Haier AU182ABNAC, AC242ACNAC, AU242ABNAC, AC28NACNAC, AU28NABNAC Service Manual

...
HCFU-14CL03/R1 (AC142ACNAC+AU142ABNAC) HCFU-18CL03/R1 (AC182ACNAC+AU182ABNAC)
HCFU-24CL03/R1 (AC242ACNAC+AU242ABNAC) HCFU-28CM03/R1 (AC28NACNAC+AU28NABNAC) HCFU-36CM03/R1 (AC36NACNAC+AU36NABNAC) HCFU-42CM03/R1 (AC42NACNAC+AU42NABNAC)
MANUAL CODE: SYJS-006 EDITION:2002.12.31.
Super low outdoor ambient cooling at -15 Auto-restart function Group control(with a group controller)
Auto-changeover
Compact design of indoor unit Weekly timing(with a weekly timer) With new environment friendly refrigerant R407C
Features
Service Manual
Commercial Air Conditioning
Convertible Type Low Ambient Cooling Series
CONTENTS
1. Description of Products & Features…………………...…….1
2. Specifications…………………………. ………………...……3
3. Safety precaution…………………………..………………….9
4. Net dimensions of indoor and outdoor unit………………...11
5. Installation instructions ……………………. ………………..17
6. Parts and functions …………………………..…… ..……….28
7. Remote controller functions………………………….………31
8. Refrigerant diagram…………………………..……………....43
9. Electrical control functions……………………………………44
10. Diagnostic information(trouble shooting)…………….……51
11. Electrical data.........................................…………….……56
12. Exploded views and parts lists...............……………. ……67
13. Perdormance curves……………............................... ……87
14. Noise level charts.....……………............................... ……93
15. Air velocity distribution …………............................... ……94
CONTENTS
Contents…….................................................………...…….1
- 1 -
1 DESCRIPTION OF PRODUCTS & FEATURES
1.1 Products coding direction
Old code
H CFU – 42 C M 03 / R1
Refers to HFC refrigerant
Power: 03(230V/50Hz).04(240V/50Hz).12(115V/60Hz).13(230v/60Hz) Low ambient cooling “H” refer to cooling and heating, ”C” refer to cooling only Nominal cooling capacity (BTU/h), 42=42000BTU/h Indoor and outdoor unit code: "CF" Convertible type; "U" Outdoor unit “H” means “Haier”
New code
A C 42 N A C N A C
Climate type: T1 (see table 1), and -15 degree cooling
Design number (A stands for fix speed type) Product type: A stands for heat pump type, refrigerant is R22 B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407 Appearance character Product series: one by one type Applicable voltage: 2 stands for 220-240V/50Hz,4 stands for 220v/60Hz N stand for 380V/50Hz Cooling / Heating capacity,42=42000BTU/h Product type : “B” stands for cassette type, “C” stands for convertible type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller
system, "E" stands for ceiling concealed type, “U” stands for outdoor unit
Air conditioner
1.2 Brief Introduction to T1 T2 T3 working condition
Table 1
Climate type
Type of Air Conditioner
T1 T2 T3
Cool only
18
43 10 35 21 52
Heat pump
-7
43 -7 35 -7 52
Electricity heating
43 35 52
1.3 Operating Range of air conditioners
Low ambient cooling
Operation Operation Range Outside / Inside
Cooling
-15
0
C – 43oC
Dehumidifying
-15
0
C – 43oC
DESCRIPTION OF PRODUCTS & FEATURES
- 2 -
1.4 Products characteristic
(2).HFC refrigerant technology
To protect the environment, we have adopted the HFC refrigerant. The HFC R407C is of zero ODP for the purpose of environmental protection.
(3).Ceiling/console convertible,flexible installation,convenient maintenance,saving the users' expenditures (4).Adopting single-phase or three-phase power supply,applicable for household and commercial usage (5).Dual air outlet design,floor air blowing,accelerating the indoor air circulation, quick temperature adjustment (6).Long-distance air blowing,large power,large cooling/heating ratio (7).Intelligent remote control,convenient and flexible control (8).Super-slim indoor unit design,luxury and nice-looking,saving space,harmonious and unitive with the indoor environment (9).Adopting screw-fastening for the air inlet grill,firmly fixed;adopting slipway insert-lock fastening method for the filter screen,convenient cleaning or replacing the filter screen without opening the air inlet grill.
.
The system can run the cooling operation at the low ambient temperature -15
(1).Low ambient temperature cooling technology
(10).Group control,units up to 128 sets can be controlled
DESCRIPTION OF PRODUCTS & FEATURES
- 3 -
Function
Cooling Heating
Capacity BTU/h
14000 /
W
2000 /
EER or COP BTU/W
7.00 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current
A
Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm
Package mm×mm×mm Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HCFU-14CL03/R1
1
1PH, 220V-230V, 50HZ
/
Indoor unit
AC142ACNAC / WHITE
CENTRIFUGAL×2
1070/1000/940
900
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
900×655×199
1150×750×300
PVC 18/20
wired
/
48/44/38
Weight (net / gross)
30/39
Panel
Dimension
L×W×H
/
/
Weight (net / gross)
/
Outdoor unit
AU142ABNAC / WHITE
ZR34K3E-TFJ-522 / COPELAND
scroll
Axial-flow×1
820
700/-/-
TP2M/9.52
2/2
0.225
43-60
Dimension
L×W×H
810×288×680 960×406×760
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
52/-/
Four way valve
/
Between I.U. & O.U.
MAX :5
MAX :15
Total power input
Weight (net / gross)
59/66
Piping
R407C
1.8
6.35
2 SPECIFICATIONS
9.4/40.7
/
SPECIFICATIONS
- 4 -
Function
Cooling Heating
Capacity BTU/h
18000 /
W
2000
/
EER or COP BTU/W
9
.00 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz Running current/Starting current A Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HCFU-18CL03/R1
1
1PH, 220V-230V, 50HZ
/
Indoor unit
AC182ABNAC / WHITE
CENTRIFUGAL×2
500/450/380
1050
TP2M/9.52
2/2
0.
199
2-7
Dimension
L×W×H
990×655×199
1160×760×310
PVC 18/20
wired
/
43/42/40
Weight (net / gross)
29/39
Panel
Dimension
L×W×H
/
/
Weight (net / gross)
/
Outdoor unit
AU182ABNAC / WHITE
ZR34K3E-TFJ-522 / COPELAND
scroll
Axial-flow×1
820
700/-/-
TP2M/9.52
2/2
0.225
43-60
Dimension
L×W×H
810×288×680 960×406×760
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
52/-/46
Four way valve
/
Between I.U. & O.U.
MAX :
5
MAX :
15
Total power input
Weight (net / gross)
58/66
Piping
R407C
1.80
6.35
/
9.3/46.0
SPECIFICATIONS
- 6 -
Function
Cooling Heating
Capacity BTU/h
24000 /
W
2800 /
EER or COP BTU/W
8.57 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current A
Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HCFU-24CL03/R1
3
1PH,220V~230V,50Hz
/
Indoor unit
AC242ACNAC / WHITE
CENTRIFUGAL×2
1300/1200/1000
1300
TP2M/9.52
2/2
0.221
2-7
Dimension
L×W×H
1320×715×235 1380×770×300
PVC 18/20
wired
/
35/32/29
Weight (net / gross)
40/57
Panel
Dimension
L×W×H
/
/
Weight (net / gross)
/
Outdoor unit
AU242ABNAC / WHITE
ZR34K3E-TFJ-522 / Copeland
scroll
Axial-flow×1
840/-/-
3240
TP2M/9.52
3/3
0.62
43-60
Dimension
L×W×H
948×830×340
1050×979×440
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
58/-/50
Four way valve
/
Between I.U. & O.U.
MAX :15
MAX : 30
Total power input
Weight (net / gross)
70/85
Piping
R407C
1.85
9.52
12.5/60.1 /
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
28000 /
W
28
00 /
EER or COP BTU/W
10.0 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current A
Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HCFU-28CM03/R1
3
3N,380V~400V,50Hz
/
Indoor unit
AC28NACNAC / WHITE
CENTRIFUGAL×2
1300/1200/1000
1300
TP2M/9.52
2/2
0.221
2-7
Dimension
L×W×H
1320×715×235 1380×770×300
PVC 18/20
wired
/
35/32/29
Weight (net / gross)
40/57
Panel
Dimension
L×W×H
/ /
Weight (net / gross)
/
Outdoor unit
AU28NABNAC / WHITE
ZR34K3E-TFJ-522 / Copeland
scroll
Axial-flow×1
840/-/-
3240
TP2M/9.52
3/3
0.62
43-60
Dimension
L×W×H
948×830×340
1050×979×440
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
58/-/50
Four way valve
/
Between I.U. & O.U.
MAX :
15
MAX :
30
Total power input
Weight (net / gross)
74/89
Piping
R407C
1.85
9.52
12.5/60.1 /
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
36000 /
W
3600 /
EER or COP BTU/W
10.0 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current A
Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HCFU-36CM03/R1
5
3N, 380V-400V, 50HZ
/
Indoor unit
AC36NACNAC / WHITE
CENTRIFUGAL×3
1300/1200/1000
1600
TP2M/9.52
3/3
0.338
2-7
Dimension
L×W×H
1920×715×235 1980×761×295
PVC 18/20
wired
/
56/54/52
Weight (net / gross)
46/52
Panel
Dimension
L×W×H
/
/
Weight (net / gross)
/
Outdoor unit
AU36NABNAC / WHITE
ZR34K3E-TFJ-522 / COPELAND
scroll
Axial-flow×2
840/-/-
6000
TP2M/9.52
5/5
0.92
43-60
Dimension
L×W×H
948×1225×340
1050×1375×440
PVC,18/20
Capillary
Defrosting
Auto
19.05
FLARED
52/-/46
Four way valve
/
Between I.U. & O.U.
MAX :30
MAX : 50
Total power input
Weight (net / gross)
85/111
Piping
R407C
3.1
9.52
6.4/32
/
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
42000 /
W
4600 /
EER or COP BTU/W
9.1
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current A
Power cable
Unit model (color) Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Control type (wireless/wired) Fresh air hole dimension mm Noise level (H-M-L) dB(A)
kg External mm×mm×mm Package mm×mm×mm
kg
Unit model (color) Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow Total area m² Temp. scope External mm×mm×mm Package mm×mm×mm
Drainage pipe (material , I.D./O.D.) Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm Connect method
Drop
m
Piping length
m
Item Model
HCFU-42CM03/R1
5
3N, 380V-400V, 50HZ
/
Indoor unit
AB42NACNAC / WHITE
CENTRIFUGAL×3
980/880/820
2040
TP2M/9.52
3/3
0.199
2-7
Dimension
L×W×H
1920×715×235 1980×761×295
PVC 18/20
wireless
/
43/41/39
Weight (net / gross)
46/53
Panel
Dimension
L×W×H
/
/
Weight (net / gross)
/
Outdoor unit
AU42NAANAC / WHITE
ZR34K3E-TFJ-522 / COPELAND
scroll
Axial-flow×2
840/-/-
6000
TP2M/9.52
5/5
0.92
43-60
Dimension
L×W×H
948×1225×340
1050×1375×440
PVC,18/20
Capillary
Defrosting
Auto
19.05
FLARED
64/-/-
Four way valve
/
Between I.U. & O.U.
MAX :30
MAX : 50
Total power input
Weight (net / gross)
85/111
Piping
R407C
3.2
9.52
/
/
9.3/32
SPECIFICATIONS
WARNING
CAUTION
WARNING
CAUTION
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior environment such as engineering shop could cause equipment malfunction. Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires. Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires. When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you purchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur,there is the danger of a resultant oxygen deficiency accident. For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit. Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit. For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires. Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire.
WARNING
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual. Moreover, ask the customer to keep this sheet together with the owner's manual.
Please read these "Safety Precautions" first then accurately execute the installation work. Though the precautionary points indicated herein are divided under two headings, and those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the section. However, there is also a possibility of serious consequences in relationship to the points listed in the section as well.
- 10 -
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (please see nameplate) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing. Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refigerant leakage. The position of indoor unit must be above the floor 2.5m.
WARNING
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone ground wire. Improper placement of ground wires can result in electric shock. The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock. Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
CAUTION
- 11 -
SAFETY PRECAUTIONS
Model: HCFU-14CL03/R1 HCFU-18CL03/R1 Indoor unit
Model: HCFU-14CL03/R1 HCFU-18CL03/R1 Outdoor unit
6
5
5
240
2
0
0
9
480
30
265
220
200
580
288
810
680
75
65
150
100 100
110
190
170
400
4 NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Model: HCFU-24CL03/R1 HCFU-28CM03/R1 Indoor unit
110
180
60
85
100
30
555
630
690
105 195
300
600 600
310.63
85
25
300
10 10
545
590
85 150
60
1200
150
235
1320
40
195
100
85
45
65
R15

drainage pipe
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Note (1) Fix the parts with screws (2)Don't intake the strong wind directly to the outlet air-flow hole. (3)A one meter distance should be kept from the unit top (4)Don't block the surroudings of the unit with sundries.
