Haier AU122AEERA, AB122ACERA, AC122ACERA, AD122ALERA Service Manual

Commercial Air Conditioning
SERVICE MANUAL
Models
Features
High energy efficiency
Infrared control type or wired control type Low ambient cooling kit (optional) and low ambient heating kit (optional)New friendly refrigerant R410a, environment protectionAdvanced technology, DC inverter control function Weekly timer (standard) Group control function Auto restart function Room card function
AB122ACERA
AC122ACERA
AD122ALERA
AU122AEERA
Can be connected with the universal outdoor unit AU122AEERA
Manual code: SYJS-020-07REV.0 Edition: 2007-05-15
2
CONTENTS
Contents………………………………………………………...2
1. Description of products & features………………………..3
2. Specification…………………………………………………7
Commercial Air Conditioner Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
3. Safety precaution…………………………………………..10
4. Net dimension………………………………………………12
5. Installation instructions………..…………………………...14
6. Parts and functions…………………………………………30
7. Controller functions…………………………………………32
8. Refrigerant circuit…………………………………………...33
9. Electrical control functions…………………………………34
10. Electrical data………………………………………………49
11. Troubleshooting …………….....………………………….57
12. Noise level.....................................................................61
Commercial Air Conditioner
3
1.1. Products code explanation
Climate type: T1 (see table 1)
Design number (R stands for design sequence, DC inverter
frequency type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407C
E stands for heat pump type, refrigerant is R410a
Q stands for cool only type, refrigerant is R410A
Outlook appearance
Product series: A stands for 1 to 1
Applicable voltage: 2 stands for 220~230V/50Hz,
4 stands for 220V/60HzN stand for 380~400VAC/50Hz
Product type : “B” stands for cassette type, “C” stands for
convertible type, ”D” stands for duct, “S” stands for wall
mounted type, ”Q” stands for chiller system, "E" stands for
ceiling concealed type, “U” stands for outdoor unit
Air Conditioner
1.2 Brief Introduction for T1T2T3 working condition
1.3 Operating Range of Air Conditioners
Temp. Mode Rated Maximum Minimum
DB
27 32 15
Indoor
WB
19 23 14
DB
35 43 -5
Cooling
Outdoor
WB
24 26 6
DB
20 27 10
Indoor
WB
14.5 --- --
DB
7 23 -10
Heating
Outdoor
WB
6 18 ---
Climate type
Type of Air
Conditioner
T1 T2 T3
Cooling Only
18 ~43 10~35 21~52
Heat pump
-7~43 -7~35 -7~52
Electricity Heating
~43 ~35 ~52
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
1.DESCRIPTION OF PRODUCTS & FEATURES
A C 12 2 A C E R A
Cooling / Heating capacity, 12=12000BTU/h
Commercial Air Conditioner
4
1.4 Product features
Adopt the much friendlier refrigerant R410a
The air conditioner system adopts the greatly friendly refrigerant R410a, which is protective for the
ozone layer and is good to avoid the earth getting warmer. Benefit for the environment.
Adopt the advanced DC inverter technology
The system adopts the advanced DC inverter technology, which can consume less power energy to
realize the equal efficiency, saving money for you.
Smart newly designed infrared remote controller
Auto–restart function (optional)
All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will
automatically recover the previous running mode once the power supply is on.
Low temperature cooling realized, super low temperature heating
realized.
Low ambient cooling kit (optional)
Group control function (with a group controller YR-E12)
Central control function, if connected with a central controller
YCZ-A001
Weekly timing function, if connected with a weekly timer YCS-A001
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
The cassette and convertible unit can be controlled by the infrared remote controller YR-H71, the remote
controller can be fixed with a remote controller holder.
Long-life& high efficiency air purify filter
Commercial Air Conditioner
5
1.5 New friendly refrigerant R410A introduction:
R410A
The working pressure of R410A is approximately 1.6 times higher than R22. Because the oil in the
refrigerant is different, please do not mix them.
Refrigerant R22 (single) R410A (mixed) R407C (mixed)
Oil Mineral oil (SONTEX 200LT) Synthetic oil (POE oil) Synthetic oil (POE oil)
Pressure ratio 1 Approx. 1.6 Approx. 1.1
Operation flow
1. Calculate the refrigerant additional charging amount, and charge a suitable amount.
1. Air purging by refrigerant is prohibited seriously
2. Use a special vacuum pump with reverse check mechanism
1. Charge the nitrogen to the set pressure
2. 24 hours later,check if the pressure in the pipe has reduced
1. Do not connect the power supply
1. Use piping material of the specified thickness
2. Do not use dirty pipe
3. Always flow nitrogen during welding work
hand over
trial running and adjustment
maintenance panel installation
gas leakage check
additional refrigerant charging
evacuation and drying
leakage test
refrigerant piping connection
outdoor unit installation
outdoor unit foundation work
electric wiring work
remote controller installation
insulation work
duct work
drain piping work
refrigerant piping work
indoor unit installation
operation chart preparation
1. Always inspect the used refrigerant
2. Always use the specified refrigerant
refrigerant inspection
prepare work schedule
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Commercial Air Conditioner
6
Piping material
1. Use the correct refrigerant piping and materials for R410A
2. For the pipe wall thickness, see the table below:
Pipe diameter Φ6.35 Φ9.52 Φ12.7 Φ15.88 Φ19.1
Pipe wall thickness 0.8 0.8 0.8 1.0 1.2
Note: Always observe and comply with the local regulations when installing the refrigerant piping.
Tools
R410A work requires a number of special tools (* symbol). Since the tools used in R22 work
cannot be used for R410A, provide the tools separately.
Tool name Process and application
Pipe cutter Piping cutting
*Flaring tool Pipe flaring work
*Torque wrench Flare nut connection
Expander Expansion at pipe connection
Pipe bender Pipe bending work
Refrigerant piping work
Nitrogen gas Pipe oxidation prevention
Welder Pipe brazing
Air tightness test
*Gauge manifold
*Charging hose
Vacuum evacuation and refrigerant
charging operation check
Air tightness test
Refrigerant additional
charging
*Vacuum pump (with
adapter)
Vacuum drying
Electronic scale
Gas leakage detector Gas leakage test
Refrigerant additional
charging
Work precautions
Refrigerant check: Before work, check the used refrigerant and prepare materials matched to the
refrigerant.
Refrigerant piping: Observe the basics of refrigerant piping to avoid the unnecessary problems. In
addition, when performing the welding work, seal in the nitrogen gas to the pipes, and prevent it
from the oxidation.
Leak pressure detection: Perform seal detection and make sure there is no refrigerant leakage.
Vacuum drying: If the vacuum pump has not the reverse flow check mechanism, use the pump
together with a reverse flow check adapter.
Additional refrigerant: Charge a suitable amount of refrigerant with a special R410A gauge
manifold and charging hose.
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Commercial Air Conditioner
2. SPECIFICATION
Function
coolin
g
heatin
g
Capacity kW 3.52(0.9--4.4) 4.4(1.0---4.8) Sensible heat ratio 0.71
W 1250(280---1650) 1210(280--1650) W 1650 1650
EER or COP
W/W
2.81C 3.64A
Dehumidifying capacity
10³×m³/h
Power cable Power source N, V, Hz
A / A 6.0(1.4--8.0)A/8A 6.0(1.4--8.0)A/8A Start Current A 3 3 Circuit breaker A 13 13
Unit model (color)
Type × Number Speed(H-M-L) r/min Fan motor output power kW Air-flow(H-M-L) m³/h Type / Diameter mm Total Area m² Temp. scope
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm Control type (Remote /wired) Fresh air hole dimension mm
dB(A)
kg / kg
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
kg / kg
Function cooling heating Capacity kW 4.1(0.9--4.6) 4.4(1.0---5.1) Sensible heat ratio 0.71
W 1270(280---1650) 1210(280--1650) W 1650 1650
EER or COP
W/W
3.23A 3.64A
Dehumidifying capacity
10³×m³/h
Power cable Power source N, V, Hz
A / A 6.0(1.4--8.0)A/8A 6.0(1.4--8.0)A/8A Start Current A 3 3 Circuit breaker A 13 13
Unit model (color)
Type × Number Speed(H-M-L) r/min Fan motor output power kW Air-flow(H-M-L) m³/h Type / Diameter mm Total Area m² Temp. scope
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm Control type (Remote /wired)
dB(A)
kg / kg
item Mod
e
AB122ACERA
Total power input Max. power input
ENERGY CLASS
1.5
3×2.5
1, 220--230, 50
1.6
Running
Indoor unit
AB122ACERA(BLACK)
Fan
Centrifugal fan*1
795/690/550±50
0.065
700/620/520
Heat exchanger
inner grooved pipe/φ7
0.272 2-7
Dimension
570×570×260mm
718×680×380mm
Noise level (H-M-L)
45/40/32
PVC 26/32
Remote
95
Weight (Net / Shipping)
18.5/23
Panel
Dimension
700×700×60mm
740×750×115mm
Weight (Net / Shipping)
3.5/4.5
Item Model AC122ACERA
Total power input Max. power input
1.6
3×2.5
1, 220--230, 50
Running
Indoor unit
AC122ACERA(WHITE)
Fan
Centrifugal fan*2
1200/1080/880
0.09
750/650/550
Heat exchanger
inner grooved pipe/φ7
0.20 2-7
Dimension
1090×655×199 1150×750×300
PVC 18/20
Remote Noise level (H-M-L) 46/44/42 Weight (Net / Shipping) 28.3/34.3
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
7
Commercial Air Conditioner
8
Function cooling heating Capacity kW 3.8(0.9--4.4) 4.1(1.0---4.8) Sensible heat ratio 0.71
W 1260(280--1650) 1260(280--1650) W 1650 1650
EER or COP
W/W
3.02B 3.25C
Dehumidifying capacity
10³×m³/h
Power cable Power source N, V, Hz
A / A 6.0(1.4--8.0)A/8A 6.0(1.4--8.0)A/8A Start Current A 3 3 Circuit breaker A 13 13
Unit model (color)
Type × Number Speed(H-M-L) r/min Fan motor output power kW Air-flow(H-M-L) m³/h Type / Diameter mm Total Area m² Temp. scope
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm Control type (Remote /wired)
dB(A)
kg / kg
Power cable Power source N, V, Hz Start Current A
Unit model (color)
Model / Manufacture Type Type × Number Speed r/min Fan motor output power kW Air-flow(H-M-L) m³/h Type / Diameter mm Total area m² Temp. scope
External
L×W×H
mm×mm×mm
Package
L×W×H
mm×mm×mm
Refrigerant control method mm/mm
Noise level dB(A)
material of reduce noise crankcase heater power W
kg / kg Type / Charge g Recharge quantity g/m Liquid mm Gas mm
Connecting Method
m m
Item Model AD122ALERA
Total power input Max. power input
1.6
3×2.5
1, 220--230, 50
Running
Indoor unit
AD122ALERA(GREY)
Fan
Centrifugal fan*1
1000/900/800±50
0.05
550/450/400
Heat exchanger
inner grooved pipe/φ7
0.11 2-7
Dimension
610×483×220 695×536×265
20/18
wired Noise level (H-M-L) 35/32/30 Weight (Net / Shipping) 14/16
Item Mod
e
AU122AEERA
3×2.5
1, 220-230, 50
3
Outdoor unit
AU122AEERAWHITE
Compressor
C-6RZ092H1A
twin rotary
Fan
axial*1
840r/min±50
0.06
2500/-/-
Heat exchanger
TP2M/Φ9.52
0.374
43-60
Dimension
775x640x245 901x341x712
Capillary tube: main φφ1.8×920assistant φφ1.8×780
Defrosting
auto
55
Type of Four way valve
SHF-4-10A
XPE
37
Weight(Net / Shipping)
39/43
PIPING
Refrigerant
R410A 1300
30
Pipe
6.35
12.7
flared
Between I.D &O.
