER or COP

 

 

 

 

 

W/W

2.65

 

3.03

Dehumidify capacity

 

 

 

 

 

10 ³×m³/h

2.95

Power cable

 

 

 

 

 

 

2X2.0+2X0.75

Power source

 

 

 

 

 

N V Hz

1PH 220V-230V 50HZ

Running /Max.Running current

 

 

 

A / A

cooling:7.8/8.5

 

heating:6.8/8.5

Start current

 

 

 

 

 

A

40

 

 

Unit model (color)

 

 

 

 

 

AD142AMBEA (white)

 

 

Fan

 

type×number

 

 

 

 

centrifugal×2

 

 

 

 

speed (H-M-L)

 

 

r/min

1290±30/1220±30/940±30/710±40

 

 

 

 

Fan motor output power

 

W

20W

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

950/850/770

 

 

Heat exchanger

Type / Diameter

 

 

mm

9.52

unit

 

 

 

Total Area

 

 

 

653*200*65

 

 

 

Temp. scope

 

 

 

5-10

indoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

830*450*225

 

 

 

Package

 

L×W×H

 

mm×mm×mm

980*543*305

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

PVC 18/21

 

 

Control type

(Remote /wired)

 

 

 

remote

 

 

Fresh air hole dimension

 

 

 

mm

 

/

 

 

Electricity Heater

 

 

 

 

kW

 

/

 

 

Noise level

(H-M-L)

 

 

dB(A)

40/38/36

 

 

Weight

(Net / Shipping)

 

 

kg / kg

25/28

Panel

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

 

/

 

 

Package

 

L×W×H

 

mm×mm×mm

 

/

 

 

 

 

 

 

 

Weight

(Net / Shipping)

 

 

kg / kg

 

/

 

 

 

 

 

 

 

Unit model (color)

 

 

 

 

 

AU142AFBEA WHITE

 

 

Compressor

 

Model / Manufacture

 

 

PG260X2CS-4KT1 toshiba

 

 

 

Type

 

 

 

 

rotary

 

 

 

 

 

 

 

 

 

 

 

 

Type × Number

 

 

 

Axial-flow

 

 

Fan

 

Speed

 

 

 

r/min

820±30

 

 

 

Fan motor output power

 

kW

35

 

 

 

 

 

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

2300

 

 

Heat exchanger

Type / Diameter

 

 

mm

TP2M/9.52

unit

 

Total area

 

 

 

0.92

 

 

 

Temp. scope

 

 

 

43-60

Outdoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

780x650x250

 

 

Package

 

L×W×H

 

mm×mm×mm

903x714x343

 

 

 

 

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

 

/

 

 

 

 

 

 

 

Refrigerant control method

 

 

 

mm/mm

main: 1.7*400 auxiliary:2.0*140

 

 

Defrosting

 

 

 

 

 

 

auto

 

 

Volume of Accumulator

 

 

 

L

 

/

 

 

Noise level

 

 

 

 

 

dB(A)

58/--/50

 

 

Type of Four way

valve

 

 

 

 

 

/

 

 

material of reduce noise

 

 

 

 

XPE

 

 

crankcase heater power

 

 

 

W

 

/

 

 

Weight

(Net / Shipping)

 

 

 

kg / kg

41/43

 

 

Refrigerant

 

Type / Charge

 

 

g

R407C

1600

PIPING

 

 

Recharge quantity

 

g/m

50

 

 

 

 

 

Pipe

 

Liquid

 

 

 

mm

6.35

 

 

Gas

 

 

 

mm

12.7

 

 

 

 

 

 

 

Connecting Method

 

 

 

 

 

flared

 

 

Between I.D &O.D

MAX.Drop

 

 

 

m

20

 

 

MAX.Piping length

 

m

30

 

 

 

 

 

Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB

item

 

 

 

 

 

Model

AB182ACBEA

Function

 

 

 

 

 

 

 

cooling

heating

Capacity

 

 

 

 

 

KW

5.27

5.86

Capacity

 

 

 

 

 

BTU/h

18000

20000

Total power input

 

 

 

 

 

W

2000

1900

Max. power input

 

 

 

 

 

W

2400

2800

EER or COP

 

 

 

 

 

WW

2.64

3.08

Dehumidify capacity

 

 

 

 

 

10 ³×m³/h

1.2

Power cable

 

 

 

 

 

 

4X0.75

Power source

 

 

 

 

 

N V Hz

1PH 220V-230V 50HZ

Running /Max.Running current

 

 

 

A / A

cooling: 10/12

heating: 9.5/14

Start current

 

 

 

 

 

A

50

 

 

Unit model (color)

 

 

 

 

 

AB182ACBEA(WHITE)

 

 

Fan

 

type×number

 

 

 

 

CENTRIFUGAL*1

 

 

 