Installation Servicing Space(at Least)
Unit:mm
Installation
I
300
100
0
0
150
0
500
100
0
II III
Dimension
L1
Leave space Leave space
Leave space
L2
L3
L4
185 185
55
70
70
Screw Hole
(M10)
580
Power Wiring Terminal
Power Wiring Distribution Hole
L1
L2
L3
L4
Back Air-flow Hole
Back Air­flow Hole
Outlet Air-flow Hole
Repairing Space
70
1024
1818
340
380
840
25
Model: HCFU-24CL03/R1 HCFU-28CM03/R1 Outdoor unit
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Model: HCFU-36CM03/R1 HCFU-42CM03/R1 Indoor unit
R15
85
100
195
1920 1800
600
690
630
100
85
310
590
545
40
235
150
180
85 150
60
195
600
105
600
300300
555
30
110
60
85
300
10
10
25
65
45
drainage pipe
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
185 185
30 52
88
Screw Hole
(M10)
580
950
Power wiring Terminal
70
1818
340
380
1250
25
Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the outlet air-flow hole. (3).A one meter distance should be kept from the unit top (4).Don't block the surroundings of the unit with sundries
Installation Servicing Space(at Least)
Unit:mm
Installation
I
300
100
0
0
150
0
500
100
0
II III
Dimension
L1
Leave space Leave space
Leave space
L2
L3
L4
L1
L2
L3
L4
Back Air-flow Hole
Back Air­flow Hole
Outlet Air-flow Hole
Repairing Space
Model: HCFU-36CM03/R1 HCFU-42CM03/R1 Outdoor unit
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to direct sunlight.(If necessary, install a blind that does not interfere with the air flow.) (2) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible. (3) Install the unit where connection to the indoor unit is easy. (4) During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed.(Reverse cycle model only) (5) Do not place animals and plants in the path of the warm air. (6) Take the weight of the air conditioner into account and select a place where noise and vibration are small. (7) Select a place where the warm air and noise from the air conditioner do not disturb neighbors. (8) Provide the space shown in Fig.2 so that the air flow is not blocked. Also for efficient operation, leave open three of the four directions front, rear, and both sides.
For authorized service personnel only
SELECTING THE MOUNTING POSITION
2. OUTDOOR UNIT
Decide the mounting position with the customer as follows:
1. INDOOR UNIT (1) Install the indoor unit level on a strong wall, floor, ceiling
which is not subject to vibration. (2) The inlet and outlet ports should not be obstructed: the air should be able to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown in Fig.1. Also install the unit where the filter can be removed.
NOTE: The appearance may be different from models.
(1) Install the unit where it will not be tilted by more than 5 (2) When installing the outdoor unit where it may be
exposed to the strong wind, fasten it securely.
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
CAUTION
(1)Do not install where there is the danger of com­ bustible gas leakage.
(2) Do not install near heat sources. (3) If children under 10 years old may approach the
unit, take preventive measures so that they can­ not reach the unit.
L2
L3
L1
500
(Servicing space)
Air outlet
Air inlet
Air inlet
Series
24,28 36,42
Case
Distance
L1 L2 L3
open open
open open
500
500
300 300
open open
0 0
100 150 100 150 150300
I II III I II III
Be careful not to scratch the room air conditioner when handing it. After installation, explain correct operation to the customer, according to the operating manual. Let the customer keep this installation manual because it will be used when the room air conditioner is serviced or moved.
WARNING
(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation manual. (2) Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our
standard parts. This installation manual describes for the correct connections so that the installation set available from our standard parts should be used.
(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only. (4) Never cut the power cord, lengthen or shorten the cord, or change the plug. (5) Also, do not use an extension cord. (6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner. (7) Do not turn on the power until all installation work is done.
WARNING
WARNING
5 INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
Floor console
Fig. 1
15.88mm dia.
2 cm or more
Ceiling
Indoor unit
30 cm or more
30 cm or more
Left
Right
30 cm or more
30 cm or more
1.5m
1.5m
1.5m
Left
Right
may be different
For series24, 28
For series 36,42
Note: For series 36, 42 no floor console type, the function below about floor console is invalid to the series.
30 cm or more
60 cm or more
40 cm or more
30 cm or more
Fig. 2
For series 14,18
60 cm or more
Under ceiling
6.35mm dia
Outdoor unit
Indoor unit
For series 14,18
INSTALLATION INSTRUCTIONS
Mark Parts name
Adhesive tape
Saddle (L.S) with screws
Connecting electric cable for indoor and outdoor
Drain hose
Heat insulation material
Piping hole cover
Putty
Plastic clamp
Optional parts
A B
C D E F
G H
STANDARD PARTS
The following installation parts are furnished. Use them as required.
ACCESSORIES
Name and shape
Q'ty
Application
6
For fixing the wall bracket. For series 24,28,36,42 no this part.
Tapping screw ( 4x20)
Coupler heat insulator(large)
1
For indoor side pipe joint (Large pipe)
Coupler heat insulator(small)
1
For indoor side pipe joint (Small pipe)
Nylon fastener
1
For fixing the drain hose
Drain hose
Non-adhesive tape
1
1
VT wire
1
For fixing the drain hose L 280mm For series 24,28,36,42 VT wire is not available
Remote controller
Battery
1
2
Use for air conditioner operation
For remote controller unit
Name and shape
Q'ty
Application
1
For series 24,28, 36,42 the two cover plate are not available
Cover plate (left)
Cover plate (right)
Installation template
Anchor bolt
Spring washer
Special nut
Pipe hole cover
Wall hole cover
Main pipes
Connecting cables
1
2
1
4
4
4
1
1
1
1
For positioning the indoor unit For under ceiling type.
For suspending the indoor unit from ceiling
4
Tapping screw ( 4x10)
Cushion
Drain-elbow
1
Only for the heat pump type
Wall bracket
2
For suspending the indoor unit on the wall.For series 24,28,36,42 no this part.
INSTALLATION INSTRUCTIONS
INSTALLATION PROCEDURE
PREPARING INDOOR UNIT INSTALLATION
1. REMOVE THE INTAKE GRILL
Install the room air conditioner as follows:
Open the intake grill and remove the three or four or six screws. (Fig. 3)
When the directions are selected, drill a 7 cm dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow. When the pipe is led out from the rear, make a hole in Fig.6, at the position shown.
(Fig. 5)
Drain hose (Left side) Drain hose (Right side)
CONNECTION PIPE REQUIREMENT
Table 1
Series
Diameter
Liquid side Gas side
Maximum length
Maximum height (between indoor and outdoor)
14,18
6.35 mm
9.52 mm
15.88 mm
19.05mm
15 m
50 m
5 m
15 m
9.52 mm 15.88 mm
30 m
15 m
24,28
36,42
Remark: The main unit can be wired before the indoor unit is installed. Select the most appropriate installation order.
For series 24,28,36,42 not the power plug, but 3-core connecting cable.
A. FLOOR CONSOLE TYPE (For series 36,42 no this type )
1. DRILLING FOR PIPING
Select piping and drain directions.(Fig.4) (For series 14,18) The piping and drain can be made in three directions as shown below.For series 24,28,36,42 can be made rear and down two directions.
The drain hose can be connected to either the left or right side.(Fig.5) For series 24,28,36,42 only right side.
(Fig. 4)
rear
right
down
Select whether the drain hose will be connected to the left or right side.(for series 24,28,36,42 only the right side).(Fig.5) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener. (Fig.8)
Wall
7cm
6mm
Indoor unit outdoor unit
2. INSTALLING DRAIN HOSE
(Fig. 6)
For series 14,18 when installing set to wall, install the accessory wall bracket at the position shown in Fig.7, and mount the set to it.
(Fig. 7)
INSTALL THE DRAIN HOSE
Wrap the insulation (drain hose) around the drain hose connection.(Fig.9)
Drain pan
Drain hose
Nylon fastener
(Fig. 8)
(Fig. 9)
Drain pan
Drain hose
Insulation (Drain hose)
Wall bracket
Side of set
Arrange the drain hose lower than this portion.
Fig. 10
Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.
OK NO NO
Drain hose
A A
CAUTION
Do not install the unit drain hose side is too high. Height A should be less than 5 mm.(Fig.11)
Fig. 11
Drain hose
Fig. 3
Machine screw
Tapping screw
Tapping screw
Intake grill
65.5cm
99cm
50cm
24.5cm
6.5cm
12.5cm 10cm
6.5cm
53cm
4.5cm
7cm hole
3.5cm hole
INSTALLATION INSTRUCTIONS
Installation template
Wall
Ceilling
Drilling position for piping
Drilling position for anchor bolt
200mm
900mm
Select piping and drain directions. For series 24,28,36,42 only rear side(Fig.13)
B. UNDER CEILING TYPE
Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.12)
Fig. 12
For series 14,18
1. DRILLING FOR PIPING
Fig. 13
CAUTION
60 to 70mm
12.7mm
Fig. 16
Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer. (Fig. 16)
2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS
Install the drain hose at the rear; it should not be installed on the top or right side.
When the directions are selected, drill 80mm and 50mm or 150mm dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow.
3. INSTALLING BRACKETS
Fig. 17
Install the brackets with nuts, washers and spring washers.(Fig. 17)
Spring washer
Special nut
Bracket
4. INSTALLING INDOOR UNIT
68
16 21 28
381
232
26.5
26.5
2-R2.5
10
18
7.5
4-R5
For series 24,28,36,42
Bracket (Right)
Bracket (Left)
For series 14,18
68
16
21
28
381
232
26.5
26.5
2-R2.5
10
18
7.5
4-R5
Reset the hex bolts as shown in Fig.18.
Hex bolt
8 to 13mm
Indoor unit
Fig. 18
Apply the indoor unit to the brackets.(Fig.19)
Now, securely tighten the hex bolts in both sides.
Fig. 19
Bolt
Bracket
Indoor unit
A B
40 40
100mm
720mm
87.5mm
147mm
326mm
247mm
85
53
series A B
24,28 36,42 1920 1840
12401320
Rear (Install the drain hose in the direction.)
Right
Wall
6mm
Fig. 15
With a concrete drill, drill four 12.7 mm dia. Holes.(Fig.15)
INSTALLATION INSTRUCTIONS
1. FLARE PROCESSING (1) Cut the connection pipe with pipe cutters so that the pipe is not deformed.
(2) Holding the pipe downward so that cuttings cannot enter the pipe, remove the burrs. (3) Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in(Table1) and insert the flare nut onto the pipe, and flare with a flaring tool. (4) Check if the flared part "L" (Fig.22)is spread uniformly and that there are no cracks.
For series 24,28,36,42
Fig. 21
When drain hose is arranged backward.Secure the drain hose with the VT wire. (Fig. 21)
5. INSTALL THE DRAIN HOSE Select whether the drain hose will be connected to the left or right side.(Fig.5) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.8) Wrap the insulation (drain hose)around the drain hose connection. (Fig.9) Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.(Fig.20)
CONNECTING THE PIPING
OUTDOOR UNIT INSTALLATION
Fig. 22
2. BENDING PIPES
Fig. 23
The pipes are shaped by your hands. Be careful not to collapse them.
L
Width across flats
L dimension
Liquid pipe
1.6 to 1.8mm(6.35mm dia) Gas pipe
2.2 to 2.4mm(15.88mm dia) Gas pipe
3.4 to 2.6mm(19.05mm) Liquid pipe
1.8 to 2.0mm(9.52mm)
Table 1
Pipe Flare nut Small pipe Large pipe
Small (width across flats 22mm) Large (width across flats 24mm)
WARNING
BE SURE TO READ THESE INSTRUCTIONS. CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND /OR PROPERTY DAMAGE. BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
1. Selection of the place of installation
Select the place of installation satisfying the following conditions and, at the same time, obtain consent from the client or user.
Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighbors. Place where there is not heavy snowfall in winter. Place where obstacles do not exist near the inlet air port and outlet air port. Place where the outlet port may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibllity. When installing several units, secure sufficient suction space to avoid short circuiting.
Fig. 20
Remove the hole cover.