MAX.Drop 10 MAX.Piping length 20
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20 DB/14.5WB Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7 DB/6WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Commercial Air Conditioner
mounting-on-ceiling unit:
Note: is the real time analyser
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level. The detailed method please refer to the following information:
duct unit without auxiliary duct: duct unit with auxiliary duct:
outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right directions.
2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, right directions. measured point: H ( height to the ground) = (h (unit height) + 1m) /2 and, it is 1m to each side.
Installati
on state: the unit should be placed on the flat floor or be mounted in horizonta
l
direction. Testing method:
built-in-ceiling unit:
1m
1m
1.4m
1.4m
2m
duct
auxiliary duct
2m
1.4m
1m
auxiliary duct
h
1m
1m
1m
1m
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
9
3. Safety precaution
3. Safety precaution
Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING! CAUTION!
Incorrect operations may result in injuries or machine damages; in some cases may cause serious consequences.
Incorrect operations may result in severe consequences of death or serious injuries.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
WARNING!
If any abnormal phenomena is found (e. g.smell of firing), please cut off the power supply immediately, and contact the dealer to find out the handling method.
Don't dismantle the outlet of the outdoor unit.
The exposed fan is very dangerous which may harm human beings.
switch
off
In such case, to continue using the conditioner will damage the conditioner, and may cause electrical shock or fire hazard.
Incorrect maintenance and repairment may cause water leak, electrical shock and fire hazard.
When the unit needs maintenance and repairment, please call dealer to handle it.
After the unit being used for a long time, the base should be checked for any damages.
If the damaged base is not repaired, the
unit may fall down and cause accidents.
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
1000
Commercial Air Conditioner
Air-conditioner can't be installed in the environment with inflammable gases because the inflammable gases near to air-conditioner may cause fire hazard.
Connect earthing wire.
Use discharge pipe correctly to ensure efficient discharge.
Earthing wire should not be con­nected to the gas pipe, water pipe, lightning rod or phone line, in-correct earthing may cause shock.
Incorrect pipe use may cause water leaking.
Earthing
WARNING!
Installed electrical-leaking circuit breaker.
It easily cause electrical shock without circuit breaker.
Please let the dealer be responsible for installing the conditioner.
Incorrect installation may cause water
leak, electrical shock and fire hazard.
Call the dealer to take measures to
prevent the refrigerant from leaking.
If conditioner is installed in a small
room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage.
When conditioner is removed or
Incorrect installation may cause water
leaking, electrical shock and fire hazard.
Nothing or nobody is permitted to placed on or stand on outdoor unit.
The falling of goods and people may cause accidents.
Don't operate the air-conditioner with damp hands.
Otherwise will be shocked.
Only use correctly-typed fuse.
May not use wire or any other materials replacing fuse, other-wise may cause faults or fire accidents.
responsible for them.
reinstalled, dealer should be
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
11
Commercial Air Conditioner
4. Net dimension
4.1 AB122ACERA
B9
A9
:;9
GFEH D
><>SS 7JMZ]MMT Y[YVMTYQUT VURMY8
LXIQTIOM VQVM
OIY VQVMRQW[QL VQVM
>@9SS 7QTLUUX [TQZ LQSMTYQUT8
?>9SS 7KMQRQTO UVMTQTO LQSMTYQUT8
@99SS 7VITMR LQSMTYQUT8
>@9SS 7QTLUUX [TQZ LQSMTYQUT8
?>9SS 7KMQRQTO UVMTQTO LQSMTYQUT8
@99SS 7VITMR LQSMTYQUT8
GFEH D
B>
:=9
:A9
NXMYP IQX PURM
Y[YVMTYQUT PURLMX
<;9SS
:>9SS
?9SS
U\MXRIVML LQYZITKM JMZ]MMT ZPM KMQRQTO ITL ZPM VITMRC ;>SS
KMQRQTO
VITMR
240
100
900 990
655
200
880
620 605 600
40 35 35 30
199
4.2 AC122ACERA
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
12
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
:
;
<
=
>
?
@
A
B
9EBG DF=>C
:
1/3;03/+1<-/-=2-,>.11?-,1@0-3A1,3
B
..,
45-..47684
4.3 AD122ALERA
6AF;B 8=B=@< 7;B?=@9>
6AF;B 8=B=@< 4=CDB=:ED=A@ 5A>;
-0
23+
1/+
0++
2
4
5
4.4 AU122AEERA
13
Commercial Air Conditioner
5. Installation Instructions
Note : (1) Fix the parts with screws
(2) Don't intake the strong wind directly to the outlet air-flow hole.
(3) A one meter distance should be kept from the unit top
(4) Don't block the surroundings of the unit with sundries
2. Selection of the place of installation
1.
Accessories
"Edging" for protection of electric wires from an
opening edge.
Select the place of installation satisfying the following conditions and, at the
same time, obtain a consent from the client or user.
Edging
Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting.
Wind direction
NO
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.
(1) Open space requirement around the unit
L
2
L
3
L
1
500
(Servicing space)
Air outlet
Air inlet
Air inlet
Case
Distance
Unit: mm
open
open
open
500
150
150
300
300
0
L
1
L2
L3
I
II
III
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
14
Commercial Air Conditioner
(a) Concrete foundation
Anchor bolt
Concrete foundation
Unit
To fix by bolts
(b) Foundation anchor
Concrete foundation
Unit
Anchor bolt
5.1 Installation of outdoor unit
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
Install the unit so that the angle of inclination must be less than 3 degrees.
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
15
Installation
~9@9>7 r?>>53D9?>
]d^ s9=5>C9?> ?6 3?>>53D9>7 @9@5
u<1B5 3?>>53D9?>
v1C @9@5
e`G1I F1<F5
x>4??B
->9D
}ED4??B E>9D
z9AE94 @9@5
f`G1I F1<F5
u<1B5 3?>>53D9?>
deaj==
iafh==
v1C @9@5
z9AE94 @9@5
]e^ ,85 =1H9=E= <5>7D8 1>4 4B?@ 85978D ?6 3?>>53D9>7 @9@5
,85 =1H9=E= <5>7D8 9C ec=
,85 =1H9=E= 4B?@ 85978D 9C
,? 5>CEB5 D85 5669395>3I _~9@5C C81<< 25 1C C8?BD 1C @?CC92<5a
u9D D85 >ED ?> 1>4 61CD5>
90 + 0.5
15m
+@1>>5B
+@1>>5B
y?9>D
|ED
r1ED9?>C 6?B @9@9>7 3?>>53D9?>
s? >?D DG9CD ?B 456?B= D85 3?>>53D9>7 @9@5a
s? >?D =9H 4ECDCa
,85 25>49>7 B149EC C81<< 25 1C <1B75 1C @?CC92<5a q?D8 71C @9@5 1>4 <9AE94 @9@5 C81<< 25 851D 9>CE<1D9?>a
|? <51;175 9> D85 6<1B5a
Commercial Air Conditioner
¡
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
2
16
Commercial Air Conditioner
Electric wiring
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
WARNING!
30mA
Item
Model
Phase
Switch breaker
(A)
Circuit breaker
Overcurrent
protector
Power
source wire
size
1
40
2
Switch
break
Earth leakage breaker
Leak
curren
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor
unit is supplied by terminals.
For the detailed wiring connection with the indoor units, see the corresponding
indoor operation and instruction manual.
WARNING!
INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG.1 INCORRECT WIRING MAY CAUSE EQUIPMENT DAMAGE.
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
17
AU122AEERA
26
A
40
mm
2.5
OUTDOOR UNIT TERMINAL BLOCK
1 2 3
To Indoor Unit
Y/G
Jhmn[ff[ncih niifm
Sn[h^[l^ []]_mmilc_m
52 S]l_q ^lcp_l
62 I[]em[q
72 Elcff qcnb [ ^c[g_n_l i` :4gg
82 Jhh_l b_r[aih mj[hh_l0mbc`ncha
mj[hh_l
92 Sj[hh_l -580 5;0 5=06806;gg.
:2 Pcj_ ]onn_l
;2 Pcj_ _rj[h^_l
<2 Khc`_
=2 Pch]_lm
542 L_[e[a_ ^_n_]nil il mi[js q[n_l
552 C[h^ n[j_
562 S]l[j_l
572 R_`lca_l[hn icf
Tb_ chmn[ff[ncih niifm fcmn_^ ch nb_ `iffiqcha mb__n ][h \_ om_^ [m l_kocl_^2
Tb_ `iffiqcha j[lnm g_hncih_^ ch nbcm g[ho[f [l_ nb_ chmn[ff[ncih []]_mmilc_m q_ jl_j[l_^2
5
6
7
8
9
5
6
8
5/5
6/8
Ni2
B]]_mmils j[lnm
Qns2
R_gin_ ]ihnliff_l
C[nn_ls
Wcl_ ]f[gj
I_[n jl_m_lp[ncih mf__p_
S]l_q
S]l_q ][j
R_gin_ ]ihnliff_l \l[]e_n
:
;
5
5/5
52S_f_]ncih i` Jhmn[ff[ncih Pf[]_
-5. Pf[]_ [\ip_ nb_ ]_cfcha qb_l_ b[p_ _hioab mj[]_ ni [ll[ha_ nb_ ohcn2
-6. Pf[]_ qb_l_ nb_ ^l[ch[a_ jcj_ ][h \_ [ll[ha_^ q_ff2
-7. Pf[]_ qb_l_ chf_n [h^ ionf_n [cl i` ch^iil [h^ ion^iil ohcn qcff hin \_ \fi]e_^2
-8. Ei hin _rjim_ nb_ ohcn ni nb_ jf[]_ qcnb b_[ps icf il gicmnol_
-_2a2ecn]b_h [h^ qilembij.2
-9. Ei hin m_n nb_ ohcn ch nb_ jf[]_ qb_l_ ^_mnlo]ncp_ a[m -mo]b [m
mof`olc] []c^ a[m. il joha_hn a[m -nbchh_l [h^ a[mifch_. ]ih]_hnl[n_m
[h^ l_n[chm2
-:. Pf[]_ mnliha _hioab ni mojjiln nb_ ohcn q_cabn2
-;. Ni _rj_hmcp_ [lnc]f_m mo]b [m n_f_pcmcih [h^ jc[hi \_fiq
ch^iil ohcn2
-<. Fhioab mj[]_ `il g[chn_h[h]_2
-=. Pf[]_ gil_ nb[h 5g [q[s `lig n_f_pcmcih [h^ l[^ci ni [pic^
^cmnol\cha n_f_pcmcih [h^ l[^ci2
-54. F[ms `il g[chn_h[h]_2
62Jhmn[ff[ncih Pl_j[l[ncih
-5. Pimcncih i` ]_cfcha ij_hcha \_nq__h ohcn [h^ momj_h^cha \ifn
-`lihn pc_q i` ohcn.2
-6. Pl_j[l_ [ff jcjcha -l_`lca_l[hn0q[n_l ^l[ch[a_ .[h^ qcl_m
-]ihh_]ncih qcl_ i` l_gin_ ]ihnliff_l0 ch^iil ohcn ]ihh_]ncih qcl_m.
