Before disposing an old air conditioner that
goes out of use, please make sure it's
inoperative and safe. Unplug the air
conditioner in order to avoid the risk of child
entrapment.
It must be noticed that air conditioner system
contains refrigerants, which require specialized
waste disposal. The valuable materials
contained in a air conditioner can be recycled.
Contact your local waste disposal center for
proper disposal of an old air conditioner and
contact your local authority or your dealer if
you have any question. Please ensure that the
pipework of your air conditioner does not get
damaged prior to being picked up by the
relevant waste disposal center, and contribute
to environmental awareness by insisting on an
appropriate, anti-pollution method of disposal.
Consult your local authorities for the name and
address of the waste materials collecting centers
and waste paper disposal services nearest to your
house.
Safety Instructions and Warnings
Before starting the air conditioner, read the
information given in the User's Guide carefully.
The User's Guide contains very important
observations relating to the assembly, operation
and maintenance of the air conditioner.
The manufacturer does not accept responsibility
for any damages that may arise due to nonĀobservation of the following instruction.
Damaged air conditioners are not to be put
into operation. In case of doubt, consult your
supplier.
Disposal of the packaging of your new
air conditioner
All the packaging materials employed in the
package of your new air conditioner may be
disposed without any danger to the
environment.
The cardboard box may be broken or cut into
smaller pieces and given to a waste paper
disposal service. The wrapping bag made of
polyethylene and the polyethylene foam pads
contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a
waste collecting center and used again after
adequate recycling.
Use of the air conditioner is to be carried out
in strict compliance with the relative instructions
set forth in the User's Guide.
Installation shall be done by professional people,
don't install unit by yourself.
For the purpose of safety, the air conditioner
must be properly grounded in accordance with
specifications.
Always remember to unplug the air conditioner
before opening inlet grill. Never unplug your air
conditioner by pulling on the power cord. Always
grip plug firmly and pull straight out from the
outlet.
The air breaker should be all-pole switch. and
the distance between it's two connecters should
be no less than 3mm.
1
Cautions
All electrical repairs must be carried out by
qualified electricians. Inadequate repairs may
result in a major source of danger for the user
of the air conditoiner.
Do not damage any parts of the air conditioner
that carry refrigerant by piercing or perforating
the air conditioner's tubes with sharp or pointed
items, crushing or twisting any tubes, or
scraping the coatings off the surfaces. If the
refrigerant spurts out and gets into eyes, it may
result in serious eye injuries.
Do not obstruct or cover the ventilation grille
of the air conditioner. Do not put fingers or any
other things into the inlet/outlet and swing
louver.
Do not allow children to play with the air
conditioner. In no case should children be
allowed to sit on the outdoor unit.
3. If the fuse on PC board is broken, please change
it with the type T 3.15A/250VAC.
The air breaker should be all-pole switch. and the
distance between it's two contacts should no less than
3mm.
4. The wiring method should be in line with the local
standard.
5. The power cable and connecting cable are
selfprovided.
The requirement of the communication cable:
Model
AC142XCERA
AC182XCERA
power cable
H05RN-F 3G (1-2.5)mm
H05RN-F 3G (1-2.5)mm
Communication cable
(sheilded wire)
2
H05RN-F 2X(0.75-1.5)mm
2
H05RN-F 2X(0.75-1.5)mm
6. The waste battery shall be disposed properly .
2
2
Specifications
The refrigerating circuit is leak-proof.
The machine is adaptive in following
situation
1. Applicable ambient temperature range:
Rated Maximum Minimum
DB C
WB C
DB C
WB C
DB C
WB C
DB C
WB C
Cooling
Heating
Indoor
outdoor
Indoor
outdoor
2. If the supply cord is damaged, it must be replaced
by the service agent or a similar qualified person.
27 32 18
19 23 14
35 43 10
24 26 6
20 27 15
14.5 -- --
7 24 -15
6 18 --
7. Do not use this unit for any other purposes
except for the Cooling and the Heating,
Dehumidifying, and air-circulation of rooms
should be in ordinary dwellings.
