Haier AB242ACBEA, AC242ACBEA, AD242AHBEA, AU242AHBEA, AP242ACBEA Service Manual

...
MANUAL CODE: SYJS-005 -03 Rev.0 .
Haier Group
Auto-Restart function Group control(with a group controller)
The same outdoor unit can match with cassette \convertible\ duct type indoor unit With new environment friendly refrigerant R407C
Weekly timing(with a weekly timer)
Features
Service Manual
Commercial Air Conditioning
24 28 Universal Outdoor Unit air conditioning
AC28NACBEA+AU28NAHBEA AD28NAMBEA+AU28NAHBEA
AB28NACBEA+AU28NAHBEA
Remotoe control and Wired remote control(Optional)
AB242ACBEA+AU242AHBEA AC242ACBEA+AU242AHBEA
AD242AMBEA+AU242AHBEA
AD242AHBE A+ AU242AHBEA
AP242ACBE A+ AU242AHBEA
AU282AHBEA
CONTENTS
1. Description of Products & Features…………………...…….2
2. Specifications…………………………. ………………...……8
3. Safety precaution…………………………..………………….12
4. Net dimensions of indoor and outdoor unit………………...14
5. Installation instructions ……………………. ………………. 16
6. Parts and functions …………………………..…… ..……….19
7. Remote controller functions………………………….………22
8. Refrigerant diagram…………………………..……………....24
9. Electrical control functions……………………………………25
10. Diagnostic information(trouble shooting)…………….……29
11. Electrical data.........................................…………….……35
12. Exploded views and parts lists...............……………. …...41
13. Performance curves……………............................... ……57
15. Air velocity distribution …………............................... ……48
CONTENTS
Contents…….................................................………...…….1
- 1 -
14. Noise level charts....... …………............................... ……48
1 .Description of Products & Features
Products coding direction
United Outdoor unit:
A U 24 2 A H B E A
Climate type: T1 (see table 1)
Design number E
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407
M stands for cool only type, refrigerant is R22
N stands for cool only type, refrigerant is R407
Appearance character
Product series: common icon-shelled outdoor unit type
Applicable voltage: 2 stands for 220-240V/50Hz
4 stands for 220v/60Hz
N stand for 380V/50Hz
Cooling / Heating capacity,24=24000BTU/h
Product type : “B” stands for cassette type
“C” stands for convertible type
“D” stands for duct
“S” stands for split type
“Q” stands for chiller system
“U” stands for outdoor unit
Abbreviation of Air conditioner
Indoor units of Cassette type:
A C 24 2 A C B E A
Climate type: T1 (see table 1)
Design number E
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407
M stands for cool only type, refrigerant is R22
N stands for cool only type, refrigerant is R407
Appearance character
Product series: common icon-shelled outdoor unit type
Applicable voltage: 2 stands for 220-240V/50Hz
4 stands for 220v/60Hz
N stand for 380V/50Hz
Cooling / Heating capacity,24=24000BTU/h
Product type : “B” stands for cassette type
“C” stands for convertible type
“D” stands for duct
“S” stands for split type
“Q” stands for chiller system
“U” stands for outdoor unit
Abbreviation of Air conditioner
-2-
a) Description of the coding rule of the models
A U 28 N A H B E A
Climate type:T1
Design serial number
Air conditioner
Product series:one-to-one
Outdoor unit
Cooling capacity:28=28000BTU/h
Adaptive voltage:380-400V/50Hz
Appearance features
Product type: heat pump R407C
A B 28 N A C B E A
Climate type:T1
Design serial number
Air conditioner
Product series:one-tag-one
Product specification:valid digit above kilobi
Adaptive voltage:380-400V/50Hz
Appearance features
Product type: heat pump R407C
Product type:indoor unit
P:Cabinet typeC:Convertible type B:Cassette type D:Duct type
b). Standard working condition
Operating Mode
Indoor Operating Mode
Outdoor Operating Mode
Nominal Cooling
Temp.
Temp.
Humidity
DB:27
WB:19
DB:35
DB:7 WB:6
WB:24
Humidity
DB:20
WB:15
Nominal Heating
No.
1 2
Temp.
Humidity
DB:27
WB:19
DB:35
DB:7 WB:6
WB:24
Humidity
DB:20
WB:15
Nominal Heating
No.
1 2
-3-
c)Brief introduction of the series:
Convertible type:
AC242ACBEA AC28NACBEA
(1).Ceiling convertible,flexible installation,convenient
maintenance,saving the users' expenditures
(2)Adopting single-phase & three-phase power supply,applicable for
household and commercial usage
(3).Dual air outlet design,floor air blowing,accelerating the indoor air
circulation, quick temperature adjustment
(4).Long-distance air blowing,large power,large cooling/heating
ratio (5).Intelligent remote control,convenient and flexible control (6).Super-slim indoor unit design,luxury and nice-looking,saving
space,harmonious and unitive with the indoor environment (7).Adopting screw-fastening for the air inlet grill,firmly
fixed;adopting slipway insert-lock fastening method for the
filter screen,convenient cleaning or replacing the filter screen
without opening the air inlet grill. (8).Group control,units up to 128 sets can be controlled .
Duct type :
AD242AMBHA AD242AHBEA AD28NAMBEA
Totally concealed machine body
All the machine body is to be installed inside the ceiling, having no effect on the beauty of the room and without taking any room space.
Air intake via the rear air intake duct
This new design has changed the former unique pattern of air intake, and a larger distance between air intake and air return cycles as well as better air quality can be achieved.
Flexible and easier installation
The machine body is to be installed in a totally concealed way,its fan system has a longer distance coverage so as to supply its airflow to several rooms, and the indoor unit may be installed inside the ceiling of a room or corridor. The installation is simple and flexible, and there is no need to have specified personnel for management, thus cutting down the expenses; the machine is lighter and smaller, and convenient for installation, it takes an extremely small building space, thus lower the construction cost; the indoor unit is to be concealed inside the ceiling, and hence the usable space can be saved and the room decoration will not be affected.
-4-
NEW
NEW
Cassette type:
AB242ACBEA AB28NACBEA
Products characteristic:
Completely invisible machine body:
The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air conditioner allows it to blend right into ceiling.
Superbly efficient healthy filter:
Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently .
Flexible and easy installation
Slim design with machine body, completely ceiling concealing and portable shape, all make it greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free"
mobile outlet grill,
the ceiling can be protected from pollution effectively and allow the airflow to fit people's comfortable need much more
.
Compensation function of power failure:
When meeting a power failure during running, no matter how long it will be, once the power is restored, air conditioner will automatic restart with the previous status.
Safety and reliable control due to various signal controls
1 Inputting with press buttons on the panel 2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors,
3 Piping pressure signals 4 Compressor current signals
5 Testing signals
6 System time-shorten signal
7 Water overflowing signal
8 Communication signals between indoor unit and front plate or between indoor unit and outdoor unit .
Silent design
The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to significantly decrease operating noise.
When using remote-controlling mode, it is comfortable and convenient to operate.
Advanced wire-controller and convenient remote-controller
The new wired controller can connect with 16 indoor units without any device such as detectors. The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient. In addition, it can be compatible with the old remote controllers.
Low ambient temperature cooling function (optional) Equipped with high/low pressure protection switch
The indoor units of AU282AHBEA and AU28NAHBEA are the same.
Climate type
Type of Air Conditioner
T1 T2 T3
Cool only 18 43 0 35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52
d). Brief Introduction for T1\
T2\
T3 working condition
Climate type
Type of Air Conditioner
T1 T2 T3
Cool only 18 43
10
35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52
-6-
2 Specifications
Model Item
AU242AHBEA AC242ACBEA AB242ACBEA AD242AMBEAE AD242AHBEA
Cooling capacity
Btu/h
24000 24000 24000 24000 24000
Heating capacity
Btu/h
27000 27000 27000 27000 27000
Power
1PH 220-230V 50Hz
Cooling power(W)
2700 2700 2700 2700 2700
Cooling EER(Btu/W)
8.89 8.89 8.89 8.89 8.89
Cooling operation current (A)
12.5 12.5 12.5 12.5 12.5
Power factor(%)
0.95 0.95 0.95 0.95 0.95
Heating power (W)
2700 2700 2700 2700 2700
Heating COP(Btu/W)
10 10 10 10 10
Cooling operation current (A)
12.5 12.5 12.5 9.5 9.5
Power factor(%)
0.95 0.95 0.95 0.95 0.95
Operation data
Noise level(high-mid-low) dB(A)
58 48-44-38 39-37-35 35-32-29 42-41-40
External (L×W×H)
948x340x830 99655×199 840×840×240 990×650×300 820×830×360
Dimension mm×mm×mm
Package (L×W×H)
1050x440x979
1150×750×300 910×910×300 1137×800×320 940×1051×510
Weight (net/gross)
Kg/Kg
74/89 30/39 28/30 40/57 48/58
Compressor Model
ZR34K3E-PFJ-522
\ \ \ \
Manufacture
Copeland \ \ \ \
Starting method
PSC \ \ \ \
Starting
current(A)
75 \ \ \ \
Protection
devices
IOL \ \ \ \
Crankcase heater power (W)
\ \ \ \
\
Heat exchanger
0.92m
2
0.084 m2 0.199m2 0.199m2 0.199m2
Refrigerant control
capillary capillary capillary capillary capillary
Refrigerant Type
R407C \ \
Charge(g)
2400 \ \ \
Defrost method
Auto Auto Auto Auto Auto
Fan Type×Number
Axial fan×1 Axial fan×2 Cross flow fan×2 Cross flow fan×2 Cross flow fan×2
Fan motor Motor output (W)
130 45 40 100 130
Air-flow
high-mid-lowm
3
/h
4000 900/840/790 1300/1100/870 1470/1300/1100 900/1250/1500
Anti-vibration and sound insulation devices
XPE XPE XPE XPE XPE
Control method
remote/wire-controlled
\
Remote
controlled
Remote
controlled
Wired
controlled
Wired
controlled
Safety devices
Fuse Fuse Fuse Fuse Fuse
Liquid pipe:(mm)
Φ9.52 Φ9.52 Φ9.52 Φ9.52 Φ9.52
Dimension of refrigerant pipe
Gas pipe:(mm)
Φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88
Connection method
Bugle joint Bugle joint Bugle joint Bugle joint Bugle joint
Drainage pipe(material , I.D./O.D.)Mm
\ PVC 26/32 PVC 25/32 PVC 25/32 PVC 26/32
Appearance colour
white white white white white
Accessories
To see manual To see manual To see manual To see manual To see manual
-7-
Function
cooling heating
Capacity BTU/h
24000 28000
Capacity kW
7.1 7.9
W
2.7 2.7
W
3.2 3.2
EER or COP
W/W
2.6 2.9
Dehumidifying capacity
10³×m³/h
Power cable
Power source
NVHz
A / A
13.5/16 14.5/19.5
Start Current A
Fuse A
Unit model (color)
Type × Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Total Area
Temp. scope
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
kW
dB(A)
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
Refrigerant
Fan
Heat exchanger
1.8
48/46/44
remote type
MAX.Piping length 30
PIPING
R407C/2400
65
Pipe
9.52
15.88
flared
Between I.D &O.
MAX.Drop 20
TP2M/9.52
Weight (Net / Shipping)
45/57
PVC 26/32
1821×532×300
item Model
AP242ACBEA
3.0
3*3.0
Total power input
Max. power input
Running /Max.Running
current
centrifugal*1
Dimension
0.338
1000/900/800
2-7
1920×625×377
0.04
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
560±30/ 490±40/380±50
1, 220~230, 50
Indoor unit
AP242ACBEA
Noise level (H-M-L)
Electricity Heater
60
21
Function
Coo
lin
g
H
eating
Capacity
BTU/h
28000 32000
W
3200 3300
W
4500 5500
EER or COP
BTU/W
8.75 9.7
Dehumidifying capacity 10³×m³/h Power cable Power source NVH
z
A / A
Start Current
A
Unit model (color) Fan Type × Number
Speed(H-M-L)
r/min
Fan motor output power
kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total Area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Control type (Remote /wired) Fresh air hole dimension
mm
kW
dB(A)
kg / kg
External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
kg / kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed
r/min
Fan motor output power kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Refrigerant control method
mm/mm
Volume of Accumulator L
Noise level
dB(A)
material of reduce noise crankcase heater power W
kg / kg
Refrigerant Type / Charge
g
Recharge quantity
g/m
Liquid
mm
Gas
mm
Connecting Method
m m
item Model
A
U28NAHBEA
Total power input
Max. power input
3
/
3N 380V-400V 50H
Z
Running /Max.Running
current
Cooling 5.5/8.0 Heating 5.8/9.5
30
Dimension
Electricity Heater
Noise level (H-M-L)
Weight (Net / Shipping)
Panel
Dimension
/
/
Weight (Net / Shipping)
/
Indoor unitOutdoor unit
A
U28NAHBEA(WHIT
E£©
ZR40K3E-TFD-522 Copela
n
Scroll
A
xial-flow×1
1180+3
0
130
4000
TP2M/9.52
0.92
43-60
Dimension
948x340x830
1050x440x979
/
main capillary 2.4x220;auxiliary capillar
y
Defrosting
A
uto
/
58/--/50
Type of Four way valve
/
MAX.Drop 20
XP
E
/
Weight (Net / Shipping)
74/89
MAX.Piping length
30
PIPING
R407C 2400
60
Pipe
9.52
15.88
flared
Between I.D &O.D
-8-
Function
cooling heating
Capacity BTU/h
28000 34000
Capacity kW
8.2 10
Sensible heat ratio 75%
W
3400 3600
W
4300 4600
EER or COP
W/W
2.41 2.77
Dehumidifying capacity
10³×m³/h
Power cable
Power source N, V, Hz
A / A
Start Current A
Unit model (color)
Model / Manufacture
Type
Type × Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Total area
Temp. scope
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20 DB Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
1, 220-240, 50
cooling: 16A/20A heating: 17A/22A
80
Item Model
AU282AHBEA
2.47
3*3.0
Total power input
Max. power input
Running /Max.Running
current
0.06
3200/-/-
Outdoor unit
AU282AHBEAWHITE
0.92
43-60
Heat exchanger
TP2M/Φ9.52
15
Dimension
948x340x830
1050x440x979
Defrosting
PIPING
R407C 2600
65
Pipe
9.52
15.88
flared
Between I.D &O.