 

speed (H-M-L)

 

 

r/min

500±30/450±40/380±50

 

 

 

 

Fan motor output power

 

W

0.04

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

1050/945/790

 

 

Heat exchanger

Type / Diameter

 

 

mm

TP2M/7

unit

 

 

 

Total Area

 

 

 

0.199

 

 

 

Temp. scope

 

 

 

2-7

indoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

750×750×280

 

 

 

Package

 

L×W×H

 

mm×mm×mm

900×900×460

 

 

 

 

 

 

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

PVC 26/32

 

 

Control type

(Remote /wired)

 

 

 

remote

 

 

Fresh air hole dimension

 

 

 

mm

 

/

 

 

Electricity Heater

 

 

 

kW

 

/

 

 

Noise level

(H-M-L)

 

 

dB(A)

43/42/40

 

 

Weight

(Net / Shipping)

 

 

kg / kg

29/39

Panel

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

750x750x80

 

 

Package

 

L×W×H

 

mm×mm×mm

800x800x180

 

 

 

 

 

 

Weight

(Net / Shipping)

 

 

kg / kg

3.5/5.8

 

 

 

 

 

 

Refrigerant

 

Type / Charge

 

 

g

R407C

1950

 

 

 

Recharge quantity

 

g/m

30

 

 

 

 

 

PIPING

 

Pipe

 

Liquid

 

 

 

mm

6.35

 

 

Gas

 

 

 

mm

15.88

 

 

 

 

 

 

 

Connecting Method

 

 

 

 

flared

 

 

 

 

 

 

 

 

Between I.D &O.D

MAX.Drop

 

 

 

m

20

 

 

MAX.Piping length

 

m

30

Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB

item

 

 

 

 

 

Model

AC182ACBEA

Function

 

 

 

 

 

 

 

cooling

heating

Capacity

 

 

 

 

 

KW

5.27

5.86

Capacity

 

 

 

 

 

BTU/h

18000

20000

Total power input

 

 

 

 

 

W

2000

1900

Max. power input

 

 

 

 

 

W

2400

2800

EER or COP

 

 

 

 

 

W/W

2.64

3.08

Dehumidify capacity

 

 

 

 

 

10 ³×m³/h

2.1

Power cable

 

 

 

 

 

 

4X0.75

Power source

 

 

 

 

 

N V Hz

1PH 220V-230V 50HZ

Running /Max.Running current

 

 

 

A / A

cooling: 10/12

heating: 9.5/14

Start current

 

 

 

 

 

A

50

 

 

Unit model (color)

 

 

 

 

 

AC182ACBEA(WHITE)

 

 

Fan

 

type×number

 

 

 

 

CENTRIFUGALX2

 

 

 

 

speed (H-M-L)

 

 

r/min

1070+30/1000+40/940+50

 

 

 

 

Fan motor output power

 

W

0.04

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

900/840/790

 

 

Heat exchanger

Type / Diameter

 

 

mm

TP2M/9.52

unit

 

 

 

Total Area

 

 

 

0.199

 

 

 

Temp. scope

 

 

 

2-7

indoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

1990×655×199

 

 

 

Package

 

L×W×H

 

mm×mm×mm

1150×750×300

 

 

 

 

 

 

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

PVC 18/20

 

 

Control type

(Remote /wired)

 

 

 

remote

 

 

Fresh air hole dimension

 

 

 

mm

 

/

 

 

Electricity Heater

 

 

 

kW

 

/

 

 

Noise level

(H-M-L)

 

 

dB(A)

48/44/38

 

 

Weight

(Net / Shipping)

 

 

kg / kg

30/39

 

 

Refrigerant

 

Type / Charge

 

 

g

R407C

1950

 

 

 

Recharge quantity

 

g/m

30

 

 

 

 

 

PIPING

 

Pipe

 

Liquid

 

 

 

mm

6.35

 

 

Gas

 

 

 

mm

15.88

 

 

 

 

 

 

 

Connecting Method

 

 

 

 

flared

 

 

 

 

 

 

 

 

Between I.D &O.D

MAX.Drop

 

 

 

m

20

 

 

MAX.Piping length

 

m

30

Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB

item

 

 

 

 

 

Model

AD182AMBEA

Function

 

 

 

 

 

 

 

cooling

heating

Capacity

 

 

 

 

 

KW

5.27

5.86

Capacity

 

 

 

 

 

BTU/h

18000

20000

Total power input

 

 

 

 

 

W

2000

1900

Max. power input

 

 

 

 

 

W

2400

2800

EER or COP

 

 

 

 

 

WW

2.64

3.08

Dehumidify capacity

 

 

 

 

 

10 ³×m³/h

1.2

Power cable

 

 

 

 

 

 

4X0.75

Power source

 

 

 

 

 

N V Hz

1PH 220V-230V 50HZ

Running /Max.Running current

 