ni nb_ ch^iil ohcn \_`il_ chmn[ff[ncih ch il^_l ni ]ihh_]n ch^iil ohcn cgg_^c[n_fs [`n_l chmn[ff[ncih2
Commercial Air Conditioner
5.2 Indoor unit ins
t
allation
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Distance between
suspending bolts 535mm
Indoor unit 570mm
Ceiling opening 650mm
Ornament panel 700mm
Indoor unit 570mm
Ceiling opening 650mm
Ornament panel 700mm
Air outlet
Air outlet
Air inlet
2.5m Over
1.5m
1.5m
0.31m
H
Overlap between ceiling and ornament panel shall be 25mm
Suspending bolts
Ceiling
Ornament panel
150mm
320mm
60mm
5.2.1 AB122ACERA
-7. Jhmn[ff [ momj_h^cha \ifn
Ti mojjiln nb_ ohcn q_cabn 0[h]bil \ifn mbiof^ \_ om_^ ch nb_ ][m_ i` [fl_[^s _rcmnm ]_cfcha2 Giq h_q ]_cfcha0 om_ `fomb1ch nsj_ \ifn0 \ocfn1ch nsj_ \ifn il j[lnm jl_n[l_^ ch nb_ `c_f^2 C_`il_ aicha ih chmn[ffcha0 [^domn mj[]_ ni ]_cfcha2
72 Jhmn[ff[ncih i` ch^iil ohcn
Jh ][m_ i` hi ]_cfcha Jhmn[ff ohcn n_gjil[lcfs Pon momj_h^cha \l[]e_n ih nb_ momj_h^cha \ifn ni b[ha nb_ ohcn oj2 C_ mol_ ni om_ hon [h^ q[mb_l [n \inb _h^
i` nb_ \l_[e_n ni m_]ol_ `clgfs2
B`n_l chmn[ff[ncih ih nb_ ]_cfcha
-5. B^domn ohcn ni cnm lcabn jimcncih -R_`_l ni jl_j[l[ncih `il chmn[ff[ncih1-5..
-6.Db_]e nb[n ohcn cm biltihn[f2
Pon momj_h^cha \l[]e_n ih nb_ momj_h^cha \ifn ni b[ha nb_ ohcn oj2C_ mol_ ni om_ hon [h^ q[mb_l [n \inb _h^ i` nb_ \l[]e_n ni m_]ol_ cn `clgfs2
W[n_l jogj [h^ `fi[ncha mqcn]b cm chmn[ff_^ chmc^_ ch^iil ohcn0]b_]e `iol ]ilh_lm i` nb_ ohcn `il cnm f_p_l omcha bilctihn[f ]igj[l[nil il PVD no\_ qcnb q[n_l2-J` ohcn cm ncfncha [a[chmn nb_ ^cl_]ncih i` q[n_l ^l[ch[a_0jli\f_g g[s i]]ol ih `fi[ncha q[n_l f_[e[a_2.
Jh nb_ ][m_ i` ]_cfcha [fl_[^s _rcmnm
-5.Jhmn[ff ohcn n_gjil[ffs
-6.B^domn nb_ b_cabn [h^ jimcncih i` nb_ ohcn2
-7.Pli]__^ qcnb jli]_^ol_ -8. i` + Jh nb_ ][m_ i` hi ]_cfcha +
Non -Pl_j[l_ ch `_cf^.
W[mb_l -Pl_j[l_^ ch `_cf^.
Somj_h^cha \ifnm
G[mn_h -^io\f_ honm.
Jhm_ln
W[mb_l `crcha j[^
-jl_j[l_^ ch `_cf^.
X m_]ol_ nb_ q[mb_l `clgfsY
f_p_f_l
Pifsnb_h_ jcj_
D_cfcha
Rii`
Bh]bil \ifn
Liha hon il nbl_[^
Somj_h^cha \cfn M54
Nin_> Bff nb_ [\ip_ g_hncih_^ j[lnm mb[ff \_ jl_j[l_^ ch `_cf^0 nb_ ^c[g_n_l i` momj_h^cha \ifn cm M54
@Jhmn[ff[ncih Fr[gjf_A
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
4. Installation of water drainage pipe
(1) Install water drainage pipe
Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size: 25mm; O.D.: 32mm )
Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming.
If downward slope of drainpipe cannot be made,lifting pipe shall be installed. Keep a distance of 1-1.5m between suspending bolts, to make water hose straight.
19
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Use the drainage hose and clip provided with unit. Insert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose. Wind the drainage hose to the clip using seal pad for heat insulation. Insulate drainage hose in the room.
5. Cautions for the water drainage lifting pipe
Installation height of water drainage lifting pipe shall be less than 280mm There should be a right angle with unit ,300mm from unit.
slope over 1/100
1-1.5m
Clip
Tape(white)
Draingage hose
Large size seal pad
4mm below
(accessory)
Clip
Clip
Water drainage lifting pipe
Suspending bracket
Drainage hose
280mm unter
500mm below
220mm
300mm below
1-1.5m
220
Drainage hose
75mm below
500mm below
< Note >
The slope of water drainage hose shall be within 75mm , make the drainage plug not to bear excessive force.
If several water hoses join together, of as per following procedures.
Specifications of the selected drainage hoses shall meet the requirements for the unit running
6. Installation of Ornament Panel
Install ornament panel on indoor unit (1) Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and
check that the dimension of the ceiling opening is correct. Take off the lever gauge before installing the ornament panel. (2) Fasten the screws to make the height difference between the two sides of indoor unit less than
5mm. (3) Firstly fix it with screws temporarily. (4) Fasten the two temporarily fixing screws and other two, and tighten the four screws. (5) Connect the wires of synchro-motor. (6) Connect the wire of signal.
(7) If no response of remote controller,check whether the wiring is correct,restart remote controller 10 seconds after shut off power supply.
Slope below 1/100
Connection drainage hose with a T-joint
100mm ¸over
20
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Panel limitation board installation (1)Install the panel board in the direction shown in the figure.
(2)The incorrect direction will result in water leakage,meanwhile swing and signal receiving are displayed that cannot be connected.
Electric control box
21
CAUTION!
INSTALLATION PROCEDURE
Install the room air conditioning unit as follows:
PREPARING INDOOR UNIT INSTALLATION
FIRST REMOVE THE INTAKE GRILL
A. FLOOR MOUNTING
(AC36/42 only suitable for exposed ceiling mounting)
1. DRILLING FOR PIPING
The piping and drain can exit the unit in two directions as shown below in (Fig. 2)
(Fig. 2)
The drain hose must be connected to the right side as shown in (Fig.3).
After the piping and drainage exit has been selected, drill a 7 cm dia. hole through the wall so that the hole is slanting downward toward the outside to ensure good drainage. When the pipe is led out from the rear, make a hole as Fig.4, at the position shown.
2. INSTALLING DRAIN HOSE
The drain hose must be connected to the right side of the unit (Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener. (Fig.5)
Be sure to arrange the drain hose correctly as shown in Fig. 7 so that it is lower than the drain hose connecting point of the indoor unit, if condensate pump is not fitted to system.
B. UNDER CEILING MOUNTING
Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.9)
1. DRILLING FOR PIPING
Select piping and drain directions. (Fig.10) Fig 10
(Fig. 6)
Drain pan
Drain hose
Insulation (Drain hose)
Arrange the drain hose lower than this portion.
Fig. 7
OK NO NO
Drain hose
rear
down
(Fig. 3)
Drain hose (Right side)
Wall
7cm
6mm
Indoor unit outdoor unit
(Fig. 4)
Drain pan
Drain hose
Nylon fastener (supplied by others)
(Fig. 5)
A
Drain hose
Rear (Install the drain hose in this direction.)
Wrap the insulation around the drain hose connection.(Fig.6)
Ensure that the unit is fixed level. Height ‘A’must be less than 5 mm.(Fig.8)
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
(Fig. 10)
Installation template
Wall
Ceilling
Drilling position for piping
Drilling position for anchor bolt
200mm
900mm
5.2.2 AC122ACERA
22
68
16 21 28
381
232
26.5
26.5
2-R2.5
10
18
7.5
4-R5
68
16
21
28
381
232
26.5
26.5
2-R2.5
10
18
7.5
4-R5
Wall
6mm
12.5mm
Fig. 11
Fig. 12
Fig. 13
Spring washer
Special nut
Bracket
CAUTION
Hex bolt
8 to 13mm
Indoor unit
Fig. 14
Fig. 16
Remove the hole cover.
OK
Arrange the drain hose lower than this portion
Drain hose
NO
Fig. 15
Bolt
Bracket
Indoor unit
Install the drain hose at the rear; it should not be installed on the top or right side.
After the piping and drainage exit has been selected, drill 80mm and 50mm or 150mm dia. hole through the wall. So that the hole is slanting downward toward the outside for smooth water flow if a condensate pump is not fitted to system.
4. INSTALLING INDOOR UNIT
Reset the hex bolts as shown in Fig.14.
Apply the indoor unit to the brackets.(Fig.15)
Now, securely tighten the hex bolts in both sides.
5. INSTALL THE DRAIN HOSE
The drain hose will be connected to the right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.5) Wrap the insulation (drain hose)around the drain hose connection. (Fig.9) Be sure to arrange the drain hose correctly so that it is lower than the drain hose connecting port of the indoor unit (Fig.16) if condensate pump is not fitted to system.
Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer. (Fig. 12)
3. INSTALLING BRACKETS
Install the brackets with nuts, washers and spring washers.(Fig. 13)
2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS
using a masonry drill, drill four 12.5 mm dia. Holes.(Fig.11)
Fig. 11
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
23
Wiring
CAUTION
(1) Match the terminal block numbers and connection cable colours with those of the outdoor unit. Incorrect wiring may cause damage to the electrical parts.
(2) Connect the connection cables firmly to the terminal block. Incorrect installation may result in a fire.
(3) Always fasten the outside covering of the connection cable with the cable clamp.(If the insulation is chafed, a short curcuit may occur.)
(4) Always connect the earth wire.
Fig. 26
Electrical component box
Remove the four self tapping screws.
CAUTION
Do not remove the screws. If the screws are removed, the electrical component box will fall.
Fig. 25
Electrical component box
ELECTRICAL WIRING
1. INDOOR UNIT SIDE (1) Remove the electrical component box.
INDOOR UNIT SIDE
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Fig. 27
Electrical component box
Fig. 28
Base
Electrical component box cover
CAUTION
Be careful not to pinch the wiring between the electric component box and base.
(1) Ensure all wiring complies with current regulations.
(2) It is recommended that a MCB of the correct rating is used to protect the system.
(3) Always use a circuit breaker that can trip all the poles of the wiring is fitted and has an isolation distance of at least 3mm between the contacts of each pole.
WARNING
(2) Pull out the electrical component box.
ELECTRICAL WIRING
(3) Remove the electrical component box cover.
(4) Wiring
See wiring diagrams for indoor unit.
Remove the three tapping screws
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual: (1) Starting and stopping method, operation switching,
temperature adjustment, timer, air flow switching, and other remote control unit operations.
(2) Air filter removal and cleaning, and how to use air
louvres.