MAX.Drop
scroll
axial×1
C-SBN261H5A(Sanyo
MAX.Piping length 30
Weight (Net / Shipping)
74/89
Type of Four way valve
/
XPE
Refrigerant
Compressor
Fan
without
56
auto
3.5
/
capillary Φ4.0XΦ2.5X600
920r/min
Function
Coo
lin
g
H
eating
Capacity
BTU/h
28000 32000
W
3200 3300
W
4500 5500
EER or COP
BTU/W
8.75 9.7
Dehumidifying capacity 10³×m³/h Power cable Power source NVH
z
A / A
Start Current
A
Unit model (color) Fan Type × Number
Speed(H-M-L)
r/min
Fan motor output power
kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total Area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Control type (Remote /wired) Fresh air hole dimension
mm
kW
dB(A)
kg / kg
External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
kg / kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed
r/min
Fan motor output power kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Refrigerant control method
mm/mm
Volume of Accumulator L
Noise level
dB(A)
material of reduce noise crankcase heater power W
kg / kg
Refrigerant Type / Charge
g
Recharge quantity
g/m
Liquid
mm
Gas
mm
Connecting Method
m m 30
item Model
A
D28NAMBEA
Total power input
Max. power input
3
/
3N 380V-400V 50H
Z
Running /Max.Running
Cooling:5.5/8.0 Heating:5.8/9.5
30
Indoor unit
AD28NAMBEA(WHITE)
CentrifugalX 2
980 +30/890 +30/810 +50
0.13
1470/1300/1100
TP2M/9.5
2
0.19
9
2-7
Dimension
990×650×30
0
1137×800×32
0
PVC 26/3
2
Wired+Remote
/
Electricity Heater /
Noise level (H-M-L)
35/32/2
9
Weight (Net / Shipping)
40/5
7
Panel
Dimension
/
/
Weight (Net / Shipping)
/
Outdoor unit
/
/////////
Dimension
///
/
Defrosting
///
Type of Four way valve
/
MAX.Drop 20
/
/
Weight (Net / Shipping)
/
MAX.Piping length
-9-
PIPING
R407C 2550
60
Pipe
9.52
15.88 flared
Between I.D &O.
D
Function
Coo
lin
g
H
eating
Capacity
BTU/h
28000 32000
W
3200 3300
W
4500 5500
EER or COP
BTU/W
8.75 9.7
Dehumidifying capacity 10³×m³/h Power cable Power source NVH
z
A / A
Start Current
A
Unit model (color) Fan Type × Number
Speed(H-M-L)
r/min
Fan motor output power
kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total Area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Control type (Remote /wired) Fresh air hole dimension
mm
kW
dB(A)
kg / kg
External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
kg / kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed
r/min
Fan motor output power kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Refrigerant control method
mm/mm
Volume of Accumulator L
Noise level
dB(A)
material of reduce noise crankcase heater power W
kg / kg
Refrigerant Type / Charge
g
Recharge quantity
g/m
Liquid
mm
Gas
mm
Connecting Method
m mMAX.Piping length 30
PIPING
R407C 2550
60
Pipe
9.52
15.88 flared
Between I.D &O.
D
MAX.Drop 20
/
/
Weight (Net / Shipping)
/
/
/
Type of Four way valve
///
Defrosting
/
/
Dimension
/
/
Outdoor unit
/
///////
/
Panel
Dimension
/
/
Weight (Net / Shipping)
/
Noise level (H-M-L)
42/40/3
8
Weight (Net / Shipping)
40/5
7
Remote
/
Electricity Heater /
Dimension
1320×715×23
5
1380×770×30
0
PVC 18/2
0
30
Indoor unit
AC28NACBEA(WHITE)
CentrifugalX2
1300 +30/1250 +40 /1150 +50
0.04
1300/1250/1150
TP2M/9.5
2
0.19
9
2-7
3
/
3N 380V-400V 50H
Z
Running /Max.Running
Cooling:5.5/8.0 Heating:5.8/9.5
item Model
A
C28NACBEA
Total power input
Max. power input
Function
Coo
lin
g
H
eating
Capacity
BTU/h
28000 32000
W
3200 3300
W
4500 5500
EER or COP
BTU/W
8.75 9.7
Dehumidifying capacity 10³×m³/h Power cable Power source NVH
z
A / A
Start Current
A
Unit model (color) Fan Type × Number
Speed(H-M-L)
r/min
Fan motor output power
kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total Area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Control type (Remote /wired) Fresh air hole dimension
mm
kW
dB(A)
kg / kg
External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
kg / kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed
r/min
Fan motor output power kW
Air-flow(H-M-L)
m³/h
Heat exchanger Type / Diameter
mm
Total area
Temp. scope ℃ External L×W×H
mm×mm×mm
Package L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.)
mm
Refrigerant control method
mm/mm
Volume of Accumulator L
Noise level
dB(A)
material of reduce noise crankcase heater power W
kg / kg
Refrigerant Type / Charge
g
Recharge quantity
g/m
Liquid
mm
Gas
mm
Connecting Method
m m
item Model
A
B28NACBEA
Total power input
Max. power input
3
/
3N 380V-400V 50H
Z
Running /Max.Running
Cooling:5.5/8.0 Heating:5.8/9.5
30
TP2M/
7
0.19
9
2-7
Dimension
Centrifugal×1
700+30/590+40/470+50
0.04
1300/1100/870
840×840×24
0
910×910×30
0
PVC 26/3
2
Remote
/
Electricity Heater /
Noise level (H-M-L)
39/37/3
5
Weight (Net / Shipping)
28/3
0
Panel
Dimension
950x950x80
980x980x100
Weight (Net / Shipping)
6/9
Indoor unit
AB28NACBEA(WHITE)
Outdoor unit
/
/////////
Dimension
///
/
Defrosting
///
Type of Four way valve
/
MAX.Drop 20
/
/
Weight (Net / Shipping)
/
MAX.Piping length
30
PIPING
R407C 2550
60
Pipe
9.52
15.88 flared
Between I.D &O.
D
11-
WARNING
CAUTION
WARNING
CAUTION
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior environment such as engineering shop could cause equipment malfunction. Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires. Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires. When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you purchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur,there is the danger of a resultant oxygen deficiency accident. For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit. Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit. For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires. Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
WARNING
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual. Moreover, ask the customer to keep this sheet together with the owner's manual.
Please read these "Safety Precautions" first then accurately execute the installation work. Though the precautionary points indicated herein are divided under two headings, and those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the section. However, there is also a possibility of serious consequences in relationship to the points listed in the section as well.
- 12 -
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (please see nameplate) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing. Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refigerant leakage. The position of indoor unit must be above the floor 2.5m.
WARNING
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone ground wire. Improper placement of ground wires can result in electric shock. The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock. Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
CAUTION
- 13 -
SAFETY PRECAUTIONS
4.Net dimensions of indoor and outdoor unit
Indoor unit Models
1) AB242ACBEA AB28NACBEA
2) AD242AMBEA AD28NAMBEA
-14-
35
260
27535
A-A
A-A
drainage pipe
B-B
fresh air outlet
655
liquid pipe
gas pipe
3) AD242AHBEA
4)
AC242ACBEA
6
5
5
240
2
0
0
9
-15-
185 185
55
70
70
Screw Hole
(M10)
580
Power Wiring Terminal
Power Wiring Distribution Hole
70
1024
1818
340
380
840
25
6)AU242AHBEA AU28NAHBEA AU282AHBEA
1
1
0
1
8
0
6
0
8
5
100
30
5
5
5
6
3
0
6
9
0
105 195 300
600
600
3
1
0
.
6
3
8
5
2
5
3
0
0
10
10
5
4
5
5
9
0
85 150
60
1200
1
5
0
2
3
5
1320
1
9
5
100
8
5
4
5
6
5
R
1
5
5)AC28NACBEA
5.Installation Instructions
1. Installation Tools
1) Driver 2) Hacksaw 3) Hole core drill 4)Hexagon wrench(5mm) 5) Spanner(14,17,19 and
24mm) 6) Torque wrench(17,22,24mm) 7) Pipe cutter 8) Flaring tool
For example: use two spanner to joint the pipe
2. Standard Accessories
The standard accessories includes : 1) Measuring type 2) Reamer 3) Refrigerant oil 4) Gas
leakage detector or soap-and-water solution 5) Knife 6) Nipper
3. Installation Dimensions of Indoor & Outdoor units
Please to see the Mechanical Data
4. Installation procedures & Points of attention
4.1 The Order of Installation Work
Work Main points
Before installation Work division To ascertain the responsible for installation of pipes and wiring
Make installation diagram To ascertain the pipe installation dimension and position of electronic
expansion valve, to make control wiring diagram
Work Installation of indoor and
outdoor unit
To prevent the ventilation from short circuit and guarantee repair space
Refrigerant pipe work Pay attention to dry, clean and seal Drain pipe work Slant downward Heat insulation work No gaps in the joint of heat insulation material Wiring work (control wire,
power cord)
Choose the proper wire and cord
Set every set switch Should be complied with control wiring system diagram Airtight test Close all the gas, liquid valve Vacuum drying Should the vacuum pump that can reach 200Pa vacuity Additional refrigerant Wire down the additional refrigerant amount on the outdoor unit body and
record table
Test run adjustment Do test run to indoor unit by one to verify if there is wrong pipes Training of use and
maintenance
Explain to user, simultaneously provide all the documents
4.2 Attentive matters of safety
· Before installing, do read this [Attention matter of safety] carefully to guarantee the proper installation.
· The below attentive matters are divided into [warning] and [note] two parts. When the wrong installation
occurs, it is very possible lead to death and severe injury, and other serious accidents will happen. For
those items are listed in [warning] part. But even the items very important contents related to safety, so
they must be obeyed.
· After installation, do test operation to verify everything is normal, after that please explains the use
method and maintenance method to the user according to the operation manual. Additionally, give the
installation manual together with operation manual to the user and ask them to keep them properly.
Edging
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.
(1) Open space requirement around the unit
2. Selection of the place of installation
1. Accessories
"Edging" for protection of electric wires from an opening edge.
Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user.
Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting.
<Heat Pump model/Cooling Only model >
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE T O FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE. BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
Wind direction
NO
Unit
Concrete foundation
Foundation anchor
Note (1) Give enough room for the concrete foundation to fix by anchor bolts.
(a)
Note (1) Place the concrete foundation deep enough.
Install the unit so that the angle of inclination must be less than 3 degrees.
3. Installation of outdoor unit
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
(1) Installation
L2
•L3
•L1
•500
(Servicing space)
Air outlet
Air inlet
Air inlet
Unit: mm
Case
Distance
I
II III
open
open
open
500
150
150
300
300
0
L1 L2 L3
To fix by bolts
Anchor bolt
Concrete foundation
Unit
Anchor bolt
Unit
Concrete foundation
(1) Outline piping
4. Refrigerant piping
(2) Piping size
(3) Limitations for one way piping length and vertical height difference.
One way piping length: less than 15m (for 14,18 series), less than 30m (for 24,28 series),
Vertical height difference: Less than 5m (for 14,18 series), Less than 15m (for 24,28 series),
(4) Purging method ( the refrigerant is R407C)
90 0.5
Outdoor unit
Service valve
Flare connection
Check joint
Gas pipe
Liquid pipe
Flare connection
Indoor unit
Install the removed flared nuts to the pipes to be connected, then flare the pipes.
Precautions for refrigerant piping
Do not twist or crush piping. Be sure that no dust is mixed in piping. Bend piping with as wide angle as possible. Keep insulating both gas and liquid piping. Check flare-connected area for gas leakage.
1
Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
To use vacuum pump
3
Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 .
2
Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.
2-way valve
3-way valve
90•
Service port
4
90• for 6 sec.
Open
For series 36,42
3
Close
2
Open
4
Open the valve rod for the 2-way valve to and angle ofanticlockwise 90 degree. After 6 seconds later, close the 2-way valve and malethe inspection of gas leakage.
Vacuum pump
For series 24,28
3-way valve
2-way valve
Gaugemanifold
Gaugemanifold
Vacuum pump
2-way valve
3-way valve
For series 36,42
3-way valve
2-way valve
Open
90•
Service port
90•
4
90• for 6 sec.
For series 24,28
90•
Model
Gas piping
Liquid piping
19.05(3/4")x1.0mm
9.52(3/8")x0.8mm
15.88(5/8")x1.0mm
9.52(3/8")x0.8mm
36,42 series
24,28 series14,18 series
15.88(5/8")x1.0mm
6.35(1/4")x0.8mm
+
_
less than 50m (for 36,42 series).
less than 30m (for 36,42 series).
30mA
5. Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length
wires with less than 2% voltage drop.)
Item
Model
Phase
3
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
30 20 2.5mm
2
1
40 26 4.0mm
2
36,42 series, 28 series (380-400V,3N~,50Hz)
14,18, 24, 28 series
(1PH,220-230V,50Hz)
Switch
breaker
Earth leakage breaker
Leak
current
30 30mA
40
Liquid pipe 9.52mm
Gas pipe 19.05mm
2-way valve
3-way valve
6
6
For series 36,42
For series 24,28
3-way valve
2-way valve
6
6
If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.
3-way valve
2-way valve
7
Valve rod cap
Service port cap
7
For series 36,42
3-way valve
2-way valve
7
Valve rod cap
Valve rod cap
7
Service port cap
7
For series 24,28
If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.
6
In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed steps.
6
No gas leakage?
5
CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to make
all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.
7
8
After attaching the each caps, check the gas leakage around the caps.
To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for 2-way valve and 3-way's a lottle more than the point where the torque increases suddenly.
Outdoor Unit Installation
Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the
outlet air-flow hole.
2. Selection of the place of installation
(3).A one meter distance should be kept from the unit top
1. Accessories
(4).Don't block the surroundings of the unit with sundries
"Edging" for protection of electric wires from an opening edge.
Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user.
Edging
Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting.
Wind direction
NO
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced
(1) Open space requirement around the unit
toward wind direction.
L2
L3
L1
500
(Servicing space)
Air outlet
Air inlet
Air inlet
Case
Distance
Unit: mm
open
open
open
500
150
150
300
300
0
L1 L2 L3
I
II
III
One way piping length:
less than 30m (for
AU242AHBEA
).
Vertical height difference:
less than 20m (for
AU242AHBEA
).
(2) Piping size
AU242AHBEA
Install the removed flare nuts to the pipes to be connected, then flare the pipes.
90+0.5
Pipe dia Fastening torque
Liquid pipe 9.52mm
Gas pipe 15.88mm
42N.m
98N.m
Liquid pipe
Gas pipe
9.52x0.8mm
15.88x1.0mm
(3) Limitations for one way piping length and vertical height difference.
Precautions for refrigerant piping Do not twist or crush piping.
Be sure that no dust is mixed in piping. Bend piping with as wide angle as possible. Keep insulating both gas and liquid piping. Check flare-connected area for gas leakage.
Connecting method (indoor unit) Apply refrigerant oil at half union as large and flare nut. To bend a pipe, give the roundness as possible not to crush the pipe. When connecting pipe, hold the pipe centre to centre then screw nut on by hand, refer to Fig. Be careful not to let foreign matters, such as sands enter the pipe.
(4) Piping connection
Forced fastening without centering may damage the threads and cause a gas leakage.
In the first to third test steps, if the pressure drops, check the leakage in each joint use sense of hearing, feeling and soap water, etc. methods to find the leaking point. After confirming the leaking point, welding it again or tighten the nut tightly again.
From pressurizing to 24 hours later, each 1* difference of ambient temperature will make 0.01MPa(0.1kg/cm2g) pressure change. It shall be corrected during test.
Checking the leaking point
Check if the pressure drops
The pressure does not drop-passed The pressure drops-check the leaking point.
First step: 0.3MPa (3. 0kg/cm2g) pressurize over 3 minutes.