OK
Arrange the drain hose lower than this portion
Drain hose
NO
VT wire hole
Drain hose
Piping hole
VT wire
Drain hose
For series 24,28,36,42 no this part
Piping hole
Base (Bottom)
Intake grill
VT wire hole
Pass the drain hose through here
Cut the grill
OK
NO
Extend the pipe by unwinding it
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following.
(1) Installation
2. Installation of outdoor unit
For series 14,18
Fig. 25
(a) Concrete foundation(Fig. 25)
For series 14,18
Anchor bolt
(b) Foundation anchor
Unit
Concrete foundation
Anchor bolt
Concrete foundation
Unit
INSTALLATION INSTRUCTIONS
Note (1)
Place the concrete
foundation
deep enough.
Connecting method Apply refrigerant oil at half union as large and flare nut. To bend a pipe, give the roundness as possible not to crush the pipe. When connecting pipe, hold the pipe centre to centre then screw nut on by hand, refer to Fig. Be careful not to let foreign matters, such as sands enter the pipe.
(4) Piping connection (Fig.26)
Note (1)
Give enough room for the concrete
foundation to fix anchor bolts.
For series 24,28
To fix by bolts
Concrete foundation
(a) Concrete foundation
For series 36,42
Fig. 25
(b) Foundation anchor
Outdoor unit
For series 14,18
For series 24,28,36, 42
(1) Outline of piping
3. Refrigerant piping
Service
Flare connection
Check joint
Gas pipe
Liquid pipe
Flare connection
Indoor unit
Outdoor unit
3-way valve
Flare connection
Gas pipe
Liquid pipe
Flare connection
Indoor unit
2-way valve
(2) Piping size
Install the removed flare nuts to the pipes to be connected, then flare the pipes.
90 0.5
One way piping length: Less than 15 mm Vertical height difference: Less than 5 m
(3) Limitations for one way piping length and vertical height difference.
Precautions for refrigerant piping
(Fig. 26)
Do not twist or crush piping. Be sure that no dust is mixed in piping. Bend piping with as wide angle as possible. Keep insulating both gas and liquid piping. Check flare-connected area for gas leakage.
Forced fastening without centering may damage the threads and cause a gas leakage.
(5) Purging mehtod ( the refrigerant is R407C )
Install the unit so that the angle of inclination must be less than 3 degrees.
Series 24,28
Gas pipe
15.88x1.0mm
Liquid pipe
Gas pipe
9.52x0.8mm
15.88x1.0mm
Series 36,42
Liquid pipe
Gas pipe
9.52x0.8mm
19.05x1.0mm
Liquid pipe
6.35x0.8mm
Series 14,18
Pipe dia Fastening torque
Liquid pipe 6.35mm Gas pipe 15.88mm
Liquid pipe 9.52mm
Gas pipe 19.05mm
18N.m 60N.m 40N.m
110N.m
For series 24,28
1
Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
To use vacuum pump
Vacuum pump
Gaugemanifold
2-way valve
3-way valve
Liquid Side
6.35mm (1/4")
Gas Side
15.88mm (5/8")
For series 14,18
For series 36,42
Gaugemanifold
Vacuum pump
2-way valve
3-way valve
Vacuum pump
3-way valve
2-way valve
Gaugemanifold
Anchor bolt
Unit
Unit
Concrete foundation
Anchor bolt
Unit
Anchor bolt
Concrete foundation
INSTALLATION INSTRUCTIONS
Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.
6
If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed steps.
6
No gas leakage?
5
4
Open the valve rod for the 2-way valve to and angle of anticlockwise 90 degree. After 6 seconds later, close the 2-way valve and male the inspection of gas leakage.
CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.
To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for 2-way valve and 3-way's a lottle more than the point where the torque increases suddenly.
7
8
After attaching the each caps, check the gas leakage around the caps.
2
Open
2
Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.
3
Close
Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 .
For series 24,28
For series 36,42
3-way valve
2-way valve
Open
90•
Service port
90•
4
90• for 6 sec.
For series 14,18
2-way valve
3-way valve
Open 90•
90•
Service port
4
90• for 6 sec.
2-way valve
3-way valve
90•
Service port
90•
4
90• for 6 sec.
Open
3
For series 24,28
3-way valve
2-way valve
6
6
For series 36,42
Liquid pipe 9.52mm
Gas pipe 19.05mm
2-way valve
3-way valve
6
6
6
6
2-way valve
3-way valve
For series 14,18
Service port cap
7
3-way valve
2-way valve
7
Valve rod cap
Valve rod cap
7
For series 24,28
2-way valve
3-way valve
7
Valve rod cap
Valve rod cap
7
Service port cap
7
For series 14,18
3-way valve
2-way valve
7
Valve rod cap
Valve rod cap
7
Service port cap
7
For series 36,42
INSTALLATION INSTRUCTIONS
GAS LEAKAGE INSPECTION
After connecting the piping, check the joints for gas leakage with gas leakage detector.
CAUTION
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)(Fig.28A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire. (2) Using a screwdriver, remove the terminal screw(s) on the terminal board. (3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw. (4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.
B. For strand wiring(Fig.28B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring. (2) Using a screwdriver, remove the terminal screw(s)on the terminal board. (3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end. (4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 28
Screw with special washer
Round terminal
Wire
Terminal board
Screw with special washer
Round terminal
Wire
A. Solid wire
Insulation
Strip 25mm
Loop
B. Strand wire
Strip 10mm
Round terminal
After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
Fig. 29
Cord clamp
Insulation tube
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.
INSTALLATION INSTRUCTIONS
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
INDOOR UNIT SIDE
(2) Pull out the electric component box.
Fig. 32
(3) Remove the electric component box cover.
Fig. 33
(1) Remove the cord clamp. (2) Process the end of the connection cords to the dimensions shown in Fig.34. (3) Connect the end of the connection cord fully into the terminal block.
(4) Wiring
Fig. 30
Electric component box
CAUTION
Be careful not to pinch the lead wires between the electric component box and base.
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 5
ELECTRICAL WIRING
Series
Connection cord (mm2)
Fuse capacity(A)
MAX MIN
14,18 24,28 36,42
3.5 3.5 3.5 3.5
2.5
2.5 2.5 2.0
20 30 30 30
CAUTION
(1) Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection cord with the cord clamp.(If the insulator is chafed, electric leakage may occur.)
(4) Always connect the ground wire.
Fig. 31
Electric component box
Remove the four tapping screws.
CAUTION
Do not remove the screws. If the screws are removed, the electric component box will fall.
(4) Fasten the connection cord with a cord clamp. (5) Fasten the end of the connection cord with the screw. (6) For series 24,28,36,42,the power cable and connecting are self-provided.
Outdoor unit
Indoor unit
Outdoor unit
1 2 3
1
2
3
For series 14,28
For series 36,42
Indoor unit
Outdoor unit
1 2 3
1 2 3
N
TSR
Base
Electric component box cover
Remove the three tapping screws.
Fig. 34
For series 14,18
Indoor unit
Outdoor unit
1 2 3 4 5 L N
1
2345
H05RN-F 4G0.75mm
2
H07RN-F 2 2.0mm
2
Electric component box
For series 14,18
Indoor unit
Outdoor unit
H07RN-F 3G 2.0mm
2
1 2 3 4 5
1
2345
L N
Heat model
Cool model
INSTALLATION INSTRUCTIONS
TEST RUNNING
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air flow switching, and other remote control unit operations. (2) Air filter removal and cleaning, and how to use air louvers. (3) Give the operating and installation manuals to the customer.
MOUNT THE COVER PLATE AND
THE INTAKE GRILL
Note: The following installing procedure only for series 14,18
1.Mount the cover plate. (Right)
(1) Cut a pipe exit hole in the right plate. This is only when the pipe exits from the right side.(This operation is not required when the protrusion is on the top or rear.)
(2) Join the cover plates (right) and mount with screws.
Cover plate (Left)
2. Mount the cover plate.(Left)
(1) Join the cover plate (left) and mount with screws.
Fig. 37
(1) The power source capacity must be the sum of the room air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is dif­ ficult to start, contact the power company the voltage raised.
CAUTION
1. CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do not air flow direction louvers operate normally? (4) Is the drain normal?
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation? (2) Will noise, wind, or drain water from the unit disturb the neighbors? (3) Is there any gas leakage?
(1) Cut the right side of the intake grill. This is only when the pipe exits from the right side
3. Mount the intake grill.
Fig. 38
(2) Insert the hinges on the bottom of the intake grill into the holes in the base assembly. Then mount the arms to the three areas on the top of the intake grill.
Fig. 39
Fig. 35
Cover plate (Right)
Fig. 36
ELECTRICAL WIRING
(1) Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.
(2) Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
(3) The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3mm between the contacts of each pole.
WARNING
(4) Perform wiring work in accordance with standards so that the room air conditioner can be operated safely and positively.
(5) Install a leakage circuit breaker in accordance with the related laws and regulations and electric company standards.
INSTALLATION INSTRUCTIONS
6.1 Drawings
Fig.1 Indoor Unit
1 Operating Control Panel (Fig.2) 2 Emergency switch 3 Remote Control Signal Receiver 4 Power Indicator Lamp (Red) 5 OPERATION Indicator Lamp (Green) 6 TIMER Indicator Lamp (Yellow) 7 Compressor Run Lamp (Green) 8 Intake Grill (Fig.3) 9 Air Filter
10
UP/DOWN Air Direction Flaps
11
RIGHT/LEFT Air Direction Louvers (behind UP/DOWN Air Direction Flaps) 12
Power Plug
Fig.4 Outdoor Unit
13
Intake grill 14 Outlet grill 15 Pipe Unit
3
1
9
8
Fig.1
12
1110
For series 14,18
For series 24,28
4
6 7
3
Fig.2
POWER OPER TIMER COMP
EMER
2
4
5 6
2
3
POWER OPER
TIMER
EMER
Fig.3
Fig.3
14
13
15
Fig.4
For series 36,42 For series 14,18
For series 36,42
For series 24,28
5
PARTS AND FUNCTIONS
6 PARTS AND FUNCTIONS
INTRODUCTION TO SPARE PARTS
Buttons and display of the remote controller.
CLOCK
MODE
SWING
Power ON/OFF
TEMP
FAN
SLEEP
SET
HOUR
RESET
LOCK
TIMER
Used for unit start and stop.
Used to set auto fan direction.
Used to select AUTO run, COOL,DRY,HEAT and FAN operation.
Used to set correct time.Used to set correct time.
Used to select TIMER ON, TIMER OFF, TIMER ON/OFF.
Used to lock buttons and LCD display.
Used to reset the controller back to normal condition.
Used to set clock and timer setting.
Used to confirm Timer and Clock settings.
Used to select sleep mode.
Used to select fan speed: LO, MID, HI, AUTO
Used to select your desired temp.
Cautions: On cooling only unit, heating mode is not available. After replacing batteries, press ON/OFF, and display becomes as follows: Operation mode: AUTO, Temp: 24 C Timer mode: No, Fan speed: AUTO
Note:
1. The above information is theexplanation of the displayed information therefore varies with those displayed in actual operation.
2. This type only has the relevant function and display as indicated in the above figure.
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK TIMER
LOCK RESET
AUTO
ON OFF
AM PM
AM PM
7 REMOTE CONTROLLER FUNCTIONS
REMOTE CONTROLLER FUNCTIONS
INTRODUCTION TO SPARE PARTS
Hints
LO
MID
HI
AUTO
AUTO
Buttons and display of the remote controller.
DRY
COOL
AUTO
SWING
FAN SPEED
SLEEP
Clock set
TIMER ON
TIMER OFF
LOCK
CLOCK
TEMP.
SIGNAL SENDING
FAN OPERATION
HEAT
When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows: Press CLOCK button, "AM" or "PM" flashes. Press or to set correct time. Each press will increase or decrease 1min. If the button is kept depressed, time will change quickly. After time setting is confirmed, press SET, "AM "and "PM" stop flashing, while clock starts working.
After replacing with new batteries, remote controller will conduct self-check, displaying all information on LCD. Then, it will become normal.
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK
TIMER
LOCK RESET
AUTO
ON OFF
AM PM
AM PM
REMOTE CONTROLLER FUNCTIONS
REMOTE CONTROLLER OPERATION
Remote controller's operation
When in use, put the signal transmission head directly to the receiver hole on the indoor unit. The distance between the signal transmission head and the receiver hole should be within 7m without any obstacle as well. Don't throw the controller, prevent it from being damaged. When electronic-started type fluorescent lamp or change-over type fluorescent lamp or wireless telephone is installed in the room, the receiver is apt to be disturbed in receiving the signals so the distance to the indoor unit should be shorter.
Loading of the battery
Load the batteries as illustrated. 2R-03 batteries, resetting key (cylinder)
Remove the battery cover :
Slightly press " " and push down the cover.