8. If the air conditioner is used under higher
temperature condition than those listed, the builtĀin protection circuit may operate to prevent
internal circuit damage. Also, during Cooling
and Dry modes, if the unit is used under
conditions of lower temperature than those listed
above, the heat-exchanger may freeze, leading
to water leakage and other damage.
Safety Precautions
WARNING
If the power supply cord of this air conditioner is damaged, it must be replaced by
the manufacturer or its authorized service personnel only.
Use copper wire only. All the cables shall have got the Local authentication certificate.
the power supply connects from the outdoor side.
The power cable and connecting cable are self-provided.
If the fuse on PC board is broken please change it with the type of T3.15A/250VAC.
DANGER
Do not attempt to install this air conditioner by yourself.
This unit contains no user-serviceable parts. Always consult authorized service personnel for repairs.
When moving, consult authorized service personnel for disconnection and installation of the unit.
Do not become excessively chilled by staying for lengthy periods in the direct cooling airflow.
Do not insert fingers or objects into the outlet port or intake grills.
Do not start and stop air conditioner operation by connecting and disconnecting the power supply cord and so on.
Take care not to damage the power supply cord.
In the event of a malfunction (burning smell, etc.), stop operation immediately, turn of f the circuit breaker ,
and consult authorized service personnel.
CAUTION
Provide occasional ventilation during use.
Do not direct air flow at fireplaces or heating apparatuses.
Do not climb on place objects on the air conditioner.
Do not hang objects from the indoor unit.
Do not set flower vases or water containers on top of the air conditioner.
Do not expose the air conditioner directly to water.
Do not operate the air conditioner with wet hands.
Do not pull power supply cord.
Turn off power source when not using the unit for extended periods.
Check the condition of the installation stand for damage.
Do not place animals or plants in the direct path of the air flow.
Do not drink the water drained from the air conditioner.
Do not use in applications involving the storage of foods, plants or animals, precision equipment, or art works.
Do not apply any heavy pressure to radiator fins.
Operate only with air filters installed.
Do not block or cover the intake grill and outlet port.
Ensure that any electronic equipment is at least one metre away from either the indoor or outdoor unit.
Avoid installing the air conditioner near a fireplace or other heating apparatuses.
When installing the indoor and outdoor unit, take precautions to prevent access to infants.
Do not use inflammable gases near the air conditioner.
Name of Parts
1110
Fig.1
1 Operating Control Panel (Fig.2)
2 Emergency switch
3 Remote Control Signal Receiver
4 Power Indicator Lamp (Red)
5 OPERATION Indicator Lamp (Green)
6 TIMER Indicator Lamp (Yellow)
7 Compressor Run Lamp (Green)
8 Intake Grill
9 Air Filter
10 UP/DOWN Air Direction Flaps
11 RIGHT/LEFT Air Direction Louvers
(behind UP/DOWN Air Direction Flaps)
1
POWER
OPER
TIMER
3
COMP
EMER
9
Fig.2
4
5
6
7
2
3
8
NOTE
For the wired control type unit, the unit state should be checked by the the wired
controller, instead of the remote receiver; and if you set the TIMER function, the
TIMER LED on the remote receiver will not be on.
4
Cleaning and Care
CAUTION
Before cleaning the air conditioner ,be sure to turn it off and disconnect
the Power Supply Cord.
Be sure the Intake Grill is installed securely.
When removing and replacing the air filters, be sure not to touch the heat
exchanger, as personal injury may result.
Cleaning the Air Filter
Open the Intake Grill
1. Pull out both sides and the center of the
Intake Grill.
About 30 mm
Arm
Intake Grill
Side Panel
Hook
Notch
Arm
4. Re-attach the Air Filters to the Intake Grill.
The Filters fit onto the inside of the intake
1
Grill. (figure 1)
2
The bottom edges of the Air Filters should
fit into the filter brackets. (figure 1)
The Air Filters should be pushed down so
3
that their top edges fit under the projections
at the top of the Intake Grill. (figure 2)
Air Filter
(Figure 1)
Filter bracket
(Figure 2)
2. Pull the Air Filters upward to remove
them.