(3) Give the operating and installation manuals to the
customer.
24
Q\Y ]bXccf ib]h g\U`` VY ]bghU``YX Uh `cWUh]cbg k\YfY Wc`X UbX \ch U]f Wci`X YjYb`m W]fWi`UhYX2 Q\Y Zc``ck]b[ `cWUh]cbg g\ci`X VY Ujc]XYX>
M`UWYg k]h\ f]W\ gU`h -gYUg]XY UfYU.2 M`UWYg k]h\ d`Ybhm cZ [Ug gi`Z]XYg -aU]b`m ]b kUfa gdf]b[ UfYUg k\YfY h\Y WcddYf hiVY UbX VfUnY kY`X ]g YUgm hc Wcffcg]cb.2 IcWUh]cbg k]h\ aiW\ c]` -]bW`iX]b[ aYW\Ub]WU` c]`. UbX ghYUa2 IcWUh]cbg ig]b[ cf[Ub]W gc`jYbhg2 M`UWYg k\YfY h\YfY UfY aUW\]bYg [YbYfUh]b[ FD Y`YWhfcaU[bYh]W kUjYg2 Mcg]h]cbg UX^UWYbh hc Xccf cf k]bXck ]b WcbhUWh k]h\ \][\1\ia]X]hm YlhYfbU` U]f2 -CUgm hc [YbYfUhY XYk.2 IcWUh]cbg ZfYeiYbh`m ig]b[ gdYW]U` UYfcgc`g2
Q\Y Zc``ck]b[ dc]bhg g\ci`X VY hU_Yb WUfY cZ>
52 PY`YWh gi]hUV`Y d`UWYg h\Y cih`Yh U]f WUb VY gYbh hc h\Y
Ybh]fY fcca0 UbX WcbjYb]Ybh hc `Um cih h\Y WcbbYWh]cb d]dY0 WcbbYWh]cb k]fY UbX h\Y XfU]bU[Y d]dY hc cihXccf2
62 Q\Y WY]`]b[ ghfiWhifY aigh VY ghfcb[ Ybci[\ hc giddcfh
h\Y ib]h kY][\h2
72 Q\Y WcbbYWh]b[ d]dY0 XfU]b d]dY UbX WcbbYWh]cb k]fY
g\U`` VY UV`Y hc [c h\ci[\ h\Y Vi]`X]b[ kU`` hc WcbbYWh VYhkYYb h\Y ]bXccf UbX cihXccf ib]hg2
82 Q\Y WcbbYWh]b[ d]dY VYhkYYb h\Y ]bXccf UbX cihXccf ib]hg Ug kY`` Ug h\Y XfU]b d]dY g\U`` VY Ug g\cfh
Ug dcgg]V`Y2 -PYY D][ifY 5.
92 GZ ]hg bYWYggUfm hc UX^igh h\Y Z]``]b[ Uacibh cZ h\Y fYZf][YfUbh0 d`YUgY fYZYf hc h\Y ]bghU``Uh]cb aUbiU`
UhhUW\YX k]h\ h\Y cihXccf ib]h2 :2 Q\Y WcbbYWh]b[ Z`Ub[Y g\ci`X VY dfcj]XYX Vm h\Y igYf \]agY`Z2 ;2 Q\Y ]bXccf ib]h \Ug hkc kUhYf cih`Yhg cbY cZ k\]W\ ]g cVghfiWhYX Uh h\Y ZUWhcfm -k]h\ U fiVVYf WUd.2 Lb`m
h\Y cih`Yh bch cVghfiWhYX -`]ei]X ]b`Yh UbX cih`Yh g]XY. k]`` VY [YbYfU``m igYX Xif]b[ ]bghU``Uh]cb2 GZ Udd`]WUV`Y0 Vch\ h\Y cih`Yhg g\ci`X VY igYX hc[Yh\Yf2
KchY> Q\Y UWWYgg \c`Y aigh VY dfcj]XYX Xif]b[ ]bghU``Uh]cb cZ ]bXccf ib]h Zcf aU]bhYbUbWY2
w*~t
GbghU``Uh]cb gdUWY
8?K>I J>C><KBE@ KA> BEJK;CC;KBFE JG;<>6 GIF<>>= KA> ?FCCFMBE@ JK>GJ7
Commercial Air Conditioner
5.2.4 AD122ALERA
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
|
74 Djadd Y `gd] af l`] oYdd Yf\ afk]jl l`] [gff][laf_ hah] Yf\ oaj] l`jgm_` Y PVC oYdd3
l`jgm_` lmZ] hmj[`Yk]\ dg[Yddq4 T`] oYdd `gd] k`Ydd Z] oal` Y gmloYj\ \gof kdgh] g^ Yl
d]Ykl 757664 /S]] Fa_mj] 80
84 B]^gj] \jaddaf_ [`][c l`Yl l`]j] ak fg hah] gj j]af^gj[af_ ZYj bmkl Z]`af\ l`] \jaddaf_
hgkalagf4 Djaddaf_ k`Ydd Ynga\ Yl hgkalagfk oal` ]d][lja[ oaj] gj hah]4
94 Mgmfl l`] mfal gf Y kljgf_ Yf\ `gjargflYd Zmad\af_ jgg^4 I^ l`] ZYk] ak fgl ^aje2 al oadd
[Ymk] fgak]2 naZjYlagf gj d]YcY_]4
:4 Smhhgjl l`] mfal ^ajedq4
;4 C`Yf_] l`] ^gje g^ l`] [gff][lagf hah]2 [gff][lagf oaj] Yf\ \jYaf hah] kg l`Yl l`]q
[Yf _g l`jgm_` l`] oYdd `gd] ]Ykadq4
Fa_ 8
25
CUW\ cZ h\Y U]f gYbX]b[ XiWh UbX U]f fYhifb XiWh g\U`` VY Z]lYX cb h\Y dfYZUVf]WUhYX dUbY` cZ h\Y Z`ccf Vm h\Y ]fcb VfUW_Yh2
Q\Y fYWcaaYbXYX X]ghUbWY VYhkYYb h\Y YX[Y cZ h\Y U]f fYhifb XiWh UbX h\Y kU`` ]g cjYf 594aa2 Q\Y [fUX]Ybh cZ h\Y WcbXYbgUhY kUhYf d]dY g\U`` _YYd cjYf 5,2 Q\Y WcbXYbgUhY kUhYf d]dY g\U`` VY h\YfaU` ]bgi`UhYX2
T\Yb ]bghU``]b[ h\Y WY]`]b[ AcbWYU`YX hmdY ]bXccf ib]h0 h\Y U]f fYhifb XiWh aigh VY XYg][bYX UbX ]bghU``YX -Ug Z][ifY g\ckb.2
KchY> T\Yb WcbbYWh]b[ h\Y g\cfh XiWhg0 igY h\Y `ck ghUh]W hYfa]bU`g0 k\]W\ Wc`cf ]g k\]hY2
Q\Y X]ghUbWY I Zfca h\Y U]f cih`Yh cZ h\Y XiWh hc h\Y U]f cih`Yh cZ h\Y g]f WcbX]h]cbYf g\U`` VY bc acfY h\Ub 5 a2
524a -igY k\]hY achcf d`i[. 924a-igY fYX achcf d`i[.
WY]`]b[
U]f gidd`m
v
@i]`X]b[ fccZ cZ ]bghU``Uh]cb
U]f fYhifb
U]f fYhifb Vcl
ib]h
Q\YfY g\ci`X VY bc cVghUW`Yg k]h\]b 5a
?]f cih`Yh [f]``Y
?]f gidd`m
U]f fYhifb
U]f fYhifb Vcl
ib]h
?]f X]ghf]VihUfm
?]f fYhifb XiWh
?]f fYhifb V`]bX
PigdYbX]b[ \cc_
BfU]b d]dY
QfUbg]h]cb XiWh
?]f cih XiWh
Q\Y g_YhW\ aUd cZ `cb[ XiWh
Q]Y1]b cZ U]f X]ghf]VihUfm
KchY> T\Yb WcbbYWh]b[ h\Y `cb[ XiWhg0 igY h\Y a]XX`Y ghUh]W hYfa]bU`g0 k\]W\ Wc`cf ]g fYX2
J< k]XY YldUbg]cb Vc`h
J< gigdYbXYf gWfYk
J< k]XY `cW_ kUg\Yf
J< gWfYk bih
?]f WcbX]h]cbYf
Q\Y X]ghUbWY I Zfca h\Y U]f cih`Yh cZ h\Y XiWh hc h\Y U]f cih`Yh cZ h\Y g]f WcbX]h]cbYf g\U` VY bc acfY h\Ub 9 a2
GbghU``Uh]cb cZ ]bXccf ib]h XiWh
52 GbghU``Uh]cb cZ U]f gYbX]b[ XiWh
Q\]g ib]h igYg fcibXYX XiWh0 h\Y X]UaYhYf cZ h\Y XiWh ]g 5<4aa2 Q\Y fcibXYX XiWh bYYXg hc UXX U hfUbg]h]cb XiWh hc WcbbYWh k]h\ h\Y U]f1gYbX]b[ XiWh cZ ]bXccf ib]h0
h\Yb WcbbYWh k]h\ fYgdYWh]jY gYdUfUhcf2 ?g D][2 5 g\ckb0 U`` h\Y ZUb gdYYX cZ Ubm cZ h\Y gYdUfUhcfrg U]f cih`Yh g\U`` VY UX^ighYX Uddfcl]aUhY`m h\Y gUaY hc aYYh h\Y fYei]fYaYbh Zcf h\Y fcca U]f WcbX]h]cbYf2
GbXccf ib]h
Z`Yl]V`Y ^c]bh
QfUbg]h]cb XiWh
OcibXYX XiWh
Rb]h> aa
D][2 5
?]f X]ghf]VihUfm
Q]Y1]b cZ U]f X]ghf]VihUfm
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
62 GbghU``Uh]cb cZ U]f fYhifb XiWh
RgY f]jYh hc WcbbYWh h\Y U]f fYhifb XiWh cb h\Y U]f fYhifb ]b`Yh cZ h\Y ]bXccf ib]h0 h\Yb WcbbYWh h\Y ch\Yf YbX k]h\
h\Y U]f fYhifb V`]bX2 ?g D][2 6 g\ckb2
7 Q\YfaU` ]bgi`Uh]cb cZ XiWh
?]f1gYbX]b[ XiWh UbX U]f fYhifb XiWh g\U`` VY h\YfaU``m ]bgi`UhYX2 D]fgh gh]W_ h\Y [`iYm bU]` cb h\Y XiWh0 h\Yb UhhUW\ h\Y \YUh dfYgYfjUh]cb Wchhcb k]h\ U `UmYf cZ h]bZc]` dUdYf UbX igY h\Y [`iYm bU]` WUd hc Z]l2 D]bU``m igY
h\Y h]bZc]` UX\Yg]jY hUdY hc gYU` h\Y WcbbYWhYX dUfh2 ?g D][2 7 g\ckb2
D][2 6
GbXccf ib]h
f]jYh
?]f fYhifb XiWh
?]f fYhifb V`]bX
D][2 7
[`iYm bU]`
[`iYm bU]` WUd
UX\Yg]jY hUdY
h]bZc]`
\YUh dfYgYfjUh]cb Wchhcb
GbghU``]b[ h\Y gigdYbg]cb gWfYk>
RgY J< cf J54 gigdYbg]cb gWfYkg -80dfYdUfYX ]b h\Y Z]Y`X.-k\Yb h\Y gigdYbg]cb gWfYk\Y][\h YlWYYXg 42=a0
