Service Manual
Commercial Air Conditioning
14 18 Universal Outdoor Fixed Frequency Series
AC142ACBEA+AU142AFBEA
AD142AMBEA+AU142AFBEA
AB142ACBEA+AU142AFBEA
AC182ACBEA+AU182AFBEA
AD182AMBEA+AU182AFBEA
AB182ACBEA+AU182AFBEA
Features
Fixed frequency
Auto-restart function
Group control(if with a group controller)
Auto-changeover
The Outdoor unit can match with cassette \convertible\duct indoor Weekly timing(if with a weekly timer)
With new environment friendly refrigerant R407C
Haier Group
MANUAL CODE: SYJS-007 rev.0
CONTENTS
CONTENTS
Contents
1.Description of Products & Features…………...…….1
2.Specifications…………………. ………………...……3
3.Mechnical Data………………..…...………………. 7
4. Electrical Data…… …......….... |
…..… |
36 |
5.Performance Curves ………...….…………. ………..45 |
||
6. Charts ……………………......... |
……..…… ..………47 |
|
7. Electrical Control Functions ….......... |
………………56 |
|
8.Diagnostic Information (Trouble Shooting) |
...............62 |
|
9. Installation Instructions and Maintenance ….......…67 |
||
10. Exploded Views and Parts lists............... |
…. ……102 |
- 1 -
DESCRIPTION OF PRODUCTS & FEATURES
1 DESCRIPTION OF PRODUCTS & FEATURES
1.1 Products coding direction
Old code
H BU – 14 H A 03/ R1
Refers to HFC refrigerant, fixed frequency
Power: 03(230V/50Hz).04(240V/50Hz).12(115V/60Hz).13(230v/60Hz) Design series number
“H” refer to cooling and heating, ”C” refer to cooling only Nominal cooling capacity (BTU/h), 14=14000BTU/h
Indoor unit code: "B" Cassette type; "C" convertible "D" Duct type
“H” means “Haier”
New code
A B 14 2 A C B E A
Climate type: T1 (see table 1)
Design number (E stands for fixed frequency heat pump air conditioner) Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407
Appearance character
Product series: one wall-mounted split type
Applicable voltage: 2 stands for 220-240V/50Hz,4 stands for 220v/60Hz N stand for 380V/50Hz
Cooling / Heating capacity,14=14000BTU/h
Product type : “B” stands for cassette type, “C” stands for convertible type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller system, "E" stands for ceiling concealed type, “U” stands for outdoor unit
Air conditioner
1.2 Brief Introduction to T1T2T3 working condition
Table 1
Type of Air Conditioner |
|
|
Climate type |
|
|
|
|
T1 |
|
T2 |
|
T3 |
|
|
|
|
|
|||
Cool only |
18 |
43 |
10 |
35 |
21 |
52 |
Heat pump |
-7 |
43 |
-7 |
35 |
-7 |
52 |
Electricity heating |
|
43 |
|
35 |
|
52 |
1.3 Operating Range of air conditioners
Normal condition
Operation |
Operation Range Outside / Inside |
Cooling |
150C – 43oC |
Drying |
150C – 43oC |
Heating |
-7oC – 18oC |
DESCRIPTION OF PRODUCTS & FEATURES
1.4 Products characteristic
The outdoor unit can match with different indoor unit
The indoor unit can be cassette type\convertible type and duct type. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish appearance of air conditioner allows it to blend right into ceiling.
Superbly efficient healthy filter
Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently.
Flexible and easy installation
Slim design with machine body, completely ceiling concealed and portable shape, all make it greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift, which allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit people's comfortable need much more.
ESP can be from 0Pa to 50Pa; in the meantime, the duct unit is equipped with a filter and air return box.
Auto-Restart function
When meeting a power failure during running, no matter how long it will be, once the power is restored, air conditioner will automatic restart with the previous status.
Safety and reliable control due to various signal controls
1.Inputting with press buttons on the panel
2.Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors)
3.Piping pressure signals 4.Compressor current signals 5.Testing signals
6.System time-shorten signal 7.Water overflowing signal
8.Communication signals between indoor unit and front plate or between indoor unit and outdoor unit.
NEW Universal convenient remote-controller
When using remote-controlling mode, it is comfortable and convenient to operate. The remote controller is used as new style; it looks like a phone, very compact. It is a universal controller and can be used for any unit such as single unit, multi free unit, MRV, etc. compatible with the old ones.
NEW New wired controller
One wired controller can control 16 indoor units without any other device such as detector.
Silent design
The use of radial outward flow turbine fan produces large airflow volume and acts to significantly decrease operating noise.
NEW Low ambient temperature cooling function (optional)
Equipped with high/low pressure protection switch
2 SPECIFICATIONS
item |
|
|
|
|
|
|
Model |
|
AU142AFBEA/AB142ACBEA |
||||||
Function |
|
|
|
|
|
|
|
|
|
|
|
cooling |
|
heating |
|
Capacity |
|
|
|
|
|
|
|
KW |
|
4.10 |
|
4.39 |
|||
Capacity |
|
|
|
|
|
|
BTU/h |
14000 |
|
15000 |
|||||
Total power input |
|
|
|
|
|
|
|
W |
|
1550 |
|
1450 |
|||
Max. power input |
|
|
|
|
|
|
|
W |
|
1800 |
|
1800 |
|||
EER or COP |
|
|
|
|
|
W/W |
|
2.65 |
|
3.03 |
|||||
Dehumidify capacity |
|
|
|
|
|
10 |
|
|
|
2.95 |
|
||||
|
|
|
|
|
|
³×m³/h |
|
|
|
||||||
Power cable |
|
|
|
|
|
|
|
|
|
|
2X2.0+2X0.75 |
||||
Power source |
|
|
|
|
|
|
V |
|
Hz |
1PH 220V-230V 50HZ |