 

 

A / A

cooling: 10/12

heating: 9.5/14

Start current

 

 

 

 

 

A

50

 

 

Unit model (color)

 

 

 

 

 

AD182AMBEA(WHITE)

 

 

Fan

 

type×number

 

 

 

 

CENTRIFUGALx2

 

 

 

 

speed (H-M-L)

 

 

r/min

780+30/710+30/630+50

 

 

 

 

Fan motor output power

 

W

0.13

 

 

 

 

Air-flow(H-M-L)

 

 

m³/h

850/770/680

 

 

Heat exchanger

Type / Diameter

 

 

mm

TP2M/9.52

unit

 

 

 

Total Area

 

 

 

0.199

 

 

 

Temp. scope

 

 

 

2-7

indoor

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

 

mm×mm×mm

990×650×300

 

 

 

Package

 

L×W×H

 

mm×mm×mm

1137×800×320

 

 

 

 

 

 

 

 

Drainage pipe

(material , I.D./O.D.)

 

 

mm

PVC 26/32

 

 

Control type

(Remote /wired)

 

 

 

wired+remote

 

 

Fresh air hole dimension

 

 

 

mm

 

/

 

 

Electricity Heater

 

 

 

kW

 

/

 

 

Noise level

(H-M-L)

 

 

dB(A)

33/31/28

 

 

Weight

(Net / Shipping)

 

 

kg / kg

38/55

 

 

Refrigerant

 

Type / Charge

 

 

g

R407C

1950

 

 

 

Recharge quantity

 

g/m

30

 

 

 

 

 

PIPING

 

Pipe

 

Liquid

 

 

 

mm

6.35

 

 

Gas

 

 

 

mm

15.88

 

 

 

 

 

 

 

Connecting Method

 

 

 

 

flared

 

 

 

 

 

 

 

 

Between I.D &O.D

MAX.Drop

 

 

 

m

20

 

 

MAX.Piping length

 

m

30

Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB

item

 

 

 

 

 

Model

AU182AFBEA

Function

 

 

 

 

 

Cooling

Heating

Capacity

 

 

 

 

KW

5.27

5.86

Capacity

 

 

 

 

BTU/h

18000

20000

Total power input

 

 

 

 

W

2000

1900

Max. power input

 

 

 

 

W

2400

2800

EER or COP

 

 

 

 

W/W

2.64

3.08

Dehumidifying capacity

 

 

 

 

10 ³×m³/h

 

2.1

Power cable

 

 

 

 

 

4X0.75

Power source

 

 

 

 

N V Hz

1PH 220V-230V 50HZ

Running /Max.Running

 

 

 

A / A

cooling: 10/12

heating: 9.5/14

Start Current

 

 

 

 

A

50

 

Unit model (color)

 

 

 

 

AU182AFBEA WHITE

 

Compressor

 

Model /

Manufacture

 

PG330X2CS-4KU1 Toshiba

 

 

 

Type

 

 

 

Rotary

 

Fan

 

Type × Number

 

Axial-flow

 

 

 

Speed

 

 

r/min

820±30

 

 

 

Fan motor

output power

kW

35

 

 

 

Air-flow(H-M-L)

m³/h

2000

 

Heat exchanger

Type / Diameter

mm

TP2M/9.52

unit

 

 

Total area

 

 

0.72

 

 

Temp. scope

 

 

43-60

Outdoor

 

 

 

 

 

 

 

 

Dimension

 

External

 

L×W×H

mm×mm×mm

810x288x680

 

 

 

 

 

 

Package

 

L×W×H

mm×mm×mm

960x406x760

 

Drainage pipe

 

(material ,

I.D./O.D.)

mm

 

/

 

Refrigerant control method

 

 

mm/mm

Main capillary2.0x450 Sub-capillary2.0x200

 

Defrosting

 

 

 

 

 

Auto

 

Volume of Accumulator

 

 

L

 

/

 

Noise level

 

 

 

 

dB(A)

52/--/46

 

Type of Four way

valve

 

 

 

 

/

 

material of reduce noise

 

 

 

XPE

 

crankcase heater power

 

 

W

 

/

 

Weight

(Net / Shipping)

 

kg / kg

59/66

 

Refrigerant

 

Type / Charge

 

g

R407C

1950

PIPING

 

 

Recharge quantity

g/m

30

Pipe

 

Liquid

 

 

mm

6.35

 

Gas

 

 

mm

15.88

 

 

 

 

Connecting Method

 

 

 

Flare

 

Between I.D &O.