Push the Air Filter handles away from the
Intake Grille in direction as illustrated, then
pull out Air Filters.
Air Filter
Bracket
Base
Handle
3. Clean the Air Filters.
Remove the dust from the Air Filters by
vacuum cleaner or washing them. After
washing, allow the Air Filters to dry
thoroughly in an area protected from sunlight.
5. Push in both sides and the center of the
Intake Grill.
Dust can be cleaned from the Air Filter either
with a vacuum cleaner, or by washing
the filter in a solution of mild detergent and
warm water. If you wash the filter, be sure to
allow it to dry thoroughly in a shady place
before reinstalling.
If dirt is allowed to accumulate on the Air Filter,
air flow will be reduced, lowering operating
efficiency and increasing noise.
During periods of normal use, the Air Filters
should be cleaned every two weeks.
5
Operation Tips
Operation and Performance
*Heating Performance
This air conditioner operates on the heat-pump
principle, absorbing heat from outdoor air and
transferring that heat indoors. As a result, the
operating performance is reduced as outdoor air
temperature drops. If you feel that insufficient
heating perfomance is being produced, we
recommend you use this air conditioner in
conjunction with another kind of heating
appliance.
Heat-pump air conditioners heat your entire room
by recirculating air throughout the room, with the
result that some time may be required after first
starting the air conditioner until the room is heated.
Instructions relating to heating (*) are applicable
only to "HEAT & COOL TYPE".
*Microcomputer-controlled Automatic Defrosting
When using the Heating mode under conditions of
low outdoor air temperature high humidity, frost
may form on the outdoor unit, resulting in reduced
operating performance.
In order to prevent this kind of reduced
performance, this unit is equipped with a
Microcomputer-controlled Automatic Defrosting
function. If frost forms, the air conditioner will
temporarily stop, and the defrosting circuit will
operate briefly (for about 7 to 15 minutes).
STANDARD PARTS
The following installation parts are furnished. Use
them as required.
Optional parts
MarkParts name
A
B
C
D
E
F
G
Adhesive tape
Saddle (L.S) with screws
Drain hose
Heat insulation material
Piping hole cover
Putty
Plastic clamp
6
Installation
Please ask the dealer or specialist to install, never try by the users themselves. After the installation please
be sure of the following conditions.
WARNING !
Please call dealer to install the air-conditioner.
Incorrect installation may cause water leaking, shock and fire hazard.
CAUTION !
Air-conditioner can't be installed in the
envi-ronment with inflammable gases
because the inflammable gases near to airĀconditioner may cause fire hazard.
Installed electrical-leaking circuit breaker.
It easily cause electrical shock without circuit
breaker.
[Location]
Air-conditioner should be located in well-vented
and easily-accessible place.
Air-conditioner should not be located in the
following places:
(a) Places with machine oils or other oil vapours.
(b) Seaside with high salt content in the air.
(c) Near to hot spring with high content of sulfide
gases.
(d) Area with frequent fluctuation of voltage e.g.
factory, etc.
(e) In vehicles or ships.
(f) Kitchen with heavy oil vapour or humidity.
(g) Near to the machine emitting electric-magnetic
waves.
(h) Places with acid, alkali vapuor.
TV, radio, acoustic appliances etc are at least 1 m
far away to the indoor unit, outdoor unit, power.
Connect earthing wire.
Earthing wire should not be conĀnected to the gas pipe, water pipe,
lightning rod or phone line, in-correct
earthing may cause shock.
Earthing
Use discharge pipe correctly to ensure
efficient discharge.
Incorrect pipe use may cause water leaking.
supply wire, connecting wire, pipes, otherwise
images may be disturbed or noises be created.
As required, take measures against heavy snow.
[Wiring]
Air-conditioner should be equipped with special
power supply wire.
[Operating noise]
Choose the following locations:
(a) Capable of supporting air-conditioner weight,
don't increase operating noise and vibration.
(b) Hot vapour from outdoor unit outlet and
operating noise don't disturb neighbour.
No obstacles around the outdoor unit outlet.