J54 g]nY ]g h\Y cb`m W\c]WY.2Q\YgY gWfYkg g\U`` VY ]bghU``YX Ug Zc``ckg k]h\ gdUWY UXUdh]b[ hc U]f WcbX]h]cbYf
cjYfU`` X]aYbg]cbg UWWcfX]b[ hc h\Y cf][]bU` Vi]`X]b[ ghfiWhifYg2
TccXYb ghfiWhifY
? geiUfY kccX g\U`` VY giddcfhYX Vm h\Y VYUag UbX h\Yb gYh h\Y gigdYbg]cb gWfYkg2
KYk WcbWfYhY g`UV
Qc gYh k]h\ YaVYXXYX dUfhg0ZcibXUh]cb Vc`hg YhW2
Lf][]bU` WcbWfYhY g`UX
RgY \c`Y \]b[Y0\c`Y d`ib[Yf cf \c`Y Vc`h2
PhYY` fY]bZcfWYaYbh ghfiWhifY
RgY ghYY` Ub[`Y cf bYk giddcfh ghYY` Ub[`Y X]fYWh`m2
PeiUfY kccX
@YUa
PigdYbg]cb gWfYk
Ei]XY d`UhY YaVYXXYX dUfh
Hb]ZY YaVYXXYX dUfh
DcibXUh]cb Vc`h
M]dY gigdYbg]cb ZcibXUh]cb Vc`h
Gfcb fY]bZcfWYaYbh
xz,~*,~{-+1
y20.},0*-, 0|/}3
y2..-/1 01}}+ z,~+}
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
27
FUb[]b[ cZ h\Y ]bXccf ib]h
DUghYb h\Y bih cb h\Y gigdYbg]cb gWfYk UbX h\Yb \Ub[ h\Y gigdYbg]cb gWfYk ]b h\Y Q g`ch cZ h\Y gigdYbg]cb dUfh cZ h\Y ib]h2 ?]XYX k]h\ U `YjY` aYhYf0UX^igh `YjY` cZ h\Y ib]h k]h\]b 9aa2
u
Gb cfXYf hc XfU]b kUhYf bcfaU``m0 h\Y XfU]b d]dY g\U`` VY dfcWYggYX Ug gdYW]Z]YX ]b h\Y ]bghU``Uh]cb aUbiU` UbX g\U`` VY \YUh ]bgi`UhYX hc Ujc]X XYk [YbYfUh]cb2 GadfcdYf \cgY WcbbYWh]cb aUm WUigY ]bXccf kUhYf `YU_U[Y2
OYei]fYaYbhg
Q\Y ]bXccf XfU]b d]dY g\U`` VY h\YfaU` ]bgi`UhYX2 Q\Y WcbbYWh]cb dUfh VYhkYYb h\Y XfU]b d]dY UbX h\Y ]bXccf ib]h g\U`` VY ]bgi`UhYX gc Ug hc dfYjYbh XYk [YbYfUh]cb2 Q\Y XfU]b d]dY g\U`` VY g`Ubh XckbkUfXg -[fYUhYf h\Ub 53544.2 Q\Y a]XX`Y dUfh g\U`` bch VY cZ P hmdY Y`Vck0 ch\Yfk]gY UVbcfaU` gcibX k]`` VY dfcXiWYX2 Q\Y \cf]ncbhU` `Yb[h\ cZ h\Y XfU]b d]dY g\U`` VY `Ygg h\Ub 64 a2 Gb WUgY cZ `cb[ d]dY0 giddcfhg g\U`` VY dfcj]XYX YjYfm 529 q 6a hc dfYjYbh kUjm Zcfa2 AYbhfU` d]d]b[ g\U`` VY `U]X cih UWWcfX]b[ hc h\Y Zc``ck]b[ Z][ifY2 QU_Y WUfY bch hc Udd`m YlhYfbU` ZcfWY cbhc h\Y XfU]b d]dY WcbbYWh]cb dUfh2
M]dY UbX ]bgi`Uh]cb aUhYf]U`
O][]X MSA d]dY SM7529aa -]bhYfbU` X]UaYhYf.
DcUaYX MC k]h\ h\]W_bYgg UVcjY ; aa
M]dY
Gbgi`Uh]cb
FcgY
BfU]b d]dY g]nY> -738+. MSA d]dY Q\Y \cgY ]g igYX Zcf UX^igh]b[ h\Y cZZ1WYbhYf UbX Ub[`Y cZ h\Y f][]X MSA d]dY2
B]fYWh`m ghfYhW\ h\Y \cgY hc ]bghU`` k]h\cih aU_]b[ Ubm XYZcfaUh]cb2 Q\Y gcZh YbX cZ h\Y \cgY aigh VY ZUghYbYX k]h\ U \cgY W`Uad2 M`YUgY Udd`m h\Y \cgY cb \cf]ncbhU` dUfh
Gbgi`Uh]cb hfYUhaYbh>
TfUd h\Y \cgY UbX ]hg W`Uad ibh]` hc h\Y ]bXccf ib]h k]h\cih Ubm W`YUfUbWY k]h\ ]bgi`Uh]b[ aUhYf]U`0 Ug g\ckb ]b h\Y Z][ifY2
BfU]b WcbZ]faUh]cb
Bif]b[ hf]U` fib0 W\YW_ h\Uh h\YfY ]g bc `YU_U[Y Uh h\Y d]dY WcbbYWh]cb dUfh Xif]b[ kUhYf XfU]b]b[ YjYb ]b k]bhYf2
TU``
Lihg]XY
P`Ubh
BfU]b d]dY -gidd`]YX Vm h\Y igYf.
SM74
Qc h\Y `Uf[Ygh -Udd2 54Wa.
Bckb g`cdY UVcjY 53544
P hmdY Y`Vck
529ao6a
Piddcfh
Gbgi`Uh]cb
-gidd`]YX Vm h\Y igYf.
Bckb g`cdY UVcjY 53544
5 9;LKBFE
FcgY FcgY W`Uad
PiVg]X]Ufm ]bgi`Uh]cb
Gbgi`Uh]cb
O][]X MSA d]dY
?``ckUV`Y d]dY `Yb[h\ UbX Xfcd
Q\YgY dUfUaYhYfg X]ZZYf UWWcfX]b[ hc h\Y cihXccf ib]h2 PYY h\Y ]bghfiWh]cb aUbiU` UhhUW\YX k]h\ h\Y cihXccf ib]h Zcf XYhU]`g2
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
28
SUWiia diad]b[
LdYb U`` jU`jYg
EUg `YU_U[Y XYhYWh]cb
T]h\ U jUWiia diad0WfYUhY jUWiia Zfca h\Y ghcd jU`jY cZ h\Y cihXccf ib]h2 Cadhm]b[ k]h\ fYZf][YfUbh gYU`YX ]b h\Y cihXccf ib]h ]g UVgc`ihY`m ZcfV]XXYb2
LdYb U`` h\Y jU`jYg cb h\Y cihXccf ib]h2
A\YW_ k]h\ U `YU_U[Y XYhYWhcf cf gcUd kUhYf h\Uh ]Z h\YfY ]g [Ug `YU_U[Y Uh h\Y d]dY WcbbYWh]cbg
UbX VcbbYhg2
Gbgi`Uh]cb hfYUhaYbh
LdYfUhY ]bgi`Uh]cb hfYUhaYbh cb Vch\ h\Y [Ug g]XY UbX `]ei]X g]XY cZ d]dYg fYgdYWh]jY`m2 Bif]b[ Wcc`]b[ cdYfUh]cb0Vch\ h\Y `]ei]X UbX [Ug g]XYg UfY Wc`X UbX h\ig g\U`` VY ]bgi`UhYX gc Ug hc Ujc]X XYk [YbYfUh]cb2
Q\Y ]bgi`Uh]b[ aUhYf]U` Uh [Ug g]XY g\U`` VY fYg]ghUbh hc U hYadYfUhifY UVcjY 564 XY[fYY2 Q\Y ]bXccf ib]h d]dY WcbbYWh]cb dUfh g\U`` VY ]bgi`UhYX2
Q\Y bchW\ idkUfX-?hhUW\YX XYhU]` j]Yk.
GbXccf ib]h
PiVg]X]Ufm ]bgi`Uh]cb hiVY
D]Y`X d]d]b[ g]XY
8<<>JJFIN ;J ?FCCFM7
Kc2
?WWYggcfm dUfhg
Nhm2
5
6
T]fY W`Uad
6
5/5
FYUh ]bgi`Uh]cb g\YUh\]b[
PWfYk WUd
7
5/5
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
t784=6
t<49;
6. Parts and Functions
Fig.1 Indoor Unit
1
4
6
7
3
Fig.2
POWER
OPER
TIMER
COMP
EMER
2
1 Operating Control Panel (Fig.2) 2 Emergency switch 3 Remote Control Signal Receiver 4 Power Indicator Lamp (Red) 5 OPERATION Indicator Lamp (Green) 6 TIMER Indicator Lamp (Yellow) 7 Compressor Run Lamp (Green) 8 Intake Grill 9 Air Filter
10
UP/DOWN Air Direction Flaps
11
RIGHT/LEFT Air Direction Louvers
(behind UP/DOWN Air Direction Flaps)
3
9
8
Fig.1
1110
5
6.1 AB122ACERA
6.2 AC122ALERA
F_RWP UX]^NZ
+9RZ OUX_ MRZNL\RXW LJW KN JMS][\NM K` ][RWP \QN FI?B> K]\\XW XW \QN ZNVX\N LXW\ZXUUNZ,
9RZ ?WUN\ >ZRUUN
9RZ =RU\NZ
+?W[RMN XO \QN ?WUN\ >ZRUUN,
CYNZJ\RWP :XW\ZXU DJWNU
ENVX\N ZNLNR^NZ :XVYZN[[XZ @JVY G?A<E @JVY CD<E9G?CB @JVY DX_NZ @JVY <VNZPNWL` [_R\LQ
a
b
c
d
e
:CAD G?A<E CD<E DCI<E
a b c d e
CYNZJ\RWP :XW\ZXU DJWNU
f
f
<A<E
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
30
Electrical components Case
Drain pan
Evaporator
Air outlet frame
6.3 AD122ALERA
6.4 AU122AEERA
Air inlet
Air outlet
Compressor
(Inside of unit)
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
31
FQERH
HIGH4RO
SIMEQ
RES
FILSEQ
B
A
HEALSH
QERES
LOCK
RLEEP
FAN
SEMP
ON
OFF
RUING
MODE
CLOCK
CODE
LIGHS
QJJ
E V U Q
HEAS
7. Controller functions
*
740:A7
+
;=34 50<
@D8<6
A4;>
2:=29
A8;4?
@4A
?42=C4?F
27429
58:A4?
?4@4A
;=34 50<
0BA=
0BA=
50< =<:F
2==:
3?F
740A
A4@
7867
;43
:=D
58E
24<A?0:
=>4?0A8=<
@A0<31F
>?4-740A
345?=@A
58:A4?
740:A7
27429
@D8<6
B<8A <=.
34;0<3
;0<B0:
24<.033.
@F@.033.
?==; A4;>.
@4A A4;>.