|||||
|
|
|
|
|
N |
|
|
|
|
|
|||||
Running /Max.Running current |
|
|
|
A / A |
|
cooling:7.8/8.5 |
heating:6.8/8.5 |
||||||||
Start current |
|
|
|
|
|
|
|
A |
|
40 |
|
||||
|
|
Unit model (color) |
|
|
|
|
|
|
|
|
AB142ACBEA (grey) |
||||
|
|
Fan |
|
|
type×number |
|
|
|
|
|
|
centrifugal×1 |
|||
|
|
|
|
|
speed (H-M-L) |
|
|
r/min |
900±30/850±30/750±30/610/540 |
||||||
|
|
|
|
|
Fan motor output power |
|
|
W |
|
20 |
|
||||
|
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
|
1100/1000/900 |
|||||
|
|
Heat exchanger |
|
Type / Diameter |
|
mm |
|
9.52 |
|
||||||
unit |
|
|
|
|
Total Area |
|
|
|
|
m² |
|
653*200*65 |
|||
|
|
|
|
Temp. scope |
|
|
|
|
|
5-10 |
|
||||
indoor |
|
|
|
|
|
|
|
|
|
||||||
|
Dimension |
|
|
External |
|
L×W×H |
mm×mm×mm |
700*570*276 |
|||||||
|
|
|
|
|
|||||||||||
|
|
|
|
|
Package |
|
L×W×H |
mm×mm×mm |
775*715*361 |
||||||
|
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
|
PVC 26/32 |
|||||||
|
|
Control type |
(Remote /wired) |
|
|
|
|
|
|
|
remote |
||||
|
|
Fresh air hole dimension |
|
|
|
mm |
|
100 |
|
||||||
|
|
Electricity Heater |
|
|
|
kW |
|
0 |
|
||||||
|
|
Noise level |
(H-M-L) |
|
|
dB(A) |
53.5/51.5/49.8 |
||||||||
|
|
Weight |
(Net / Shipping) |
|
kg / kg |
26/28 |
|
||||||||
Panel |
|
Dimension |
|
|
External |
|
L×W×H |
mm×mm×mm |
630*630*93 |
||||||
|
|
|
|
Package |
|
L×W×H |
mm×mm×mm |
685*685*155 |
|||||||
|
|
|
|
|
|
||||||||||
|
|
Weight |
|
(Net / Shipping) |
|
kg / kg |
4.2/6.3 |
||||||||
|
|
Unit model (color) |
|
|
|
|
|
|
|
AU142AFBEA WHITE |
|||||
|
|
Compressor |
|
|
Model / |
Manufacture |
|
|
|
|
|
PG260X2CS-4KT1 toshiba |
|||
|
|
|
|
Type |
|
|
|
|
|
|
|
rotary |
|||
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
Type × Number |
|
|
|
|
|
Axial-flow |
||||
|
|
Fan |
|
|
Speed |
|
|
|
r/min |
820±30 |
|||||
|
|
|
|
Fan motor output power |
|
kW |
|
35 |
|
||||||
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
Air-flow(H-M-L) |
|
m³/h |
2300 |
|
||||||
|
|
Heat exchanger |
Type / Diameter |
|
mm |
|
TP2M/9.52 |
||||||||
unit |
|
Total area |
|
|
|
m² |
|
0.92 |
|
||||||
|
|
|
|
Temp. scope |
|
|
|
|
|
43-60 |
|
||||
Outdoor |
|
|
|
|
|
|
|
|
|
||||||
|
Dimension |
|
|
External |
|
L×W×H |
mm×mm×mm |
780x650x250 |
|||||||
|
|
|
|
|
|||||||||||
|
|
|
|
Package |
|
L×W×H |
mm×mm×mm |
903x714x343 |
|||||||
|
|
|
|
|
|
||||||||||
|
|
Drainage pipe |
|
(material , |
I.D./O.D.) |
|
mm |
|
|
/ |
|
||||
|
|
Refrigerant control method |
|
|
mm/mm |
main: 1.7*400 auxiliary:2.0*140 |
|||||||||
|
|
Defrosting |
|
|
|
|
|
|
|
|
|
|
auto |
||
|
|
Volume of Accumulator |
|
|
|
|
L |
|
|
/ |
|
||||
|
|
Noise level |
|
|
|
|
|
dB(A) |
58/--/50 |
||||||
|
|
Type of Four way |
valve |
|
|
|
|
|
|
|
|
/ |
|
||
|
|
material of reduce noise |
|
|
|
|
|
|
|
XPE |
|||||
|
|
crankcase heater power |
|
|
|
|
W |
|
|
/ |
|
||||
|
|
Weight |
|
(Net / Shipping) |
|
kg / kg |
41/43 |
|
|||||||
|
|
Refrigerant |
|
|
Type / Charge |
|
|
|
g |
|
R407C |
1600 |
|||
PIPING |
|
|
|
Recharge quantity |
|
g/m |
|
50 |
|
||||||
|
|
|
|
|
|
|
|||||||||
|
Pipe |
|
|
Liquid |
|
|
|
mm |
|
6.35 |
|
||||
|
|
|
Gas |
|
|
|
mm |
|
12.7 |
|
|||||
|
|
|
|
|
|
|
|
|
|||||||
|
Connecting Method |
|
|
|
|
|
|
|
flared |
||||||
|
|
Between I.D &O. |
MAX.Drop |
|
|
|
m |
|
20 |
|
|||||
|
|
|
|
|
|
|
|
|
|||||||
|
|
MAX.Piping length |
|
|
m |
|
30 |
|
|||||||
|
|
|
|
|
|
|
|
|
item |
|
|
|
|
|
Model |
AU142AFBEA/AC142ACBEA |
||||
Function |
|
|
|
|
|
|
|
cooling |
|
heating |
|
Capacity |
|
|
|
|
|
KW |
4.10 |
|
4.39 |
||
Capacity |
|
|
|
|
|
BTU/h |
14000 |
|
15000 |
||
Total power input |
|
|
|
|
|
W |
1550 |
|
1450 |
||
Max. power input |
|
|
|
|
|
W |
1800 |
|
1800 |
||
EER or COP |
|
|
|
|
|
W/W |
2.65 |
|
3.03 |
||
Dehumidify capacity |
|
|
|
|
|
10 ³×m³/h |
2.95 |
|
|||
Power cable |
|
|
|
|
|
|
2X2.0+2X0.75 |
||||
Power source |
|
|
|
|
|
N V Hz |
1PH 220V-230V 50HZ |
||||
Running /Max.Running current |
|
|
|
A / A |
cooling:7.8/8.5 |
heating:6.8/8.5 |
|||||
Start current |
|
|
|
|
|
A |
40 |
|
|||
|
|
Unit model (color) |
|
|
|
|
|
AC142ACBEA (white) |
|||
|
|
Fan |
|
type×number |
|
|
|
|
centrifugal×2 |
||
|
|
|
|
speed (H-M-L) |
|
|
r/min |
1350±30/1280±30/1210±30 |
|||
|
|
|
|
Fan motor output power |
|
W |
20W |
||||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
1100/1000/900 |
|||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
9.52 |
|
|||
unit |
|
|
|
Total Area |
|
|
|
m² |
653*200*65 |
||
|
|
|
Temp. scope |
|
|
|
5-10 |
||||
indoor |
|
|
|
|
|
||||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
830*450*225 |
|||
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
976*526*288 |
|||
|
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
PVC 26/32 |
||||
|
|
Control type |
(Remote /wired) |
|
|
|
remote |
||||
|
|
Fresh air hole dimension |
|
|
|
mm |
|
/ |
|
||
|
|
Electricity Heater |
|
|
|
|
kW |
|
/ |
|
|
|
|
Noise level |
(H-M-L) |
|
|
dB(A) |
53.5/51.5/49.8 |
||||
|
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
20/22 |
||||
Panel |
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
|
/ |
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
|
/ |
|
||
|
|
|
|
|
|
|
|||||
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
|
/ |
|
|||
|
|
|
|
|
|
||||||
|
|
Unit model (color) |
|
|
|
|