7
Installation Procedures
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of
the indoor and outdoor units and install positively
so that the units will not topple or fall
CAUTION
(1)Do not install where there is the danger of comĀ bustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach
the unit, take preventive measures so that they
cannot reach the unit.
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1) Install the indoor unit level on a strong wall, floor,
ceiling which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed:
the air should be able to blow all over the room.
(3) Install the unit near an electric outlet or special
branch circuit.
(4) Do not install the unit where it will be exposed to
direct sunlight.
(5) Install the unit where connection to the outdoor
unit is easy.
(6) Install the unit where the drain pipe can be easily
installed.
(7) Take servicing, etc. into consideration and leave the
spaces shown in Fig.A. Also install the unit where
the filter can be removed.
Floor console
Fig.A
Left
30 cm
or more
Under ceiling
Left
30 cm
or more
may be difference
1.5m
Indoor unit
Ceiling
1.5m
1.5m
Right
30 cm
or more
Right
2 cm
or more
Indoor unit
8
Installation Procedures
PREPARING INDOOR UNIT INSTALLATION
REMOVE THE INTAKE GRILL
Open the intake grill and remove the three or four or six screws.(Fig. 1)
Fig. 1
Remark:
The main unit can be wired before the indoor
unit is installed. Select the most appropriate
Intake grill
installation order.
A. FLOOR CONSOLE TYPE
1. DRILLING FOR PIPING
Select piping and drain directions.(Fig.2)
The piping and drain can be made in three
directions as shown below.
(Fig.2)
rear
right
down
The drain hose can be connected to either the
left or right side.(Fig.3)
(Fig. 3)
When the directions are selected, drill a 7 cm dia.
hole on the wall so that the hole is tilted downward
toward the outdoor for smooth water flow. When
the pipe is led out from the rear, make a hole in
Fig.4, at the position shown.
(Fig.4)
Wall
6mm
7cm
Indoor unitoutdoor unit
When installing set to wall, install the accessory wall
bracket at the position shown in Fig.5,and mount the
set to it.
(Fig. 5)
65.5cm
53cm
4.5cm
99cm
50cm
6.5cm
3.5cm hole
24.5cm
Wall bracket
Side of set
7cm hole
6.5cm
Drain hose (Left side)Drain hose (Right side)
12.5cm10cm
9
Installation Procedures
2. INSTALLING DRAIN HOSE
Select whether the drain hose will be connected
to the left or right side.(Fig.3) Insert the drain
Wrap the insulation (drain hose) around the drain
hose connection. (Fig.7)
hose into the drain pan, then secure the drain
hose with a nylon fastener. (Fig.6)
(Fig. 6)
Drain pan
(Fig. 7)
Drain pan
Nylon fastener
Insulation
Drain hose
Drain hose
(Drain hose)
Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port
of the indoor unit.
Fig. 8
Arrange the drain hose
lower than this portion.
OKNONO
Drain hose
Do not install the unit drain hose side is too high. Height A should be less than 5 mm.(Fig.9)
Fig. 9
B. UNDER CEILING TYPE
Using the installation template, drill holes for
piping and anchor bolts(for holes).(Fig.10)
Drain hose
AA
Fig. 10
CAUTION
200mm
10
900mm
Installation
template
Drilling position
for piping
Drilling position
for anchor bolt
Ceilling
Wall
Installation Procedures
1. DRILLING FOR PIPING
Select piping and drain directions.
(Fig.11)
Rear (Install the drain
hose in the direction.)
Right
Fig. 11
CAUTION
Install the drain hose at the rear; it should not
be installed on the top or right side.
When the directions are selected, drill 80mm and
50mm or 150mm dia. hole on the wall so that the
hole is tilted downward toward the outdoor for
smooth water flow.
Fig. 12
Wall
6mm
3. INSTALLING BRACKETS
Install the brackets with nuts, washers and spring
washers.(Fig. 15)
Fig. 15
Spring washer
Special nut
Bracket (Left)
4. INSTALLING INDOOR UNIT
Bracket (Right)
Bracket
Reset the hex bolts as shown in Fig.16.
Fig. 16
Hex bolt
2. DRILLING HOLES FOR ANCHOR BOLTS AND
INST ALLING THE ANCHOR BOLTS
With a concrete drill, drill four 12.7 mm dia. Holes.