Second step: 1.5Mpa (15kg/cm2g) pressurize over 3 minutes. Large leakage will be found.
Third step: 3.0 MPa (30kg/cm2g) pressurize about 24 hours. Little leakage will be found.
5. Air discharging method
After finishing connection of refrigerant pipe, it shall perform air tightness test. The air tightness test adopts nitrogen tank to give pressure according to the pipe connection mode as the following figure shown. The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the circulation system of outdoor unit, tighten the valve rod before giving pressure (both gas and liquid valve rods).
Outdoor
Completely tightened
Completely tightened
Flare part
Outdoor units
Manhole
Discharging valve
3-way valve totally closed (Gas side)
Low pressure peizometer
High pressure peizometer
Meter separator
Dropping valve
2-way valve totally closed (Liquid side)
Nitrogen tank
VL VH
Indoor units
Indoor
Flare part
It shall use the vacuum pump of (lower than -755mmHg)high vacuum degree and large air
discharging (over 40l/min). The vacuumizing time depends on the length of the connecting pipe, generally is 1~2 hours. When vacuumizing, it shall be confirmed both gas and liquid side valves are closed. If after 2 hours vacuumizing, it cannot reach the vacuum degree below -755mmHg, it can be vacuumized for other 1 hour. If after 3 hours vacuumizing, it still cannot reach the vacuum degree below -755mmHg, check if there is any leaking point and repair the them. If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the V
L and VH on the meter separator and stop vacuumizing. 1 hour later to confirm if the vacuum degree changes. If changes, it indicates there is leaking point in the system. Check the leaking point and repair. After finishing the above vacuumizing, change the vacuum pump into refrigerant pump to charge the refrigerant.
Use vacuum pump to perform vacuumizing. It is strictly forbidden to use the refrigerant to remove the air inside the system. After air tightness test and discharging all the nitrogen, connect the vacuum pump as the following figure shown.
When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary to charge additional refrigerant. If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter. That is: Refrigerant charging amount = (L-5) x M (g)
For AU242AHBEA, M=65
Only in COOLING operation can charge the additional refrigerant. When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle. Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the additional refrigerant in liquid condition.
6. Piping and indoor unit vacuumizing
7. Charging amount of refrigerant
2-way valve totally closed (Liquid side)
Indoor units
Indoor
Outdoor
Completely tightened
Completely tightened
Outdoor units
Vacuum pump
Discharging valve
3-way valve totally closed (Gas side)
Low pressure peizometer
High pressure peizometer
Meter separator
V L VH
Flare part
Flare part
P
Warning
· The distributing shop, where you brought the air conditioner, or the specified shops shall do the
installation work. If you do the installation work by yourself, the improper installation will cause water
leakage, electric shock fire and other accidents.
· The installation work shall be in line with what the installation manual specified. If installation is not
proper, water leakage, electric shock, fire and other accidents will occur.
· Install the conditioner to a place where can definitely stand its weight. Please not firm enough, it will
cause droop down of unit resulting in body hurt.
· The installation work shall be preventive to typhoon and earthquake. If the installation work is not met
with the requirements, overturn of the unit will occur resulting in accidents.
· The wiring work should be down by a qualified person and referred to the “technical standard of electric
equipment “, ”indoor wiring regulation” and what the manual specified. Do use special circuit. If the
capacity of the circuit is not enough or bad work, electric shock, fire and other accidents will happen.
· Using the specified cable to do wiring work and connecting firmly and properly. Fix the connecting part
of the terminals to prevent it from the external force. Improper connection and fixing will cause heating
and fire etc. accidents.
· Wring shall be kept in correct shape avoiding extrusion. After installation, the electric box cover and the
external panel shall not nip the wire. Improper installation will cause heating and fire etc. accidents.
· when setting or moving the air conditioner do not let the air and things alike get into the refrigeration
system except the specified refrigerant (R407C). If air and other things enter, abnormal high pressure will
occur, which easily cause breaks and body injuries etc. accidents.
· When installing, do not use the accessories or specified parts. If not using the parts specified by our
company, water leakage, electric shock, fire and refrigerant leakage will occur.
· Do not lead the drainpipe to where the sulphur gas may be involved. Otherwise, the poisonous gas will
enter into the door.
· During installation, if refrigerant leakage occur, do the ventilation work immediately. As soon as the
refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas enter into room and meet
the air blowing heater, heater or stove etc. fire source, the poisonous gas may be produced. After
installation, confirm there is no leakage of refrigerant.
· Do not install the unit in a place where the combustible gas may be leaks. In any case the
combustible gas leaks and accumulated around the unit, fire accident will occur.
· Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose of heat
preservation. If the heat insulation measure is not sufficient, water generated by condensing dew will drip
leading to wet the floor and indoor articles.
· Do not damage the power line or change it arbitrarily to avoid occurrence of fire or electric shock.
· Do not extend the power line or using other electric appliance in the same power receptacle to avoid fire
or electric shock.
Note
· Do grounding work. Do not connect the grounding wire to gas pipe, tap, lighting rod or telephone line.
Improper grounding will cause electric shock.
·In some places the electric leakage breaker shall be installed. If do not install the breaker, electric shock
may occur.
·After installation, power on to do electric leakage detecting test.
5.3 Special Work and Main Points in Installation
Warning
· During installation, if refrigerant leakage occurs, take ventilation measurement immediately.
·As soon as the leaked refrigerant gas meets fire, poisonous gas will generate.
·After finishing installation, confirm the refrigerant gas dose not leak.
·If the refrigerant gas leaks in the room, once it meets heater, burner and gas stove etc. fire source, the poisonous gas will generate.
A. Choosing of pipes
According to the following indoor unit and unit installation diagram to choose the material and size of
pipes and branch pipes.
B. Connection of pipes
1. Method of pipe connection
·The pipe shall be as short as possible to guarantee efficiency
·Daub the refrigerant oil on the connection and flare nut
· When bending the pipes, give the roundness as large as possible, to avoid crashing the pipes
·To connect the pipe, fit the center and screw the nut with hand, the use spanner or torque
wrench to tighten it. The fastening torque showed in below table, and shown in figure.
·Be careful alien matter, such as sands, water etc. shall not enter the pipes. Forced fastening
without careful centering may damage the threads and cause gas leakage
2. Welding of pipes
·In welding, the nitrogen shall be used to avoid oxidation of the pipe inner part.
·The refrigerating pipe shall use clean new pipes. When working, it shall take steps to prevent
water and dust from entering.
·When loosening and tightening the nuts, two spanners shall be used. If using one spanner, it can
not reach the desired degree of tightness.
Using the specified fastening torque to fasten nuts.
Pipe diameter (mm) Installation torque(N.M.) Fastening torque (N.M.)
Φ6.35
11.8(1.20kgf.m) 13.7(1.4kgf.m)
Φ9.52
24.5(2.50kgf.m) 29.4(3.0kgf.m)
Φ1 2.7
49.0(5.0kgf.m) 53.9(5.5kgf.m)
Φ15.88
78.4(8.0kgf.m) 98.0(10.0 kgf.m)
5 Checks after the installation
After the installation, please to check the connection of wire:
If the wire have the same diameter in the two sides of the terminal
If the wire placed on both the side of terminal but one side
To see the follow figure:
Ο means the right connection × means wrong
5.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner, shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter
7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor
11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump
15 .Flat screwdriver
5.2 Standard accessories
Part name
QTY
Shape
Clamp
2 Piece
Washer
8 Piece
6 Piece
Clamp Paper pattern
1 Set
6321
3 Piece
Screw(M5 size)
For installation of paper pattern
Drain hose
1 Piece
Please check if your unit is delivered with following
Part name
QTY
Shape
Dry battery
Insulator Sealing pad Sealing pad Sealing pad
7
8 9
12
1 Piece 1 Piece
Insulator
2 Piece 1 Piece 1 Piece 2 Piece
Small sizeMedium sizeLarge size
For liquid pipeFor gas pipe
R03, 7#
[Other]
Operation Manual
Ornament panel
Remote controller
54
1110
5.3 Installation of indoor unit
5.3.1 Before installation
Determine the way kto carry unit to installation place. Don't remove packing until unit reaches installation place. If unpacking is unkavoidable, protect unit properly.
5.3.2 Selection of installation place
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured. No block to air flow. Water drainage is smpoth. Place strong enough to support unit weight. Place where inclination is not evident on ceiling. Enough space for mainenance. Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.) Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This is helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio wave is strong)
INSTALLATION INSTRUCTIONS
5 INSTALLATION INSTRUCTIONS
8
260
260
(2) Ceiling height
Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and Installation Manual of ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)
Installation space
Air inlet
Air outlet
2500 Over
Air outlet
1500 Over
1500 Over
1500 Over
1500 Over
Air outlet
Air inlet
Air inlet
5.3.3 Preparation
Ornament panel 630mm
ceiling opening 600mm
Indoor unit 570mm
Distance between
Indoor unit 570mm
Ceiling opening 600mm
Ornament panel 630mm
suspending bolts 460mm
210mm
335mm
35mm
Overlap between ceiling and ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
(1) Position of ceiling opening between unit and suspending bolt.
AB14, 18
Unit: mm
INSTALLATION INSTRUCTIONS
50~100
Roof Anchor bolt Long nut
Suspending bolt
Ceiling
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer
(3) Install a suspending bolt. (Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field. Before going on installing adjust space between ceiling.
<Installation example>
Note: All the above mentioned parts shall be prepared in field.
A
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
780
(Distance between suspending bolts)
(Distance between suspending bolts)
A
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
Suspending bolts
Refrigerant pipe
A
(160)
Suspending bracket
Ceiling
890(Ceiling opening)
(Distance between suspending bolts)
1070
515
515
(Distance between suspending bolts)
860(Ceiling opening)
780
20 Over
Note: Dimension of ceiling opening marked with * can be as large as 910mm, but the matching part of ceiling with ornament panel shall be over 20mm.
AB24,28
AB36,42
INSTALLATION INSTRUCTIONS
5.3.4 Installation
4
5
7
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.
(1) Install unit temporally
In the case of new ceiling
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1)) (4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem
may occur on floating switch, causing water leakage.) (5) Remove the washer mounlting , and tighten the nut above. (6) Remove the paper pattern.
(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly. (2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ). (3) Proceed with and of "In the case of new ceiling".
Level
Polythene pipe
3
4
In the case of ceiling already exists
Scrtews at the piping outlet is fixed at the corner of drain pan.
Center of ceiling hole Paper pattern
4
Paper pattern
5
Screw (accessory)
5
Screw (accessory)
[Fix the paper pattern]
5.3.5 Refrigerant piping
As for outdoor piping, please refer to installation Manual of outdoor unit.
6
9
Apple refrigerant oil
Torque spanner
spanner
Piping joing
Flare nut
Medium size seal pad 9 (accessory)
Clip 3
Gas pipe
Liquid pipe
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
7
6
(Cover the piping joint with seal pad.)
R0.4 ~ 0.8
A
Pipe size
Tighten torque
A(mm) Flare shape
9.52
3270~3990N.cm
(333~407kgf.cm)
6180~7540N.cm
(630~770kgf.cm)
15.88
19.05
9720~11860N.cm (990~1210kgf.cm)
12.0~12.4
18.6~19.0
22.9~23.3
90
0.5
45
2
Outdoor is precharged with refrigerant. Be sure to see the Fig.1, when connecting and removing piping from unit. For the size of the flare nut, please refer to Table 1. Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it. Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage). Check piping joints for gas leakage. Insulate piping as shown in Fig. below. Cover joint of gas piping and insulator with seal .
Table 1
Diameter of Pipe Liquid Pipe 6.35mm
Gas Pipe 12.7mm
Tighten Torque 18 N. m
50N. m
INSTALLATION INSTRUCTIONS
5.3.6 Installation of drainage pipe
1-1.5m
Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape. Tighten the clip until head of the screw is less than 4mm from hose. Wind the drain hose to the clip using seal pad 8 . Insulate drain hose in the room.
2
<Cautions for the drain water lifting pipe>
Clip
2
Tape (White)
Self-provided stiff pipe
Clip
2
4mm below
(accessory)
(accessory)
Large size seal pad
Clip
2
10
Installation height shall be less than 280mm. There should be a right angle with unit, 300mm from unit.
Waterring can of plastic
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm) Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening. If downward slope can't be made, take other measures to lift it up. Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
Slope over 1/100
75 below
Self-provided stiff pipe
(accessory)
500 below
300mm below
1~1.5m
280 below
500 below
220
Drain hose 1
(accessory)
drain water lifting pipe
Suspending bracket
Clip
(accessory)
2
Over 100
(Note)
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Specifieations of the water hoses shall meet the requirements for the unit running.
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
Method of water charging
11
When wiring is not complete
Charge water from air outlet
Charge water from inspecting hole
Watering can of plastic pipe should be about 100 mm long
100mm
Water drainage port for maintenance
(Drain water from this hole)
Self-provided stiff pipe
Maintenance
Inspecting hole
Cover of controll box
PCB on indoor
Terminal
Terminal block
Connect with outdoor unit
1 2 3
L
N
Power
1 2 3
Indoor
Outdoor
H07RN-F 3G 4mm
2
H05RN-F 4G 0.75mm
2
1 2 3
R S T
1 2 3
N
Indoor
Power
Outdoor
H05RN-F 4G 0.75mm
2
H07RN-F 5G 2.5mm
2
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block. Note, in this operation, fan will be running. Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove short connection of "CHECK" terminal.
Check water drainage in cooling operation. See also test run.
INSTALLATION INSTRUCTIONS
5.3.7 Wiring
Terminal block
Clip A
Cover of control box
1
Rubber tube A
Grounding lead
Cover of control box
2
Terminal block
Connect with outdoor unit
Out
In
Field wiring
Attach seal pad
Don't fail to seal it, or, water may come in.
Rubber tube
Note: Have it sealed, leaving no space.
Seal pad (small size)( ) (Wind around wire)
12
All supplied parts. materials and wiring operation must in appliance with local code and regulations. Use copper wire only. When make wiring, please refer to wiring diagram also. All wiring work must be done by qualified electricians. A circuit breaker must be installed, which can cut power supply to all system. See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unit Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires, tighten clamp A. Connect wires of correct pole to the terminal block inside. Wind seal (12) around wires. (Be sure to do that, or, dew may occur). Upon connecting, replace control box cover (1) and (2).
Obscrve the following when connecting power supply terminal block: Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit) Connect wires of same specifications as shown in right Fig.
Connect wires of the same specifications at two sides.
Don't connect wires of the same specifications at one side.
Don't connect wires of the different specifications.
<<WARNING>>
5.3.8 Wiring example
As for outdoor unit circuit, please see Installation Manual of outdoor unit. Note: All electric wires have their own poles, poles must match that on terminal block.
5.3.9 Installation of ornament panel
1. Prepare ornament panel Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither on an uneven object. Don' t bend carelessly the swing flap, or, problem may occur.
(1)
Remove air inlet grill from ornament panel:
Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
Lift it up for about 45 degree and remove it from ornament. Tear off adhesive tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 2)
Cautions for the installation
Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read also the Installation Manual of indoor unit. With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.