|
AU142AFBEA WHITE |
|||
|
|
Compressor |
|
Model / Manufacture |
|
|
PG260X2CS-4KT1 toshiba |
||||
|
|
|
Type |
|
|
|
|
rotary |
|||
|
|
|
|
|
|
|
|
||||
|
|
|
|
Type × Number |
|
|
|
Axial-flow |
|||
|
|
Fan |
|
Speed |
|
|
|
r/min |
820±30 |
||
|
|
|
Fan motor output power |
|
kW |
35 |
|
||||
|
|
|
|
|
|
||||||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
2300 |
|||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
TP2M/9.52 |
||||
unit |
|
Total area |
|
|
|
m² |
0.92 |
|
|||
|
|
|
Temp. scope |
|
|
|
43-60 |
||||
Outdoor |
|
|
|
|
|
||||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
780x650x250 |
|||
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
903x714x343 |
||||
|
|
|
|
|
|||||||
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
|
/ |
|
|||
|
|
|
|
|
|
||||||
|
|
Refrigerant control method |
|
|
|
mm/mm |
main: 1.7*400 auxiliary:2.0*140 |
||||
|
|
Defrosting |
|
|
|
|
|
|
auto |
||
|
|
Volume of Accumulator |
|
|
|
L |
|
/ |
|
||
|
|
Noise level |
|
|
|
|
|
dB(A) |
58/--/50 |
||
|
|
Type of Four way |
valve |
|
|
|
|
|
/ |
|
|
|
|
material of reduce noise |
|
|
|
|
XPE |
||||
|
|
crankcase heater power |
|
|
|
W |
|
/ |
|
||
|
|
Weight |
(Net / Shipping) |
|
|
|
kg / kg |
41/43 |
|||
|
|
Refrigerant |
|
Type / Charge |
|
|
g |
R407C |
1600 |
||
PIPING |
|
|
Recharge quantity |
|
g/m |
50 |
|
||||
|
|
|
|
|
|||||||
|
Pipe |
|
Liquid |
|
|
|
mm |
6.35 |
|
||
|
|
Gas |
|
|
|
mm |
12.7 |
|
|||
|
|
|
|
|
|
|
|||||
|
Connecting Method |
|
|
|
|
|
flared |
||||
|
|
Between I.D &O.D |
MAX.Drop |
|
|
|
m |
20 |
|
||
|
|
MAX.Piping length |
|
m |
30 |
|
|||||
|
|
|
|
|
|
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB
item |
|
|
|
|
|
Model |
AU142AFBEA/AD142AMBEA |
||||
Function |
|
|
|
|
|
|
|
cooling |
|
heating |
|
Capacity |
|
|
|
|
|
KW |
4.10 |
|
4.39 |
||
Capacity |
|
|
|
|
|
BTU/h |
14000 |
|
15000 |
||
Total power input |
|
|
|
|
|
W |
1550 |
|
1450 |
||
Max. power input |
|
|
|
|
|
W |
1800 |
|
1800 |
||
EER or COP |
|
|
|
|
|
W/W |
2.65 |
|
3.03 |
||
Dehumidify capacity |
|
|
|
|
|
10 ³×m³/h |
2.95 |
||||
Power cable |
|
|
|
|
|
|
2X2.0+2X0.75 |
||||
Power source |
|
|
|
|
|
N V Hz |
1PH 220V-230V 50HZ |
||||
Running /Max.Running current |
|
|
|
A / A |
cooling:7.8/8.5 |
|
heating:6.8/8.5 |
||||
Start current |
|
|
|
|
|
A |
40 |
||||
|
|
Unit model (color) |
|
|
|
|
|
AD142AMBEA (white) |
|||
|
|
Fan |
|
type×number |
|
|
|
|
centrifugal×2 |
||
|
|
|
|
speed (H-M-L) |
|
|
r/min |
1290±30/1220±30/940±30/710±40 |
|||
|
|
|
|
Fan motor output power |
|
W |
20W |
||||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
950/850/770 |
|||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
9.52 |
||||
unit |
|
|
|
Total Area |
|
|
|
m² |
653*200*65 |
||
|
|
|
Temp. scope |
|
|
|
5-10 |
||||
indoor |
|
|
|
|
|
||||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
830*450*225 |
|||
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
980*543*305 |
|||
|
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
PVC 18/21 |
||||
|
|
Control type |
(Remote /wired) |
|
|
|
remote |
||||
|
|
Fresh air hole dimension |
|
|
|
mm |
|
/ |
|||
|
|
Electricity Heater |
|
|
|
|
kW |
|
/ |
||
|
|
Noise level |
(H-M-L) |
|
|
dB(A) |
40/38/36 |
||||
|
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
25/28 |
||||
Panel |
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
|
/ |
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
|
/ |
|||
|
|
|
|
|
|
||||||
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
|
/ |
||||
|
|
|
|
|
|||||||
|
|
Unit model (color) |
|
|
|
|
|
AU142AFBEA WHITE |
|||
|
|
Compressor |
|
Model / Manufacture |
|
|
PG260X2CS-4KT1 toshiba |
||||
|
|
|
Type |
|
|
|
|
rotary |
|||
|
|
|
|
|
|
|
|
||||
|
|
|
|
Type × Number |
|
|
|
Axial-flow |
|||
|
|
Fan |
|
Speed |
|
|
|
r/min |
820±30 |
||
|
|
|
Fan motor output power |
|
kW |
35 |
|||||
|
|
|
|
|
|||||||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
2300 |
|||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
TP2M/9.52 |
||||
unit |
|
Total area |
|
|
|
m² |
0.92 |
||||
|
|
|
Temp. scope |
|
|
|
43-60 |
||||
Outdoor |
|
|
|
|
|
||||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
780x650x250 |
|||
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
903x714x343 |
||||
|
|
|
|
|
|||||||
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
|
/ |
||||
|
|
|
|
|
|||||||
|
|
Refrigerant control method |
|
|
|
mm/mm |
main: 1.7*400 auxiliary:2.0*140 |
||||
|
|
Defrosting |
|
|
|
|
|
|
auto |
||
|
|
Volume of Accumulator |
|
|
|
L |
|
/ |
|||
|
|
Noise level |
|
|
|
|
|
dB(A) |
58/--/50 |
||
|
|
Type of Four way |
valve |
|
|
|
|
|
/ |
||
|
|
material of reduce noise |
|
|
|
|
XPE |
||||
|
|
crankcase heater power |
|
|
|
W |
|
/ |
|||
|
|
Weight |
(Net / Shipping) |
|
|
|
kg / kg |
41/43 |
|||
|
|
Refrigerant |
|
Type / Charge |
|
|
g |
R407C |
1600 |
||
PIPING |
|
|
Recharge quantity |
|
g/m |
50 |
|||||
|
|
|
|
||||||||
|
Pipe |
|
Liquid |
|
|
|
mm |
6.35 |
|||
|
|
Gas |
|
|
|
mm |
12.7 |
||||
|
|
|
|
|
|
||||||
|
Connecting Method |
|
|
|
|
|
flared |
||||
|
|
Between I.D &O.D |
MAX.Drop |
|
|
|
m |
20 |
|||
|
|
MAX.Piping length |
|
m |
30 |
||||||
|
|
|
|
|
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB
item |
|
|
|
|
|
Model |
AB182ACBEA |
|||