Load the battery :
Be sure that the loading is in line with the " + " / " - " pole request as illustrated.
Put on the cover again Confirmation indicator :
In disorderation, reload the batteries or load the new batteries after 5mins.
Note :
Use two new same-typed batteries when loading. If the remote controller can't run normally or doesn't work at all, use a sharp pointed item to press the reset key.
Hint :
Remove the batteries in case unit won't be in usage for a long period. If there is any display after taking-out just need to press reset key.
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK TIMER LOCK RESET
AM
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
FAN operation
Remote controller can memorize settings in each operation mode. To run it next time just select the operation mode and it will start with the previous setting. No reselecting is needed.(TIMER ON/OFF needs reselecting)
Hints
(1) Unit start
(2) Select operation mode
(3) Fan
(4) Unit stop
AUTO COOL DRY HEAT FAN
Press ON/OFF button, unit starts. Previous operation status appears on display. (Not Timer setting) Power indicator on indoor unit lights up.
Press MODE button. For each press, operation mode changes as follows:
Unit will run in selected mode. stop display at " " FAN.
Press FAN button. For each press, fan speed changes as follows:
Unit will run at selected fan speed. Adjust air flow direction if necessary, refer to page13.
Press ON/OFF button. Only time remains on LCD. All indicators on indoor unit go out. Vertical flap closed automatically.
LO
MID HI
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK TIMER
LOCK RESET
AM
2
4
1
3
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
AUTO run, COOL,HEAT and DRY operation
Use COOL in summer. Use HEAT in winter. Use DRY in spring,autumn and in damp climate.
(1) Unit start
(2) Select operation mode
(3) Select temp.setting
Press ON/OFF button, unit starts. Previous operation status appears on display.(Not Timer setting) Power indicator on indoor unit lights up.
Press MODE button. For each press, operation mode changes as follows:
Unit will run in operation mode displayed on LCD. Stop display at your desired mode.
Hints
Unit will start running to reach the temp. setting on LCD.
Remote controller can memorize each operation status. When starting it next time, just press ON/OFF button and unit will run in previous status.
AUTO COOL DRY HEAT FAN
Press TEMP button Every time the button is pressed, temp. setting increases 1 C Every time the button is pressed, temp. setting decreases 1 C
Recommendations
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK TIMER
LOCK RESET
AM
1
4
3
2
3
6
5
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
Press FAN button. For each press, fan speed changes as follows:
(4) Fan speed selection
Unit runs at the speed displayed on LCD. In HEAT mode, warm air will blow out after a short period of time due to cold-draft prevention function. In DRY mode, when room temp. becomes 2 C higher than temp. setting, unit will run intermittently at LO speed regardless of FAN setting.
AUTO
LO
MID HI AUTO
Press ON/OFF button. Only time remains on LCD. All indicators on indoor unit go out. Vertical flap closes automatically.
(6) Unit stop
As cold air flows downward in COOL mode, adjusting air flow horizontally will be much more helpful for a better air circulation. As warm air flows upward in HEAT mode, adjusting air flow downward will be much more helpful for a better air circulation. Be careful not to catch a cold when cold air blows downward. It is harmful to your health in summer to go frequently in and out of places where temp.difference is above 7 C . Temp. difference of 3-5 C will remove your fatigue. More than this, unit's load can be reduced and power consumption cut down as well. So, you'd better set a temp. diff of 3-5 C between indoor and outdoor temp. in COOL mode.
Hints
COOL operation starts when room temp. is higher than temp. setting.
On reaching temp. setting,unit will run in mild DRY mode.
Ultra-low air flow
Temp. setting+2 C Temp. setting
(5) Air flow direction adjust
After operation mode is selected, vertical flap will open automatically according to the mode.
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
TIMER operation
Hints
Set Clock correctly before starting Timer operation(refer to page 6)
You can let unit start or stop automatically at following times: Before you wake up in the morning, or get back from outside or after you fall asleep at night.
TIMER ON/OFF
(1)After unit start, select your desired operation mode. Operation mode will be displayed on LCD. Power indicator on indoor unit lights up.
(2)TIMER mode selection
Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows:
Select your desired TIMER mode (TIMER ON or TIMER OFF) ON or OFF will flash.
(3)Timer setting
Press HOUR button.
Every time the button is pressed, time increases 10min. If button is kept depressed, time will change quickly. Every time the button is pressed, time decreases 10min. If button is kept depressed, time will change quickly. Time will be shown on LCD. It can be adjusted within 24hours.
(4)Confirming your setting
After setting correct time, press SET button to confirm "ON" or "OFF" stops flashing Time displayed: Unit starts or stops at x hour x min (TIMER ON or TIMER OFF). Timer mode indicator on indoor unit lights up.
To cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
After replacing batteries or a power failure happens, Time setting should be reset. Remote controller possesses memory function, when use TIMER mode next time, just press SET button after mode selecting if timer setting is the same as previous one.
ON
OFF
ON
OFF
blank
TIMER OFFTIMER ON TIMER ON-OFF
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK TIMER
LOCK RESET
ON
AM
2
1
4
3
3
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK TIMER
LOCK RESET
ON
AM
2
1
6
3
5
OFF
PM
4
Every time the button is pressed, time increases 10min. If button is kept depressed, time will change quickly. Every time the button is pressed, time decreases 10min. If button is kept depressed, time will change quickly. Time will be shown on LCD. It can be adjusted within 24hours. AM refers to morning and PM to afternoon.
TIMER ON-OFF
Operation mode will be displayed on LCD. Power indicator on indoor unit lights up.
(3)Time setting for TIMER ON
(4)Time confirming for TIMER ON
After time setting, press TIMER button to confirm. "ON" stops blinking, While "OFF" starts blinking. Time displayed: Unit starts at X hour X min.
To cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears. According to the Time setting sequence of TIMER ON or TIMER OFF, either Start­Stop or Stop-Start can be achieved.
Press HOUR button.
(1)After unit start, select your desired operation mode
Every time the button is pressed, display changes as follows:
(2)Press TIMER button to change TIMER mode
ON
OFF
ON
OFF
blank
TIMER OFFTIMER ON TIMER ON-OFF
Select TIMER ON-OFF, "ON" will flash.
(5)Time confirming for TIMER OFF
Follow the same procedures in "Time setting for TIMER ON".
(6)Time setting for TIMER OFF
After time setting, press SET button to confirm "OFF" stops flashing. Time displayed: Unit stops at X hour X min.
REMOTE CONTROLLER FUNCTIONS
AIR FLOW DIRECTION ADJUSTMENT PROCEDURE
CAUTION
Adjusting up/down air flow direction
Up/down direction can be adjusted by using the SWING button on the remote c ontroller. Each time pressing this button, the mode changes in the following sequence.
SWING
No indication (louver stopped)
Change to the AIRFLOW mode.
SWING
LOUVER STOPPED
Louver moves in up­ward and downward directions continuous­ly.
When the LOUVER button is pushed during SWING mode, it stops swinging at the just angle.
Avoid direct air flow to the body for many hours. Avoid downward blowing operation of cooling mode for many hours. Do not touch the swing louver during swing operation.
REMOTE CONTROLLER FUNCTIONS
At night, before going to bed you can press down the SLEEP button on the controller and the air-conditioner will run by the comfortable sleeping mode to make you sleep more comfortable.
One hour after sleeping operation start, the temp. is 1 C higher than the setting one. After another hour the temp. rises 1 C and then run continuously for another 6hrs' and then close. The actual temp. is higher than the setting one which is to prevent from being too cool to your sleep.
In cooling, dehumidifying mode
Press SLEEP button once to make the air conditioner have the previous-set sleep time (first power-on is "1h"), the sleep symbol will appear. Press time button / , you can choose the time in 1~8 hours. Each press of / , the time increases/reduces 1 hour and "xh" appears in the humidity setting part, "OFF" appears in "TIMER OFF" display part and timer-off time; press SLEEP button again to cancel sleep function, the sleep symbol diappears.
One hour after start up, the temp. decrease 2 C lower than the setting one. After another hour decrease by more 2 C. The temperature will automatically rise by 1 C after another 3hrs' operation, and then automatically close after 3hrs' continuous operation. The actral temperature is lower than the setting one which is to prevent from being too hot to your sleep.
In heating mode
Note: In AUTO mode, unit will run in SLEEP function according to the operation mode. After setting SLEEP function, it is forbidden to calibrate clock. If the set sleep-time does not reach 8 hours, the unit will stop operation automatically after set time is complete. Set "TIMER-OFF" function first, then set SLEEP, and press the sleep-set-performance; set TIMER-ON function first, the sleep function can only be set before TIMER-ON; if set the SLEEP function first, the TIMER function can not be set. After setting SLEEP, press CLOCK button to show the time; press TEMP. button to show the temperature; press again to change temperature. When the set SLEEP time is 8 hours, connect it as shown in the following figure.
SETTING T
SLEEP RUN BEGINS SLEEP RUN STOPS
1 hr
1 hr
3 hrs
about 3 hrs
decrease 2 C
decreases 2 C
increase1 C
SHUT DOWN
SLEEP RUN STOPS
Heat mode
SLEEP RUN BEGINS
SETTING T
SHUT DOWN
Cooling mode
TEMP
SWING
FAN
ON
OFF
MODE
SLEEP
SET
CLOCK
TIMER
LOCK RESET
Comfortable Sleep
OFF
AM
about 6 hrs
1 hr
1 hr
increase 1 C
increase 1 C
REMOTE CONTROLLER FUNCTIONS
15
Power Failure Resume (to be applied for a necessary situation)
:
Setting Method: When the remote controller is on (excluding timer mode and fan mode),
press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 4 times, the air conditioner will enter
the state of power failure compensation. Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 2 timer, the power failure compensation mode will be cancelled.
Notes: When a power failure suddenly occurs during the air conditioner is working after the power after the power failure compensation is set, if the air conditioner will not be used for a long time, please cut off the power supply to prevent its operation from being resumed after the power is supplied again, or press the "Switch On/Off" button after the power comes again.
After the power failure compensation is set, if power failure suddenly occurs while the air conditioner is working, it will resume the previous working state when the power is supplied again.
Remote Control
:
There is a telecommunication interface for remote control on the control panel of the
indoor unit. After the peripheral equipment have been installed in accordance with the
instruction manual of the selected remote control detector, the air conditioner will be
computerized and controlled from a far-away place.
REMOTE CONTROLLER FUNCTIONS
SWING
ON
OFF
TEMP
FAN
180
58
22
AFTER SIX MINUTES
DISORDER AND RELOAD NEW'S
WHEN THE REMOTE CONTROLLER
3.PLEASE REMOVE THE BATTERIES
BATTERIES IN THE POLARITY
OF DIFFERENT TYPES TOGETHER
2.INSERT CORRECTLY 2
TWO R-03
RIES AND DO NOT USE BATTERIES
1.DO NOT MIX OLD WITH NEW BATTE
REMOTE CONTROL UINT
MODEL
YR-D23
Indoor unit
Stop value
Capillary tube
Heat exchanger
Heat exchanger
Stop value
Muffler
Compressor
Cooling
Outdoor unit
Filter
Capillary tube
Accumulator
7.2 Dimensions of the controller
8 REFRIGERANT DIAGRAM
REMOTE CONTROLLER FUNCTIONS & REFRIGERANT DIAGRAM
9.1 Control Features
The brief introduction includes those for each item of various types of air conditioners and
their electric control functions.
The brief introduction includes those for each item of various types of air conditioners and
their electric control functions.
7.1 Brief introduction of electric control 7.1 Brief introduction of electric control
(1) Automatic run (1) Automatic run
a. Cooling-heating type
After the machine being started and running mode changes to AUTO, the system will
decide running mode according to difference between the present room temperature and
setting temperature, then runs as the decided mode. In the following selections, Tr means
room temperature and Ts means setting temperature.