2
Accessory
Pad
Pad
1
Bar
INSTALLATION INSTRUCTIONS
5 _ 8mm
3
2
2
1
4
Holding ring
Piping hole position
Swing flap motor
Fig. 7
Seal
Indoor unit
Ceiling material
Ornament panel
(2)
Remove cover plate at corner
Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)
(1)
(2)
2. Install ornament panel on indoor unit.
As shown in Fig . 7, match the position of
swing flap motor with that of the indoor unit
piping hole , so that ormament panel can be
placed on to indoor unit.
Installation of ornament panel
Place the holding ring on swing flao motor
side teporarily on hooks of the indoor unit.
(2 pcs)
Put the other two holding rings on the hooks at
both side of the indoor unit. (Care should be
taken not to push wiring of swing flap motor
into seals).
Screw in all 4 screws under holding ring for
about 15mm. (Pancl will rise).
Adjust the ornament panel as per Fig. 7 to
cover opening on the ceiling.
Tighten screws to redrce the thickness of seals
between ornament and indoor unit to 5-
8mm.
1
2
3
4
5
If indoor unit is at horizontal level and water drainage is smooth, then, indoor unit height can be ad­justed throrgh holes at corners of ornament panel.
If screws are not tighten tight, problems in Fig, 8 might occur. Tighten screws properly.
If there are still space after tightening of screws, please readjust the height of indoor unit. (Refer to Fig. 9)
Leave no space.
Fig. 9
Gas leakage.
Gas leakage from roof.
Contamination
Mist exists and drop down.
Fig. 8
45
Fig. 2
Adhesive tape
Slide
Fig. 3
For indoor unit installation, please refer to Installation Manual.
Hook
Caution
1 2
Leave no space.
Fig. 6
3. Mounting on high ceiling
(1) Ornament panel can be mounted on ceiling as high as 3 m.
(2) Please install pad as accessary.
Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4) Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
Fig. 4
(3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10)
50
Cutting line
100
a
b
Place it on the frame.
Part a of the pad
Part a of the pad
Swing flap motor
Fig. 5
Side of ornament panel
Fig. 10 Wiring diagram
Side of indoor unit
If connecting is not made, error code (A7) appears on remote controller. So, make proper connecting.
INSTALLATION INSTRUCTIONS
1
2
4. Installation of inlet grill and cover plate
Installation of inlet grill Install in reversed order ofPrepare ornament pandl”. Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as per customers request.
(1)
When installing inlet grill, take care not to twist wiring of swing flap motor.
Install cover plate on the corner As shown in Fig. 11 tie the cover plate onto the bolt on ornament plate. Install cover plate onto ornament plate. (Refer to Fig. 12)
(2)
Slide all five hold rings
to let them drop in holes on ornament plate,
Fig. 12
Fig. 11
bolt
5.3.10 Test running
Refer to Take special care during installation, check after working
(1) (2) (3) (4) (5) (6)
Proce­dure
Operation
Open check valve on gas pipe. Open check valve on liquid pipe. Press ON/OFF button, select Cooling mode. Let it run for 3 min. Press air flow adjust button to make unit run properly Confirm unit functions according to Operation Manual.
Upon installation of piping, water drainage and wiring work, make test run to ensure proper unit operation.
(1) (2) (3) (4) (5)
Procedure
Operation
Open check valve on gas pipe. Open check valve on liquid pipe. Press ON/OFF button, select Cooling mode. Let it run for 3 min. Cut main power supply after operation.
Conduct test run before installing ornament panel
Note: If unit doesn’t run due to certain problem, please see ‘‘Note to unit maintenance’’.
Conduct test run after installation of ornament panel
INSTALLATION INSTRUCTIONS
Preparation before installing convertible type unit
Before installation of convertible type unit, please confirm which type will be selected: in
the ceiling or on the floor.
There is a dial switch K1 on the PCB, if you select D, that means the installation is in the
ceiling. If you select L, that means installation position is on the floor.
In the ceiling mode, there will a 4 degrees temperature compensation in heating mode.
Because in heating mode, the warm air will rise and stay in higher position. If there is not
temperature compensation, when the set temperature has arrived, it may happen that the
air in higher position has become the set temperature, but the air in lower position has not
arrived the set temperature.
There is no different for the operation of swing and the heating capacity.
D
L
K1
Installation procedure of convertible type unit
CAUTION!
INSTALLATION PROCEDURE
Install the room air conditioning unit as follows:
PREPARING INDOOR UNIT INSTALLATION
FIRST REMOVE THE INTAKE GRILL
A. FLOOR MOUNTING
(AC36/42 only suitable for exposed ceiling mounting)
1. DRILLING FOR PIPING
The piping and drain can exit the unit in two directions as shown below in (Fig. 2)
(Fig. 2)
The drain hose must be connected to the right side as shown in (Fig.3).
After the piping and drainage exit has been selected, drill a 7 cm dia. hole through the wall so that the hole is slanting downward toward the outside to ensure good drainage. When the pipe is led out from the rear, make a hole as Fig.4, at the position shown.
2. INSTALLING DRAIN HOSE
The drain hose must be connected to the right side of the unit (Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener. (Fig.5)
Be sure to arrange the drain hose correctly as shown in Fig. 7 so that it is lower than the drain hose connecting point of the indoor unit, if condensate pump is not fitted to system.
B. UNDER CEILING MOUNTING
Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.9)
Fig 9
1. DRILLING FOR PIPING
Select piping and drain directions. (Fig.10) Fig 10
(Fig. 6)
Drain pan
Drain hose
Insulation (Drain hose)
Arrange the drain hose lower than this portion.
Fig. 7
OK NO NO
Drain hose
rear
down
(Fig. 3)
Drain hose (Right side)
Wall
7cm
6mm
Indoor unit outdoor unit
(Fig. 4)
Drain pan
Drain hose
Nylon fastener (supplied by others)
(Fig. 5)
A
Drain hose
Rear (Install the drain hose in this direction.)
A
B
40 40
100mm
720mm
87.5mm
147mm
326mm
247mm
85
53
Wrap the insulation around the drain hose connection.(Fig.6)
Ensure that the unit is fixed level. Height ‘A’must be less than 5 mm.(Fig.8)
Model A B
AC24 990 500 AC28 1320 1240
AC36/42 1920 1840
68
16 21 28
381
232
26.5
26.5
2-R2.5
10
18
7.5
4-R5
68
16
21
28
381
232
26.5
26.5
2-R2.5
10
18
7.5
4-R5
Wall
6mm
12.5mm
Fig. 11
Fig. 12
Fig. 13
Spring washer
Special nut
Bracket
CAUTION
Hex bolt
8 to 13mm
Indoor unit
Fig. 14
Fig. 16
Remove the hole cover.
OK
Arrange the drain hose lower than this portion
Drain hose
NO
Fig. 15
Bolt
Bracket
Indoor unit
Install the drain hose at the rear; it should not be installed on the top or right side.
After the piping and drainage exit has been selected, drill 80mm and 50mm or 150mm dia. hole through the wall. So that the hole is slanting downward toward the outside for smooth water flow if a condensate pump is not fitted to system.
4. INSTALLING INDOOR UNIT
Reset the hex bolts as shown in Fig.14.
Apply the indoor unit to the brackets.(Fig.15)
Now, securely tighten the hex bolts in both sides.
5. INSTALL THE DRAIN HOSE
The drain hose will be connected to the right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.5) Wrap the insulation (drain hose)around the drain hose connection. (Fig.9) Be sure to arrange the drain hose correctly so that it is lower than the drain hose connecting port of the indoor unit (Fig.16) if condensate pump is not fitted to system.
Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer. (Fig. 12)
3. INSTALLING BRACKETS
Install the brackets with nuts, washers and spring washers.(Fig. 13)
2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS
using a masonry drill, drill four 12.5 mm dia. Holes.(Fig.11)
Fig. 11
Installation procedure of convertible type unit
Wiring
CAUTION
(1) Match the terminal block numbers and connection cable colours with those of the outdoor unit. Incorrect wiring may cause damage to the electrical parts.
(2) Connect the connection cables firmly to the terminal block. Incorrect installation may result in a fire.
(3) Always fasten the outside covering of the connection cable with the cable clamp.(If the insulation is chafed, a short curcuit may occur.)
(4) Always connect the earth wire.
Fig. 26
Electrical component box
Remove the four self tapping screws.
CAUTION
Do not remove the screws. If the screws are removed, the electrical component box will fall.
Fig. 25
Electrical component box
ELECTRICAL WIRING
1. INDOOR UNIT SIDE (1) Remove the electrical component box.
INDOOR UNIT SIDE
Wiring
Fig. 27
Electrical component box
Fig. 28
Base
Electrical component box cover
CAUTION
Be careful not to pinch the wiring between the electric component box and base.
(1) Ensure all wiring complies with current regulations.
(2) It is recommended that a MCB of the correct rating is used to protect the system.
(3) Always use a circuit breaker that can trip all the poles of the wiring is fitted and has an isolation distance of at least 3mm between the contacts of each pole.
WARNING
(2) Pull out the electrical component box.
ELECTRICAL WIRING
(3) Remove the electrical component box cover.
(4) Wiring
See wiring diagrams for indoor unit.
Remove the three tapping screws
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual: (1) Starting and stopping method, operation switching,
temperature adjustment, timer, air flow switching, and other remote control unit operations.
(2) Air filter removal and cleaning, and how to use air
louvres.
(3) Give the operating and installation manuals to the
customer.
NOTICE
All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULL Y BEFORE BEGINNING INSTALLATION. FAI­LURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEA TH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
(1) Preparation of indoor unit
Before or during the installation of the unit, assemble necessary optional panel etc. depending on the specific type.
(2) Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user.
(a) Places where chilled or heated air circulates freely. When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases, suggest your client users to install air circulators. (b) Places where perfect drainage can be prepared and sufficient drainage. (c) Places free from air disturbances to the suction port and blowout hole of the indoor unit, places where the fire alarm may not malfunction or short-circuit. (d) Places with the environmental dew-point temperature is lower than 28 and the relative humidity is less than 80%. (When installing at a place under a high humidity environment, pay sufficient attention to the prevention of dewing such as thermal insulation of the unit.) (e) Ceiling height shall have the following height.
Combination with silent panel
416mm
366mm
50 or more
Obstacle
100 or more
100 or more
1000 or more
Unit: mm
Installation space
36,42 series
14,18,24,28 series
(a) Size of hole at ceiling and position of hanging bolts
<Combination with silent panel>
57
A
B
C
(Hanging bolt position)
(Ceiling hole size)
(Panel dimensions)
137
30
30
(Ceiling ~ panel wrap dimensions)
(Ceiling ~ panel
wrap dimensions)
(Hanging bolt position)
(Ceiling hole size)
(Panel dimensions)
75
545
690
750
70
(Pipe co-
nnection side)
(b) Hanger bolts installation
Use care of the piping direction when the unit is
Dimensions
A
Unit: mm
B C
1406 1600
1660
986 1180
1240
Model
36,42 series
14,18,24,28 series
Hanging bolt M10
Hole-in anchor Hole-in plug
Insert
Concrete
installed.
Installation procedure of mid ESP duct type
(5) Installation of indoor unit
Fix the indoor unit to the hanger bolts.If required, it is possible to suspend the unit to the beam, etc. Directly by use of the bolts without using the hanger bolts.
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket.
Note
Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method.
Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
Tap selection on blower unit
(When the high performance filter is used.)
Taps of blower unit are set at the standard selection at the shipping from factory. Where the static pressure is raised by employing such option as the high performance filter, etc., change the connection of connectors provided at the flank of control box as shown below.
(6) Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.
When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit. For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).
Drain hose
Stage difference part
Drain socket
Drain socket
Main unit
VP 25 joint (field purchased)
Pipe cover(large) [for insulation] (accessory)
VP 25 (field purchased)
Pipe cover [for insulation] (field purchased)
Drain hose (accessory)
Pipe cover(small) [for insulation] (accessory)
Clamp (accessory)
Adhesion
PVC hose
Piping side
Supply water
Water level
0~5 mm
(0~0.2")
Bring the piping side slightly lower.
Hanging bolt
M10 nut
Main unit
M10 washer
M10 spring washer
Do not pipe under water
Keep free from traps
Avoid riding across an elevation
Air vent
Inproper pipingGood piping
1.5m ~ 2m
Suspension bolts
Heat insulation
A downhill grade of 1/100 or more
(b)
(c)
Red
Yellow
White
Standard tap (at shipping) High speed tap
Black
White
Connector white
Connector white
Control box side
Moter side
Moter side
Red
Blue
Red
Yellow
White Blue
Red
Yellow
White Blue
White Blue Red
VP 30
Secure the elevation as high as possible (approx. 100 mm)
A downhill grade of 1/100 or more
Drain hose
Joint for VP 25 (Local procurement)
600
(Maximum local drain up dimension)
Right overhead
290~325mm
Attached drain hose clamp
Drain piping
Main unit
Drain situation can be checked with transparent socket
Remove grommet. Make sure to install it back after test.
Insert water supply hose for 20 mm ~ 30 mm to supply water. (Insert hose facing toward bottom.)
Pour water into a convex joint.
When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4") or thicker pipe for this purpose. Be sure to provide heat insulation to hard PVC pipes of indoor placement. Do not ever provide an air vent. The height of the drain head can be elevated up to a point 500 mm above the ceiling, and when an obstacle exists in the ceiling space, elevate the piping to avoid the obstacle using an elbow or corresponding gadget. When doing this, if the stretch for the needed height is higher than 500 mm, the back-flow quantity of drain at the event of interruption of the operation gets too much and it may cause overflow at the drain pan. Therefore, make the height of the drain pipe within the distance given in the sketch below. Avoid positioning the drain piping outlet at a place where generation of odor may be stimulated. Do not lead the drain piping direct into a sewer from where sulfur gas
Drainage Test
Conduct a drainage test after completion of the electrical work. During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. In case of a new building, conduct the test before it is furnished with the ceiling. Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
(d)
(e)
(f)
(h)
(g)
1 2
3
4
1 2
(In the electrical work has not been completed, connect a convex joint in the drain pipe connection to provide a water inlet. Then, check if water leaks from the piping system and that drain flows through
Exhaust hole
State seeing from top of unit
Side fresh air inlet
Rear fresh air inlet
Fig.1
Fig.2
(7) Installation work for air outlet ducts
Calculate the draft and external static pressure and select the length, shape and blowout.
A Blowout duct
2-spot, 3-spot and 4-spot with 200 type duct are the standard specifications. Determine the number of spots based on following table.
Note (1) Shield the central blowout hole for 2-spot. (2) Shield the blowout hole around the center for 3-spot.
Limit the difference in length between spots at less than 2:1. Reduce the length of duct as much as possible. Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
Use a band. etc. to connect the main unit and the blowout duct flange. Conduct the duct installation work before finishing the ceiling.
(8) Connection of suction, exhaust ducts
(a) Duct connection position
i) Fresh air inlet
Inlet can be selected from the side or rear faces depending on the working conditions. Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. (Side inlet cannot be used.)
ii) Exhaust (Make sure to use also the suction.)
Use the side exhaust port.