Function |
|
|
|
|
|
|
|
cooling |
heating |
|
Capacity |
|
|
|
|
|
KW |
5.27 |
5.86 |
||
Capacity |
|
|
|
|
|
BTU/h |
18000 |
20000 |
||
Total power input |
|
|
|
|
|
W |
2000 |
1900 |
||
Max. power input |
|
|
|
|
|
W |
2400 |
2800 |
||
EER or COP |
|
|
|
|
|
WW |
2.64 |
3.08 |
||
Dehumidify capacity |
|
|
|
|
|
10 ³×m³/h |
1.2 |
|||
Power cable |
|
|
|
|
|
|
4X0.75 |
|||
Power source |
|
|
|
|
|
N V Hz |
1PH 220V-230V 50HZ |
|||
Running /Max.Running current |
|
|
|
A / A |
cooling: 10/12 |
heating: 9.5/14 |
||||
Start current |
|
|
|
|
|
A |
50 |
|||
|
|
Unit model (color) |
|
|
|
|
|
AB182ACBEA(WHITE) |
||
|
|
Fan |
|
type×number |
|
|
|
|
CENTRIFUGAL*1 |
|
|
|
|
|
speed (H-M-L) |
|
|
r/min |
500±30/450±40/380±50 |
||
|
|
|
|
Fan motor output power |
|
W |
0.04 |
|||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
1050/945/790 |
||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
TP2M/7 |
|||
unit |
|
|
|
Total Area |
|
|
|
m² |
0.199 |
|
|
|
|
Temp. scope |
|
|
|
2-7 |
|||
indoor |
|
|
|
|
|
|||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
750×750×280 |
||
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
900×900×460 |
||
|
|
|
|
|
|
|||||
|
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
PVC 26/32 |
|||
|
|
Control type |
(Remote /wired) |
|
|
|
remote |
|||
|
|
Fresh air hole dimension |
|
|
|
mm |
|
/ |
||
|
|
Electricity Heater |
|
|
|
kW |
|
/ |
||
|
|
Noise level |
(H-M-L) |
|
|
dB(A) |
43/42/40 |
|||
|
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
29/39 |
|||
Panel |
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
750x750x80 |
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
800x800x180 |
|||
|
|
|
|
|
||||||
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
3.5/5.8 |
||||
|
|
|
|
|||||||
|
|
Refrigerant |
|
Type / Charge |
|
|
g |
R407C |
1950 |
|
|
|
|
Recharge quantity |
|
g/m |
30 |
||||
|
|
|
|
|
||||||
PIPING |
|
Pipe |
|
Liquid |
|
|
|
mm |
6.35 |
|
|
|
Gas |
|
|
|
mm |
15.88 |
|||
|
|
|
|
|
|
|||||
|
Connecting Method |
|
|
|
|
flared |
||||
|
|
|
|
|
|
|||||
|
|
Between I.D &O.D |
MAX.Drop |
|
|
|
m |
20 |
||
|
|
MAX.Piping length |
|
m |
30 |
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB
item |
|
|
|
|
|
Model |
AC182ACBEA |
|||
Function |
|
|
|
|
|
|
|
cooling |
heating |
|
Capacity |
|
|
|
|
|
KW |
5.27 |
5.86 |
||
Capacity |
|
|
|
|
|
BTU/h |
18000 |
20000 |
||
Total power input |
|
|
|
|
|
W |
2000 |
1900 |
||
Max. power input |
|
|
|
|
|
W |
2400 |
2800 |
||
EER or COP |
|
|
|
|
|
W/W |
2.64 |
3.08 |
||
Dehumidify capacity |
|
|
|
|
|
10 ³×m³/h |
2.1 |
|||
Power cable |
|
|
|
|
|
|
4X0.75 |
|||
Power source |
|
|
|
|
|
N V Hz |
1PH 220V-230V 50HZ |
|||
Running /Max.Running current |
|
|
|
A / A |
cooling: 10/12 |
heating: 9.5/14 |
||||
Start current |
|
|
|
|
|
A |
50 |
|||
|
|
Unit model (color) |
|
|
|
|
|
AC182ACBEA(WHITE) |
||
|
|
Fan |
|
type×number |
|
|
|
|
CENTRIFUGALX2 |
|
|
|
|
|
speed (H-M-L) |
|
|
r/min |
1070+30/1000+40/940+50 |
||
|
|
|
|
Fan motor output power |
|
W |
0.04 |
|||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
900/840/790 |
||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
TP2M/9.52 |
|||
unit |
|
|
|
Total Area |
|
|
|
m² |
0.199 |
|
|
|
|
Temp. scope |
|
|
|
2-7 |
|||
indoor |
|
|
|
|
|
|||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
1990×655×199 |
||
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
1150×750×300 |
||
|
|
|
|
|
|
|||||
|
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
PVC 18/20 |
|||
|
|
Control type |
(Remote /wired) |
|
|
|
remote |
|||
|
|
Fresh air hole dimension |
|
|
|
mm |
|
/ |
||
|
|
Electricity Heater |
|
|
|
kW |
|
/ |
||
|
|
Noise level |
(H-M-L) |
|
|
dB(A) |
48/44/38 |
|||
|
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
30/39 |
|||
|
|
Refrigerant |
|
Type / Charge |
|
|
g |
R407C |
1950 |
|
|
|
|
Recharge quantity |
|
g/m |
30 |
||||
|
|
|
|
|
||||||
PIPING |
|
Pipe |
|
Liquid |
|
|
|
mm |
6.35 |
|
|
|
Gas |
|
|
|
mm |
15.88 |
|||
|
|
|
|
|
|
|||||
|
Connecting Method |
|
|
|
|
flared |
||||
|
|
|
|
|
|
|||||
|
|
Between I.D &O.D |
MAX.Drop |
|
|
|
m |
20 |
||
|
|
MAX.Piping length |
|
m |
30 |
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB
item |
|
|
|
|
|
Model |
AD182AMBEA |
|||
Function |
|
|
|
|
|
|
|
cooling |
heating |
|
Capacity |
|
|
|
|
|
KW |
5.27 |
5.86 |
||
Capacity |
|
|
|
|
|
BTU/h |
18000 |
20000 |
||
Total power input |
|
|
|
|
|
W |
2000 |
1900 |
||
Max. power input |
|
|
|
|
|
W |
2400 |
2800 |
||
EER or COP |
|
|
|
|
|
WW |
2.64 |
3.08 |
||
Dehumidify capacity |
|
|
|
|
|
10 ³×m³/h |
1.2 |
|||
Power cable |
|
|
|
|
|
|
4X0.75 |
|||
Power source |
|
|
|
|
|
N V Hz |
1PH 220V-230V 50HZ |
|||
Running /Max.Running current |
|
|
|
A / A |
cooling: 10/12 |
heating: 9.5/14 |
||||
Start current |
|
|
|
|
|
A |
50 |
|||
|
|
Unit model (color) |
|
|
|
|
|
AD182AMBEA(WHITE) |
||
|
|
Fan |
|
type×number |
|
|
|
|
CENTRIFUGALx2 |
|
|
|
|
|
speed (H-M-L) |
|
|
r/min |
780+30/710+30/630+50 |
||
|
|
|
|
Fan motor output power |
|
W |
0.13 |
|||
|
|
|
|
Air-flow(H-M-L) |
|
|
m³/h |
850/770/680 |
||
|
|
Heat exchanger |
Type / Diameter |
|
|
mm |
TP2M/9.52 |
|||
unit |
|
|
|
Total Area |
|
|
|
m² |
0.199 |
|
|
|
|
Temp. scope |
|
|
|
2-7 |
|||
indoor |
|
|
|
|
|
|||||
|
Dimension |
|