Select running mode according to the following conditions at the first time to enter Auto
mode:
TrTs -3 to select cooling mode (with setting temperature being Ts +3)
Tr<Ts-3 to select heating mode (with setting temperature being Ts)
After the system entering auto run mode, the running mode can convert automatically
according to variation of room temperature between cooling, blowing and heating in the way
shown as the chart below:
R o o m
t e m p e r a t u r e
f a
n g
l l i
Cooling
Ts+3
Cooling
Room
temperature
rising
Blowing
Ts-3
Ts-3
Heating
b. Single Cooling Type
Select running mode according to the following conditions at the first time to enter Auto
mode:
Tr
Ts + 3 to select cooling mode
Tr < Ts + 3
to select blowing mode
After the system entering auto run, the running mode can convert automatically
according to variation of room temperature between cooling and blowing functions in the way
shown as the chart below:
R o o m
t e m p e r a t u r e
a l l
f
i n g
Cooling
Ts+3
Room
temperature
rising
Blowing
Cooling
Blowing
Ts-3
9 ELECTRICAL CONTROL FUNCTIONS
ELECTRICAL CONTROL FUNCTIONS
(2) Auto Selection of Wind Speed
In the following, Tr means room temperature while Ts means setting temperature.
a. During cooling program
conversion of wind speed from the low to high won’t work until
the present speed has continued for 3 minutes while conversion from the high to low needs
no time delay. The chart below is the sketch map of conversion:
Ts
2
Ts
1
Medium speed
Medium speed
Temperature
falling
Temperature
rising
Low speed
High speed
Low peed
High speed
Ts
3
Ts
b. During heating program
applicable for cooling-heating type , conversion of wind speed
from the low to high won’t work until the present speed has continued for 3 minutes while
conversion from the high to low needs no time delay. The hart below is the sketch map of
conversion:
Low speed
Ts
1
Ts
2
Medium speed
Medium speed
Temperature
rising
High speed
High speed
Temperature
falling
Ts
Low speed
Ts
3
(3) Dehumidifying program
In the following, Tr means room temperature while Ts means setting temperature.
a. After the system entering dehumidifying program, the compressor, outdoor and indoor
blowing fans run according to the following rules:
(1) Tr > Ts + 2
, the compressor and outdoor blowing fan run continuously while indoor
ELECTRICAL CONTROL FUNCTIONS
blowing fan runs at setting wind speed. This working area is defined as area A.
(2) Ts
Tr Ts + 2 , the compressor and outdoor blowing fan run for 10 minutes then
pause for 6 minutes, while indoor blowing fan runs at low wind speed. This working
area is defined as area B.
(3) Tr < Ts, the compressor and outdoor blowing fan stop working while outdoor blowing
fan runs at low wind speed. This working area is defined as area C.
a. After dehumidifying program starting, the system converts between A, B and C areas
according to variations of room temperature with running mode being shown as the chart
below:
Room
temperature
falling
Area B
Area B
Area C
Ts
Area A
Area A
Ts 3
Ts 1
Room
temperature
rising
Ts 1
Area C
(4) Cutoff protection against overload and overheat
During heating program, if the indoor blowing fan has been started and the compressor
has been running more than 2 minutes, and the temperature of indoor coil pipe (Ticp)
> 64
, the outdoor blowing fan will stops running; If Ticp 50 and the outdoor
blowing fan has kept stop state for 45 seconds, then it will restore rotation; If Ticp > 67
and such temperature has last for 10 seconds, the compressor will stop running and
indoor blowing fan run according to conditions as it reaches setting temperature. When
Ticp < 58
, and the compressor has kept stop state over 3 minutes, then the
compressor and outdoor blowing fan will restore normal running.
Cutoff protection for heating current
After 60 seconds from the compressor being started, if CT current exceeds I1 (9.2A) and
such case has kept 5 seconds, the outdoor blowing fan will stop. If 45 seconds has passed
after the outdoor blowing stops and the current of the compressor is less than I2 (7.5A), the
blowing fan will restore running. If CT current exceeds I3 (14.3A) and such case lasts for 3
seconds, the compressor and outdoor blowing fan will stop. The compressor will not restore
running until 3 minutes passes with CT current less than 12A.
(5) Cool wind prevention during heating program
At the first time entering heating program or after ending the latest frost removal, if the
temperature of indoor coil pipe (Ticp) < 28
, the indoor blowing fan will stop running; If
28
Ticp < 38 , the indoor blowing fan will run at low speed; If Ticp > 38 or the
compressor has been running for more than 4 minutes, the indoor blowing fan will run at
ELECTRICAL CONTROL FUNCTIONS
setting wind speed.
(6) Afterheat blowing during heating program
During heating program, the compressor will stop running (except overheat protection or
frost removal) while the indoor blowing fan will firstly run for 50 seconds at low speed then
stop.
(7) Frost removal control (applicable for cooling-heating type)
Starting conditions for frost removal:
A The indoor unit is in overload protection and outdoor blowing fan stops. The outdoor
blowing fan does not enter overheat mode in 10 minutes after it is restarted, the
compressor has run over 45 minutes totally while 20 minutes continuously, and the
temperature of indoor coil pipe is lower than 43 ;
B After the compressor continuously running for 20 minutes, the temperature of indoor
coil pipe falls 1 every 6 minutes and such case continuously appears three times,
and the temperature of indoor coil pipe is less than 40 , and 5 minutes have passed
after the compressor is restarted;
C The compressor has run totally over 3 hours while 20 minutes continuously, and the
temperature of indoor coil pipe is less than 40 ;
D The difference between room temperature and the one of indoor coil pipe is less than
16 and the compressor has totally run over 45 minutes while 20 minutes
continuously;
Frost removal will start if any one of the above conditions is satisfied.
Ending conditions for frost removal:
1 Time of frost removal has exceeded 9 minutes; 2 CT current exceeds I4(8.2A)
Actions of each load after the frost removal starts:
The compressor and outdoor blowing fan stop, and indoor blowing fan also stops.
55 seconds later the reversal valve is closed and next 5 seconds later the compressor is
started.
Actions of each load after the frost removal ends:
The compressor stops running while outdoor blowing fan immediately runs at high
speed, 55 seconds later the reversal valve is opened and next 5 seconds later the
compressor restores running and indoor blowing fan runs as conditions for cool wind
prevention.
(8) Freeze protection
After the compressor has run for 9 minutes, the system will check temperature of
indoor coil pipe (Ticp). If Ticp is less than -1
, the compressor and outdoor blowing
fan will stop. They will run again after the compressor stops if both the following
conditions are satisfied:
1) 3 minutes have passed since compressor stops.
2) Ticp exceeds 7
.
(9) 3 minutes protection for compressor
After compressor stops, it cannot be started until 3 minutes later. During the machine’s
running, if time after loosing power not exceeds 3 minutes, the compressor cannot be
ELECTRICAL CONTROL FUNCTIONS
restarted until 3 minutes later after it is reenergized.
10 Power breakdown memory
If the machine suddenly loses power while running, or stops for maintenance or trouble
shooting, it will restart running as the status when it stops after the power is restored.
Note: 1.
Function setting: Continuously press sleep button on the remote controller 10
times in 5 seconds and buzzer on control panel shall beep 4 times.
2. Memory content: Running mode, wind speed setting, temperature setting,
swing status.
3. Cancel: Press sleep button on the remote controller 10 times and buzzer on
control panel beeps 2 times.
(11) Control of water pump
a. In cooling (including automatic cooling mode) and dehumidifying modes, the water
pump works if the compressor runs while stops 5 minutes later after the compressor
stops.
b. When water tank is fully filled, the float switch will be off. The water pump will start
to work after a controller has detected this signal and it will continue working for 5
minutes after the float restores to normal state.
c. If the full water signal is detected continuously over 5 minutes, the water pump
indicator lamp will flash to alarm and compressor stops running. The water pump
will run 5 minutes, then pause for 5 seconds before next 5 minutes’ running, ... until
the float restores to normal state, after which the pump will run for 5 minutes then
stop.
(12) Monitoring of remote network
Through preset interface, the air conditioner is connected to remote control detector
(made by Haier) with 2-core cables for wire communication, to execute instructions sent
from computer or centralized controller via remote control detector and meanwhile send
present running status and trouble information of the machine to remote control detector.
Connection between air conditioner and remote control detector:
CN11
PC board
1 2
A-
A+
Interface for remote control detector
(13) Trial run
Under shut-down state, hold pressing mandatory button. The buzzer will beep once,
then twice after 5 seconds. Release the button to enter mandatory cooling mode, under
which the indoor blowing fan runs at high speed with both the compressor and outdoor
blowing fan working. Press the mandatory button again can end the mandatory mode.
ELECTRICAL CONTROL FUNCTIONS
9.2 Introduction to the fan speed controller
210V
60V
27 35 39 42
The low ambient temperature cooling system realizes starting normally at the
temperature -15
by the method of: The sensor collects the coil temperature to change
the voltage of the outdoor fan motor, thus to change the fan speed. As a result, the system
pressure is restricted.
1.When the coil temperature exceeds 42
,the voltage would be the highest value
210V and the fan motor runs in the normal way. As the outdoor temperature descends, the
condensator temperature descends too, and the pressure of the compressor discharge
lowers. The voltage of the fan motor falls along with the coil temperature. According to the
above chart (the coil temperature descends, the fan speed descends too), when the
temperature falls to 39
, the fan motor runs in the lowest voltage 60V, and if the
temperature falls continuously to 27
, the outdoor fan motor stops.
2.When the fan motor stops, the pressure of the compressor discharge rises
gradually, and also the condensator temperature. If the temperature rises to 35
, the
outdoor fan motor starts and runs in the lowest voltage 60V. If the condensator
temperature can not stop rising, when it is 39
, the fan speed will rise according to the
line in the above chart until the temperature be 42
, and then the fan motor will run in the
normal way.
1 2 3 4 56
A
B
C
D
6
54321
D
C
B
A
1
1
2
2
3
3
4
4
5
5
6
6
7
7
889
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
IC1
TDA1085C
PortA
PortB
PortC
PortD
R1 220 1W
C1
0.15u 275V
C2
0.01U 275V
R2 220 1W
C3
0.22u 275V
R3 330K
C5
0.33u 63V
R4
330K
E1
1u 50V
Q1 9014
Q3 9014
R5 33k
R7 330k
R6
330k
R10
220
R8 680k
E2
4.7u 50V
R9
5.6k
E3 10u 63V
R11
270K
C6
47n
D1
1N4007
D2
1N4007
C7
684 400V
R12
220
E4 220u 35V
L1
VCC
R28
5.6K
R29
3.3M
R31 680k
D6
E7
4.7u 50V
R13
5.6K
E6
Port
VR1
5K
VCC
Port
D3
1N4007
R26
2.2M
R17 330K
VR2 10K
R18
3.3K
VCC
R19
1.2K
R24
3.3K
R25 180K
R27 33K
Port
Port
R22 2M
R23 1K
C16
104 400V
IC3
E5
4.7u 50V
R20
470
R21
2.2K
4-way valve input 1
4-way valve input 2
VR3 5K
R16
5.6K
R14
2.2K
R15
33K
VCC
AC
1
V+
2
AC3V-
4
BD
SCR
Q2 9012
R30
56K
temperature adjusting
Voltage adjusting
IC2
OPAMP
IC2
OPAMP
7
1
2
3
8
5
6
8
4
4
VCC
VCC
neutral wire
Vref
Vref
VCC
Vref
VCC
TO P5
P5
Pin
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
current in-phase voltage in-phase current restrict
setting fan speed
real fan speed
Ramp Generator
the output of ramp generator
Gnd
Vcc
Vcc parallel connected manostat
F/VC Pump Generator Digital Speed Sense Trigger Pulse Output
toothed wave capacitor
setting current of toothed wave
Closed Loop Stability
temp. sensor
S2
S1
neutral wire input 1
neutral wire output 2
live wire input 2
live wire output 2
E xplanation
Pin
Explanation
ELECTRICAL CONTROL FUNCTIONS
Return
Return
9.3 Defrost operation flow chart
Return
Condition
for
compress
or
OFF
OFF
compressor
Open outdoor fun
Compressor
off or 55s?
4-way value
ON
Compressor
ON ?
Clear the sign of
defrosts
Return
Operation indoor
fun motor
Return
Come to defrost
Compressor
ON
E-Heat off for 30s?
Turn off compressor
outdoor fun
Turn off
4-way value
Compressor
ON
Return
Return
Turn off for
55s?