Good exampleBad exampleBad example
Ceiling surface
Heat
insulation
Suction panel (Silent panel)
Air conditioner main unit
B Special blowout (Option)
A Blowout duct (Optional or marketed item)
C
Hole for check
special inlet (option) (with air filter)
inlet duct
(optional or
marketat item)
1. Before installation [Before finishing installation, do not throw the attached parts installation needs]
Confirm the way to move the unit to the installation place. Before moving the unit to the installation place, do not remove their packages. When have to remove the package, use a soft material or protection board with rope to lift the unit
assembly to avoid unit damage or bumping a scrape.
2. Choose installation place
(1) The chosen installation place should meet the following requirements and get the userís consent.
Place ensures ideal airflow distribution. The passage of airflow has no obstacles. When importing outside air, it should be imported directly from outdoors. (if the pipe can not be
extended, it also can not be imported from top) Place ensures enough space for maintenance. The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit
installation part). The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television
and radio. This is to avoid the image disturbance and noise caused by the above-mentioned home appliance. (Even if 1m away, if the electromagnetic wave is too strong, it can also cause noise.)
(2) The height of ceiling
The indoor unit can install on the ceiling, which height is no more than 3m.
(3) Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly.
If not certain, strengthen it before install the unit.
(600x600)
Over 100
Over 900
Air out
Air in
Checking meatus
Ceiling
Over 300
Over 200
Indoor unit installation (High ESP Indoor unit installation (High ESP duct)
(1) The position relation among hoisting screw (unit: mm)
(3) Hanger bolts installation
Use care of the piping direction when the unit is installed.
Hanging bolt M10
Hole-in anchor Hole-in plug
Insert
Concrete
370
250
910
603
628
590
Down side
Up side
(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling)
Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be immediately connected with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and flat and prevent the ceiling from vibration. For details, please consult to the builder.
(Use M10 screw bolt) In order to bear the weight of the unit, for existed
ceiling, using foundation screw bolt, for new ceiling, using burying embedded screw bolt, burying screw bolt or spot supplied other parts.
Before going on installation, adjust the gaps with ceiling.
3. Preparation before installation
AD242AHBEA
4. Installation of indoor unit
Fix the indoor unit to the hanger bolts. If required, it is possible to suspend the unit to the beam, etc. Directly by use of the bolts without using the hanger bolts.
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket.
Note
Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method.
Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
PVC hose
Piping side
Supply water
Water level
0~5 mm
(0~0.2")
Bring the piping side slightly lower.
Hanging bolt
M10 nut
Main unit
M10 washer
M10 spring washer
Drain hose
Stage difference part
Drain socket
Drain socket
Main unit
VP 25 joint (field purchased)
Pipe cover(large) [for insulation] (accessory)
VP 25 (field purchased)
Pipe cover [for insulation] (field purchased)
Drain hose (accessory)
Pipe cover(small) [for insulation] (accessory)
Clamp (accessory)
Adhesion
For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).
(c)
5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.
When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit.
Do not pipe under water
Keep free from traps
Avoid riding across an elevation
Air vent
Inproper piping
Good piping
1.5m ~ 2m
Suspension bolts
Heat insulation
A downhill grade of 1/100 or more
(b)
26
Drainage Test
Conduct a drainage test after completion of the electrical work. During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. In case of a new building, conduct the test before it is furnished with the ceiling. Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
Supply about 1000 cc of water to the unit through the air outlet using a feed water pump. Check the drain while cooling operation.
(g)
1 2
3
4
1 2
VP 30
Secure the elevation as high as possible (approx. 100 mm)
A downhill grade of 1/100 or more
When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4") or thicker pipe for this purpose.
(d)
(e)
The stiff PVC pipe put indoor side should be heat insulated.
(f)
Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into drainage, where the gas with sulfur may be generated.
Backwater bend Because the drain spout is at the position, which negative pressure may occur. So with the rise of water
level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint. The backwater bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
H1H2
H1=100mm or the static pressure of air sending motor
H2=1/2H1 (or between 50~100mm)
6. Installation of air suction and discharging duct
A
Insulation
muffler cavity (air sending)
Sacking joint
Air volume adjuster
Air outlet
Enlarging chart of profile chart A
Vibration resistance hook
Checking meatus
Air conditioner main unit
Ceiling
Air suction grille with air filter
Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing and outer static pressure, and choose the discharging duct with proper length and shape.
The calculation of duct resistance (the simple calculation is as follow table)
Straight part Bend part Air out part
Static pressure box Air inlet grille (with air filter)
Calculate as per 1m length 1Pa, 1Pa/m Each bend takes as a3~4m long straight duct
Calculate as 25Pa Calculate as 50Pa/each
Calculate as 40Pa/each
Good exampleBad exampleBad example
The length difference among every duct is limited below 2:1. Reduce the length of duct as possible as can. Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main unit and the flare part of air discharging duct. Perform duct installation work, before the fitment of ceiling.
7. Calculation method of the dimension of the simple quadrate air duct
Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of the air duct is fixed as 250mm, as shown below:
Note:1Pa/m=0.1mmAg/m
The chosen chart of simple duct
m3/h(m3/n)
100 200 300 400 500 600(10)
800 1,000 1,200(20)
250 x 60
(mmxmm)
250 x 90 250 x 120 250 x 140
250 x 170 250 x 190 250 x 230 250 x 270 250 x 310
Shape
Item
Air volume
Square duct
Dimension
m3/h(m3/n)
1,400 1,600
1,800(30) 2000 2400 3,000(50) 3,500 4,000 4,500 5,000 5,500 6,000(100)
(mmxmm)
250 x 350 250 x 390
250 x 430 250 x 470 250 x 560 250 x 650 250 x 740 250 x 830 250 x 920 250 x 1000 250 x 1090 250 x 1180
Shape
Item
Air volume
Square duct
Dimension
Static pressure box
Air conditioner
Equipped with air filter (bought)
B
A
A
A
600m3/h (10m3/min)
2400m3/h (40m3/min)
Air volume
B
A
8. The attentive matters in installation of air suction and discharging duct
Recommend to use anti-frost and sound-absorbing duct. (locally bought) The duct installation work should be finished before the fitment of ceiling.
The duct must be heat insulated. The specific air-discharging outlet should be installed at
the place where the airflow can be reasonably distributed. The surface should leave a checking meatus for checking
and maintenance.
9. The examples of improper installation
Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular outer air mass, strong wind and sunshine, the humidity is increased.
There may be water drop on the outside of duct. For cement and other new constructions, even if not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber to perform heat preservation to the whole. (use iron net to bind the glass fiber)
Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction, when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow, leading to water leakage.
Air
Air
Duct
Special air discharging outlet
Use screw bolt to fix
Air discharging fan
Improper example
200
150
100
50
0
26 30 34 35 40 43
*
*
*
*
*
*
*
*
*
*
*
*
*
*
Figure 1
Figure 2
Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted.
10. The operation method of fan controller
It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment). The air volume set should be in the operation air volume range. Figure I shows the position of fan controller in the electric box and operation method.
After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No. accordant. And confirm if it reaches the needed air volume.
Note:
1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply.
2) Do not set the dial at the position less than 1.
3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity number may exceed the permitted operation capacity range, so it is impossible to operate.
4) When delivering from factory, the capacity number of fan controller is set at ìNo.5î.
Rotate this switch
(capacity number setting: No. 1 ~ No. 8)
Once the fan controller has trouble, this linker can perform emergency assistant control. When this linker is connected to the linker from the PCB, it can operate with total load.
When this linker is connected to the linker from the PCB, through the fan speed adjustment panel to adjust speed.
High
Condition of standard air volume
Low
(air volume 100Pa)
Outer static pressure Pa
Example of duct
Lower limit
Upper limit
Standard air volume
(m3/min)
The example of the method of choosing capacity number:
1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 2.
2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 4.
310
30
530
80 510
11. Refrigerant pipe
[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.]
The outdoor unit has been charged with refrigerant. When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,
use spanner and torque spanner together. When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use
hand to twist 3-4 rings, then fasten with spanner. Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown. Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here
Torque spanner
Spanner
Pipe joint
Cone nut
Middle size seal cushion (accessory)
(Use seal cushion to bind the pipe joint)
Clamp
Heat insulation (accessory)
(for liquid pipe)
(for gas pipe)
Heat insulation (accessory)
Gas pipe
Liquid pipe
Liquid pipe
Gas pipe
Electric box
Upper
Air inlet
Air outlet
Down side
Drain hose connection mouth VP25 PVC pipe
9.52
12.0~12.4
3270~3990 N.cm
(333~407 kgf.cm)
(mm)
Specification of pipe
Tighten torque
Cone
Cone dimension A (mm)
R0.4~0.8
A
90 0.5
45 2
22.9~23.3
9720~11860 N.cm (990~1210 kgf.cm)
19.05
Drain Hose
Swing fender
Refrigerant pipe Cable line Earthing line
Air filter
Outlet
(located in the suction grill)
In cooling operation,to discharge the water from inside the room.
Discharge unit (built in)
(located in the outlet)
Remote Controller
6.PARTS AND FUNCTIONS
3
Air inlet
AB242ACBEA AB28NACBEA
High ESP duct type:
Air outlet
Air inlet
Duct
Duct
Drainpipe
Air outlet
Air inlet
Compressor (inside)
Fig.1 Indoor Unit
1 Operating Control Panel (Fig.2) 2 Emergency switch 3 Remote Control Signal Receiver 4 Power Indicator Lamp (Red) 5 OPERATION Indicator Lamp (Green) 6 TIMER Indicator Lamp (Yellow)
4
5 6
2
3
POWER OPER
TIMER
EMER
Fig.3
AC28NACBEA
PARTS AND FUNCTIONS
Air outlet
Air inlet
Duct
AU242AHBEA AU28NAHBEA
1
AD242AMBEA AD28NAMBEA
Fig.1 Indoor Unit
1
4
6 7
3
Fig.2
POWER OPER TIMER COMP
EMER
2
1 Operating Control Panel (Fig.2) 2 Emergency switch 3 Remote Control Signal Receiver 4 Power Indicator Lamp (Red) 5 OPERATION Indicator Lamp (Green) 6 TIMER Indicator Lamp (Yellow) 7 Compressor Run Lamp (Green) 8 Intake Grill (Fig.3) 9 Air Filter
10
UP/DOWN Air Direction Flaps
11
RIGHT/LEFT Air Direction Louvers
(behind UP/DOWN Air Direction Flaps)
3
9
8
Fig.1
1110
5
AC242ACBEA
REMOTE CONTROLLER FUNCTIONS
14.HIGH/SO Button
Used to select HIGH or SOFT operation.
21
22
31
29
32
FRESH
HIGH/SO
TIMER
SET
FILTER
B
A
M D
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
OFF
A U T O
1
2
3
4
6 7
9
10
11
15
13
5
8
16
17
30
34
35
33
23
24
25
26
27
28
20
12
14
Remote controller
1.TEMP Setting Button
(Used to set temperature. Setting ranges: 16 C to 30 C)
In Up/Down function, for controlling up and down filter.
2.SWING Button
If you press this button once, auto swing will be activated. If you press this button again, the louver will fix in the present position.
3.Power ON/OFF Button
Used for unit start and stop After power on, the LCD of remote controller
will display the previous operation state (except for TIMER,SLEEP and SWING state).
4.Operation MODE
Used to select operation mode. Every time you press MODE button, operation mode
changes according to following sequence:
5.HEALTH Button
Used to set health mode, if the unit has the negative ion function and oxygen bar function.
AUTO
FAN
HEAT
COOL
DRY
6.CLOCK Button
Used to set correct time.
(Note: if time of TIMER ON is the same as TIMER OFF ,TIMER ON/OFF cannot be set)
10.RESET Button
Press this button by using a sharp article to resume the correct operation of the remote controller in case of need, i.e. for example in case of malfunctions due to electromagnetic noise.
17.SLEEP Button
(The clock must be corrected before setting sleep function)
Used to set sleep mode.
13.Up and down Button
Used to set TIMER and CLOCK up or down.
8. FILTER Button
Used to set up/down function of filter.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating.
2.HIGH/SO button This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high functon" will be cancelled automatically after 15 minutes running.
11.LOCK Button
Used to lock operation button and LCD display contents: by pressing this button, other buttons comes out of function and lock state display appears; if you press it again, lock state will be no more active and lock state display will disappear.
7.Remote controller functions
7.CLOCK Button
Used to select TIMER ON, TIMER OFF.
9. CODE Button
Used to select code A or B, for this unit, the code is A.
18
12.LIGHT Button
Used to light the control panel (only for cabinet unit)
15.SET Button
Used to confirm TIMER and CLOCK settings.
16.FRESH Button
Used to set fresh mode, the unit will draw in fresh air.
19
36
Clock Set
Displays when healthy run function is set.
22.TEMPERATURE Display
34.LOCK State Display
33.BATTERY Energy Display
Notify the user when it is time to change the batteries.
24.HIGH/SO Display
25.SIGNAL SENDING Display
26.FRESH AIR Display
27.ELECTRICAL HEATING Display
29.HEALTH Display
32.SLEEP State Display
31.Operation MODE Display
AUTO RUN
COOL RUN
DRY RUN
HEAT RUN
FAN RUN
35.FAN SPEED Display
23.AUTO SWING Display
19.TIMER OFF Display
21.FILTER Display
36.TIMER ON Display
When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows:
1.Press CLOCK button, clock indication of " AM " or " PM " flashes.
2.Press or to set correct time. Each press will increase or decrease 1 min. If the button is kept pressed, time will increase or decrease quickly.
3.After time setting is confirmed, press "SET" : AM or PM stop flashing, while clock starts working. Note:AM means morning and PM means afternoon.
When operating the remote controller in an area where electronically controlled lights are installed or wireless handsets are used, please move closer to the indoor unit as the function of the remote controller might be affected by signals emitted by the above mentioned equipments.
Battery loading
Confirmation indicator
If no indication is displayed after press ON/OFF button, reload the batteries.
AUTO
LO MID
HI
AUTO
Remote Controller' Operation
When in use, direct signal transmission head to the receiver placed on the indoor unit
The distance between the remote controller and the receiver should be max 7m and there should be no obstacle between them. Do not throw the remote controller; prevent it from being damaged.
18.FAN Button
Used to select fan speed:LOW,MID,HIGH,AUTO.
Note: It is recommended that the batteries be removed from the compartment if the remote controller is not used for an extended period. The remote controller is programmed for automatic test of operation mode after the batteries are replaced. When the test is conducted, all icons will appear on the screen and then disappear if the batteries are properly fitted.
Caution: If the remote controller does not operate as designed after
fitting new batteries of the same type, press the Reset button (marked ) with a pointed article.
20.CLOCK Display
30.DEHUMIDIFICATION Display
28.Some other buttons
All these functions are not available now.
FRESH
HIGH/SO
TIMER
SET
FILTER
HEALTH
RESET
LOCK
SLEEPMODE
CLOCK
CODE
LIGHT
3
2
1
Battery loading Batteries are fitted as follows:
Loading the battery
Ensure that batteries are correctly placed in the compartment as required for positive and negative terminals.
Replacing the battery compartment lid
The battery compartment lid is reinstalled in the reverse sequence.