External |
|
L×W×H |
|
mm×mm×mm |
990×650×300 |
||
|
|
|
Package |
|
L×W×H |
|
mm×mm×mm |
1137×800×320 |
||
|
|
|
|
|
|
|||||
|
|
Drainage pipe |
(material , I.D./O.D.) |
|
|
mm |
PVC 26/32 |
|||
|
|
Control type |
(Remote /wired) |
|
|
|
wired+remote |
|||
|
|
Fresh air hole dimension |
|
|
|
mm |
|
/ |
||
|
|
Electricity Heater |
|
|
|
kW |
|
/ |
||
|
|
Noise level |
(H-M-L) |
|
|
dB(A) |
33/31/28 |
|||
|
|
Weight |
(Net / Shipping) |
|
|
kg / kg |
38/55 |
|||
|
|
Refrigerant |
|
Type / Charge |
|
|
g |
R407C |
1950 |
|
|
|
|
Recharge quantity |
|
g/m |
30 |
||||
|
|
|
|
|
||||||
PIPING |
|
Pipe |
|
Liquid |
|
|
|
mm |
6.35 |
|
|
|
Gas |
|
|
|
mm |
15.88 |
|||
|
|
|
|
|
|
|||||
|
Connecting Method |
|
|
|
|
flared |
||||
|
|
|
|
|
|
|||||
|
|
Between I.D &O.D |
MAX.Drop |
|
|
|
m |
20 |
||
|
|
MAX.Piping length |
|
m |
30 |
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB
item |
|
|
|
|
|
Model |
AU182AFBEA |
|
Function |
|
|
|
|
|
Cooling |
Heating |
|
Capacity |
|
|
|
|
KW |
5.27 |
5.86 |
|
Capacity |
|
|
|
|
BTU/h |
18000 |
20000 |
|
Total power input |
|
|
|
|
W |
2000 |
1900 |
|
Max. power input |
|
|
|
|
W |
2400 |
2800 |
|
EER or COP |
|
|
|
|
W/W |
2.64 |
3.08 |
|
Dehumidifying capacity |
|
|
|
|
10 ³×m³/h |
|
2.1 |
|
Power cable |
|
|
|
|
|
4X0.75 |
||
Power source |
|
|
|
|
N V Hz |
1PH 220V-230V 50HZ |
||
Running /Max.Running |
|
|
|
A / A |
cooling: 10/12 |
heating: 9.5/14 |
||
Start Current |
|
|
|
|
A |
50 |
||
|
Unit model (color) |
|
|
|
|
AU182AFBEA WHITE |
||
|
Compressor |
|
Model / |
Manufacture |
|
PG330X2CS-4KU1 Toshiba |
||
|
|
|
Type |
|
|
|
Rotary |
|
|
Fan |
|
Type × Number |
|
Axial-flow |
|||
|
|
|
Speed |
|
|
r/min |
820±30 |
|
|
|
|
Fan motor |
output power |
kW |
35 |
||
|
|
|
Air-flow(H-M-L) |
m³/h |
2000 |
|||
|
Heat exchanger |
Type / Diameter |
mm |
TP2M/9.52 |
||||
unit |
|
|
Total area |
|
|
m² |
0.72 |
|
|
|
Temp. scope |
|
|
43-60 |
|||
Outdoor |
|
|
|
|
|
|
|
|
Dimension |
|
External |
|
L×W×H |
mm×mm×mm |
810x288x680 |
||
|
|
|
||||||
|
|
|
Package |
|
L×W×H |
mm×mm×mm |
960x406x760 |
|
|
Drainage pipe |
|
(material , |
I.D./O.D.) |
mm |
|
/ |
|
|
Refrigerant control method |
|
|
mm/mm |
Main capillary2.0x450 Sub-capillary2.0x200 |
|||
|
Defrosting |
|
|
|
|
|
Auto |
|
|
Volume of Accumulator |
|
|
L |
|
/ |
||
|
Noise level |
|
|
|
|
dB(A) |
52/--/46 |
|
|
Type of Four way |
valve |
|
|
|
|
/ |
|
|
material of reduce noise |
|
|
|
XPE |
|||
|
crankcase heater power |
|
|
W |
|
/ |
||
|
Weight |
(Net / Shipping) |
|
kg / kg |
59/66 |
|||
|
Refrigerant |
|
Type / Charge |
|
g |
R407C |
1950 |
|
PIPING |
|
|
Recharge quantity |
g/m |
30 |
|||
Pipe |
|
Liquid |
|
|
mm |
6.35 |
||
|
Gas |
|
|
mm |
15.88 |
|||
|
|
|
|
|||||
Connecting Method |
|
|
|
Flare |
||||
|
Between I.D &O. |
MAX.Drop |
|
|
m |
20 |
||
|
MAX.Piping length |
m |
30 |
|||||
|
|
|
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB
Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB
3 MECHANICAL DATA
3.1 Drawings / Dimensions
3.1.1 Cassette Indoor unit
Swing louver
(Air flow direction can be adjusted by using the SWING button on the remote controller)
Electrical Components Case
Air Inlet Grille
Air Filter (Inside of the Inlet Grille)
3.1.2 outdoor unit
Air inlet
Compressor(inside of unit)
Air outlet
18 series
Dimension
|
. |
I |
N |
M |
|
MIN.
|
. |
|
N |
I |
|
M |
|
|
|
|
M |
|
|
|
I |
|
|
|
N |
|
|
|
. |
|
|
110 |
|
|
190 |
|
|
|
|
|
170 |
|
|
75 |
220 |
400 |
|
|
|
65 |
|
||
|
|
||
|
|
150 |
|
|
100 |
100 |
|
(Ceiling opening hole)
|
|
eecl ctri al bo |
|
|
( ) |
(Ceiling opening hole) |
|
|
|
|
|
||||
|
|
|
|
||||
|
|
x |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Needed minimum position
480
265
30
200
680
810
580
288
Convertible type
10 11
3
9
8
Fig.1
Dimension
1
POWER 4
OPER 5
TIMER 6
COMP 7
EMER 2
Fig.2 |
3 |
|
Fig.1 Indoor Unit
1Operating Control Panel (Fig.2)
2Emergency switch
3Remote Control Signal Receiver
4Power Indicator Lamp (Red)
5OPERATION Indicator Lamp (Green)
6TIMER Indicator Lamp (Yellow)
7Compressor Run Lamp (Green)
8Intake Grill (Fig.3)
9Air Filter
10UP/DOWN Air Direction Flaps
11RIGHT/LEFT Air Direction Louvers (behind UP/DOWN Air Direction Flaps)
200 655
9
240
ceiling concealed type Indoor unit
fan inside
|
motor inside |
electric control box |
air duct |
|
|
|
evaporator |
A
C B
D
@
E
F
G
?
9JLM?HH?MGKJ BGICJLGKJ4 +=JGM4 II, |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
<>;8 |
? |
@ |
|
A |
B |
C |
D |
E |
F |
G |
|
57.1/5:685 |
2-- |
30- |
|
12- |
//2 |
3- |
//2 |
./0 |
// |
.-- |
7.Remote controller functions
Remote controller
29 |
|
|
|
|
28 |
|
|
|
|
27 |
|
30 |
|
|
|
|
26 |
31 |
|
|
|
B A |
25 |
32 |
|
|
|
|
24 |
33 |
|
|
|
|
23 |
34 |
|
A |
|
|
22 |
|
|
U |
|
|
21 |
35 |
|
T |
|
|
|
|
O |
|
|
||
36 |
|
OFF |
|
20 |
|
M |
D |
|
|
||
1 |
|
|
TEMP |
|
19 |
|
|
|
|
|
|
2 |
|
|
ON |
|
18 |
|
|
OFF |
|
||
3 |
SWING |
|
FAN |
|
|
|
|
|
|||
|
|
|
|
|
|
4 |
MODE |
|
SLEEP |
17 |
|
HEALTH |
FRESH |
|
|||
5 |
|
16 |
|||
|
|
|
|
||
6 |
CLOCK |
|
SET |
15 |
|
TIMER |
|
HIGH/SO |
|||
7 |
|
14 |
|||
|
|
|
|
||
8 |
FILTER |
|
|
13 |
|
|
|
|
|
||
|
RESET |
CODE |
LIGHT LOCK |
12 |
|
9 |
|
|
|
|
11 |
10
1.TEMP Setting Button
(Used to set temperature. Setting ranges: 16C to 30 C)
In Up/Down function, for controlling up and down filter.