A8;4? 2:=29
B>
3=D<
C4<A8:0A8=<
=<
=55
308:F
0BA=
?42=C4?F
<=?;0:
=</=55
Mg_jZj^] \hgljhee^j YS<LB@
Wired controller YR-E12
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
32
Commercial Air Conditioner
8. Refrigerant circuit
main
capillary
assistant
capillary
one-way valve
condenser air-i nlet temp.
sensor Tci
cooling
heating
defrost
temp.
sensor
Te
condenser
4-way
valve
check
valve
high pressure
switch
discharge
temp.
sensor
Td
check
valve
2-way stop valve
(liquid side)
evaporator
indoor
coil
temp.
sensor
Tc
3-way stop
valve (air side)
compressor
muffle
low pressure
switch
outdoor
ambient
temp.
sensor
Tao
indoor
ambient
temp.
sensor
Tai
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
33
9. Electrical Control Functions
9.1. Outdoor electric control functions
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
System main functions
Definition of sensor sign: Tnh=indoor ambient temp., Twh=outdoor ambient temp., Tpg=indoor coil, Ttc=discharge, Tcs= outdoor coil, Txr=suction.
1.1 Outdoor running frequency and the control procedure
1.1.1 Outdoor running frequency control Outdoor running frequency range:
Compressor max. running frequency in cooling mode:
outdoor ambient temp. ~15 15~38 38~ Max. running frequency Hz(E) 60 100 80
Compressor min. running frequency in cooling mode:
outdoor ambient temp. ~38 38~ Min. running frequency Hz(E) 16 16
Compressor max. running frequency in heating mode:
outdoor ambient temp. ~0 0~15 15~ Max. running frequency Hz(E) 120 100 80
Compressor min. running frequency in heating mode:
outdoor ambient temp. ~10 10~ Min. running frequency Hz(E) 30 30
1.1.2 Compressor startup
When compressor startup for the first time, compressor running frequency must be stay at 60Hz(E) and 80Hz(E) for 1 minutes (At outdoor discharg temp. overhigh protection and compressor overcurrent protection, the frequency will be reduced), and then rise up to the target frequency. After the unit is in normal, the above procedure is not available.
1.2.3 Heating mode, cooling mode
After performing the compressor startup procedure, the unit will run according to the indoor frequency.
2 minutes later, the unit will compensate the running frequency due to the relative condition.
1.2.4 Compressor frequency rising/reducing speed
Rapid rising/reducing frequency speed 1----1Hz/second
Slow rising/reducing frequency speed 2----1Hz/10 seconds
Slow reducing frequency speed 3----2Hz/second
1.2 Outdoor motor control
Note: When the outdoor motor needs to change the class, there will be 45-second interval to avoid the fan speed changing frequently. 4 pulse for each circuit.
1.2.1 Fan motor speed class has 7 steps, the rotation and class is as follow:
Class-0 Class-1 Class-2 Class-3 Class-4 Class-5 Class-6 Class-7
Stop
250 400 550 650 850 900 950
1.2.2 Blowing remain heat after compressor shuts off
In cooling mode, when compressor shuts off, outdoor motor will enter speed Class-5 automatically, and will shut off after blowing remaining heat for 30 seconds.
1.2.3 Outdoor motor control in cooling/dry mode Fan motor locked rotor: When fan motor is requested to work, if fan speed is measured to be below
50RPM and keep for 10 seconds, the compressor will stop, but 3 minutes later, it will re-start up again.
If within 10 minutes, the condition occurs 3 times, the unit will stop and alarm. When compressor starts up, the unit will adjust automatically in 3 minutes according to the outdoor
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
ambient temperature, and 3 minutes later, the unit will adjust according to the outdoor ambient temperature and compressor running frequency. Fan speed chart in 3 minutes after compressor starts up:
Ambient temp. ~10 10~25 25~ Cool Class-3 Class-5 Class-6 heat Class-6 Class-5 Class-3
Fan speed chart in 3 minutes after compressor runs due to the ambient temp. and compressor
frequency:
Compressor frequency in cooling F<40Hz
40HzF<50Hz 50F
Over 28
Class-3 Class-5 Class-6
Twh
Below 28
Class-1 Class-3 Class-5
Compressor frequency in heating F<40Hz
40HzF<50Hz 50F
Over 15
Class-1 Class-3 Class-4
Twh
Below 15
Class-3 Class-5 Class-6
Low temp. cooling mode:
Outdoor temp. To To <0
0To <5 5To <10 10To <15
DC fan speed Class-1 Class-2 Class-3 Class-4
Rated running mode:
Outdoor fan motor runs in class-7(DC motor) in rated mode.
1.2.4 Fan motor speed control when outdoor select inverter moter Select fan motor by SW4 on the outdoor small indicate board, ON means DC motor, OFF means
inverter motor.
Blowing remain heat function: In cooling mode, when compressor shuts off, outdoor motor will run in
low speed, and will shut off after 30 seconds.
Fan speed chart in 3 minutes after compressor starts up:
Ambient temp. ~15 15~25 25~ Cool Low speed High speed High speed Ambient temp. ~10 10~20 20~ heat High speed High speed Low speed
Fan speed chart in 3 minutes after compressor runs due to the ambient temp. and compressor
frequency:
Compressor frequency in cooling ~25 25~45 45~
Over 28
Low speed High speed High speed
Twh
Below 28
Low speed Low speed High speed
Compressor frequency in heating ~25 25~45 45~
Over 15
Low speed Low speed High speed
Twh
Below 15
Low speed High speed High speed
Remark: 1. There are 45 seconds delay when changing fan speed;
2. When in non-heating mode, if outdoor ambient temp. is lower than 15, the fan will run in low speed;
3. When in heating mode, if outdoor ambient temp. is lower than 20, the fan will run in low speed.
1.3 Outdoor electronic expansion valve (EEV) control
1.3.1 Movement of EEV Full-close, full-open, open angle upper limitation, open angle lower limitation, open/close valve speed.
35
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Initialize movement: 600 pulse close, then 50 pulse open, that is stop at 50 pulse at last; Full-open: 480 pulse open(E); Upper/lower
limitation of open angle: 480---50 pulse;
Driving speed: open direction: 30.3 PPS; close direction: 83.3 PPS; Electrify initialize movement: act as full-close; The movement of valve after compressor startup/shut off ; Compressor startup: the compressor will startup after the open angle of valve has reached the
fiducial open angle;
Compressor shut off: valve begin to full-close after the compressor has stopped.
1.3.2 Enter the fiducial open angle after compressor startup(no matter 2 minutes later or 2 minutes ago), 4 minutes later adjust automatically according to the target over-heat value, 10 minutes later begin to modify the over-heat value and open angle of valve. Cool Outdoor temp.
~22 22~ Compressor frquency ~50 50~80 80~ ~50 50~80 80~ PMV open angle 230 220 240 260 250 280 Heat Outdoor temp.
~6 6℃~ Compressor frquency ~50 50~80 80~ ~50 50~80 80~ PMV open angle 200 180 220 240 230 260
1.3.3 Confirmation of over-heat degree Standarded over-heat degree
Actual running Hz ~20 ~30 ~40 ~50 ~60 ~70 ~80 ~90 90~
Cool, dry 2 2 1 1 1 1 1 2 2 TXRH0
(℃)
heat 2 2 1 1 1 1 1 1 1 When discharging temp. Td is too high or too low, modify the EEV angle Mode Modification angle Max. modification Cooling
Ttc100, standarded over-heat degree -1 degree / 2 minutes 90< Ttc<100, keep the angle Ttc<90, +1 degree / 2 minutes, and plus to 0 degree gradually
Max. -5
Cooling
Ttc<35, standarded over-heat degree +1 degree / 2 minutes 35< Ttc<40, keep the angle Ttc40, -1 degree / 2 minutes, and reduce to 0 degree gradually
Max. +5
Heating
Ttc100, standarded over-heat degree -1 degree / 2 minutes 90< Ttc<100, keep the angle Ttc<90, +1 degree / 2 minutes, and plus to 0 degree gradually
Max. -5
Heating
Ttc<35, standarded over-heat degree +1 degree / 2 minutes 35< Ttc<40, keep the angle Ttc40, -1 degree / 2 minutes, and reduce to 0 degree gradually
Max. +5
1.4 4-way valve control
The 4-way valve control in defrosting: refer to the defrosting procedure. 4-way valve control in other modes:
In heating mode, 4-way valve will open in 15 seconds after compressor starts up. When compressor not startup or in non-heating mode, 4-way valve will close to ensure the compressor has stopped for at least 2 minutes.
36
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
1.5 Outdoor defrosting control
1.5.1 Enter condition
In heating mode, if the compressor has run for 10 minutes continuously and run for 45 minutes in all(clear the compressor
accumulative operation time when defrost over or enter cooling mode), the system
will measure the defrosting temp. sensor Tcs(check the frosting condition of outdoor heat exchanger) and outdoor ambient temp. sensor Ta, if the below condition can be met for continous 5 minutes, the unit will enter defrosting operation:
Tc s≤C×Ta -α
Herein: C: Ta<0℃, C=0.8(E)
Ta≥0℃, C=0.6(E) Set α= 8 according to the data of EEPROM. Herein: when C×Ta -α exceed the range of -12℃≤C×Ta-α≤-6℃,
If C×Ta -α<-12℃, regard it as equal to -12℃; if C×Ta-α>-6℃, regard it as equal to -6℃.
1.5.2 Defrost interval time When C×Ta -α>-12, compressor defrost
accumulative operation time is 45 minutes;
When C×Ta -α≤-12, compressor defrost
accumulative operation time is 45 minutes
1.5.3 Defrost operation
when defrost begins, compressor will stops for 1 minute, outdoor fan runs, after 50 seconds, 4-way
valve OFF.
Outdoor fan stops when compressor starts up, compressor running frequency must be stay at 60Hz
(E) for 1 minute, and then rise up to the target frequency 88Hz.
Compressor current and discharge protections are valid during defrost, when compressor stops because of protection or failure in defrost mode, resume after stopping for 3 minutes, accumulative operation time will not be cancelled. Enter defrost when the continuous operation time is met.
When enter defrost, quit defrost only when 2 minutes of the compressor min. operation time is met.
1.5.4 Quit condition
When any of the following condition is met, change defrost to heating mode.
(1): Outdoor heat exchanger temp. over 10℃ last for 60 senconds contineously;
(2): Outdoor heat exchanger temp. over 14℃ last for 30 senconds contineously;
(3): Defrost for 9 minutes contineously.
1.6 PTC output control
When outdoor unit is electrified, PTC output is 0, 3 seconds later, it is 1.
1.7 Heater control
When compressor stops and outdoor ambient temp. less than 26, heater will work, or stop it.
1.8 auto-checking function(pre-set)
Auto-checking function: When first short-circuit CJ601 then electrified, enter auto-checking. The process is as following: failure lamp LED001---PTC---4-way valve---heater---high speed---low speed--­expansion valve(A—B—C—D)---LED lamp board(LED5—LED4—LED3—LED2—LED1—compulsory cooling—compulsory heating—DC fan motor—inverter fan motor)
Compulsory cooling when SW5-2 on LED lamp board is “ON”, LED5, LED4, LED3, LED2 and LED1 are all light, or all are black out.
Compulsory heating when SW5-1 on LED lamp board is “ON”, LED5, LED4, LED3 and LED2 are all light, LED1 is black out, or all are black out.