Display review
Press the button to see if batteries are properly fitted. If no display appears, refit the batteries.
Remove the battery compartment lid Slightly press and disengage the battery compartment lid marked with ì
î and then hold the remote controller by the upper section and then remove the battery compartment lid by pressing in the direction of the arrow as shown in the figure above.
* *
* *
Fan Operation
1.Unit start
Press ON/OFF button to start your air conditioner. Previous operation status appears on LCD (except for TIMER, SLEEP, and SWING setting).
2.Select operating mode
Press MODE button. At each press, operation mode changes as follows:
3. Adjust fan speed
Press FAN button. At each press, fan speed changes as follows:
Air conditioner will run at the selected fan speed. When in AUTO mode, unit will adjust fan speed according to room temperature automatically.
4. Unit stop
Press ON/OFF button to stop unit.
Then select FAN
About FAN mode When the air conditioner runs in F AN mode, it is not possible to select AUTO FAN or to set temperature.
AUTO
FANHEATCOOL DRY
A
FRESH
HIGH/SO
TIMER
SET
FILTER
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
A U T O
4
1
3
2
LOW
MID
HIGH
AUTO, COOL , HEAT and DRY Operation
1. Unit start
Press ON/OFF button,unit starts. Previous operation status appears on LCD (except for TIMER, SLEEP and SWING setting)
3.T emperature setting
Then select AUTO run or select COOL operation or select DRY operation or select HEAT operation
2.Select operation mode
Press MODE button. At each press, operation mode changes as follows:
Press TEMP button. Every time the button is pressed, temp. setting increases
1 C; if the button is kept pressed, temp. setting will increase quickly.
Every time the button is pressed, temp. setting decreases 1 C, if the button is kept pressed, temp. setting will decrease quickly.
Set proper temperature
4.Adjust FAN button
Press F AN button. At each press, fan speed changes as follows:
Air conditioner will run at the selected fan speed.
5. Unit stop
Press ON/OFF button,unit stops.
In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner will select COOL, HEAT or F AN mode automatically according to the room temperature. In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently at LOW speed regardless of F AN setting. When room temperature is lower than temperature setting, unit will only run F AN operation. In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.
AUTO
FANHEATCOOL DRY
AUTO
LOW
MID HIGH
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
A U T O
Temp. setting +2 C
Temp.setting
On reaching temp.setting +2 C, unit will run in mild DRY mode.
Ultra-low air flow
COOL operation starts when room temp.is higher than temp. setting.
3
5
1
3
4
2
A U T O
Press SWING button. Up and down airflow varies upwards and downwards. Left and right airflow varies left and right sides.
Always use SWING button on the remote controller to adjust flaps. Adjusting them by hand may result in air conditioner's abnormally running.
Displays on the LCD disappear. All indicators on the indoor unit go out. Swing louver automatically close the air outlet.
After unit stops:
AUTO SWING
Adjusting air flow direction
AUTO SWING
When the automatic swing louver moves to the proper angle, press SWING button can fix the airflow direction.
Please carefully set temperature when children, old or infirm people ues the air conditioner.
In case of great humidity, If the vertical flaps are completely turned towards left or right, the louver will drop water.
Never adjust the louver directly by hand, as this could make it work abnormally .If the louver work abnormally , stop unit, restart and adjust the louver by remote controller.
Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful for a better air circulation As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for a better air circulation. Be careful not to catch a cold when cold air blows downward directly.
In COOL or DRY mode, do not leave the louver in downward position for a long time, as the water vapor close to the grille may condense and water may drop from the air conditioner.
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
A U T O
Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make you sleep more comfortably. Before using this function, the clock must be set.
Use of SLEEP function
After the unit's start, set running mode and then press SLEEP button once to make the air conditioner have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button / : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1 hour: "xh" and "OFF" indications appear on the display.
Operation Mode
1.In COOL, DRY mode
One hour after sleeping operation start, the temperature is 1 C higher than the setting one. After another hour, temperature rises 1 C: sleep run continuously for another 6 hours and then stops. The actual temperature is higher than the setting one which is to prevent from being too cold to your sleep.
2.In HEAT mode
One hour after sleeping operation start, the temperature is 2 C lower than the setting one. After another hour, temperature decreases by 2 C more. Temperature will automatically rise by 1 C after another 3 hours' continuous operation. The actual temperature is lower than the setting one which is to prevent from being too hot to your sleep.
3.In AUTO mode.
The air conditioner will run in corresponding sleep operation according to the automatically selected operation mode.
SLEEP RUN BEGINS
SLEEP RUN STOPS
SETTING T
SHUT DOWN
about 6 hrs
1 hrs
In COOL,DRY mode
increase 1 C
increase 1 C
SLEEP RUN BEGINS
SLEEP RUN STOPS
SETTING T
SHUT DOWN
1 hrs
1 hrs
3 hrs
about 6 hrs
increase 1 C
decrease 2 C
decrease 2 C
Notes:
After setting SLEEP function, it is not possible to set clock. If set-sleep time does not reach 8 hours, unit will automatically stop operation
after set time is reached. Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first,
then set SLEEP. After set SLEEP function, the TIMER function cannot be set.
In HEAT mode
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
OFF
A U T O
Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time changes quickly.
Timer ON/OFF Function
Set clock correctly before starting TIMER operation
1.Unit start
After unit start, select your desired operation mode (operation mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:
ON OFF ON OFF
AM
12:00
AM
12:00
PM
12:00
PM
12:00
TIMER ON
TIMER OFF
TIMER ON-OFF
blank
Then select TIMER mode as needed (TIMER ON or TIMER OFF). Now or will flash.
3.TIMER setting (press time adjust buttons )
Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed, time changes quickly. It can be adjusted within 24 hours at will.
4.Confirm setting
After setting correct time, press SET button to confirm time. Now
Time displayed: unit starts or stops at X hour X min (TIMER ON or TIMER OFF)
5.Cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
Hints:
After replacing batteries or if a power failure occurs, TIMER setting must be reset.
Remote controller has memory function. When you use TIMER mode next time, just press SET button after mode selection if timer setting is the same as the previous one.
Note:
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time, just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you can adjust clock). 5 seconds later, the display will show TIMER time again.
ON
OFF
ON
OFF
or stop flashing.
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
1
2
3
4
Timer ON-OFF Function
Set clock correctly before starting TIMER operation
1.Unit start
After unit start, select your desired operation mode (operation mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:
OFF
3.Time setting for TIMER ON
4.Timer confirming for TIMER ON
After setting correct time, press TIMER button to confirm time. Now
5.Timer setting for TIMER OFF
Press time buttons and follow the same procedures in " Time setting for TIMER ON"
Press time button
ON
stops to flash, while
starts flashing.
Time displayed : unit starts at X hour X min.
6.Time confirming for TIMER OFF
After time setting, press SET button to confirm time.
stops to flash.
Time displayed: unit starts at X hour X min.
7.Canel TIMER mode
Just press TIMER button several times until TIMER mode disappears. According to the time setting sequence of TIMER ON and TIMER OFF,
either start-stops or stops-start can be realized. If the time setting of TIMER ON is the same as TIMER OFF, TIMER
ON-OFF function cannot be set.
ON
Then select TIMER ON-OFF mode.
will flash.
Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time will changes quickly.
Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed ,time will changes quickly. It can be adjusted within 24 hours at will. AM refers to morning and PM refers to afternoon.
OFF
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
OFF
1
3
6
5
4
2
ON
OFF
ON
OFF
AM
12:00
AM
12:00
PM
12:00
PM
12:00
TIMER ON
TIMER OFF
TIMER ON-OFF
blank
After the air conditioner has operated for a certain period, dust has accumulated on the filter, and the filter up/down function can be used to clean it.
1.Whether unit starts or stops, continuously press FILTER button for 3 seconds, and enter the filter up/down waiting status (when unit stops, the yellow TIMER indicator flashes, and filter and clock indication are displayed on the remote controller. Only the FILTER button, the temperature buttons " " " " and time buttons are active).
2.Press temperature button or time button in filter up/down waiting status: the up/down mechanism makes the filter moving downward and does not stop until it has reached the maximum limit.
3.Press temperature button or time button in filter up/down waiting status: the up/down mechanism makes the filter to moving upward till near the surface board and then automatically adjusts it to reset (when adjusting to reset, it will not be controlled by the remote controller till the adju­ stment is finished).
4.During moving downward, press temperature button or time button: moving stops.
5.During moving downward, press temperature button or time button: moving stops.
6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter goes back to the original position, the remote controller goes back to off status and only clock is displayed).
Note: If the filter does not thoroughly go back to the original position, only needs to operate several times repeatedly.
Filter Up/Down
" "
" "
" "
" "
" "
" "
" "
" "
(Only for AB182ACBEA)
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
1
Press the HIGH/SO button twice
NOTICE: When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time. Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.
" High mode " Operation
If the button is pressed once, the indication is displayed on the remote controller. If you press the button once again, the indication disappears, regular operation is restored and fan speed goes back to the mode set before "High Mode" operation.
Press the HIGH/SO button noce
The indication appears on the display of the remote controller and operation in "High Mode" starts. The AUT O fan speed is automatically set and the corresponding indication is also displayed.
Outline of operation in "High Mode"
This function is suitable when the set temperature must be reached in the shortest delay. The button "HIGH/SO", referred to this function, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).
ON
OFF
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
A U T O
1
Press the HIGH/SO button twice
NOTICE: When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time. Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.
" Soft mode " Operation
If the button is pressed once, the indication is disappears from the remote controller's display. If you press the button once again, regular operation is restored and fan speed goes back to the mode set before "Soft Mode" operation.
Press the HIGH/SO button twice
The indication appears on the display of the remote controller and operation in "Soft Mode" starts. The AUT O fan speed is automatically set and the corresponding indication is also displayed.
Outline of operation in "Soft Mode"
Operation in "Soft Mode", more silent, is suitable when noises should be reduced, e.g.. for reading or sleeping. The button "HIGH/SO", referred to this operation, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).
ON
OFF
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
OFF
A U T O
1
Auto restart function setting
Setting method (to be applied for a necessary situation)
:
Setting Method: When the remote controller is on (excluding timer mode and fan mode),
press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 4 times, the air conditioner will enter the state of power failure compensation.
Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 2 timer, the power failure compensation mode will be cancelled.
Notes: When a power failure suddenly occurs during the air conditioner is working after the power failure compensation is set, if the air conditioner will not be used for a long time, please cut off the power supply to prevent its operation from being resumed after the power is supplied again, or press the "Switch On/Off" button after the power comes again.
After the power failure compensation is set, if power failure suddenly occurs while the air conditioner is working, it will resume the previous working state when the power is supplied again.
FRESH
HIGH/SO
TIMER
SET
FILTER
A
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWING
MODE
CLOCK
CODE
LIGHT
A U T O
C
HEALTH
SET RECOVERY
CHECK
F
Cautions: On cooling only unit, heating mode is not available.
Note: The above information is the explanation of the displayed information therefore varies with those displayed in actual operation.
CLOCK
Used to adjust time.
TIMER
Used to set timer mode.
stands for time plus/minus, used to adjust time.
Used for unit start and stop.
POWER ON/OFF
MODE
Used for select indoor operation mode.
FAN SPEED
Used for select indoor air flow.
HEALTH
Used for setting indoor health function.
TEMP + -
Used for changing set temperature.
RECOVERY
used to switch over air­exchanging mode.
SWING
Used for setting indoor swing mode.
Auto-diagnostic button.
Filter-cleaned button.
FILTER
RESET
Reset correct mode button.
Wired controller functions:
CHECK
+ -
Buttons and functions of the wired controller
Buttons function MODEused for select indoor operation mode. FAN:used for select indoor air flow. SWINGused for setting indoor swing mode. HEALTHused for setting indoor health function.
TEMP + -used for changing set temperature.
CLOCKused to adjust time.
+-stands for time plus/minus, used to adjust time.
TIMERused to set timer mode.
RECOVERYused to switch over air-exchanging mode.
CHECKauto-diagnostic button.
FILTERfilter-cleaned button.
RESETreset correct mode button.
Display description
[MODE] [AUTO]auto operation mode [MODE] [FAN ONLY]air-throwing mode [MODE] [COOL]Cooling operation mode [MODE] [DRY]Dehumidification mode [MODE] [HEAT]Heating operation mode [MODE] [HEAT] [TES]In heating mode, auxiliary electric heater is running. Only when the
unit with auxiliary electric heater is in auxiliary electric heating mode, it will display.
[FAN] [AUTO]auto fan running
[FAN] [HIGH]high fan speed [FAN] [MED]: medium fan speed [FAN] [LOW]: low fan speed [FAN] [FIX]: fixed fan speed, it will display only when fixed fan speed is requested to main
indoor unit.
[CENTRAL] central control mode [OPERATION] running mode [STAND BY] waiting mode [PRE-HEAT] pre-heating mode [DEFROST] defrosting mode [FILTER] request of filter to be cleaned [HEALTH]health function [UNIT NO.] [CEN.ADD]central control address, the address number will display on “88 [SYS.ADD.]system address, the address number will display on “88 [CHECK]auto-diagnostic, trouble shooting [DEMAND]compulsory operation function, when it works, [CENTRAL] will flash [SWING]swing mode [ROOM TEMP.]indoor ambient temperature [SET TEMP.]:set admired temperature [TIMER][ON] timer function is on, it will switch over in the sequence below:
[ON][OFF] [ON][OFF][DAILY] [ ] [TIMER][OFF] timer function is off [TIMER][ON][OFF] timer function ON-OFF [TIMER][ON][OFF][DAILY]timer ON-OFF will switch over in turn daily [CLOCK]clock display, the displaying time is the current time of the clock. [UP][DOWN]indicator of filter elevating [VENTILATION][AUTO]auto ventilation mode [VENTILATION][RECOVERY]fully heat exchanging ventilation mode [VENTILATION][NORMAL]normal ventilation mode
FAN ONLY OPERATION
1Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO][FAN][AUTO][ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”. 2 Select MODE: press the MODE button, then you will see in the display section [MODE]
switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→ [FAN ONLY]. Select [FAN ONLY].
3)Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed. 4Power off: press ON/OFF button, indoor unit will be powered off, there are only time and the ambient temperature in the screen.
AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation
1) Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO][FAN][AUTO][ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”.
2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY]. Select [FAN ONLY].
3) Change set temperature: press TEMP + or – every time, [SET] will display, and set temperature will increase/reduce 1℃(F).
4) Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed.
5) Select [SWING]: press [SWING] button, swing function is valid. Press again, swing
function is invalid.
6) Set [HEALTH]: used to set the indoor health function. Press it once, [HEALTH] will display in the display section, then indoor health function is valid. Press it again, [HEALTH] will disappear, then the health function is invalid. This function is valid only for the unit with health function.
7) Power off: press ON/OFF button, indoor unit is powered off. There are only time and the ambient temperature in the screen.
Set TIMER operation:
Adjust clock: when powered on, for the first time to set timer function, the clock will be adjusted. Press “CLOCK” button, and set the current clock. Now, “CLOCK” will flash at the frequency of 2Hz every minute. Press the clock +/- button; the current clock can be adjusted. Until the proper time comes, press [SET].