B
ELECTRICAL CONTROL FUNCTIONS
No. Code
Flash time of
compressor
running indicate
lamp
Trouble contents (new)
1 E0 10 drainage system trouble 2 E1 1 indoor temperature sensor broken
3 E2 2 indoor coil temperature sensor broken 4 E3 3 outdoor temperature sensor broken 5 E4 4 outdoor coil temperature sensor broken 6 E5 5 over current protect limit
7 E6 6 pressure protect 8 E7 7 three phase protect
9 E8 8
Communication trouble between wired remote controller and indoor unit
10 E9 9 communication trouble between indoor and outdoor unit
Indicate lamp of remote control receiver board:
Green----power lamp
Yellow----timer lamp
Red----running of compressor
Red----water pump
The faults are shown by lamp flashing or display on the remote controller
10 DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
10.1 Fault codes
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
10.2 Trouble shooting - Detailed for engineer
Trouble Checkup result Possible reasons Corresponding solution
Unavailable voltage at input part of
circuit board
The power supply coil isn’t plugged
well
Plug the supply coil properly
Damaged wave filtering component
Return to the controller manufacturer for
repair
Unavailable voltage at one end of
the fuse
Damaged fuse Replace with a good one
Unavailable output from the
consequent pole of transformer
The transformer isn’t plugged well or
is damaged
Plug the transformer well or replace with a
good one
Improper output of 7805
Damaged component on power
supply unit of indoor board
Return to the controller manufacturer for
repair
No response after
power being
connected
Normal power supply for major
chip
Damaged major chip
Return to the controller manufacturer for
repair
Damaged connection cable between
display board and indoor board
Replace with a good connection cable
Indicator lamps do not light
Connection cable between display
board and indoor board isn’t
connected well
Connect the cable well
Damaged reception adaptor Replace with a good one
Display board does
not make normal
response
Remote control cannot be received
Damaged remote circuit or major chip
Return to the controller manufacturer for
repair
Damaged dynatron Q1 Replace with a good one
Unavailable square wave signal at
wo ends of the buzzer
t
Damaged major chip
Return to the controller manufacturer for
repair
The buzzer does
not beep while
making remote
control
Available square signal at two
ends of the buzzer
Damaged buzzer Replace with a good one
No output from 2803 on indoor
board
Damaged 2803
Replace with a good 2803
Indoor blowing fan
does not run
Normal output of relays K1, JK2,
JK3
CN8 on indoor board is not plugged
well with connection cable
Connect connection parts well
No output at 16 pin of 2803 on
indoor board
Damaged 2803 Replace with a good 2803
Unavailable voltage on COM port
JK2 on indoor board
of relay
Damaged relay JK2 Replace with a good one
Indoor blowing fan
cannot not
generate low wind
No output at relay JK1 on indoor
board
Damaged relay JK1 Replace with a good one
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
Trouble Checkup result Possible reasons Corresponding solution
No output at 15 pin of 2803 Damaged 2803
Replace with a good 2803
No voltage at COM of relay JK3 on
oor board ind
Damaged relay JK3 Replace with a good JK3e
Indoor blowing fan
cannot generate
medium wind
No output at relay JK2 on indoor
board
Damaged relay JK2 Replace with a good JK2
No output at 14 pin of 2803 Damaged 2803
Replace with a good 2803
Indoor blowing fan
cannot generate
high wind
No output at relay JK3 on indoor
board
Damaged relay JK3 Replace with a good JK3
No output at 11 pin of 2803 Damaged 2803 Replace with a good 2803
No output of swing
No output at relay JK6 of indoor
board
Damaged relay JK6 Replace with a good JK6
Unavailable power
breakdown memory
No setting has been made
Press sleep button 10 times within 5
seconds (and the buzzer will beep 4 times),
the system is then set to power breakdown
memory mode.
Unavailable power
breakdown memory
Damaged chip IC6 of indoor board
Return to the controller manufacturer for
repair
No output at 18 pin of 2803 Damaged 2803 Replace with a good 2803
No
boar
output of relay JK7 on indoor
d
Damaged relay JK7 Replace with a good JK7
No output of
four-way valve
during heating
program
Available output of relay JK7 on
indoor board
Socket CN6 is not plugged well with
connection cable
Plug CN6 and the connection cable well
No output at 12 pin of 2803 Damaged 2803 Replace with a good 2803
No output of relay JK5 on indoor
board
Damaged relay JK5 on indoor board Replace with a good JK5
No swing wind
under swing mode
Available output of relay JK5 on
indoor board
Socket CN4 is not plugged well with
connection cable
Plug CN4 well with the connection cable
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
Trouble Checkup result Possible reasons Corresponding solution
Three minutes’ protection for compressor
The compressor will work normal
after three minutes
Too low temperature of indoor coil pipe
causes overcooling protection
It will restore automatically when
the temperature of indoor coil pipe
rises to 7
No output at 11 pin of 2803 on
or board
indo
Damaged 2803 Replace with a good 2803
No output of relay JK6 on indoor
board
Damaged relay JK6 on indoor board Replace with a good JK6
During cooling program,
the compressor does not
start when the
temperature meets
proper conditions
No output of relay JK6 on indoor
board
Connection cable between the compressor
and JK6 isn’t plugged well
Plug the connection cable well
3 minutes’ delay protection for compressor
It will restore normally after 3
it
Too high temperature of indoor coil pipe
causes overheat protection
It will automatically restore when
the temperature of indoor coil pipe
falls to 57
During heating program,
the compressor does not
start when the
temperature meet proper
conditions
No output at 11 pin of 2803 of
indoor board
Damaged 2803 Replace with a good 2803
No output of relay JK6 on indoor
board
Damaged relay JK6 on indoor board Replace with a good JK6
During heating program,
the compressor does not
start when the
temperature meet proper
conditions
Available output of relay JK6 on
indoor board
Connection cable between compressor
and JK6 isn’t plugged well
Plug the connection cable well
No output at collector of Q2 on
indoor board
Damaged Q2 Replace with a good Q2
No output of relay JK8 on indoor
board
Damaged relay JK8 on indoor board Replace with a good JK8
During cooling program,
the compressor works
while outdoor blowing
fan does not
Available output of relays on
indoor board
Socket CN6 is not plugged well with
connection cable
Plug the connection cable well
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
Trouble Checkup result Possible reasons Corresponding solution
During heating program,
the compressor work while
outdoor blowing fan does
not
Too high temperature of indoor coil pipe
causes overheat protection
It will automatically restore when
the temperature of indoor coil
pipe falls to 57
No output at collector of Q2 on
indoor board
Damaged Q2 Replace with a good Q2
No output of relay JK8 on indoor
board
Damaged relay JK8 on indoor board Replace with a good JK8
During heating program,
the compressor work while
outdoor blowing fan does
not
Available output of relays on
indoor board
Socket CN6 is not plugged well with
connection cable
Plug the connection cable well
Current transformer outputs
normally
Damaged rectification diode D6-D7 etc.
Return to the controller
manufacturer for repair
Transformer CT1outputs
ormally
abn
Damaged transformer CT1 Replace with a good one
Inaccurate protection current Adjust the adjustable potentiometer
Abnormal overcurrent
detection
Damaged major chip
Return to the controller
manufacturer for repair
With timing indicator and
compressor indicator
extinguishing, the
operation indicator flashes
every second
Damaged indoor temperature sensor Replace with a good one
With timing indicator and
compressor indicator
lighting, the operation
indicator flashes every
second
Damaged temperature sensor for indoor
coil pipe
Replace with a good one
No output at 13 pin of 2803 on
indoor board
Damaged 2803 Replace with a good 2803
N
b
o output of relay JK6 on indoor
oard
Damaged relay JK4 on indoor board Replace with a good JK4
Available output of relay JK6 on
indoor board
Socket CN5 is not plugged well with
connection cable
Plug the connection cable well
Water pump indicator
flashes every second
(trouble for water
discharging)
Faulty connection cable to transmit float
feedback signal
Replace with a good one
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
11.1 Wiring Diagram
HCFU-14CL03/R1 HCFU-18CL03/R1
11 ELECTRICAL DATA
ELECTRICAL DATA
HCFU-24CL03/R1
3.15A/250V
TRANSFORMER
INDOOR WIRING DIAGRAM
THE PART IN THE DASHED FRAME IS OPTIONAL ELEMENT
LOUVER MOTOR
FAN MOTOR
Y/G: YELLOW/GREEN
CAPACITOR
W: WHITE
B: BLACK
R: RED
NOTE:
REMOTE CONTROL
TO OUTDOOR UNIT
FUSE
SIGNAL RECEIVER
INDOOR PCB
BOARD
DETECTOR
PIPING TEMP. SENSOR
AMBIENT
SENSOR
TEMP.
ELECTRICAL DATA
HCFU-28CM03/R1
3.15A/250V
TRANSFORMER
INDOOR WIRING DIAGRAM
THE PART IN THE DASHED FRAME IS OPTIONAL ELEMENT
LOUVER MOTOR
FAN MOTOR
Y/G: YELLOW/GREEN
CAPACITOR
W: WHITE
B: BLACK
R: RED
NOTE:
REMOTE CONTROL
TO OUTDOOR UNIT
FUSE
SIGNAL RECEIVER
INDOOR PCB
BOARD
DETECTOR
PIPING TEMP. SENSOR
AMBIENT
SENSOR
TEMP.
ELECTRICAL DATA
3.15A/250V
INDOOR PCB
INDOOR WIRING DIAGRAM
LOUVER MOTOR
FAN MOTOR
CAPACITOR
CAPACITOR
FAN MOTOR
TRANSFORMER
FUSE
TO OUTDOOR UNIT
SIGNAL RECEIVER
PIPING
TEMP. SENSOR
SENSOR
TEMP.
AMBIENT
BOARD
REMOTE CONTROL DETECTOR
NOTE:
THE PART IN THE DASHED FRAME IS OPTIONAL ELEMENT
W: WHITE
B: BLACK
R: RED
Y/G: YELLOW/GREEN
HCFU-36CM03/R1 HCFU-42CM03/R1
ELECTRICAL DATA
HCFU-14CL03/R1
+5
C12
4.7UF/50V
L1
101K
L3 331K
R15
20K-1%
R13
10K
+12
+12
IC7
LM358
C20
104
C21
104
R33
10K
R32
10K
R31 10K
I81I72I63I54I45I36I27I18GND
9
VCC
10
Q111Q212Q313Q414Q615Q5
16
Q818Q7
17
IC3 2803
OSC
C23
104
JK5
C6
104
C5
100UF/16V
C3
2200UF/35V
C4
104
T1
+5
Vin
1
GND
2
Vout
3
7805
C1
0.1uF/275V
FUSE
T3.15A/250V
+12
Q6
9013 4wayvalve
W.F.J
CN13
CN11
CN1
EX TH
CN5
CN6
N
LFMFHF
PUMP
CN8
FM
CN4
D1D2D3D4
CN9CN3
L
N
1
2
3
4
8
VR
550NR-14D
876
5
123
4
IC6
24C01
C19
104
Q7
9013
Q5
9013
Q4
9013
R39
10K
R38
5.1K
R37
5.1K
R36
10K
+12
R40
3K
R41
3K
R11
10K
C18
103
Check
+5
+5
C17
4.7UF/50V
C16
104
R10
10K
R9
1K
IC2
R2
10K
C14
103
XT
+5
R8
10K
C9104
R7
1K
+5
CN12
+5
C25 103
+5
R19
10K
C26 103
LN
R20
10K
331K
L2
R12
10K
C8
102
R14
20K-1%
C7 102
C13
4.7uF/50V
TM TH
BUZ
+5
R18
5.6K
Q1
9013
R17
1K
JK4
C27 103
R29
5.6K
Q3
9013
R30
1K
DL1
CN2
R34
10K
+5
+5
R16
10K
JK3
JK2
JK1
LX
LX102
C2
0.1uF/275V
+12
JK6
DOOR
DOOR
R_Recive
R_Receive
+12
T600D
DL2
+5
R42
10K
RC3 0.033uF120
RC1
0.033uF+120
0.033uF120
RC2
R35
27
D11
4148
B4B-XH-A(
white
)
B2P3(white)
B2P3(blue)
B6P-VH
B3P5(
WHITE)
B2B-XH-A(
red
)
B4B-XH-A(
red)
B7B-XH-A (white)
B3B-XH-A(red)
RTB-1.5-2P
B3B-XH-A(white)
JQ1P-12V
JQ1aP-12V
JQ1aP-12V
JQ1aP-12V
JQ1P-12V
G41-1A
C15
103
+5
0010450174
compressor
out
SDA
1
Tel-In9TimeDisp11FM14Pump15Float16TEST17RESET18Xin19Xout20GND
21
Vref
22
Energency
23
RoomTH
24
ExchTH
25
CT
26
SlaveHeat
27
3
28
Door-Sign
29
Crankcase-Heat
30
High
31
Middle
32
Low
33
Buzzer
34
Compressor
35
Tel-Out
36
Valve
37
OutdoorFan
38
Select539Select440Select3
41
Vcc
42
SCL2Power3Down/Up41/605Select16Select27IR8CompDisp10RunDisp12PumpDisp
13
TMP87PH46N
TMP87C846
ELECTRICAL DATA
11.2 Circuit Diagram
11.2.1 Indoor unit
1 2 3 4 5 6 78
A
B
C
D
8
7654321
D
C
B
A
+5
R32 10K
+5
+5
C8
4.7UF/50V
C9
102
L1
101K
L2 331K
R13 20K
R14
10K
+5
C7
104
+5
+12
+12
+12
+12
IC5
LM358
Q4
9014
Q3
9014
C20 104
C21 104
R28
10K
R22 10K
R29 10K
R27 10K
R30
1K
R31
5.6K
+12
C22
0.01UF/275
R23
47
I8
1
I7
2
I6
3
I5
4
I4
5
I3
6
I2
7
I1
8
GND
9
VCC
10
Q1
11
Q2
12
Q3
13
Q4
14
Q6
15
Q5
16
Q8
18
Q7
17
IC3 2803
+5
DB1
RV1
101
C23 104
C13
470UF/16V
D5
4148
R24 560
R20
1K
R18
1K
R2
10K
OSC
+5
C17
4.7UF/50V
C18 104
R17
10K
R16 1K
C19 103
R19
1K
R8 10K
R33
10K
C24
103
JK3
JK2
JK4
JK7
JK1
JK6
JK5
C25 104
C6
104
C5
100UF/16V
C3
2200UF/35V
C4
104
T1
+5
Vin
1
GND
2
Vout
3
7805
C1
0.1UF/275V
FUSE
3.15A/250V
+5
+12
R21
10K
+5
+5
Q6
9014
LM358
+12
R36 10K
+5
R34 1k
+12
R35 10K
+12
R37 10K
C26 103
R1
10K
Y.S.J
H.X.F
W.F.J
CN12
DL1
CN11
28
CN2
EX TH
CN5
CN8
CN9
PUMP
N
LF
MF
HF
N
V
OF
CN4
FM
CN7
C
IC2
600D
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
2221
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
VDD
VREFGND
XOUT
XIN
RESET
TEST
XT
VR
D1
D2
D3D4
CN14CN3
L
N
IC1
TMP87C846
LN
41
1
2
3
4
8
CN13
CT1
RX
TX
A
B
C
D
4
8
6
75
DL2
DL5
DL3
DL4
J14
PIN.