MAX.Drop

 

 

m

20

 

MAX.Piping length

m

30

 

 

 

Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB

Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB

3 MECHANICAL DATA

3.1 Drawings / Dimensions

3.1.1 Cassette Indoor unit

Swing louver

(Air flow direction can be adjusted by using the SWING button on the remote controller)

Electrical Components Case

Air Inlet Grille

Air Filter (Inside of the Inlet Grille)

3.1.2 outdoor unit

Air inlet

Compressor(inside of unit)

Air outlet

18 series

Haier AU142AFBEA, AU182AFBEA Schematic

Dimension

 

.

I

N

M

 

MIN.

 

.

 

N

I

 

M

 

 

 

 

M

 

 

 

I

 

 

 

N

 

 

 

.

 

 

110

 

 

190

 

 

 

 

170

 

 

75

220

400

 

 

65

 

 

 

 

 

150

 

 

100

100

 

(Ceiling opening hole)

 

 

eecl ctri al bo

 

 

( )

(Ceiling opening hole)

 

 

 

 

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Needed minimum position

480

265

30

200

680

810

580

288

Convertible type

10 11

3

9

8

Fig.1

Dimension

1

POWER 4

OPER 5

TIMER 6

COMP 7

EMER 2

Fig.2

3

 

Fig.1 Indoor Unit

1Operating Control Panel (Fig.2)

2Emergency switch

3Remote Control Signal Receiver

4Power Indicator Lamp (Red)

5OPERATION Indicator Lamp (Green)

6TIMER Indicator Lamp (Yellow)

7Compressor Run Lamp (Green)

8Intake Grill (Fig.3)

9Air Filter

10UP/DOWN Air Direction Flaps

11RIGHT/LEFT Air Direction Louvers (behind UP/DOWN Air Direction Flaps)

200 655

9

240

ceiling concealed type Indoor unit

fan inside

 

motor inside

electric control box

air duct

 

 

evaporator

A

C B

D

@

E

F

G

?

9JLM?HH?MGKJ BGICJLGKJ4 +=JGM4 II,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<>;8

?

@

 

A

B

C

D

E

F

G

 

57.1/5:685

2--

30-

 

12-

//2

3-

//2

./0

//

.--

7.Remote controller functions

Remote controller

29

 

 

 

 

28

 

 

 

 

27

30

 

 

 

 

26

31

 

 

 

B A

25

32

 

 

 

 

24

33

 

 

 

 

23

34

 

A

 

 

22

 

 

U

 

 

21

35

 

T

 

 

 

O

 

 

36

 

OFF

 

20

M

D

 

 

1

 

 

TEMP

 

19

 

 

 

 

 

2

 

 

ON

 

18

 

 

OFF

 

3

SWING

 

FAN

 

 

 

 

 

 

 

 

 

4

MODE

 

SLEEP

17

HEALTH

FRESH

 

5

 

16

 

 

 

 

6

CLOCK

 

SET

15

TIMER

 

HIGH/SO

7

 

14

 

 

 

 

8

FILTER

 

 

13

 

 

 

 

 

RESET

CODE

LIGHT LOCK

12

9

 

 

 

 

11

10

1.TEMP Setting Button

(Used to set temperature. Setting ranges: 16C to 30 C)

In Up/Down function, for controlling up and down filter.

2.SWING Button

If you press this button once, auto swing will be activated.

If you press this button again, the louver will fix in the present position.

4.Operation MODE

Used to select operation mode.

Every time you press MODE button, operation mode changes according to following sequence:

AUTO COOL DRY HEAT FAN

5.HEALTH Button

Used to set health mode, if the unit has the negative ion function

and oxygen bar function.

6.CLOCK Button

Used to set correct time.

7.CLOCK Button

Used to select TIMER ON, TIMER OFF.

(Note: if time of TIMER ON is the same as TIMER OFF,TIMER ON/OFF cannot be set)

8. FILTER Button

Used to set up/down function of filter.

9. CODE Button

Used to select code A or B, for this unit, the code is A.

10.RESET Button

Press this button by using a sharp article to resume the correct operation of the remote controller in case of need, i.e. for example in case of malfunctions due

to electromagnetic noise.

11.LOCK Button

Used to lock operation button and LCD display contents: by pressing this button, other buttons comes

out of function and lock state display appears; if you press it again, lock state will be no more active and lock state display will disappear.

12.LIGHT Button

Used to light the control panel (only for cabinet unit)

13.Up and down Button

Used to set TIMER and CLOCK up or down.

14.HIGH/SO Button

Used to select HIGH or SOFT operation.

3.Power ON/OFF Button

Used for unit start and stop

After power on, the LCD of remote controller will display the previous operation state (except for TIMER,SLEEP and SWING state).

15.SET Button

Used to confirm TIMER and CLOCK settings.

16.FRESH Button

Used to set fresh mode, the unit will draw in fresh air.

17.SLEEP Button

(The clock must be corrected before setting sleep function)

Used to set sleep mode.

NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating. 2.HIGH/SO button

This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high functon" will be cancelled automatically after 15 minutes running.