2.SWING Button
If you press this button once, auto swing will be activated.
If you press this button again, the louver will fix in the present position.
4.Operation MODE
Used to select operation mode.
Every time you press MODE button, operation mode changes according to following sequence:
AUTO COOL DRY HEAT FAN
5.HEALTH Button
Used to set health mode, if the unit has the negative ion function
and oxygen bar function.
6.CLOCK Button
Used to set correct time.
7.CLOCK Button
Used to select TIMER ON, TIMER OFF.
(Note: if time of TIMER ON is the same as TIMER OFF,TIMER ON/OFF cannot be set)
8. FILTER Button
Used to set up/down function of filter.
9. CODE Button
Used to select code A or B, for this unit, the code is A.
10.RESET Button
Press this button by using a sharp article to resume the correct operation of the remote controller in case of need, i.e. for example in case of malfunctions due
to electromagnetic noise.
11.LOCK Button
Used to lock operation button and LCD display contents: by pressing this button, other buttons comes
out of function and lock state display appears; if you press it again, lock state will be no more active and lock state display will disappear.
12.LIGHT Button
Used to light the control panel (only for cabinet unit)
13.Up and down Button
Used to set TIMER and CLOCK up or down.
14.HIGH/SO Button
Used to select HIGH or SOFT operation.
3.Power ON/OFF Button
Used for unit start and stop
After power on, the LCD of remote controller will display the previous operation state (except for TIMER,SLEEP and SWING state).
15.SET Button
Used to confirm TIMER and CLOCK settings.
16.FRESH Button
Used to set fresh mode, the unit will draw in fresh air.
17.SLEEP Button
(The clock must be corrected before setting sleep function)
Used to set sleep mode.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating. 2.HIGH/SO button
This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high functon" will be cancelled automatically after 15 minutes running.
18.FAN Button
Used to select fan speed:LOW,MID,HIGH,AUTO.
19.TIMER OFF Display 20.CLOCK Display
21.FILTER Display 22.TEMPERATURE Display
23.AUTO SWING Display 24.HIGH/SO Display 25.SIGNAL SENDING Display
26.FRESH AIR Display 27.ELECTRICAL HEATING Display
28.Some other buttons
All these functions are not available now.
29.HEALTH Display
Displays when healthy run function is set.
30.DEHUMIDIFICATION Display 31.Operation MODE Display
AUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN
32.SLEEP State Display 33.BATTERY Energy Display
Notify the user when it is time to change the batteries.
34.LOCK State Display 35.FAN SPEED Display
LO
MID
HI
AUTO
AUTO
36.TIMER ON Display
Remote Controller' Operation
When in use, direct signal transmission head to the receiver placed on the indoor unit
The distance between the remote controller and the receiver should be max 7m and there should be no obstacle between them.
Do not throw the remote controller; prevent it from being damaged.
When operating the remote controller in an area where electronically controlled lights are installed or wireless handsets are used, please move closer to the indoor unit as the function of the remote controller might be affected by signals emitted by the above mentioned equipments.
Battery loading
Battery loading |
|
* |
Batteries are fitted as follows: |
* |
* |
Remove the battery compartment lid |
|
* |
|
|
Slightly press and disengage the battery compartment lid marked with ìî and then hold the remote controller by the upper section and then remove the battery compartment lid by pressing in the direction of the arrow as shown in the figure above.
Loading the battery
Ensure that batteries are correctly placed in the compartment as required for positive and negative terminals.
Replacing the battery compartment lid
The battery compartment lid is reinstalled in the reverse sequence.
Display review
Press the button to see if batteries are properly fitted. If no display appears, refit the batteries.
Confirmation indicator
If no indication is displayed after press ON/OFF button, reload the batteries.
Caution:
If the remote controller does not operate as designed after fitting new batteries of the same
type, press the Reset button (marked ) with a pointed article.
Note:
It is recommended that the batteries be removed from the compartment if the remote controller is not used for an extended period.
The remote controller is programmed for automatic test of operation mode after the batteries are replaced. When the test is conducted, all icons will appear on the screen and then disappear if the batteries are properly fitted.
Clock Set
When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows:
1.Press CLOCK button, clock indication of " AM " or " PM " flashes. 2.Press or to set correct time. Each press will increase or decrease
1 min. If the button is kept pressed, time will increase or decrease quickly. 3.After time setting is confirmed, press "SET" : AM or PM stop flashing,
while clock starts working.
Note:AM means morning and PM means afternoon.
MODE |
|
SLEEP |
HEALTH |
FRESH |
|
CLOCK |
|
SET |
1 TIMER |
2 |
HIGH/SO 3 |
FILTER |
|
|
RESET CODE |
LIGHT |
LOCK |
Fan Operation
A
A
U
T
O
TEMP
ON
SWING |
4 OFF |
FAN |
|
|
|
1 |
3 |
MODE |
|
SLEEP |
|
2HEALTH |
FRESH |
|
|
CLOCK |
|
SET |
|
TIMER |
|
HIGH/SO |
|
FILTER |
|
|
|
RESET |
CODE |
LIGHT |
LOCK |
1.Unit start
Press ON/OFF button to start your air conditioner. Previous operation status appears on LCD (except for TIMER, SLEEP, and SWING setting).
2.Select operating mode
Press MODE button. At each press, operation mode changes as follows:
AUTO COOL DRY HEAT FAN
Then select FAN
3. Adjust fan speed
Press FAN button. At each press, fan speed changes as follows:
|
LOW |
MID |
HIGH |
|
|
|
|
|
|
Air conditioner will run at the selected fan speed. When in AUTO mode, unit will adjust fan speed according to room temperature automatically.
4. Unit stop
Press ON/OFF button to stop unit.
About FAN mode
When the air conditioner runs in FAN mode, it is not possible to select AUTO FAN or to set temperature.
AUTO, COOL , HEAT and DRY Operation
A
A
U
T
O
1. Unit start
Press ON/OFF button,unit starts.
Previous operation status appears on LCD (except for TIMER, SLEEP and SWING setting)
2.Select operation mode
Press MODE button. At each press, operation mode changes as follows:
TEMP
3 |
|
ON |
3 |
|
|
OFF |
|||
SWING |
|
FAN |
||
5 |
1 |
|||
|
4 |
|||
MODE |
|
|
SLEEP |
|
2 HEALTH |
FRESH |
|
||
CLOCK |
|
|
SET |
|
TIMER |
|
|
HIGH/SO |
|
FILTER |
|
|
|
|
RESET CODE |
LIGHT |
LOCK |
COOL operation starts when room temp.is higher than temp.
setting.