TIMER ON operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] [ ]. Select [TIMER] [ON], then [TIMER] [ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press [SET] button.
TIMER OFF operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] [ ]. Select [TIMER] [OFF], then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET] button.
TIMER ON-OFF operation:
Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] [ ]. Select [TIMER] [ON] [OFF]. Firstly, [TIMER][ON] flashes, press the clock +/- button to adjust the time of
TIMER ON, press [TIMER]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will determine the mode is [TIMER] [ON] [OFF] or [TIMER] [OFF] [ON]. If you want the current time, press [CLOCK] once, current time will display; press again, [CLOCK] will flash, and press [+][-] to adjust the time. Note: 1. If the two times are same, the timer state which is set later will flash, in this case, timer can not be set.
2. When entering TIMER setting state, if you do not input any button in continuous 10 seconds, the unit will quit from the TIMER mode.
Cancel TIMER operation:
In the timer operation state, press [TIMER] button, the unit will quit from the current timer operation state, and the set data will be memorized, then enter the next timer mode.
[FILTER] function
When the wired controller receives the filter-cleaned signal from indoor unit, [FILTER] will display. After finishing clean, press [FILTER], the sign [FILTER] disappears, and the controller will send the filter reset signal to indoor unit. When the sign [FILTER] not display, it is invalid to press [FILTER] in short time.
FILTER ELEVATING function: (only for the unit with elevating function)
When the filter needs to be cleaned, the panel can be lowered to the admired height by the [FILTER][UP][DOWN] function. Method is below: In power off state, press [HEALTH] for 15 seconds to enter filter elevating set state. In this state, the sign [FILTER] will flash and [UP] [DOWN] will display simultaneously, Press TEMP [+], in timer section [UP] will display, while press TEMP [-], in timer section [DOWN] will display. When it arrives the appropriate position, press [UP], [UP][DOWN] will display simultaneously, filter will stop going down. Press [UP] again, filter will go up. Press [FILTER] button to quit the mode.
DEMAND operation function:
By this function, all the indoor units can be made in nominal mode. Set the operation mode in cooling and then shut off the unit. In the stop state, press [ON/OFF] button for 5 seconds to enter cooling trial operation state. If it is in heating mode before shut off the unit, then press [ON/OFF] button for 5 minutes, it will enter heating trial operation state.
In cooling, there will be “LL” in the position where the set temperature displays. In heating, there will be “HH” in the position where the set temperature displays. The wired controller will send the [DEMAND] signal to indoor unit. In the [DEMAND] operation, “COOL” or “HEAT” will display at 1Hz frequency. Indoor fan motor will be fixed at “AUTO” mode. The indoor units in the same group will quit the [DEMAND] in turn.
At this time, only the buttons of [ON/OFF] and temperature [+] [-] are valid. Press [ON/OFF] to quit [DEMAND] mode.
CENTRAL control function
When the central controller selects [CENTRAL] mode, the buttons in the wired controller except for [CHECK] will be invalid.
VENTILATION mode (only for the unit with fresh air function or heat recovery function)
Press [RECOVERY] button, then the unit will switch over the ventilation mode: [ ] [VENTILATION][AUTO] [VENTILATION][RECOVERY] [VENTALATION][NORMAL] [ ], please select appropriate ventilation mode.
Query indoor malfunction history:
In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time malfunction, the displaying format is [XX:YY], in which XX stands for the current malfunction, if normal, it will display “――”; YY stands for the latest time malfunction. The failure code of every unit will display for 3 seconds. After the failure codes of all indoor units in the whole group are displayed, the mode will quit automatically.
Clear abnormal state and malfunction history:
In normal state, press [CHECK] button for 5 seconds to clear abnormal states, at the same time, wired controller will send the data of “clear abnormal state”, but the malfunction history still retains. In normal state, press [CHECK] button for 15 seconds, except for malfunction states, the malfunction history in wired controller will be cleared.
Query indoor performance state:
In normal state, press both buttons of [CHECK] and [FILTER] for 5 seconds, in the set temperature region in the screen, [XX] will display, XX is indoor number, which can be selected by pressing [TEMP] [+] [-]. In the timer region in the screen, [YZZZ] will display, in which Y stands for data type, ZZZ stands for the corresponding data. which can be selected by pressing [CLOCK] [+] [-].
Y ZZZ Type A Indoor capacity (W) Nominal cooling
capacity/10, decimal
B Request of indoor capacity(Hz) Actual value, decimal C Temperature of indoor ambient
temp. sensor TA
Actual value, decimal
d Temperature of indoor gas pipe
sensor TC1
Actual value, decimal
E Temperature of indoor liquid pipe
sensor TC2
Actual value, decimal
F Open degree of indoor PMV Actual value, decimal
g Preset ―――
H Outdoor total capacity Actual value, decimal
In check mode, press [CHECK] to quit the check mode, and go into normal running mode.
How to change the function switches?
No. Type State of
switch
Function description
Connected Central controller
J01
Changeover of Wired
controller and central
controller
Cut off Wired controller
Connected Set as simple controller
J02
Changeover of type of
wired controller
Cut off Set as standard controller
Connected Use the sensor in the wired
controller
J06
Selection of room temp.
sensor
Cut off Use the sensor in the indoor unit
Connected Common control
J07
Auto restart after power
failure
Cut off Auto restart after power failure
Connected Yes
J03
Display of room
temperature
Cut off No
ON Set as slave controller
SW01
Changeover of master or
slave controller
OFF Set as master controller
ON
SW01
or
OFF
Connected Indoor unit in shorted time
function
D1
Shorten time function
Cut off Common control
Connected Send compulsorily defrost signal
to indoor unit
D2
Compulsorily defrost
Cut off Common control
Note: 1. The switches in grey can be operated after opening the cover of wired controller.
2. Switches or jumper wire must be adjusted when the wired controller is powered off. If the wired controller is powered on, the above operations will be invalid.
3. Shorten time function In normal operation, D1 is in short circuit, it will enter shorten time mode, and the time will be shortened in the proportion of 60:1. In shorten time mode, LED will flash at the frequency of
0.5 second. Cut off D1, it will quit the shorten time mode and return to the normal operation mode.
4. Compulsorily defrost In heating mode, D2 is in short circuit, it will enter compulsorily defrost mode; cut off D2, it will quit.
5. Lock function There is no lock function only in the wired controller. But when it is connected with a central
controller, if the central controller is set to “central”, the buttons in the wired controller will be invalid, or the buttons will be valid.
Failure code:
For
remote
type,
flash
times
Failure
code on
wired
controller
For
central
control,
failure
code
Failure description Reason Remarks
10 08(08H) 21D Drainage system
abnormal
Float switch broken down
for more than 25m
continuously
1 01(01H) 01D Indoor ambient temp.
sensor failure
sensor broken down or
short circuit for more than
2m continuously
2 02(02H) 02D Indoor coil temp.
sensor failure
sensor broken down or
short circuit for more than
2m continuously
3 74(4AH) 11D Outdoor ambient
temp. sensor failure
sensor broken down or
short circuit for more than
2m continuously
4 73(49H) 12D Outdoor coil temp.
sensor failure
(compressor
discharging temp.
sensor)
Sensor broken down or
short circuit for more than
2m continuously
5 72(48H) 10D Over-current
protection
CT check abnormal 3 times
in 30m
6 83(53H) 14D High pressure
abnormal
High pressure switch acts 3
times in 30m
7 71(47H) 22D Power supply
abnormal
Fault phase, short of
phase, out of balance
greatly
8 07(07H) 06D Communication
between wired
controller and indoor
abnormal
Communication abnormal
for more than 4m
continuously
9 06(06H) 05D Communication
between indoor and
outdoor abnormal
Communication abnormal
for more than 4m
continuously
11 11(0BH) 30D Outside alarm signal
input
Outside signal broken
down for more than 10s
12 03(03H) 20D Gas pipe temp.
sensor abnormal
Sensor broken down or
short circuit for more than
2m continuously
13 13(0DH) 31D Solenoid valve
abnormal
Solenoid valve act
incorrectly 3 times
continuously
14 76(4CH) 15D Discharging temp.
sensor abnormal
Sensor broken down or
short circuit for more than
2m continuously
15 05(05H) 17D EEPROM abnormal EEPROM data missing Run as the
default
value
16 84(54H) 26D Pressure
abnormal(low
pressure)
Low pressure switch acts in
normal running
17
80(50H)
15D Compressor overheat the discharging
temperature is higher than
120degree
Resumable
if lower
than
100degree
18
12(0CH)
23D Abnormal mode Indoor operation mode is
different with the running
indoor unit.
19
75(4BH)
18D Outdoor coil
B(suction temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
20
77(4DH)
15D Outdoor discharging
B(oil temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
shows resumable fault, shows it is not resumable fault.
Setting address method:
The address setting can be realized by setting indoor PCB. If you use the group control function, there should be a master unit and 15 sets of slave units. For the master unit, the SW5-3 should be at “1”. For the slave units, the SW5-3 should be at “0”. Please refer the below table,
Indoor
unit
address
SW1-4 SW1-3 SW1-2 SW1-1
1 OFF OFF OFF OFF 2 OFF OFF OFF ON 3 OFF OFF ON OFF 4 OFF OFF ON ON 5 OFF ON OFF OFF 6 OFF ON OFF ON 7 OFF ON ON OFF
8 OFF ON ON ON 9 ON OFF OFF OFF
10 ON OFF OFF ON
11 ON OFF ON OFF 12 ON OFF ON ON 13 ON ON OFF OFF 14 ON ON OFF ON 15 ON ON ON OFF 16 ON ON ON ON
If you use central control type, SW1, SW2 will be used simultaneously. Wiring request in central control type: port A-B is connected with indoor port CN16(A-B) through 2-core shield wire. Requirements:
1. Port A connects with port CN16(A)of all indoor units.
2. Port B connects with port CN16(B)of all indoor units. Address on central controller
Indoor unit address
SW2-3 SW2-2 SW2-1 SW1-4 SW1-3 SW1-2 SW1-1
1 1 ON OFF OFF OFF OFF OFF OFF 2 2 ON OFF OFF OFF OFF OFF ON 3 3 ON OFF OFF OFF OFF ON OFF 4 4 ON OFF OFF OFF OFF ON ON 5 5 ON OFF OFF OFF ON OFF OFF 6 6 ON OFF OFF OFF ON OFF ON 7 7 ON OFF OFF OFF ON ON OFF 8 8 ON OFF OFF OFF ON ON ON 9 9 ON OFF OFF ON OFF OFF OFF 10 10 ON OFF OFF ON OFF OFF ON 11 11 ON OFF OFF ON OFF ON OFF 12 12 ON OFF OFF ON OFF ON ON 13 13 ON OFF OFF ON ON OFF OFF 14 14 ON OFF OFF ON ON OFF ON 15 15 ON OFF OFF ON ON ON OFF 16 16 ON OFF OFF ON ON ON ON 17 -------- ON OFF ON OFF OFF OFF OFF 18 -------- ON OFF ON OFF OFF OFF ON 19 -------- ON OFF ON OFF OFF ON OFF 20 -------- ON OFF ON OFF OFF ON ON 21 -------- ON OFF ON OFF ON OFF OFF 22 -------- ON OFF ON OFF ON OFF ON 23 -------- ON OFF ON OFF ON ON OFF 24 -------- ON OFF ON OFF ON ON ON 25 -------- ON OFF ON ON OFF OFF OFF
26 -------- ON OFF ON ON OFF OFF ON 27 -------- ON OFF ON ON OFF ON OFF 28 -------- ON OFF ON ON OFF ON ON 29 -------- ON OFF ON ON ON OFF OFF 30 -------- ON OFF ON ON ON OFF ON 31 -------- ON OFF ON ON ON ON OFF 32 -------- ON OFF ON ON ON ON ON 33 -------- ON ON OFF OFF OFF OFF OFF 34 -------- ON ON OFF OFF OFF OFF ON 35 -------- ON ON OFF OFF OFF ON OFF 36 -------- ON ON OFF OFF OFF ON ON 37 -------- ON ON OFF OFF ON OFF OFF 38 -------- ON ON OFF OFF ON OFF ON 39 -------- ON ON OFF OFF ON ON OFF 40 -------- ON ON OFF OFF ON ON ON 41 -------- ON ON OFF ON OFF OFF OFF 42 -------- ON ON OFF ON OFF OFF ON 43 -------- ON ON OFF ON OFF ON OFF 44 -------- ON ON OFF ON OFF ON ON 45 -------- ON ON OFF ON ON OFF OFF 46 -------- ON ON OFF ON ON OFF ON 47 -------- ON ON OFF ON ON ON OFF 48 -------- ON ON OFF ON ON ON ON 49 -------- ON ON ON OFF OFF OFF OFF 50 -------- ON ON ON OFF OFF OFF ON 51 -------- ON ON ON OFF OFF ON OFF 52 -------- ON ON ON OFF OFF ON ON 53 -------- ON ON ON OFF ON OFF OFF 54 -------- ON ON ON OFF ON OFF ON 55 -------- ON ON ON OFF ON ON OFF 56 -------- ON ON ON OFF ON ON ON 57 -------- ON ON ON ON OFF OFF OFF 58 -------- ON ON ON ON OFF OFF ON 59 -------- ON ON ON ON OFF ON OFF 60 -------- ON ON ON ON OFF ON ON 61 -------- ON ON ON ON ON OFF OFF 62 -------- ON ON ON ON ON OFF ON 63 -------- ON ON ON ON ON ON OFF 64 -------- ON ON ON ON ON ON ON 65 -------- ON OFF OFF OFF OFF OFF OFF 66 -------- ON OFF OFF OFF OFF OFF ON 67 -------- ON OFF OFF OFF OFF ON OFF
-------- ON OFF OFF OFF OFF ON ON
-------- ON OFF OFF OFF ON OFF OFF
-------- ON OFF OFF OFF ON OFF ON
-------- ON OFF OFF OFF ON ON OFF
-------- ON OFF OFF OFF ON ON ON
-------- ON OFF OFF ON OFF OFF OFF
-------- ON OFF OFF ON OFF OFF ON
-------- ON OFF OFF ON OFF ON OFF
-------- ON OFF OFF ON OFF ON ON
-------- ON OFF OFF ON ON OFF OFF
-------- ON OFF OFF ON ON OFF ON
-------- ON OFF OFF ON ON ON OFF
-------- ON OFF OFF ON ON ON ON
-------- ON OFF ON OFF OFF OFF OFF
-------- ON OFF ON OFF OFF OFF ON
-------- ON OFF ON OFF OFF ON OFF
-------- ON OFF ON OFF OFF ON ON
-------- ON OFF ON OFF ON OFF OFF
-------- ON OFF ON OFF ON OFF ON
-------- ON OFF ON OFF ON ON OFF
-------- ON OFF ON OFF ON ON ON
-------- ON OFF ON ON OFF OFF OFF
-------- ON OFF ON ON OFF OFF ON
-------- ON OFF ON ON OFF ON OFF
-------- ON OFF ON ON OFF ON ON
-------- ON OFF ON ON ON OFF OFF
-------- ON OFF ON ON ON OFF ON
-------- ON OFF ON ON ON ON OFF
-------- ON OFF ON ON ON ON ON
-------- ON ON OFF OFF OFF OFF OFF
-------- ON ON OFF OFF OFF OFF ON
-------- ON ON OFF OFF OFF ON OFF
-------- ON ON OFF OFF OFF ON ON
-------- ON ON OFF OFF ON OFF OFF
-------- ON ON OFF OFF ON OFF ON
-------- ON ON OFF OFF ON ON OFF
-------- ON ON OFF OFF ON ON ON
-------- ON ON OFF ON OFF OFF OFF
-------- ON ON OFF ON OFF OFF ON
-------- ON ON OFF ON OFF ON OFF
-------- ON ON OFF ON OFF ON ON
-------- ON ON OFF ON ON OFF OFF
-------- ON ON OFF ON ON OFF ON
-------- ON ON OFF ON ON ON OFF
-------- ON ON OFF ON ON ON ON
-------- ON ON ON OFF OFF OFF OFF
-------- ON ON ON OFF OFF OFF ON
-------- ON ON ON OFF OFF ON OFF
-------- ON ON ON OFF OFF ON ON
-------- ON ON ON OFF ON OFF OFF
-------- ON ON ON OFF ON OFF ON
-------- ON ON ON OFF ON ON OFF
-------- ON ON ON OFF ON ON ON
-------- ON ON ON ON OFF OFF OFF
-------- ON ON ON ON OFF OFF ON
-------- ON ON ON ON OFF ON OFF
-------- ON ON ON ON OFF ON ON
-------- ON ON ON ON ON OFF OFF
-------- ON ON ON ON ON OFF ON
-------- ON ON ON ON ON ON OFF 128 -------- ON ON ON ON ON ON ON
Electrical functions of wired controller:
1.Function difference between master wired controller and slave one:
Contrastive items Master wired controller Slave wired controller Function All of functions Only with below functions:
ON/OFF, MODE, FAN SPEED, SET TEMP., SWING
2. Wiring connections of wired controller:
indoor N
B
A
C
wired controller
indoor 1 indoor 2
indoor 1
2
1
3
ABC
ABC
indoor 16
control wiring of wired controller, polar.