18.FAN Button

Used to select fan speed:LOW,MID,HIGH,AUTO.

19.TIMER OFF Display 20.CLOCK Display

21.FILTER Display 22.TEMPERATURE Display

23.AUTO SWING Display 24.HIGH/SO Display 25.SIGNAL SENDING Display

26.FRESH AIR Display 27.ELECTRICAL HEATING Display

28.Some other buttons

All these functions are not available now.

29.HEALTH Display

Displays when healthy run function is set.

30.DEHUMIDIFICATION Display 31.Operation MODE Display

AUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN

32.SLEEP State Display 33.BATTERY Energy Display

Notify the user when it is time to change the batteries.

34.LOCK State Display 35.FAN SPEED Display

LO

MID

HI

AUTO

AUTO

36.TIMER ON Display

Remote Controller' Operation

When in use, direct signal transmission head to the receiver placed on the indoor unit

The distance between the remote controller and the receiver should be max 7m and there should be no obstacle between them.

Do not throw the remote controller; prevent it from being damaged.

When operating the remote controller in an area where electronically controlled lights are installed or wireless handsets are used, please move closer to the indoor unit as the function of the remote controller might be affected by signals emitted by the above mentioned equipments.

Battery loading

Battery loading

 

*

Batteries are fitted as follows:

*

*

Remove the battery compartment lid

 

*

 

 

Slightly press and disengage the battery compartment lid marked with ìî and then hold the remote controller by the upper section and then remove the battery compartment lid by pressing in the direction of the arrow as shown in the figure above.

Loading the battery

Ensure that batteries are correctly placed in the compartment as required for positive and negative terminals.

Replacing the battery compartment lid

The battery compartment lid is reinstalled in the reverse sequence.

Display review

Press the button to see if batteries are properly fitted. If no display appears, refit the batteries.

Confirmation indicator

If no indication is displayed after press ON/OFF button, reload the batteries.

Caution:

If the remote controller does not operate as designed after fitting new batteries of the same

type, press the Reset button (marked ) with a pointed article.

Note:

It is recommended that the batteries be removed from the compartment if the remote controller is not used for an extended period.

The remote controller is programmed for automatic test of operation mode after the batteries are replaced. When the test is conducted, all icons will appear on the screen and then disappear if the batteries are properly fitted.

Clock Set

When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows:

1.Press CLOCK button, clock indication of " AM " or " PM " flashes. 2.Press or to set correct time. Each press will increase or decrease

1 min. If the button is kept pressed, time will increase or decrease quickly. 3.After time setting is confirmed, press "SET" : AM or PM stop flashing,

while clock starts working.

Note:AM means morning and PM means afternoon.

MODE

 

SLEEP

HEALTH

FRESH

 

CLOCK

 

SET

1 TIMER

2

HIGH/SO 3

FILTER

 

 

RESET CODE

LIGHT

LOCK

Fan Operation

A

A

U

T

O

TEMP

ON

SWING

4 OFF

FAN

 

 

1

3

MODE

 

SLEEP

2HEALTH

FRESH

 

CLOCK

 

SET

TIMER

 

HIGH/SO

FILTER

 

 

RESET

CODE

LIGHT

LOCK

1.Unit start

Press ON/OFF button to start your air conditioner. Previous operation status appears on LCD (except for TIMER, SLEEP, and SWING setting).

2.Select operating mode

Press MODE button. At each press, operation mode changes as follows:

AUTO COOL DRY HEAT FAN

Then select FAN

3. Adjust fan speed

Press FAN button. At each press, fan speed changes as follows:

 

LOW

MID

HIGH

 

 

 

 

 

 

Air conditioner will run at the selected fan speed. When in AUTO mode, unit will adjust fan speed according to room temperature automatically.

4. Unit stop

Press ON/OFF button to stop unit.

About FAN mode

When the air conditioner runs in FAN mode, it is not possible to select AUTO FAN or to set temperature.

AUTO, COOL , HEAT and DRY Operation

A

A

U

T

O

1. Unit start

Press ON/OFF button,unit starts.

Previous operation status appears on LCD (except for TIMER, SLEEP and SWING setting)

2.Select operation mode

Press MODE button. At each press, operation mode changes as follows:

TEMP

3

 

ON

3

 

OFF

SWING

 

FAN

5

1

 

4

MODE

 

 

SLEEP

2 HEALTH

FRESH

 

CLOCK

 

 

SET

TIMER

 

 

HIGH/SO

FILTER

 

 

 

RESET CODE

LIGHT

LOCK

COOL operation starts when room temp.is higher than temp.

setting.

Ultra-low air flow

Temp. setting +2C

Temp.setting

AUTO COOL DRY HEAT FAN

Then select AUTO run or select COOL operation or

select DRY operation or select HEAT operation

3.Temperature setting

Press TEMP button.