(Fig.13)
Fig. 13
60 to 70mm
12.7mm
Insert the anchor bolts into the drilled holes, and drive
the pins completely into the anchor bolts with a hammer.
(Fig. 14)
Fig. 14
11
Indoor unit
8 to 13mm
Apply the indoor unit to the brackets.(Fig.17)
Fig. 17
Bolt
Indoor unit
Bracket
Now, securely tighten the hex bolts in both sides.
Installation Procedures
5. INSTALL THE DRAIN HOSE
Select whether the drain hose will be connected to
the left or right side.(Fig.3)
Insert the drain hose into the drain pan, then secure
the drain hose with a nylon fastener.(Fig.6)
Wrap the insulation (drain hose)around the drain
hose connection.(Fig.7)
Be sure to arrange the drain hose correctly so that
it is leveled lower than the drain hose connecting
port of the indoor unit.(Fig.18)
Fig. 18
Remove the hole cover.
Arrange the drain hose
lower than this portion
OK
Drain hose
OUTDOOR UNIT INSTALLATION
CONNECTING THE PIPING
1. FLARE PROCESSING
(1) Cut the connection pipe with pipe cutters so
that the pipe is not deformed.
(2) Holding the pipe downward so that cuttings
cannot enter the pipe, remove the burrs.
(3) Remove the flare nut from the indoor unit pipe
and outdoor unit and insert the flare nut onto the
pipe, and flare with a flaring tool.
2. BENDING PIPES
The pipes are shaped by your hands. Be careful
not to collapse them.
Fig. 21
NO
Fig. 19
VT wire hole
Pass the drain hose through here
VT wire
Drain hose
Piping hole
Base (Bottom)
Cut the grill
Intake grill
12
OK
Extend the pipe by unwinding it
NO
Installation Procedures
3. PIPING CONNECTION
AC142XCERA
AC182XCERA
Flare connection
Indoor
Unit
Gas pipe
Liquid
pipe
Flare connection
A(adaptor, from 9.52 to 12.7)
To gas pipe
(1) Dimension of connecting pipe
AC142XCERA
AC182XCERA
Fit the nut on and fasten
(2) The maximum length and drop height of connecting pipe
Please refer to the installation manual of outdoor unit
To ensure the efficiency , Pipes shall be as short as possible.
Gas pipe
Liquid pipe
3-way valve
A
Outdoor
unit
2-way valve
To outdoor unit
12.7mm
6.35mm
90 0.5
Spanner
O
Joint
Cautions for piping connection
Do not twist or deform the connecting pipe.
Do not mix dusts.
The bending radius shall be as large as possible.
Both gas pipe and liquid pipe shall be heat insulation.
No leakage in the flare.
(3) Piping connection
Connecting method
Smear refrigerant oil on the joints of piping and flare.
The bending radius shall be as large as possible.
Align the pipe center when fastening, and tighten the
nut, as shown in the figure.
Pay attention to not mix foreign matters such as sands
in.
13
Spanner
Diameter of Pipe
Liquid Pipe 6.35mm
Gas Pipe 12.7mm
Nut
Tighten Torque
(N. m)
11.8
49.0
If not aligned ,tighten the nut by force will
damage the nut that result in gas leakage
Installation Procedures
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)(Fig.24A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the
exposed solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal
screw using a screw driver.
B. For strand wiring(Fig.24B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the
exposed strand wiring.
(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 24
Wire
A. Solid wire
Strip 25mm
Insulation
Screw with
special washer
Round
terminal
Terminal
board
Loop
B. Strand wire
Round
terminal
Strip 10mm
Screw with
special washer
Round
terminal
Wire
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT
THE CORD CLAMP
After passing the connection cord and power cable through the insulation tube, fasten it with the cord
clamp, as shown in Fig.25
Fig. 25
Insulation tube
Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
14
Installation Procedures
ELECTRICAL WIRING
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection
cord with the cord clamp.(If the insulator is chafed,
electric leakage may occur.)
(4) Always connect the ground wire.