DC fan motor when SW5-4 on LED lamp board is “ON”, LED5, LED4, LED3 and LED1 are all light, LED2 is black out.
Inverter fan motor when SW5-4 on LED lamp board is “OFF”, LED5, LED4 and LED3 are light, LED2
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
and LED1 are black out.
1.9 Time shorting function
Time shorting function: If the time shorting port is in short circuit after electrifying CJ601, the unit will
perform a 1/60 time shorting control.
1.10 Additional functions
1.10.1 The interval between compressor stop and startup again is 3 minutes, which can protection compressor. If being electrified for the first time, compressor will start up only when the valve opens to the normal operation angle.
1.10.2 Ttc high temperature protection Ttc discharg temp. over-heat protection can be executed once the unit is ON, but the discharge temp.
sensor can only alarm after the compressor has started up for 4 minutes.
If Ttc>=115 keeping for 10s, the discharge temp. over-heat protection excutes and unit stops,
resumable after quit the protection. If in 60 minutes the protection occurs for 3 times, the failure can be sent to indoor unit.
1.10.3 In heating indoor Tc high temperature protection Indoor heat exchanger temp. sensor will check the indoor coil temperature, if it is over 55, the unit
will reduce the compressor motor speed to perform the indoor heat exchanger temp. overhigh protection. If it is below 48, the unit will resume to be normal control.
P: reduce at the speed of 1Hz/10s
Q: remain the previous value
R: rise at the speed of 1Hz/10s
TC
P reduce slowly 55 Q remaining 52 R rise slowly 48
1.10.4 Over current protection:
Discharging temp. Ttc
quick reduce FQY 2HZ/S
quick reduce FQY 1HZ/S
slow reduce FQY 1HZ/10S
keep FQY
slow rise FQY 1HZ/10S
114
111
108
105
95
90
38
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
The compressor will stop and alarm if current exceed 11A for 3 seconds contineously during compressor startup, the compressor can re-start up after 3 minutes. but the compressor will stop and alarm and confirm the failure if it stop abnormally 3 times in 60 minutes, the system will work continued after been power-off.
Over current reducing frequency(FQY) protection
When current exceed (B)A, the compressor will reduce FQY at 1HZ/S, if current is less than (B)A and more than (B-1)A, stop reducing FOY and then rise FQY at 1HZ/10S, when current is less than (B-A)A, reaume to the target FQY. (B is setted in the EEPROM)
Compressor power protection
1) In dry and cooling mode, when compressor power over (a)W, the compressor will reduce FQY 1HZ/S, if compressor power over (b)W, the compressor will reduce FQY 0.1HZ/S, when compressor power over (c)W, rise the compressor FQY is forbidden, when compressor power over (d)W, the compressor will rise FQY 0.1HZ/S.
2) In heating mode, when compressor power over (a1)W, the compressor will reduce FQY 1HZ/S, if compressor power over (b1)W, the compressor will reduce FQY 0.1HZ/S, when compressor power over (c1)W, rise the compressor FQY is forbidden, when compressor power over (d1)W, the compressor will rise FQY 0.1HZ/S.
Remark: a, b, c, d and a1, b1,c1,d1 are written in EEPROM, can be adjusted according to different
system.
1.10.5 High, low pressure protection
High pressure protection: high pressure switch will not detect when in standby, detect after
compressor has started for 3 minutes.
Low pressure protection: low pressure switch will detect after compressor has started for 3 minutes,
and will shield during defrost or 6 minutes after defrost.
1.10.6 Sensor management: the detect time for sensor short-circuit or open-circuit is 4.5s, 3 minutes is needed for resume if failure is detected, the unit will work normally when the failure is cancelled.
Discharge temp. sensor will not detect if it short-circuit or open-circuit, detect when compressor has
started for 3 minutes.
When the AD value of all sensor is less than 3, regard as the outdoor temp. too low and all sensor
failtures will not alarm.
Outdoor add high temp. protection Te 62℃
quick reduce FQY 1HZ/S, when Te>=70℃, quick reduce FQY 1HZ/S, and stop the unit
if it lasts for 10 senconds
59℃ remaining
55
slow reduce FQY 1HZ/10S
1.10.7 Indoor heat exchanger anti-freezed protection Anti-freezed in cooling mode
39
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
normal control 11℃ slow rise FQY 1HZ/10S
9
remaining
6
slow reduce FQY 1HZ/10S
1.10.8 Rated operation(the value can be setted by EEPROM)
Rated cooling:
When receiving the indoor rated operation command, the unit will enter rated cooling operation.
Rated cooling:
When receiving the indoor rated operation command, the unit will enter rated heating operation.
1.10.9 Outdoor compulsory operation(select by the outdoor dip switch)
Compulsory heating operation
Dial SW1 of the outdoor small indicate board in ON state, set the heat exchanger temp. from indoor unit 16, each protection is available, FQY(20—120Hz), fan speed(inverter: high/middle/low; DC motor: class 1—7) and expansion valve(10—400) can be manual adjusted.
Compulsory cooling operation
Dial SW2 of the outdoor small indicate board in ON state, set the heat exchanger temp. from indoor unit 16, each protection is available, FQY(20—120Hz), fan speed(inverter: high/middle/low; DC motor: class 1—7) and expansion valve(10—400) can be manual adjusted.
Note: the dip switches for compulsory cooling and compulsory heating can not be setted ON synchronously.
1.10.10 Failure code and troubleshooting The outdoor lamp will flash if there is failure, the flash FQY is 1HZ, the flash time is according to the
following table, the lamp will off for 3 seconds after one flash circuit, meanwhile, the lamps on LED board will light in 5-bit binary system(light is 1, LED1-LED5 from low bit to high bit).
Alarm lamp is always light when there is no failure.
1.10.11 Special funtions
1) Power operation When receiving the Power operation signal from indoor, the unit will operate as the set frequency by
EEPROM. Fan speed will depend on the ambient temperature and the frequency. When the Power signal is cancelled by indoor, the Power operation will stop.
2) Soft operation When receiving the Soft operation signal from indoor, the unit will operate as the set frequency by
EEPROM. Fan speed will depend on the ambient temperature and the frequency. When the Soft signal is cancelled by indoor, the Soft operation will stop.
3) Time shorting operation After receiving the time shorting signal, the unit will perform the 1/60 time shorting operation.
4) Compulsory cooling/heating operation Controlled by the buttons on the outdoor small board, only indoor heat exchanger protection is invalid,
all the other protections are valid.
40
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Trouble description
Display of
LED borad
LED 5-4-3-2-1
Analyze and diagnose
Flash times of LED on mainborad
01111
Eeprom failure 01110 Outdoor main board eeprom fail 14
IPM failure 00001 IPM failure 1
Compressor U-phase over-current
00101 The current of compressor U-phase is too high 32
Communication error between main board and spdu module
10110 Communication fail over 4min 22
High pressure protection 01000 System high pressure over 4.5Mpa 8
Module over-voltage protection (only for ISPM)
11010 Send from ISPM module 26
Compressor start-up abnormal 10001 Compressor start-up abnormal 17
Compressor discharging temprerture protection
00100
Compressor discharging tempreature over 120 centigrade
4
Abnormal of DC moter 00010 Jam of DC motor or motor failure 2
Abnormal of piping sensor 00111
Piping sensor short-circuit or open-circuit last 60 sec
7
Abnormal of Compressor suction sensor
10101
Compressor suction sensor short-circuit or open-circuit last 60 sec
21
Abnormal of outdoor ambient sensor
00110
Outdoor ambient sensor short-circuit or open-circuit last 60 sec
6
Abnormal of compressor discharge sensor
01001
Compressor discharge sensor short-circuit or open-circuit last 60 sec
9
Spdu / IPM module over current protection
00101 Current of spdu / ISPM module over limit 5
Communication error between indoor and outdoor unit
00011 Communication fail over 4min 3
Compressor V-phase over-current
00101 The current of compressor V-phase is too high 33
Compressor W-phase over-current
00101 The current of compressor W-phase is too high 34
Compressor jam(only for spdu) Inner compressor is abnormal jamed 15
Compressor phase loss 11110 U/V/W loss 30
Module lack-voltage protection (only for ISPM)
11011 Send from ISPM module 27
Module PWM select circuit error 01011 Module PWM select wrong circuit 11
Detect PFC over-current
01100
The current of PFC circuit is too high
12
Compressor parameter error 10010
Wrong compressor parameter is selected in the Eeprom
18
SPDU Communication error 10110 Communication error send from SPDU 22
Circuit error detected by current 10011 Circuit damage detected by the current 19
PFC voltage abnormal 11111 Voltage of PFC circuit is abnormal 31
Module error 01101 Module error 13
The power supply is not the 50Hz
01010 The power supply is not the 50Hz 10
Condenser air inlet temp. sensor failure
11001
Condenser air inlet temp. sensor short-circuit or open-circuit last 60 sec
25
Low pressure protection 11000 System low pressure under 0.05Mpa 24
4-way valve reverse failure 11100
Alarm and stop if detect Td-Tci<=25 last for 1min after compressor has started for 10min in heating mode, confirm the failure if it appears 3 times in one hour.
28
Lack off refrigerant or discharge side dirty
11101
Alarm and stop if detect Td-Tci>=25 last for 1min after compressor has started for 10min in cooling mode, confirm the failure if it appears 3 times in one hour
29
41
High
Mid
3
1
Mid
Low
Low
High
2
0
ΔT
ΔT
1.General features
1.1 Control mode: remotr or wired control + connecting port of long-distance control + passive
port switch control.
1.2 Temperature control: 16-30;
1.3 Precise of temperature control: ±1;
1.4 Indoor fan speed: AUTO, HIGH, MIDDLE, LOW (no AUTO when in FAN mode);
1.5 Swing control: the swing are controlled by the synchronous motor, main control board receive usable signal and set in swing mode or remain in other mode;
1.6 running mode: AUTO , COOL, DRY, FAN and HEAT;
1.7 Healthy function: 5VDC UV generator, 12VDC negrative ion generator - high voltage collecting-dirt, 220VAC negrative ion generator – oxygen pump;
1.8 Filter up-down control: adopt double-direction synchronous motor;
1.9 Auxiliary electric heating function: 12VDC control signal, 220VAC control signal or control switch;
1.10 Fresh air control: 12VDC DC motor,220VAC AC control port output;
1.11 CLOCK setting, TIMER ON, OFF, ON/OFF and SLEEP fuction (only TIMER function is viable and temperature variety is unviable when running the SLEEP function in FAN mode);
1.12 Drain system function: Water level inspection and water pump control
1.13 Compulsory cooling operation;
1.14 Safety and protection devices: 3-minute protection for compressor startup, freeze protection device, overheat protection device, temperature cutoff protection, sensor failure, drainage, pressure, communication etc. protection.
1.15 Indoor ambient temperature, indoor and outdoor coil temperature inspection.
1.16 start current control: the outdoor fan start after compressor running 2s in normal situation.
2. LED function:
The LED for remote control type includes POWER, TIMER, COMPRESSOR, WATER PUMP; the POWER LED also indicate failure; when the unit is switched on by the controller, the POWER LED will be ON, when being switched off, the POWER LED will be OFF.; If the controller is in TIMER and SLEEP mode, the TIMER LED will be on; if it is not in TIMER and SLEEP mode, the TIMER LED will be off. When the compressor is running, the compressor LED will be on; when it stops, this LED will be off. POWER LED flashes when there are system failure, the flash times ti indicate the failure code.