Every time the button is pressed, temp. setting increases

1 C; if the button is kept pressed, temp. setting will increase quickly.

Every time the button is pressed, temp. setting decreases

1 C, if the button is kept pressed, temp. setting will decrease quickly.

Set proper temperature

4.Adjust FAN button

Press FAN button. At each press, fan speed changes as follows:

A

U

T

O

AUTO LOW MID HIGH

Air conditioner will run at the selected fan speed.

5. Unit stop

Press ON/OFF button,unit stops.

On reaching temp.setting +2 C, unit will run in mild DRY mode.

In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner will select COOL, HEAT or FAN mode automatically according to the room temperature.

In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will only run FAN operation.

In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.

Adjusting air flow direction

AUTO SWING

Press SWING button.

Up and down airflow varies upwards and downwards. Left and right airflow varies left and right sides.

A

A

 

 

U

 

 

T

 

 

O

 

 

 

TEMP

 

 

ON

 

SWING

OFF

FAN

 

MODE

 

SLEEP

HEALTH

FRESH

 

CLOCK

 

SET

TIMER

 

HIGH/SO

FILTER

 

 

RESET CODE

LIGHT LOCK

AUTO SWING

When the automatic swing louver moves to the proper angle, press SWING button can fix the airflow direction.

Always use SWING button on the remote controller to adjust flaps. Adjusting them by hand may result in air conditioner's abnormally running.

In COOL or DRY mode, do not leave the louver in downward position for a long time, as the water vapor close to the grille may condense and water may drop from the air conditioner.

Please carefully set temperature when children, old or infirm people ues the air conditioner.

In case of great humidity, If the vertical flaps are completely turned towards left or right, the louver will drop water.

Never adjust the louver directly by hand, as this could make it work abnormally.If the louver work abnormally, stop unit, restart and adjust the louver by remote controller.

After unit stops:

Displays on the LCD disappear.

All indicators on the indoor unit go out.

Swing louver automatically close the air outlet.

Hints:

As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful for a better air circulation

As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for a better air circulation.

Be careful not to catch a cold when cold air blows downward directly.

Sleep Function

Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make you sleep more comfortably.

Before using this function, the clock must be set.

Use of SLEEP function

After the unit's start, set running mode and then press SLEEP button once to make the air conditioner

have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button /: you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1

hour: "xh" and "OFF" indications appear on the display.

Operation Mode

1.In COOL, DRY mode

One hour after sleeping operation start, the temperature is 1C higher than the setting one. After another hour, temperature rises 1 C: sleep run continuously for another 6 hours and then stops. The actual temperature is higher than the setting one which is to prevent from being too cold to your sleep.

2.In HEAT mode

One hour after sleeping operation start, the temperature is 2 C lower than the setting one. After another hour, temperature decreases by 2 C more. Temperature will automatically rise by 1 C after another 3 hours' continuous operation. The actual temperature is lower than the setting one which is to prevent from being too hot to your sleep.

3.In AUTO mode.

The air conditioner will run in corresponding sleep operation according to the automatically selected operation mode.

Notes:

SLEEP RUN BEGINS

SLEEP RUN STOPS

about 6 hrs

 

increase 1 C

1 hrs

increase 1 C

SETTING T

SHUT DOWN

In COOL,DRY mode

SETTING T

 

SHUT DOWN

1 hrs

decrease 2 C

1 hrs

 

 

decrease 2 C

 

 

about 6 hrs

 

3 hrs

increase 1 C

SLEEP RUN BEGINS

 

SLEEP RUN STOPS

In HEAT mode

 

 

A

 

 

A

 

 

U

 

 

T

 

 

O

 

 

OFF

After setting SLEEP function, it is not possible to set clock.

If set-sleep time does not reach 8 hours, unit will automatically stop operation after set time is reached.

Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first, then set SLEEP. After set SLEEP function, the TIMER function cannot be set.

 

TEMP

 

 

ON

 

SWING

OFF

FAN

 

MODE

 

SLEEP

HEALTH

FRESH

 

CLOCK

 

SET

TIMER

 

HIGH/SO

FILTER

 

 

RESET CODE

LIGHT LOCK

Timer ON/OFF Function

Set clock correctly before starting TIMER operation

A

1.Unit start

After unit start, select your desired operation mode (operation mode will be displayed on LCD)

 

TEMP

 

 

 

ON

 

 

SWING

OFF

1

FAN

 

 

 

 

MODE

 

 

SLEEP

HEALTH

FRESH

 

 

CLOCK

 

 

SET

TIMER

 

3 HIGH/SO 4

2 FILTER

 

 

 

RESET CODE

LIGHT LOCK

Note:

2.TIMER mode selection

Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:

 

 

ON

 

 

 

OFF

 

 

 

 

ON

 

 

 

OFF

 

 

blank

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AM 12:00

PM 12:00

AM 12:00

 

 

PM 12:00

TIMER ON

TIMER OFF

 

TIMER ON-OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Then select TIMER mode as needed (TIMER ON or TIMER OFF). Now ON or OFF will flash.