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
(2) Pull out the electric component box.
Fig.28
Electric component box
(3) Remove the electric component box cover.
Fig. 29
Base
Electric component box cover
Remove the three tapping screws.
Fig. 26
Electric component box
Fig. 27
Electric component box
Remove the four tapping
screws.
CAUTION
Do not remove the screws. If the screws
are removed, the electric component box
will fall.
CAUTION
Be careful not to pinch the lead wires between the
electric component box and base.
(4) Wiring
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the
dimensions shown in Fig.34.
(3) Connect the end of the connection cord fully into the
terminal block.
(4) Fasten the connection cord with a cord clamp.
(5) Fasten the end of the connection cord with the
screw.
15
Installation Procedures
(5). Wiring of indoor unit
The distance between the signal wires and the power cabes should be at least 50mm.
To other
indoor unit
P
1(L) 2(N)2(N)1(L)
Q
BA
C
Communication cable (Shield wire):
H05RN-F 2X (0.75-1.5)mm
2
Power cable : H05RN-F 3G (1-2.5)mm
WARNING
2
P
L N
To outdoor unit
AB
Q
To wired controller
(In case of using wired
controller)
C1 C2
(P) (Q)
C
1.Incorrect address setting will cause abnormal to the system.
2.Communication cable must be use sheilded type.
3.Communication cable and power cable must be use ring terminal type.
16
Installation Procedures
(6). Indoor unit communication addresses setting
CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK.
1.There are two methods to set the communication address
A. Use the remote controller(default status in first installation).
B. Use dip switches on the indoor unit PCB.
2. Address setting procedure when using the remote controller.
A. Set the addresses only after the successful installation of the refrigerant pipes and connecting cables,
and open all the stop valves;
B. Please confirm that the indoor units and the outdoor unit in the same system use the same power source;
C. Power on the units, but put all the indoor units in the status of STANDBY;
D. Please note that the address must be set as following:
Indoor unit that connect to valve A, the address must be 1;
Indoor unit that connect to valve B, the address must be 2;
Indoor unit that connect to valve C, the address must be 3;
Indoor unit that connect to valve D, the address must be 4;
the LED board is blank.
E. Example: set unit A to address 1.
Continuously press the emergency switch for about 15 seconds, the buzzer will sound 4 times(PI PI PI PI) and
then leave go of the switch. At this time, the indoor unit has entered the address setting procedure. But F. Use the
controller to turn on the indoor unit. At this time, the controller should be changed from OFF to ON, and then
theTIMER LED flshes once. That is to say, the address setting is enabled.
G. Press the button"SLEEP " on the controller , the times you press it stands for the address you want to set, detailed
as following:
Press button " SLEEP " once, the address is "1 ", and the TIMER LED flashes once;
Press button " SLEEP " twice, the address is " 2 ", and theTIMER LED flashes twice;
Press button " SLEEP " three times, the address is " 3 ", and the TIMER LED flashes three times;
Press button " SLEEP " four times, the address is " 4 ", and the TIMER LED flashes four times;
H. Use the remote controller to turn off the unit, At this time, the controller should be changed from ON to OFF,
and the unit will exit the address setting procedure, the address will be memorized. The LED board will always
display the address of this indoor unit until the system be powered off.
I. If you want to change the address, please repeat the above steps from E to G.
J. After setting all the addresses, please power off the system and then power on again. Otherwise the system will
not start to work.
K. Once the addresses are successfully set, please do not change it any more to avoid confusion.
3. Address setting procedure when using the DIP switches SW01 and SW03.
A. The DIP switches SW01 and SW03 are on the indoor unit PCB.
B. Before carrying out the address setting work, the system must be powered off.
C. Take off the front panal and the filters, then take off the flaps and also the front cover,disconnect the
swing motor connectors from the PCB and then take out the lower part of the PCB.
D. Change the position of DIP 7 of SW01 from OFF to ON, if fail to do this, the addresses set by SW03
will not work.