H IGH
LOW
COOLING
AND
HEATING
COOLING ONLY
A UTO
RESTART
NO AUTO RESTART
HCFU-18CL03/R1
ELECTRICAL DATA
1
+5
+5
+5
+5
+5
+12
+12 +12
+12
+5
+5
+5
+5
+5
+5
+5
+5
+5
+12
1 2 3 4 5 6 78
A
B
C
D
8
765432
D
C
B
A
B
C23
104
LX
C2
0.1UF/275V
R27
5.6K
Q2
9014
R28
330
IC4
TLP371
R24
33K
C11 103
LED
D5 4007
IC5
TLP521
R22
1K
R21
5.6K
C19
103
C10
103
R23
2.2K
FUSE
3.15A/250V
C1
0.1UF/275V
Vin
1
GND
2
Vout
3
7805
T1
C4
104
C3
2200UF/35V
C5
100UF/16V
C6
104
JK1
JK6
JK5
JK2
JK3
R16 10K
C15 103
C14
103
R1 10K
R2 10K
R8
10K
R7 1K
C9 103
R9 1K
R10
10K
C16 104
C17
4.7UF/50V
OSC
R11
10K
C18
103
I8
1
I7
2
I6
3
I5
4
I4
5
I3
6
I2
7
I1
8
GND
9
VCC
10
Q1
11
Q2
12
Q3
13
Q4
14
Q6
15
Q5
16
Q8
18
Q7
17
IC3 2803
R35
47
C22
0.01UF/275
R29
5.6K
R30
1K
R31 10K
R32 10K
R34 10K
R33 10K
C21 104
C20 104
Q3 9014
Q4 9014
IC7
LM358
R12 10K
R13
10K
R14 20K
R15 20K
L3
331K
L2
331K
L1 101K
C8
102
C7 102
C12
4.7UF/50V
C13
4.7UF/50V
R18
5.6K
Q1
9014
BUZ
R17
1K
R25
10K/0.5W
R26
10K/0.5W
D6
4007
C24 104
93C46
DL1
DL2
CN10
CHECK
28
CN1
EX HT
84
32
1
41
LN
TM P87PH4 6N
IC1
N
L
CN3 CN9
D4 D3
D2
D1
VR
CA1
XT
D0 DI SK CS
TEST
RESET XIN XOUT GND VREF
VDD
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21 22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
1
2
3
45
6
7
8
IC6
EEPROM
600D
IC2
FM
CN4
HF
MF
LF
N
PUMP
CN8
CN2
TM TH
CN5
S
S
N
40
SHY
CN11
RA1
39
CN12
REV
C
T
R
PUMP
Pin. high low
cooling and heating
cooling only
with outdoor PCB
w
i thout outdoor PCB
wireless re mote controller
wired remote controller
auto­restart
without auto­restart
HCFU-24CL03/R1 HCFU-28CM03/R1 HCFU-36CM03/R1 HCFU-42CM03/R1
ELECTRICAL DATA
11.2.2 Outdoor unit
1 2 3 4 5 6 78
A
B
C
D
8
7654321
D
C
B
A
C19 103
C9
104
C5
100UF/16V
JK4
JK2
JK3
RW
101
DB1
R7
560
C13
470UF/16V
1
2
CN4
4PIN
1
2
CN1
4PIN
C2
0.1UF/275V
C8
10UF/16V
R5 1K
R6
1K
R3
5.1K
R4
5.1K
R18
2.2K
C4
104
C3
2200UF/35V
Vin
1
GND
2
Vout
3
2
VOLTREG
FUS2
C6
104
A1
1
A2
2
A3
3
A4
4
A5
5
A6
6
A7
7
Q7
10
Q6
11
Q5
12
Q4
13
Q3
14
Q2
15
Q1
16
GND
8
VCC
9
IC2
ULN2003A
R14
200K
D8
4148
C16 103
C14
22UF/250V
C7
10UF/16V
R13
C1
0.1UF/275V
R9
10K
C10
4.7UF/50V
OSC
8MHz
1
2
CN7
2PIN
1
2
CN6
2PIN
LX
TEST
C11
104
R8 1K
R10 10K
R12
R11
62K/1W*3
D6
C12 104
JK5
D5
4007
R17 33K
R21 10K
C18 103
IC3
TLP521-1
IC4
TLP371
R20 1K
R19
5.6K
R15 560
C15 103
C17 103
D7
D9 4007
R22
10K/0.5W
R23
10K/0.5W
R16 10k
CT1
25
J9
IC5
CN9
TEST
CS SK DIVSS
DO
VAREF
T600D
D1 D4
D3
D2
L
S
CN3
VR
CN2
N
V
C
COOL
HEAT
OF
RESET
VCC
H
L
N
IC1
TMP87P808N
1
2
3
4
5
6
7
8
9
10
11
12
13
14 15
16
17
18
19
20
21
22
23
24
25
26
27
28
CA1
RA1
EX HT
TM TH
5
FS
840R7 560
+12
+12
+12
+5
+5
+5
+5
+5+5
+5
+5
+5
+5
+5
+5
Pin. high low
2 speed
single speed
standard
ELECTRICAL DATA
Model: HCFU-14CL03/R1 HCFU-18CL03/R1 HCFU-24CL03/R1 HCFU-28CM03/R1
Ambient temperature sensor Coil temperature sensor
23K 10K
Ambient temperature sensor Coil temperature sensor Fan speed controller sensor
5K 5K 5k
Indoor
Outdoor
HCFU-36CM03/R1 HCFU-42CM03/R1
ELECTRICAL DATA
11.3 Thermostat chart (Sensor resistance-temperature graph)
R/T CHART OF SENSOR R25=23K
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
-20
-18
-16
-14
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
Resistance
K
ELECTRICAL DATA
R/T CHART OF SENSOR R25 =5K
012345678
9
1011121314151617181920212223242526272829303132333435363738394041424344454647484950
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Resistance
(K )
ELECTRICAL DATA
R/T CHART OF SENSOR R25
=
10K
02468
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
-20
-18
-16
-14
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
Temp.
Resistance
K
ELECTRICAL DATA
12 EXPLODED VIEWS & PART LISTS
12.1 Model HCFU-14CL03/R1 HCFU-18CL03/R1 indoor unit
EXPLODED VIEWS & PARTS LISTS
HCFU-14CL03/R1 HCFU-18CL03/R1 Part list of indoor unit
No. Name of part specialized number QTY. Remark
1 air filter 001A2400087 2 2 inlet grill assy 001A0100330 1 3 fixing plate 001A1301398 2 4 strengthen tendon 001A1301395 1 5 pinch plate 001A1301399 2 6 wiring assembly 001A4400509 1 7 Fan motor capacitor 2uf 001A3600009B 1 8 transformer 001A3800141 1
9 indoor PCB 0010400020 1 10 termonal block 001A4000084 1 11 Power line clip 001A14311292 1 12 wiring block 001A1431326 1 13 environment temp. Sensor indoor 001A3900005 1 14 clamp plate of motor 001A1301382 1 15 connecting rod of motor 001A1301383 1 16 Fan motor bracket 001A1301381 1 17 small block 001A1443592 1 18 Indoor fan motor 001A3000109 1 19 centrifugal fan 001A2300042 2 20 drainage elbow 001A1436664 1 21 scroll case 1 001A1431608 2 22 scroll case 2 001A1431609 2 23 Pipe temp. sensor indoor 001A3900006 1 24 Air inlet tube assy. 001A2111677 1 25 liquid pipe 0010750130 1 26 back framework 001A1734862 2 27 handle 001A1436606 4 28 right wallboard 001A1101104 1 29 plate assy right 001A1101041 1 30 long blade
001A1431593 1 31 strengthen tendon 001A1301394 1 32 outlet grill hold middle 001A1231180 1 33 mini fan blade 001A1431599 1 34 cover 001A0100329 1 35 display panel 001A1431586 1 36 Airflow oriented board affix 001A1431827 3 37 curving connecting rod 001A1431598 1 38 receive panel 001A0600249 1 39 Indicator light base 001A1431587 1 40 Motor bracket 001A1301133 2 41 stepping motor 001A3000107 2 42 fixing layering 001A1301396 1 43 Drain pan 001A1233191 1 44 Evaporator left holder 001A1301400 1 45 Evaporator assembly 001A0400069 1 46 plate assy left 001A1101099 1 47 left wallboard 001A1101103 1 48 assistant drain pan 001A1231192 1 49 cover assy 001A1231182 1 50 back framework 001A1101098 1 51 Evaporator right holder 001A1301401 1
52 Remote Controller 0010400256 1
EXPLODED VIEWS & PARTS LISTS
Model HCFU-14CL03/R1 HCFU-18CL03/R1 outdoor unit
EXPLODED VIEWS & PARTS LISTS
HCFU-14CL03/R1 HCFU-18CL03/R1 Part list of outdoor unit
No. Name of parts Part specialized code QTY. Remark
1 Front guard assy. 001A0100122 1 2 Front panel 001A1101038 1 3 Axial fan 001A2331024 1 4 Fan mortor 001A3000026 1 5 Motor mounting plate 001A1301133 1 6 Condenser assy. 001A0400130 1 7 Slide plate(left) 001A0100356 1 8 handle 001A1436182 2
9 Top cover assy. 001A0100124 1 10 Slide plate(right) 001A0100126 1 11 Wire cover 001A0100125 1 12 cable clamp 001A6645002 1 13 filter 001A2411072 1 14 2-way valve 0010700252 1 15 3-way valve 0010700028 1 16 Running capacitor 001A3600030 1 17 Terminal block 001A4000107 1 18 Compressor 0010700818 1 19 damping mat 001A1752164 1 20 Electrical box 001A1301129A 1 21 fan mortor capacitor 001A3600098 1 22 Valve pedestal 001A1301127 1 23 Partition plate 001A0100127 1 24 Bottom cover assy. 001A0100129 1 25 Fan Speed Controller 0010450176 1 26 Wiring assy. 0010450407 1
EXPLODED VIEWS & PARTS LISTS
12.2 Model HCFU-24CL03/R1 HCFU-28CM03/R1 indoor unit
EXPLODED VIEWS & PARTS LISTS
EXPLODED VIEWS & PARTS LISTS
No. Name of parts Part specialized code QTY.