Ultra-low air flow
Temp. setting +2C
Temp.setting
AUTO COOL DRY HEAT FAN
Then select AUTO run or select COOL operation or
select DRY operation or select HEAT operation
3.Temperature setting
Press TEMP button.
Every time the button is pressed, temp. setting increases
1 C; if the button is kept pressed, temp. setting will increase quickly.
Every time the button is pressed, temp. setting decreases
1 C, if the button is kept pressed, temp. setting will decrease quickly.
Set proper temperature
4.Adjust FAN button
Press FAN button. At each press, fan speed changes as follows:
A
U
T
O
AUTO LOW MID HIGH
Air conditioner will run at the selected fan speed.
5. Unit stop
Press ON/OFF button,unit stops.
On reaching temp.setting +2 C, unit will run in mild DRY mode.
In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner will select COOL, HEAT or FAN mode automatically according to the room temperature.
In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will only run FAN operation.
In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.
Adjusting air flow direction
AUTO SWING
Press SWING button.
Up and down airflow varies upwards and downwards. Left and right airflow varies left and right sides.
A
A |
|
|
U |
|
|
T |
|
|
O |
|
|
|
TEMP |
|
|
ON |
|
SWING |
OFF |
FAN |
|
||
MODE |
|
SLEEP |
HEALTH |
FRESH |
|
CLOCK |
|
SET |
TIMER |
|
HIGH/SO |
FILTER |
|
|
RESET CODE |
LIGHT LOCK |
AUTO SWING
When the automatic swing louver moves to the proper angle, press SWING button can fix the airflow direction.
Always use SWING button on the remote controller to adjust flaps. Adjusting them by hand may result in air conditioner's abnormally running.
In COOL or DRY mode, do not leave the louver in downward position for a long time, as the water vapor close to the grille may condense and water may drop from the air conditioner.
Please carefully set temperature when children, old or infirm people ues the air conditioner.
In case of great humidity, If the vertical flaps are completely turned towards left or right, the louver will drop water.
Never adjust the louver directly by hand, as this could make it work abnormally.If the louver work abnormally, stop unit, restart and adjust the louver by remote controller.
After unit stops:
Displays on the LCD disappear.
All indicators on the indoor unit go out.
Swing louver automatically close the air outlet.
Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful for a better air circulation
As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for a better air circulation.
Be careful not to catch a cold when cold air blows downward directly.
Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make you sleep more comfortably.
Before using this function, the clock must be set.
Use of SLEEP function
After the unit's start, set running mode and then press SLEEP button once to make the air conditioner
have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button /: you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1
hour: "xh" and "OFF" indications appear on the display.
Operation Mode
1.In COOL, DRY mode
One hour after sleeping operation start, the temperature is 1C higher than the setting one. After another hour, temperature rises 1 C: sleep run continuously for another 6 hours and then stops. The actual temperature is higher than the setting one which is to prevent from being too cold to your sleep.
2.In HEAT mode
One hour after sleeping operation start, the temperature is 2 C lower than the setting one. After another hour, temperature decreases by 2 C more. Temperature will automatically rise by 1 C after another 3 hours' continuous operation. The actual temperature is lower than the setting one which is to prevent from being too hot to your sleep.
3.In AUTO mode.
The air conditioner will run in corresponding sleep operation according to the automatically selected operation mode.
Notes:
SLEEP RUN BEGINS |
SLEEP RUN STOPS |
about 6 hrs |
|
|
increase 1 C |
1 hrs |
increase 1 C |
SETTING T |
SHUT DOWN |
In COOL,DRY mode |
SETTING T |
|
SHUT DOWN |
1 hrs |
decrease 2 C |
|
1 hrs |
|
|
|
decrease 2 C |
|
|
|
about 6 hrs |
|
3 hrs |
increase 1 C |
SLEEP RUN BEGINS |
|
SLEEP RUN STOPS |
In HEAT mode |
||
|
|
A |
|
|
A |
|
|
U |
|
|
T |
|
|
O |
|
|
OFF |
After setting SLEEP function, it is not possible to set clock.
If set-sleep time does not reach 8 hours, unit will automatically stop operation after set time is reached.
Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first, then set SLEEP. After set SLEEP function, the TIMER function cannot be set.
|
TEMP |
|
|
ON |
|
SWING |
OFF |
FAN |
|
||
MODE |
|
SLEEP |
HEALTH |
FRESH |
|
CLOCK |
|
SET |
TIMER |
|
HIGH/SO |
FILTER |
|
|
RESET CODE |
LIGHT LOCK |
Timer ON/OFF Function
Set clock correctly before starting TIMER operation
A
1.Unit start
After unit start, select your desired operation mode (operation mode will be displayed on LCD)
|
TEMP |
|
|
|
ON |
|
|
SWING |
OFF |
1 |
FAN |
|
|||
|
|
|
|
MODE |
|
|
SLEEP |
HEALTH |
FRESH |
|
|
CLOCK |
|
|
SET |
TIMER |
|
3 HIGH/SO 4 |
|
2 FILTER |
|
|
|
RESET CODE |
LIGHT LOCK |
Note:
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:
|
|
ON |
|
|
|
OFF |
|
|
|
|
ON |
|
|
|
OFF |
|
|
blank |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
AM 12:00 |
PM 12:00 |
AM 12:00 |
|
|
PM 12:00 |
|||||||||||||
TIMER ON |
TIMER OFF |
|
TIMER ON-OFF |
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Then select TIMER mode as needed (TIMER ON or TIMER OFF). Now ON or OFF will flash.
3.TIMER setting (press time adjust buttons )
Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time changes quickly.
Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed, time changes quickly.
It can be adjusted within 24 hours at will.
4.Confirm setting
After setting correct time, press SET button to confirm time. Now ON or OFF stop flashing.
Time displayed: unit starts or stops at X hour X min (TIMER ON or TIMER OFF)
5.Cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
Hints:
After replacing batteries or if a power failure occurs, TIMER setting must be reset.
Remote controller has memory function. When you use TIMER mode next time, just press SET button after mode selection if timer setting is the same as the previous one.
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time, just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you can adjust clock). 5 seconds later, the display will show TIMER time again.
Timer ON-OFF Function
Set clock correctly before starting TIMER operation
1.Unit start
A
After unit start, select your desired operation mode (operation mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:
ON OFF ON OFF blank
OFF |
PM 12:00 |
AM 12:00 |
PM 12:00 |
AM 12:00 |
|||
TIMER ON |
TIMER OFF |
TIMER ON-OFF |
|
TEMP |
|
|
ON |
|
SWING |
OFF |
FAN |
|
||
|
|
1 |
MODE |
|
SLEEP |
HEALTH |
FRESH |
|
CLOCK |
|
SET |
2 TIMER |
|
3HIGH/SO 6 |
4FILTER 5 |
|
|
RESET CODE |
LIGHT LOCK |
Then select TIMER ON-OFF mode. ON will flash.
3.Time setting for TIMER ON
Press time button
Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time will changes quickly.
Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed ,time will changes quickly.
It can be adjusted within 24 hours at will.
AM refers to morning and PM refers to afternoon.
4.Timer confirming for TIMER ON
After setting correct time, press TIMER button to confirm time. Now
ON stops to flash, while OFF starts flashing.
Time displayed : unit starts at X hour X min.
5.Timer setting for TIMER OFF
Press time buttonsand follow the same procedures in " Time setting for TIMER ON"
6.Time confirming for TIMER OFF
After time setting, press SET button to confirm time. OFF stops to flash. Time displayed: unit starts at X hour X min.