E. Use SW03 to set the addresses as following (DO NOT CHANGE OTHER DIP SWITCHES):
17
Installation Procedures
SW01
1 2 3 4 5 6 7 8
ON
OFF
4. How to check the addresses?
When finish all the above works, please power off and power on again to the whole system but set all
the indoor units in STANDBY. Then continously press the emergency switch until you hear the buzzer
sound 5 times(Pi Pi Pi Pi Pi), and then the TIMER LED board will show the address of this indoor unit.
Press any key on the remote controller, it will exit the address checking precedure.
SW03INDOOR
1 2 3 4 5 6 7 8
ON
OFF
1 2 3 4 5 6 7 8
ON
OFF
1 2 3 4 5 6 7 8
ON
OFF
1 2 3 4 5 6 7 8
ON
OFF
UNIT ADDRESS
1
2
3
4
(7).Setting method of temperature compensation (For heating function only)
Set method of temperature compensation(-8 oC~6 oC) in heating mode with the remote controller.
In 24 oC heating mode,press sleep 7 times continuously.Indoor buzzer sounds 2 times,that show temp.compensatoin
works.Swith on the unit in heating mode by the remote controller,press the time button to set the set
temp.compensatoin.so the set temp. compensation=the current set temp.-24 oC.For example,if the set temp.
is 24 oC,the temp.compensation is 0 oC;if the set temp.is 25 oC,the temp. compensation is 1 oC;if the set temp.is
30 oC,the temp. compensation is 6 oC;if the settemp.is 23 oC,the temp. compensation is -1 oC;if the set temp.is
16 oC,the temp. compensation is -8 oC;If setting is finished, press ON/OFF button, then the unit quits the
temp. compensation.
18
Installation Procedures
ELECTRICAL WIRING
WARNING
(1) Always use a special branch circuit and install a special
receptacle to supply power to the room air conditioner.
(2) Use a circuit breaker and receptacle matched to
the capacity of the room air conditioner.
(3) The circuit breaker is installed in the permanent wiring.
Always use a circuit that can trip all the poles of the
wiring and has an isolation distance of at least 3mm
between the contacts of each pole.
(4) Perform wiring work in accordance with standards so
that the room air conditioner can be operated safely
and positively.
(5) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company
standards.
CAUTION
(1) The power source capacity must be the sum of the
room air conditioner current and the current of other
electrical appliances. When the current contracted
capacity is insufficient, change the contracted
capacity.
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during
operation?
(2) Will noise, wind, or drain water from the unit disturb
the neighbors?
(3) Is there any gas leakage?
CUSTOMER GUIDANCE
Explain the following to the customer in accordance
with the operating manual:
(1) Starting and stopping method, operation switching,
temperature adjustment, timer, air flow switching,
and other remote control unit operations.
(2) Air filter removal and cleaning, and how to use
air louvers.
(3) Give the operating and installation manuals to
the customer.
MOUNT THE COVER PLATE AND
THE INTAKE GRILL
1.Mount the cover plate. (Right)
(1) Cut a pipe exit hole in the right plate. This is
only when the pipe exits from the right side.
(This operation is not required when the
protrusion is on the top or rear.)
Fig. 31
Cover plate (Right)
(2) When the voltage is too low and the air conditioner
is difficult to start, contact the power company the
voltage raised.
TEST RUNNING
1. CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control
unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(2) Join the cover plates (right) and mount with screws.
Fig. 32
19
Installation Procedures
2. Mount the cover plate.(Left)
(1) Join the cover plate (left) and mount with screws.
Fig. 33
3. Mount the intake grill.
(1) Cut the right side of the intake grill. This is only when the pipe exits from the right side
Fig. 34
(2) Insert the hinges on the bottom of the intake grill into the holes in the base assembly. Then mount the arms to
the three areas on the top of the intake grill.
Fig. 35
20
Trouble Shooting
Followings are not problems
Sound of water flowing is
not a problem.
Sound of cracking is heard.
Smell are generated.
During operation, white fog or steam
comes out from the indoor unit.
In cooling operation, unit switches to
blowing operation.
Unit will not restart after stop.
Won't start?
During unit operation or at stop, a swishing or
gurgling noise may be heard. This noise is generated
by refrigerant flowing in the system.
During unit operation, a cracking noise may be heard.