Remark
1 inlet grill assy 001A1231278 2 2 air filter 001A2400108 2 3 front panel assy 001A1101174 1 4 pad 001A17341062 1 5 Pipe temperature sensor 001A3900006 1 6 drain pan assy 001A1200185 1 7 mounting plate 001A1101179 1 8 left scroll case 001A1301574 1
9 motor holder 001A1301581 1 10 centrifugal fan 001A2331071 2 11 motor bracket 001A1301580 2 12 motor 001A3000172 1 13 electric box assy 001A1301379 1 14 Eletrical box 001A13011280 1 15 indoor  PCB 0010400407 1 18 transformer 001A3800066 1 19 capacitor 001A3600018 1 20 termonal block 001A4000151 1 22 Power line clip 001A5701009 1 23 scroll case right 001A1301582 1 24 environment temperature sensor 001A3900159 1 25 air pipe 001A2111028 1 26 liquid pipe 001A2111033 1 27 partition plate 001A1301588 1 28 plate assy right 001A1301577 1 29 right wallboard 001A1301579 1 30 ornamental plate right 001A1231277 1 31 evaportor 001A0400126 1 32 ornamental plate left 001A1231276 1 33 left wallboard 001A1301578 1 34 plate assy left 001A1301575 1 35 rear guard plate 001A1101178 1 36 blade assy 001A1101176 1 37 fixing bracket right 001A1431746 1 38 prompting pole 001A1443745 1 39 Synchromotor 001A3000198 1 40 Indicator light cover 001A1431878 1 41 receive panel 0010400410 1 42 ornamental plate of panel(left) 001A1231279 1 43 fixing bracket left 001A1431800 1 44 middle ornamental plate 001A1231280 2 45 left top cover assy 001A1231272 1 46 Ornamental plate of panel right 001A1231281 1 47 front top cover assy 001A1231274 1 48 left fixing bracket 001A0100431 1 49 blade assy2 001A1101177 1 50 top cover assy 001A1231275 1 51 middle outlet grill hold 001A1231284 1 52 right top cover assy 001A1231273 1 53 outlet grill hold right 001A0100432 1 54 Remote Controller 0010400256 1
Model HCFU-24CL03/R1 HCFU-28CM03/R1 outdoor unit
EXPLODED VIEWS & PARTS LISTS
HCFU-24CL03/R1 HCFU-28CM03/R1 Part list of outdoor unit
No Name of parts Part specialized code QTY. Remark
1 Front grille 001A1236028 1 2 handle 001A1436160 2 3 Front panel 001A1101078 1 4 service panel assy 001A0100524 1 5 Axial fan 001A5402022 1 6 Fan motor 001A3000082 1 7 Bracket for fan motor 001A0100266 1 8 Condenser assy. 001A0400119 1
9 Electric box 001A1301453 1 10 Capacitor for fan motor 001A3600018 1 11 connection block 001A4000011 1 12 Capacitor for compressor 001A3600030 1 13 Capacitor clamp 0010100001 1 14 AC contactor 001A3900161 1 15 Terminal block 001A4000151 1 16 electrical source connection block 001A4000110 1 17 cable clamp 001A5731054 1 18 outlet Air pipe assy. 001A0500368 1 19 inlet Air pipe assy. 001A0500364 1 20 filter 001A2411023 1 21 3-way stop valve 001A2500154 1 22 2-way stop valve 001A2500153 1 23 muffle 001A2111911 1 24 Compressor(ZR34K3E-PFJ-522) 001A2000201 1 25 Partition plate 001A0100350 1 26 Top cover assy. 001A0100264 1 27 Back grille 001A0100109 1 28 Junction box 001A0100394 1 29 Slide plate(right) 001A0100390 1 30 Valve pedestal 001A1301506 1 31 branch triby 001A1301117 2 32 Bottom cover assy. 001A0100351 1 33 Wiring assy. 0010450408 1 34 Fan Speed Controller 0010450176 1
EXPLODED VIEWS & PARTS LISTS
12.3 Model HCFU-36CM03/R1 HCFU-42CM03/R1 indoor unit
EXPLODED VIEWS & PARTS LISTS
HCFU-36CM03/R1 HCFU-42CM03/R1 Part list of indoor unit
No. Name of parts Part specialized code QTY.
Remark
1 inlet grill assy 001A1231278 3 2 air filter 001A2400108 3 3 front panel assy 001A1101167 1 4 pad 001A17341009 1 5 Eletrical box 001A13011280 1 6 Eletrical box cover 001A1301379 1 7 PCB 0010400407 1 8 transformer 001A3800066 1
9 capacitor 01A3600018 2 10 termonal block 001A4000151 1 11 Power line clip 001A5701062 1 12 environment temp. sensor indoor 001A3900159 1 13 motor bracket 001A1301580 4 14 scroll case right 001A1301582 2 15 drain pan assy 001A1200325 1 16 mounting plate 001A1101172 1 17 air pipe 001A0500403 1 18 liquid pipe 001A0500404 1 19 partition plate 001A1301588 1 20 plate assy right 001A1301577 1 21 right wallboard 001A1301579 1 22 Ornamental plate right 001A1231277 1 23 left scroll case 001A1301574 2 24 centrifugal fan 01A2331071 4 25 motor bracket 001A1301581 2 26 Indoor fan motor 001A3000172 2 27 left wallboard 001A1301578 1 28 ornamental plate
left 001A1231276 1 29 Pipe temp. sensor indoor 001A3900006 1 30 Indicator light cover 001A1431878 1 31 receive panel 0010400410 1 32 ornamental plate of panel(left) 001A1231279 1 33 middle ornamental plate 001A1231280 4 34 Long blade assy 001A1101169 1 35 fixing bracket left 001A1431800 1 36 left fixing bracket 001A0100431 1 37 left top cover assy 001A1231272 1 38 front top cover assy 001A1231274 3 39 Ornamental plate of panel right 001A1231281 1 40 outlet grill hold middle 001A0100435 3 41 top cover assy 001A1231275 3 42 long blade
001A1101170 1 43 outlet grill hold right 001A0100432 1 44 right top cover assy 001A1231273 1 45 fixing bracket right 001A1431746 1 46 prompting pole 001A1443745 1 47 Synchromotor 001A3000198 1 48 Remote Controller 0010400256 1 49 Heat insulation pipe1 001A1734260 1 50 plate assy left 001A1301575 1 51 evaportor 0010700388 1 52 Rear guard plate 001A1101171 1
EXPLODED VIEWS & PARTS LISTS
HBU-36CM03/R1 HBU-42CM03/R1 Outdoor Units
EXPLODED VIEWS & PARTS LISTS
HCFU-36CM03/R1 HCFU-42CM03/R1 Part list of indoor unit
No. Name of parts Part specialized code QTY. Remark
1 Front grille 001A1236028 2 2 Front panel 001A0100492 1 3 Axial fan 001A5402022 2 4 Fan motor 001A3000244 2 5 Bracket for fan motor 001A0100740 1 6 AC contactor 001A3900161 1 7 Capacitor for fan motor 001A3600018 2 8 Condenser assy. 001A0400165 1
9 connection block 001A4000011 1 10 cable clip 001A5701062 1 11 Terminal block 001A4000158 1 12 Electric box 001A1301708 1 13 Top cover assy. 001A0100827 1 14 Slide plate(right) 001A0100733 1 15 Back grille 001A0100495 1 16 segregator 001A2000175 1 17 muffle 001A2400128 1 18 fix panel 001A1301465 1 19 Compressor 001A2000200 1 20 2-way stop valve 001A2500149 1 21 3-way stop valve 001A2500150 1 22 wiring harness 0010450409 1 23 Valve pedestal 001A1301762 1 24 Bottom cover assy. 001A0100735 1 25 Partition plate 001A0100734 1 26 Partition plate tray 001A17561212 1 27 service panel assy 001A1301707 1 28 handle 001A1436160 1 29 cover 001A1301763 1 30 Fan Speed Controller 0010450176 1
EXPLODED VIEWS & PARTS LISTS
13 PERFORMANCE CURVES
HCFU-14CL03/R1
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
5.50
6.00
6.50
-15 -10 -5 5 15 25 35 43
Outdoor temperatur( )
Cooling capacity(KW)
20
22
25
27
30
32
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
-15 -10 -5 5 15 25 35 43
Outdoor temperature( )
EER
20
22
25
27
30
32
Cooling capacity graph
EER graph
a
b
Indoor
DB( )
Indoor
DB( )
PERFORMANCE CURVES
HCFU-18CL03/R1
Cooling capacity graph
EER graph
a
b
2.00
2.50
3.00
3.50
4.00
4.50
5.00
5.50
6.00
6.50
7.00
7.50
-15 -10 -5 5 15 25 35 43
Outdoor temperature(
)
Cooling capacity(KW)
20
22
25
27
30
32
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
-15 -10 -5 5 15 25 35 43
Outdoor temperature(
)
EER
20
22
25
27
30
32
Indoor
DB( )
Indoor
DB(
)
PERFORMANCE CURVES
HCFU-24CL03/R1
Cooling capacity graph
EER graph
a
b
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
-15 -10 -5 5 15 25 35 43
Outdoor temperature(
)
Cooling capacity(KW)
20
22
25
27
30
32
Outdoor temperature( )
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
-15 -10 -5 5 15 25 35 43
EER
20
22
25
27
30
32
Indoor
DB( )
Indoor
DB( )
PERFORMANCE CURVES
HCFU-28CM03/R1
Cooling capacity graph
EER graph
a
b
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
11.00
12.00
-15 -10 -5 5 15 25 35 43
Outdoor temperature(
)
Cooling capacity(KW)
20
22
25
27
30
32
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
-15 -10 -5 5 15 25 35 43
Outdoor temperature(
)
EER
20
22
25
27
30
32
Indoor
DB( )
Indoor
DB( )
PERFORMANCE CURVES
HCFU-36CM03/R1
Cooling capacity graph
EER graph
a
b
0.00
1.50
3.00
4.50
6.00
7.50
9.00
10.50
12.00
13.50
15.00
16.50
18.00
-15 -10 -5 5 15 25 35 43
Outdoor temperature(
)
Cooling capacity(KW)
20
22
25
27
30
32
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
-15 -10 -5 5 15 25 35 43
Outdoor temperature( )
EER
20
22
25
27
30
32
Indoor
DB( )
Indoor
DB( )
PERFORMANCE CURVES
Cooling capacity graph
EER graph
a
b
0.0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
-15 -10 -5 5 15 25 35 43
20
22
25
27
30
32
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
-15 -10 -5 5 15 25 35 43
EER
20
22
25
27
30
32
Indoor
DB( )
Indoor
DB( )
Outdoor DB( )
Outdoor DB( )
Cooling capacity(KW)
HCFU-42CM03/R1
PERFORMANCE CURVES
14 NOISE LEVEL TEST CHART
NOISE LEVEL TEST CHART
Model: HCFU-14CL03/R1 HCFU-18CL03/R1
Air Velocity Distribution
Cooling
Blowy angle: 25
Temperature Distribution
Cooling
Blowy angle:25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
2.4
5.5
0
15.1 Floor type
/
s
1.0
/
s
0.5
/
s
0
2.4
22
25
27
5.5
1.0m/s
1.5m/s
0.5m/s
15 AIR VELOCITY DISTRIBUTION
AIR VELOCITY DISTRIBUTION
Model: HCFU-24CL03/R1 HCFU-28CM03/R1
Air Velocity Distribution
Cooling
Blowy angle:25
Temperature Distribution
Cooling
Blowy angle:25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
0
2.4
5.5
1.0m/s
1.5m/s
0.5m/s
25
0
2.4
22
27
5.5
AIR VELOCITY DISTRIBUTION
Model: HCFU-36CM03/R1 HCFU-42CM03/R1
Air Velocity Distribution
Cooling
Blowy angle:25
Temperature Distribution
Cooling
Blowy angle:25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
0
2.4
5.5
27
0
2.4
22
25
5.5
1.0m/s
1.5m/s
0.5m/s
AIR VELOCITY DISTRIBUTION
15.2 Ceiling type
Model: HCFU-14CL03/R1 HCFU-18CL03/R1
Air Velocity Distribution
Cooling
Blowy angle: 25
Temperature Distribution
Cooling
Blowy angle:25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
5.5
0
2.4
m/s
1.0m/s
0.5m/s
0
2.4
22
25
27
5.5
AIR VELOCITY DISTRIBUTION
0
m/s
0.5m/s
1.0m/s
5.5
2.4
Model: HCFU-24CL03/R1 HCFU-28CM03/R1
Air Velocity Distribution
Cooling
Blowy angle:
25
Temperature Distribution
Cooling
Blowy angle:
25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
0
2.4
22
27
25
5.5
AIR VELOCITY DISTRIBUTION
Model: HCFU-36CM03/R1 HCFU-42CM03/R1
Air Velocity Distribution
Cooling
Blowy angle:
25
Temperature Distribution
Cooling
Blowy angle:
25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
0.5m/s
m/s
0
1.0m/s
2.4
5.5
27
5.5
0
2.4
22
25
AIR VELOCITY DISTRIBUTION
Sincere Forever
Tel: 86-532-8938356
Web site: http: //www.haier.com
Loading...