7.Canel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
According to the time setting sequence of TIMER ON and TIMER OFF, either start-stops or stops-start can be realized.
If the time setting of TIMER ON is the same as TIMER OFF, TIMER ON-OFF function cannot be set.
Filter Up/Down
(Only for AB182ACBEA)
A
|
TEMP |
|
|
ON |
|
SWING |
OFF |
FAN |
|
||
MODE |
|
SLEEP |
HEALTH FRESH |
|
|
CLOCK |
|
SET |
TIMER |
|
HIGH/SO |
FILTER |
|
|
RESET CODE1 |
LIGHT |
LOCK |
|
|
After the air conditioner has operated for a certain period, dust has accumulated on the filter, and the filter up/down function can be used to clean it.
1.Whether unit starts or stops, continuously press FILTER button for 3 seconds, and enter the filter up/down waiting status (when unit stops, the yellow TIMER indicator flashes, and filter and clock indication are displayed on the remote controller. Only the FILTER button, the temperature buttons "" "" and time buttons are active).
2.Press temperature "" button or time " " button in filter up/down waiting status: the up/down mechanism makes the filter moving downward and does not stop until it has reached the maximum limit.
3.Press temperature"" button or time" "button in filter up/down waiting status: the up/down mechanism makes the filter to moving upward till near the surface board and
then automatically adjusts it to reset (when adjusting to reset, it will not be controlled by the remote controller till the adjustment is finished).
4.During moving downward, press temperature"" button or time " " button: moving stops.
5.During moving downward, press temperature"" button or time " " button: moving stops.
6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter goes back to the original position, the remote controller goes back to off status and only clock is displayed).
Note:
If the filter does not thoroughly go back to the original position, only needs to operate several times repeatedly.
" High mode " Operation
Outline of operation in "High Mode"
A
This function is suitable when the set temperature must be reached in the shortest delay.
The button "HIGH/SO", referred to this function, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).
A U T O
|
TEMP |
|
|
ON |
|
SWING |
OFF |
FAN |
|
||
MODE |
|
SLEEP |
HEALTH |
FRESH |
|
CLOCK |
|
SET |
TIMER |
|
HIGH/SO |
FILTER |
|
1 |
RESET CODE |
LIGHT LOCK |
ON
Press the HIGH/SO button noce
The indication appears on the display of the remote controller and operation in "High Mode" starts.
The AUTO fan speed is automatically set and the corresponding indication is also displayed.
OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is displayed on the remote controller. If you press the button once again, the indication disappears, regular operation is restored and fan speed goes back to the mode set before "High Mode" operation.
NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.
" Soft mode " Operation
A
A |
|
|
U |
|
|
T |
|
|
O |
|
|
OFF |
|
|
|
TEMP |
|
|
ON |
|
SWING |
OFF |
FAN |
|
||
MODE |
|
SLEEP |
HEALTH |
FRESH |
|
CLOCK |
|
SET |
TIMER |
|
HIGH/SO |
FILTER |
|
1 |
RESET CODE |
LIGHT LOCK |
Outline of operation in "Soft Mode"
Operation in "Soft Mode", more silent, is suitable when noises should be reduced, e.g.. for reading or sleeping.
The button "HIGH/SO", referred to this operation, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).
|
ON |
Press the HIGH/SO button twice |
|
The indication |
appears on the display of the remote |
controller and operation in "Soft Mode" starts.
The AUTO fan speed is automatically set and the corresponding indication is also displayed.
OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is disappears from the remote controller's display. If you press the button once again, regular operation is restored and fan speed goes back to the mode set before "Soft Mode" operation.
NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.
AIR FLOW DIRECTION ADJUSTMENT PROCEDURE-Cassette type
Adjusting up/down air flow direction
Up/down direction can be adjusted by using the SWING button on the remote controller.
Each time pressing this button, the mode changes in the following sequence.
SWING No indication (louver stopped)
Change to the AIRFLOW mode.
SWING |
|
LOUVER STOPPED |
|
|
|
When the LOUVER button is pushed during SWING mode, it stops swinging at the just angle.
Louver moves in upward and downward directions continuously.
CAUTION
Avoid direct air flow to the body for many hours.
Avoid downward blowing operation of cooling mode for many hours. Do not touch the swing louver during swing operation.
AIR FLOW DIRECTION ADJUSTMENT PROCEDURE-Convertible type
Adjusting up/down air flow direction
Up/down direction can be adjusted by using the SWING button on the remote controller. Each time pressing this button, the mode changes in the following sequence.
SWING No indication (louver stopped)
Change to the AIRFLOW mode.
SWING
LOUVER STOPPED
Louver moves in upward and downward directions continuously.
CAUTION
Avoid direct air flow to the body for many hours.
Avoid downward blowing operation of cooling mode for many hours.
Do not touch the swing louver during swing operation.
When the LOUVER button is pushed during SWING mode, it stops swinging at the just angle.
Recommendable stopping angle of the louver
COOL |
|
and |
|
DRY |
(Horizontal Blowing) |
|
HEAT
(Downward Blowing)
Wired controller functions:
Buttons and functions of the wired controller
CLOCK |
MODE |
|
Used to adjust time. |
Used |
for select |
TIMER |
indoor |
operation |
mode. |
|
|
|
|
Used to set timer |
|
FAN SPEED |
mode. |
|
|
CHECK |
|
Used for select indoor |
Auto-diagnostic |
|
air flow. |
|
|
|
button. |
|
SWING |
|
|
Used for setting |
|
|
indoor swing mode. |
|
HEALTH |
|
|
|
HEALTH |
F |
SET RECOVERY |
Used for setting |
C |
|
|
|
|
indoor health |
|
CHECK |
function. |
|
|
TEMP + - |
+ - |
|
Used for changing |
|
|
set temperature. |
stands for time plus/minus, |
|
RECOVERY |
used to adjust time. |
|
|
|
|
FILTER |
|
|
used to switch |
|
|
over air- |
|
|
|||
Filter-cleaned button. |
exchanging mode. |
||
|
|||
POWER ON/OFF |
|
|
RESET |
|
|
Reset correct |
|
|
|
||
|
|
|
|
Used for unit start and |
mode button. |
||
stop. |
|
Cautions: |
Note: |
On cooling only unit, heating |
The above information is the explanation of |
mode is not available. |
the displayed information therefore varies |
|
with those displayed in actual operation. |
Buttons function
MODE used for select indoor operation mode. FAN used for select indoor air flow. SWING used for setting indoor swing mode. HEALTH used for setting indoor health function. TEMP + - used for changing set temperature. CLOCK used to adjust time.
+ - stands for time plus/minus, used to adjust time.
TIMER used to set timer mode.
RECOVERY used to switch over air-exchanging mode. CHECK auto-diagnostic button. FILTER filter-cleaned button.
RESET reset correct mode button.
Display description
[MODE] [AUTO] auto operation mode
[MODE] [FAN ONLY] air-throwing mode
[MODE] [COOL] Cooling operation mode
[MODE] [DRY] Dehumidification mode [MODE] [HEAT] Heating operation mode
[MODE] [HEAT] [TES] In heating mode, auxiliary electric heater is running. Only when the unit with auxiliary electric heater is in auxiliary electric heating mode, it will display.
[FAN] [AUTO] auto fan running