3.TIMER setting (press time adjust buttons )

Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time changes quickly.

Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed, time changes quickly.

It can be adjusted within 24 hours at will.

4.Confirm setting

After setting correct time, press SET button to confirm time. Now ON or OFF stop flashing.

Time displayed: unit starts or stops at X hour X min (TIMER ON or TIMER OFF)

5.Cancel TIMER mode

Just press TIMER button several times until TIMER mode disappears.

Hints:

After replacing batteries or if a power failure occurs, TIMER setting must be reset.

Remote controller has memory function. When you use TIMER mode next time, just press SET button after mode selection if timer setting is the same as the previous one.

After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time, just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you can adjust clock). 5 seconds later, the display will show TIMER time again.

Timer ON-OFF Function

Set clock correctly before starting TIMER operation

1.Unit start

A

After unit start, select your desired operation mode (operation mode will be displayed on LCD)

2.TIMER mode selection

Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:

ON OFF ON OFF blank

OFF

PM 12:00

AM 12:00

PM 12:00

AM 12:00

TIMER ON

TIMER OFF

TIMER ON-OFF

 

TEMP

 

 

ON

 

SWING

OFF

FAN

 

 

 

1

MODE

 

SLEEP

HEALTH

FRESH

 

CLOCK

 

SET

2 TIMER

 

3HIGH/SO 6

4FILTER 5

 

 

RESET CODE

LIGHT LOCK

Then select TIMER ON-OFF mode. ON will flash.

3.Time setting for TIMER ON

Press time button

Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time will changes quickly.

Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed ,time will changes quickly.

It can be adjusted within 24 hours at will.

AM refers to morning and PM refers to afternoon.

4.Timer confirming for TIMER ON

After setting correct time, press TIMER button to confirm time. Now

ON stops to flash, while OFF starts flashing.

Time displayed : unit starts at X hour X min.

5.Timer setting for TIMER OFF

Press time buttonsand follow the same procedures in " Time setting for TIMER ON"

6.Time confirming for TIMER OFF

After time setting, press SET button to confirm time. OFF stops to flash. Time displayed: unit starts at X hour X min.

7.Canel TIMER mode

Just press TIMER button several times until TIMER mode disappears.

According to the time setting sequence of TIMER ON and TIMER OFF, either start-stops or stops-start can be realized.

If the time setting of TIMER ON is the same as TIMER OFF, TIMER ON-OFF function cannot be set.

Filter Up/Down

(Only for AB182ACBEA)

A

 

TEMP

 

 

ON

 

SWING

OFF

FAN

 

MODE

 

SLEEP

HEALTH FRESH

 

CLOCK

 

SET

TIMER

 

HIGH/SO

FILTER

 

 

RESET CODE1

LIGHT

LOCK

 

 

After the air conditioner has operated for a certain period, dust has accumulated on the filter, and the filter up/down function can be used to clean it.

1.Whether unit starts or stops, continuously press FILTER button for 3 seconds, and enter the filter up/down waiting status (when unit stops, the yellow TIMER indicator flashes, and filter and clock indication are displayed on the remote controller. Only the FILTER button, the temperature buttons "" "" and time buttons are active).

2.Press temperature "" button or time " " button in filter up/down waiting status: the up/down mechanism makes the filter moving downward and does not stop until it has reached the maximum limit.

3.Press temperature"" button or time" "button in filter up/down waiting status: the up/down mechanism makes the filter to moving upward till near the surface board and

then automatically adjusts it to reset (when adjusting to reset, it will not be controlled by the remote controller till the adjustment is finished).

4.During moving downward, press temperature"" button or time " " button: moving stops.

5.During moving downward, press temperature"" button or time " " button: moving stops.

6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter goes back to the original position, the remote controller goes back to off status and only clock is displayed).

Note:

If the filter does not thoroughly go back to the original position, only needs to operate several times repeatedly.

" High mode " Operation

Outline of operation in "High Mode"

A

This function is suitable when the set temperature must be reached in the shortest delay.

The button "HIGH/SO", referred to this function, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).

A U T O

 

TEMP

 

 

ON

 

SWING

OFF

FAN

 

MODE

 

SLEEP

HEALTH

FRESH

 

CLOCK

 

SET

TIMER

 

HIGH/SO

FILTER

 

1

RESET CODE

LIGHT LOCK

ON

Press the HIGH/SO button noce

The indication appears on the display of the remote controller and operation in "High Mode" starts.

The AUTO fan speed is automatically set and the corresponding indication is also displayed.