This noise is generated by the casing expanding or
shrinking because of temperature changes.
This is because the system circulates smells from the
interior air such as the smell of cigarettes or the
painting on the furniture.
When unit is running at places like restaurant, etc. where
dense edible oil fumes always exist, this will happen.
To prevent frost from accumulating on indoor heat
exchanger, unit will switch to blowing operation for a
while then resume cooling operation.
Though ON/OFF button is set
to ON, unit won't resume cooling,
dry or heating operation
in 3 min after it is stopped, this
is because of 3-min-delay
protection circuit.
Please wait 3 minutes
No outlet air or fan speed can't be changed
in dry mode.
In heating operation, water or steam are
blown out of outdoor unit.
In heating operation, indoor fan won't stop
even if unit is stopped.
Unit will reduce fan speed repeatedly and automatically
if room temp. is too low in dry operation.
This occurs when frost accumulated on the outdoor
unit is removed.
(during defrosting operation)
After unit stop, indoor fan will go on running
until indoor unit cools down.
21
Trouble Shooting
Before ask for services, please first check your unit against the following.
Air conditioner won't start.
Is power supply switch
turned on?
Power supply
switch is not
set at ON.
Are operation control
adjusted correctly
as specified?
Proper
temp
Are horizontal louvers at
up position (in heating
mode)?
Is city power supply normal?Is leakage current breaker
activated?
Power
failure?
This is very dangerous, please
disconnect power supply
immediately and contact your
dealer.
Poor cooling or heating
Is air filter too dirty?
Any doors or windows left
open?
Are there any obstacles in inlet
or outlet grill?
Poor cooling
Is there any direct sunlight
in the room?
Cold air blows out
(in heating mode)
Is air conditioner in standby
condition in heating mode?
If there are unexpected heat
sources in the room?
If your unit still can't work properly after above mentioned
checks, or following problems occur, please stop it immediately
and contact your dealer.
Fuses or circuit breakers often blow out.
W ater comes out in cooling/dry operation.
Operation is abnormal or sound is heard.
Too many people in the room?
22
Trouble Shooting
FAILURE CODE
TROUBLE SHOOTING
Faulty temperature sensor Tai
Faulty temperature sensor Tc1
Faulty temperature sensor Tc2
Faulty temperature sensor Tm4 TIMES
Faulty EEPROM on indoor
unit PCB
Abnormal communication
between indoor and outdoor unit
(TIMER LED OF INDOOR
RECEIVER BOARD FLASHES
TIMES)
ONCE
TWICE
3 TIMES
5 TIMESFaulty indoor unit PCB
6 TIMES
POSSIBLE REASONS
*
*
*
*
*
Sensor disconnected, or broken, or at wrong
position, or short circuit
Sensor disconnected, or broken, or at wrong
position, or short circuit
Sensor disconnected, or broken, or at wrong
position, or short circuit
Sensor disconnected, or broken, or at wrong
position, or short circuit
Wrong connection, or the wires be disconnected,
or wrong address setting of indoor units, or faulty
power supply or faulty PCB
Abnormal communication
between wired controller and
7 TIMES
Wrong connection, or use the wired controllerbe
disconnected, faulty PCB
*
indoor unit PCB
Pump motor disconnected, or at wrong
Drainage system abnormal
Indoor unit address repeated
Abnormal communication
between chip TMP/807 and
chip TMP/846
Malfunction on outdoor unit20 TIMESCheck the outdoor unit failure code
8 TIMES
9 TIMES
14 TIMESFaulty indoor unit PCB
*
*
position, or the float switch broken down
or the float switch disconnected,or at
wrong position
Wrong setting of indoor unit address
Note:
1. Please contact the installers or distributors when trouble happens to repair it.
2. Turn the power off and power on again, if the failure code recurs, please inform the franchiser.
3. Failrue codes maked with are resumable.
23
HAIER GROUP
Qingdao Haier Air Conditioner Electric Co., Ltd.
Address: Haier Garden, Qianwangang Road, Economic Development Zone,
Qingdao, Shandong 266500, P.R.China
Web Site: http://www.haier.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.