indoor 15
123
ABC
wired controller
wired controller wired controller
wired controller
wired controller
wired controller
wired controller
indoor 1
wired controller
wired controller
wired controller
A
B
C
(master unit)
polar wire
polar wire
polar wire
There are three methods to connection wired controller and the indoor
units:
A. One wired controller can control max. up to 16 sets of indoor units, and
3 pieces of polar wire must connect the wired controller and the master
unit (the indoor unit connected with wired controller directly), the others
connect with the master unit through 2 pieces of polar wire.
B. One wired controller controls one indoor unit, and the indoor unit
connects with the wired controller through 3 pieces of polar wire.
C. Two wired controllers control one indoor unit. The wired controller
connected with indoor unit is called master one, the other is called slave
one. Master wired controller and indoor unit; master and slave wired
controllers are all connected through 3 pieces of polar wire.
3. Communication wiring:
The wired controller is equipped with special communication wiring in the
accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the terminal A、B、C of wired controller respectively.
The communication wiring is 4 meter long; if the actual length is more than
it, please distribute wiring according to below table:
Communication wiring length(m) Dimensions of wiring <100 0.3mm2X3-core shielded wire
100 and <200 0.5mm2X3-core shielded wire ≥200 and <300 0.75mm2X3-core shielded wire ≥300 and <400 1.25mm2X3-core shielded wire ≥400 and <600 2mm2X3-core shielded wire
One side of the shielded sheet of communication wire must be earthed.
8.Refrigerant Diagram
Heating operation
Cooling operation
air-liquid departor
compressor
4-way vavle
Outdoor unit
muffler
one way vavle
heat exchanger of
indoor unit
Indoor unit
-44-
9.Electrical Control Functions
Flow Chart for Operation
1) Turn on/off unit
On/off
Trouble
Mode
determinati
Heating
operation
Cooling
operation
Fan motor turn off, electronic expansion valve close, louve
r
motor turn off
Dehumidifying
operation
A
Power indicator turn off,
operation indicator turn
off
Trouble indication
A
bnormal
o
p
eration
Chose mode
Buzzer sound twice,
refuse to receive
signal
No
Ye
Off
Ye
On
Off
Control function treat module
-45-
2) Cooling operation
Electronic expansion valve: overheat control,Swing flap: cooling standard position
Fan motor: rated speed
Close
Open
No
No
Yes
Yes
No
Yes
Electronic expansion valve: close, send turning off uni
t
signal to outdoor unit
A
ccording to the
state of thermostat
Electronic expansion valve:
overheat control, send
turning on unit signal to
Emergenc
y
Electronic expansion valve: overheat control,Swing flap: cooling standard position
Fan motor: auto
Electronic expansion valve: overheat control,Swing flap: cooling standard position
Fan motor: hi
g
h speed
Rated
operation
Te st
No
Yes
Yes
No
A
djust fan speed
according to
temperature set and in
Operate in fan
A
utomatic
fan speed
Swing action
Swing flap in the
cooling standard
position
Swin
g
Cooling
-46-
Note: When abnormal phenomenon occur, the indoor unit indicator will indicate abnormality according
to the abnormal parts. When temperature of the evaporator inlet is lower than 0 and keeps for 5 minutes, unit will operate
in anti-icing mode.
3)Dehumidifying operation
-47-
Swin
g
No
Swing flap in the cooling
standard position
Swing action
If enter cooling
operation
A
djust fan speed
according to
temperature set and in
Yes
Yes
No
A
nti-defro
sting n
Yes
No
Yes
No
Determine if dehumidify
according to ai
r
temperature
Send indoor unit Operation State to outdoor unit
Electronic expansion
valve totally open
Electronic expansion
valves open, indoor unit
fan motor weak wind
Electronic expansion
valves open, indoor unit
fan motor weak wind
A
Dehumidifying
4) Heating operation
-48-
or unit
Heating operation
No
Swing flap in set fan
speed position
Swin
g
Yes
Swing action
On side: wind off,
expansion valve steady
Off side: Electronic
expansion valve totally
o
p
en
Yes
Defrosting
No
No
Rated
A
ccording to temperature
sensor to adjust state and
valve o
p
en degree
Fan motor operate in rated
fan speed
Yes
If stop unit
protection
Overload protection
No Yes
No (not rated
Electronic expansion
valve close
A
uto fan
Yes
Operate in set fan
speed
A
ccording to room temp and set
temp to determine fan speed
Protect according to
temperature difference
section value
Send indoor unit Operation State to outdo
A
10. Diagnostic information
10.1 Failure code remote control type unit:
failure description
indoor running
lamp flash times
indoor ambient temp. sensor failure
1
indoor coil temp.sensor failure
2
outdoor ambient temp. sensor failure or 4-way valve broken down in heating mode
3
outdoor coil temp. sensor failure
4
over-current protection failure or phase sequence fault
5
refrigerant system pressure too high or low
6
communication between indoor PCB and receiver panel failure
8
communication between indoor PCB and outdoor PCB
9
drainage failure
10
Note: For convertible type unit, drainage failure is not available.
Wired control type unit failure code:
Failure description Failure code on wired
controller Indoor ambient temp. sensor abnormal E1 Indoor coil temp. sensor abnormal E2 Outdoor ambient temp. sensor abnormal E3 Outdoor coil temp. sensor abnormal E4 Over current protection E5 Over high or low pressure protection E6 Communication between panel and indoor abnormal
E8
Communication between indoor and outdoor abnormal
E9
Water pump failure E0
Failure code with wired controller YR-E12:
For
remote
type, flash
times
Failure
code on
wired
controller
For central
control,
failure code
Failure description Reason
10 08 21 Drainage system failure Float switch broken down for more than
25m continuously
1 01 01 Indoor ambient temp. sensor
failure
sensor broken down or short circuit for
more than 2m continuously
2 02 02 Indoor coil temp. sensor failure sensor broken down or short circuit for
more than 2m continuously
3 4A 11 Outdoor ambient temp. sensor
failure
sensor broken down or short circuit for
more than 2m continuously
4 49 12 Outdoor coil temp. sensor
failure (compressor
discharging temp. sensor)
Sensor broken down or short circuit for
more than 2m continuously
5 48 10 Over-current protection CT check abnormal 3 times in 30m
6 53 14 High pressure abnormal High pressure switch acts 3 times in 30m
8 07 06 Communication between wired
controller and indoor abnormal
Communication abnormal for more than
4m continuously
9 06 05 Communication between
indoor and outdoor abnormal
Communication abnormal for more than
4m continuously
11 0B 30 Outside alarm signal input Outside signal broken down for more than
10s
12 03 20 Gas pipe temp. sensor
abnormal
Sensor broken down or short circuit for
more than 2m continuously
13 0D 31 Solenoid valve abnormal Solenoid valve act incorrectly 3 times
continuously
15 05 17 EEPROM abnormal EEPROM data missing
10.2 Trouble Shooting - Detailed for engineer
Malfunction flow chart: analyze and diagnose
If the air-condition fails to cooling or heating function and other functions, please check
the system as follows:

1.Cooling 
Y
change the designed TEMP.
replacing compressor
superaddition condensate
clear the filter
enact fan speed of
high or middle speed
airiness circle improperly
heat insulation of condensate pipeline between indoor unit and outdoor unit is normal
N
N
compressor fault
quantity of condensate charge is not enough
fan speed at
low-speed
air entrance filter obstruct
Y
Y
Y
Y
condensate flowage failure
fails in cooling
begining
N
N
fault in 4-way vavle
the cooling load beyond the allowable arange
the enactment TEMP. right or not
Y
Y
Y
insulate the two pipeline respective
redesign the TEMP.
change the 4-way vavle
use arange is right
or not
Y
Figure 7-1
-50-
2. Heating
Y
change the designed TEMP.
replacing compressor
superaddition condensate
clear the filter
enact fan speed of
high or middle speed
airiness circle
improperly
heat insulation of condensate pipeline between indoor unit and outdoor unit is normal
N
N
compressor fault
quantity of condensate charge is not enough
fan speed at
low-speed
air entrance filter obstruct
Y
Y
Y
Y
condensate flowage failure
fails in heating
begining
N
N
fault in 4-way vavle
the heating load beyond the allowable arange
the enactment TEMP. right or not
Y
Y
Y
insulate the two pipeline respective
redesign the TEMP.
change the 4-way vavle
use arange is right or not
Y
blowing cold air
fault in 4-way vavle
replacing the
4-way vavle
Y
prevent cold air failure
pipe sensor of indoor unit is fault
replacing the
4-way vavle
Y
Figure 7-2
-51-
3 Malfunction and Solution of Wired controller
1) There is nothing on display of wire control organ, and the air-conditioner failure to
operate
if the di ode on indoor unit is lumines
if there
'
s voltage on the pr imary side of tranaformer
if the fuse of indoor unit PCB.is normal
if the primary side of power supply
transformer is short
replacing the transformer
check the port row of power supply
if the t ransf orm of PCB.socket is normal
replacing t he transformer
redo the connection work
if power suppl y and communicati on li ne are connected correctl y
replacing the PCB. of i ndoor uni t
if there' e DC 12V between the four ports:A,B,C and D which on wire control organ
begini ng
Y
Y
if there's AC 220V of power suplay on PCB. of indoor unit
Y
repacing the wire
control organ
Y
N
Y
Y
Y
N
N
Y
N
N
if there's AC 15V on
transformer subside
of i ndoor uni t PCB.
N
Y
Figure 7-3
-52-
2) The wire control organ displays the alarm signal with “E0”
“E0” means the floater switch of indoor unit is abnormal
replacing the switch
if the function of the floater is normal
if the floater swith is orientated correctly
the alarm signal of wire control organ is E0
begining
amend the oritation of
the floater switch
N
Y
N
Figure 7-4
3) The wire control organ displays the alarm signal with “E1”
“E1” means indoor ambient temperature sensor is abnormal
amend the position of the sensor
if the indoor ambient sensor is orientated correctly
replacing the sensor
N
if the resistance of sensor is right
Y
N
wire control organ displays the alarm signal with E1
begining
Figure 7-5
Notation: The resistance of indoor ambient sensor is 23K
-53-
4) The wire control organ displays the alarm signal with “E2”  “E2” means indoor piping temperature sensor is abnormal
the alarm signal of wire control organ is E2
replacing the sensor
if the resistance of the sensor is right
N
Y
amend the position of sensor
N
begining
if the position of piping Temp.sensor is right
Figure 7-6
Notation: The resistance of piping temperature sensor is 10K
8) The wire control organ displays the alarm signal with “E8”
 “E8” means malfunction of communication between control panel and indoor units

if the potrs A and B,or C and D are short
replacing the wire
control organ
connect the wire correctly
if the four ports on wire control
connected corresponding with the port on PCB of indoor unit
if the ports:A,B,C and D are connected well
if the wire control organ can matches the PCB of indoor units
begining
connect the wire correctly
connect the wire correctly
N
Y
Y
Y
N
N
N

Figure 7-7
-54-
11. Electrical Data
11.1 Wiring Diagram
11.1.1 Outdoor unit
2. Dashed parts is optional for Low Ambient Temp. Cooling,and there is
no relay in only Cooling type
NOTE:
1. Dashed parts is not available for only Cooling type
single phase outdoor wiring diagram
3. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type
2. Dashed parts are not available for only Cooling type
NOTE:
1. Dashed parts is not available for Cooling capacity below 42000Btu/h
3-phase outdoor wiring diagram
11.1.2 Indoor unit
NOTE:
1. Dashed parts
are not availble in convertib le type
2. Dashes part is not avaliable below Cooling capacity 42000Btu type
3. Remote central controller
is optional
4. P16 and P17 are used for roo m card function
over 24000BTU/h convertible type wiring diagram
NOTE:
1. Parts
in dashed frame are not available for cassette type
unit
2. Central controller is optional
3. P16 and P17 are used for room card function
over 24000BTU/h cassette type wiring diagram
2. Dashed part is ont avaliable below Cooling capac ity 28000Btu type
over 24000BTU/h mid ESP duct type wiring diagram
Note:
1.Dashed parts are not available in duct type.
3.Remote central controller is optional.
4.P16 and P17 are used for room card function
W
Y R
High ESP duct type wiring diagram
Note:
1.Dashed parts are not available in duct type
2.Dashed part is fan speed controller kit.
3.Remote central controller is optional
4.P16 and P17 are used for room card function
W
Y R
Cabinet unit wiring diagram:
Wiring Diagram For 24000/42000BTU/h cabinet Unit
TERMINAL
BLOCK
TO OUTDOOR UNIT
Y/G
RBW
Y/G
R
B
W
T3.15A/250VAC
FUSE
TRANS.
PIPING
TEMP
CONTROLLER
CN3
CN12
CN11
CN8
DOOR
SWITCH
CN5
CN6
CN7
SWING MOTOR
FAN MOTOR
FAN MOTOR CAP.
CN1
N
S(N-W)
CN9
ROOM TEMP.
Loading...