OFF

Press the HIGH/SO button twice

If the button is pressed once, the indication is displayed on the remote controller. If you press the button once again, the indication disappears, regular operation is restored and fan speed goes back to the mode set before "High Mode" operation.

NOTICE:

When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time.

Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.

" Soft mode " Operation

A

A

 

 

U

 

 

T

 

 

O

 

 

OFF

 

 

TEMP

 

 

ON

 

SWING

OFF

FAN

 

MODE

 

SLEEP

HEALTH

FRESH

 

CLOCK

 

SET

TIMER

 

HIGH/SO

FILTER

 

1

RESET CODE

LIGHT LOCK

Outline of operation in "Soft Mode"

Operation in "Soft Mode", more silent, is suitable when noises should be reduced, e.g.. for reading or sleeping.

The button "HIGH/SO", referred to this operation, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).

 

ON

Press the HIGH/SO button twice

The indication

appears on the display of the remote

controller and operation in "Soft Mode" starts.

The AUTO fan speed is automatically set and the corresponding indication is also displayed.

OFF

Press the HIGH/SO button twice

If the button is pressed once, the indication is disappears from the remote controller's display. If you press the button once again, regular operation is restored and fan speed goes back to the mode set before "Soft Mode" operation.

NOTICE:

When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time.

Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.

AIR FLOW DIRECTION ADJUSTMENT PROCEDURE-Cassette type

Adjusting up/down air flow direction

Up/down direction can be adjusted by using the SWING button on the remote controller.

Each time pressing this button, the mode changes in the following sequence.

SWING No indication (louver stopped)

Change to the AIRFLOW mode.

SWING

 

LOUVER STOPPED

 

 

 

When the LOUVER button is pushed during SWING mode, it stops swinging at the just angle.

Louver moves in upward and downward directions continuously.

CAUTION

Avoid direct air flow to the body for many hours.

Avoid downward blowing operation of cooling mode for many hours. Do not touch the swing louver during swing operation.

AIR FLOW DIRECTION ADJUSTMENT PROCEDURE-Convertible type

Adjusting up/down air flow direction

Up/down direction can be adjusted by using the SWING button on the remote controller. Each time pressing this button, the mode changes in the following sequence.

SWING No indication (louver stopped)

Change to the AIRFLOW mode.

SWING

LOUVER STOPPED

Louver moves in upward and downward directions continuously.

CAUTION

Avoid direct air flow to the body for many hours.

Avoid downward blowing operation of cooling mode for many hours.

Do not touch the swing louver during swing operation.

When the LOUVER button is pushed during SWING mode, it stops swinging at the just angle.

Recommendable stopping angle of the louver

COOL

 

and

 

DRY

(Horizontal Blowing)

 

HEAT

(Downward Blowing)

Wired controller functions:

Buttons and functions of the wired controller

CLOCK

MODE

Used to adjust time.

Used

for select

TIMER

indoor

operation

mode.

 

 

 

Used to set timer

 

FAN SPEED

mode.

 

CHECK

 

Used for select indoor

Auto-diagnostic

 

air flow.

 

 

button.

 

SWING

 

 

Used for setting

 

 

indoor swing mode.

 

HEALTH

 

 

 

HEALTH

F

SET RECOVERY

Used for setting

C

 

 

 

 

indoor health

 

CHECK

function.

 

 

TEMP + -

+ -

 

Used for changing

 

 

set temperature.

stands for time plus/minus,

 

RECOVERY

used to adjust time.

 

 

 

FILTER

 

 

used to switch

 

 

over air-

 

Filter-cleaned button.

exchanging mode.

 

POWER ON/OFF

 

 

RESET

 

 

Reset correct

 

 

 

 

 

Used for unit start and

mode button.

stop.

 

Cautions:

Note:

On cooling only unit, heating

The above information is the explanation of

mode is not available.

the displayed information therefore varies

 

with those displayed in actual operation.

Buttons function

MODE used for select indoor operation mode. FAN used for select indoor air flow. SWING used for setting indoor swing mode. HEALTH used for setting indoor health function. TEMP + - used for changing set temperature. CLOCK used to adjust time.

+ - stands for time plus/minus, used to adjust time.

TIMER used to set timer mode.

RECOVERY used to switch over air-exchanging mode. CHECK auto-diagnostic button. FILTER filter-cleaned button.

RESET reset correct mode button.

Display description

[MODE] [AUTO] auto operation mode

[MODE] [FAN ONLY] air-throwing mode

[MODE] [COOL] Cooling operation mode

[MODE] [DRY] Dehumidification mode [MODE] [HEAT] Heating operation mode

[MODE] [HEAT] [TES] In heating mode, auxiliary electric heater is running. Only when the unit with auxiliary electric heater is in auxiliary electric heating mode, it will display.

[FAN] [AUTO] auto fan running