3. Indoor AUTO FAN control
a) If the unit enters AUTO FAN for the first time, when ΔT>2, select high speed; whenΔT≤
0, select low speed; or it will select med speed; when thermostat is OFF, fan will be low speed. (the conversion temperature difference is 1 degree).
b) If the present fan speed is AUTO
HIGH, whenΔT<2, fan speed will change to AUTO MED.
c) If the present fan speed is AUTO
MED, whenΔT<0, fan speed will change to AUTO LOW; whenΔT 3, fan speed will change to
AUTO HIGH.
d) If the present fan speed is AUTO LOW, whenΔT>1, fan speed will chenge to AUTO MED. e) Fan speed conversion in AUTO FAN mode: the conversion will delay for 3 minutes from HIGH to
LOW, and no delay from LOW to HIGH.
f) When the fan speed is HIGH/LOW/MED, on the condition that the protection does not act, the unit
will run at the set fan speed; when the protection acts, for the sake of the normal operation, the fan speed will be forced to conversion; in Dry mode, fan motor will be changed as request.
4. AUTO mode control
4.1 When entering AUTO for the first time, the unit will select the running mode due to the below
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
AB122ACERA AC122ACERA AD122ALERA electric control function:
42
conditions, then perform the selected mode.
TrTs -3 select COOL mode (includes FAN mode) TrTs -3 select HEAT or FAN mode
4.2 After entering the AUTO mode, the mode can change over among COOL, HEAT or FAN modes according to the indoor ambient temperature (conversion temperature difference is ±3℃).
4.3 If the unit is in COOL mode, when it arrives compressor-stop temperature, the compressor will stop; after compressor stops for 15 minutes, the unit will check the room temperature, if Tr<Ts -3 ℃ , the unit will enter HEAT or FAN mode, or the unit will still be in COOL mode;
4.4 For the heat pump unit, if the unit is in HEAT mode at present, when it arrives
compressor-stop temperature, the compressor will stop; after the compressor stops for 15 minutes, the unit will check the room temperature, if Tr>Ts+ 3℃, the unit will enter COOL mode, or it will still be in HEAT mode.
4.5 For cooling only unit, if the unit is at FAN mode, if Tr>Ts + 3℃, the unit will enter COOL mode.
4.6 When the unit is in HEAT mode, if indoor heat exchanger temperature rises up to over 63℃,
the unit will change into COOL mode. And within 1 hour, the heat exchanger temperature will not be limited, the heating operation will stop temporarily. 1 hour later, the unit will select the proper mode due to the above condition.
5. COOL mode control
5.1 4-way valve being powered off, compressor run/stop will depends on the temperature difference between the room temperature and the set temperature.
5.2 In cooling mode, every time the compressor starts up, within 6 minutes, the compressor will not be limited by the temperature sensor, but the set temperature change, shutoff signal and protection action will not be limited by 6-minute protection, and the compressor can stop immediately.
5.3 ΔT≥1 compressor will run; ΔT-1 compressor will stop;
-1<ΔT<1 compressor will stay in original state
5.4 Anti-freezed protection (invalid in compulsory operation,
trial running, heating mode)
When the unit has run for over 6 minutes after compressor
starts up, if indoor coil temperature Tg<1, the compressor and the outdoor motor will stop, and the unit will change to FAN mode; 9 minutes later after compressor stops and when indoor coil temperature rises to 10℃, the unit will resume to COOL mode, the compressor and the outdoor motor will run again.
5.5 Outdoor fan control: (realized by outdoor when with outdoor conmmunication function)
if the temp. of indoor coil sensor Tg<6, control the outdoor fan by the temp. of outdoor coil
sensor;
if the temp. of outdoor defrost sensor Tc<34, the outdoor fan will be OFF and lasted 45s at least; if the temp. of outdoor defrost sensor Tc>44℃, the outdoor fan will be ON; if the temp. of outdoor defrost sensor 34℃≤Tc≤44℃, the outdoor fan will remain in the original
state.
5.6 Temperature cutoff protection
In cooling mode, the unit will check indoor coil temperature every time the compressor has run for 1
minutes, when indoor coil temperature Tg>Tr5, the unit will stop and 3 minutes later restart up; if the temperature cutoff occurs for 3 times continuously, the unit will stop and alarm.
6. DRY mode control
6.1 When the uint enters DRY mode for the first time, the compressor, outdoor motor and indoor
motor will perform according to the below conditions:
Ts +3
Ts -3
cooling
heating/blowing
cooling
Te mp .
Te mp .
heating/blowing
run
stop
1
1
run
stop
ΔT
ΔT
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
43
ΔT2, the compressor and the outdoor motor will run continuously, indoor motor will run at the set speed, this area is defined as Area A; 0≤ΔT2, the compressor and the outdoor motor will always run for 10 minutes and then stop for 6 minutes, indoor motor will be LOW speed, this area is defined as Area B; ΔT0, the compressor and the outdoor motor will stop, indoor motor will run at Low speed, this area is defined as Area C.
6.2 After the unit is running in DRY mode, the system will
change over among Area A, Area B, and Area C (the conversion temperature difference ±1℃) If the system is in Area A, when ΔT<1, change to Area B; If the system is in Area C, when ΔT>1, change to Area B; If the system is in Area B, when ΔT>3, change to Area A; WhenΔT<-1, change to Area C.
6.3 Anti-freezed protection (invalid in compulsory operation,
trial running, heating mode)
When the unit has run for over 6 minutes after compressor
starts up, if indoor coil temperature Tg<1, the compressor and the outdoor motor will stop, and the unit will change to FAN mode; 9 minutes later after compressor stops and when indoor coil temperature rises to 10, the unit will resume to COOL mode, the compressor and the outdoor motor will run again.
6.4 Outdoor fan control: (realized by outdoor when with outdoor conmmunication function)
if the temp. of indoor coil sensor Tg<6, control the outdoor fan by the temp. of outdoor coil
sensor;
if the temp. of outdoor defrost sensor Tc<34, the outdoor fan will be OFF and lasted 45s at least; if the temp. of outdoor defrost sensor Tc>44℃, the outdoor fan will be ON; if the temp. of outdoor defrost sensor 34℃≤Tc≤44℃, the outdoor fan will remain in the original
state.
6.5 Temperature cutoff protection
In cooling mode, the unit will check indoor coil temperature every time the compressor has run for 1
minutes, when indoor coil temperature Tg>Tr5, the unit will stop and 3 minutes later restart up; if the temperature cutoff occurs for 3 times continuously, the unit will stop and alarm.
7. HEAT mode control
7.1 4-way valve control: in heating mode, compressor startup----4-way valve being electrified 10
seconds ahead; compressor running----4-way valve retains original state; compressor shutoff----4-way valve being powered off 2 minutes and 50 seconds later (except for defrosting, 4-way valve being electrified 5 seconds ahead, and being powered off 55 seconds later).
7.2 In heating mode, for everytime the compressor startup (thermostat ON), within 6 minutes, the
4-way valve will not be limited by the temperature sensor, but for the set temperature change, shutoff signal and the protection, the compressor can stop immediately without 6-minute limitation.
7.3 ΔT≥1 compressor running, indoor motor runs at anti-cold air mode; ΔT-1 compressor stops, indoor motor runs at blowing remaining heat mode;
-1<ΔT<1 compressor retains original state
7.4 Overheat protection (for the unit with outdoor PCB, the outdoor motor is controlled by outdoor unit,
but the compressor is still controlled by indoor unit, and their temperature points will not be accordant completely)
In heating mode, compressor has started up and indoor motor has run for over 30 seconds, if
indoor coil temperature Tg>60, outdoor motor will stop; if Tg<56, and outdoor motor has stop for 45s, outdoor motor will run again; if Tg>73, the compressor will stop and indoor motor will run according to the thermostat state. After the compressor stops for 3 minutes and Tg reduces to 48℃, the unit will resume to heating mode, and the compressor and the outdoor motor will run again.
7.5 Temperature cutoff protection
In heating mode (besides the defrosting), the unit will check indoor coil temperature every time the
compressor has run for 1 minutes, when indoor coil temperature TgTr-5, the unit will stop and 3 minutes later restart up; if the temperature cutoff occurs for 3 times continuously, the unit will stop and
A
B
3
1
1
1
B
C
C
A
ΔT
ΔT
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
44
alarm.
7.6 Anti-cold air function in heating mode
After entering heating mode, or last defrosting is over, the compressor will start up, if Tg<28℃,
indoor motor will stop; if 38℃>Tg≥28℃, indoor motor will run at low speed; if Tg≥38℃ or the compressor has run for over 4 minutes, indoor motor will run at the set speed; once the motor has started up, it will not stop because of Tg reduction.
7.7 Blowing remaining heat function
In heating mode, the thermostat is OFF, the compressor stops, indoor motor will run at low speed
until Tg<28℃ and has run for 50 seconds at least.
Note: in heating mode, “the compressor stops----indoor motor delays to stop” adjust if the pipe blows remaining heat; “the compressor startup----indoor motor delays to start up” adjust if the pipe is anti-cold air; in other conditions, the compressor and the indoor motor are allowable not to be in company. In cooling mode, the motor will run according to the control, not together with the compressor.
7.8 Defrosting function in heating mode In defrosting and when the compressor resumes to run for 3 minutes after defrosting is over, the unit will not adjust the sensor failure.
7.8.1 Manual defrost: In heating mode, the set temperature 30 and in high speed, in 5 seconds, press SLEEP button 6 times continuously, then the buzzer will sound 3 times, you can enter the manual defrosting. At this moment, the unit will not adjust the enter condition of defrost and begin to defrost function directly, whose procedure is as the same as the auto defrost; the quit condition is that the defrosting time is up to 5 minutes.
7.8.2 Auto defrost enter condition: a) the compressor has run for 45 minutes continuously or for 75 minutes in all and has run for over 10 minutes continuously. b) the compressor and outdoor fan running normally. c) the temp. of indoor coil sensor lower than 45, d) the defrosting temp. lower
than –8 (use the defrosting start signal from outdoor in the condition of with outdoor communication ).
7.8.3 Auto defrost quit condition: The defrosting temp. over 14 or the defrosting time is over 12 minutes (use the defrosting end signal from outdoor in the condition of with outdoor communication )
7.8.4 Defrost process : a) enter defrosting mode, the compressor, outdoor and indoor fan motor stops;
b) 55 seconds later, 4-way valve will be reverse, after more 5 sensonds, compressor begins to run; c)
defrosting is over, compressor stops, outdoor fan running at high speed; d) 55 seconds later, 4-way
valve runs and compressor starts up. The indoor fan motor will run at anti-cold air condition.
7.8.5 For the unit with auxiliary electric heating function: a. If the auxiliary electric heating function is working when the defrosting condition is met, please
stop electric heater firstly, 20 seconds later, defrosting can begin;
b. After defrosting, the unit will adjust the working state of electric heater according to the setting
before defrosting.
7.9 Auxiliary electric heating function (valid in heating mode or heating state in AUTO mode) Enter condition: 1) ΔT>1; 2) Thermostat ON and running for 1 minute; 3) Tr<26; 4) Indoor motor running; 5) Electric heating function start signal available (cancelled); 6) The system working in heating mode or in heating state of AUTO mode; 7) Tg<48
If the above conditions can all be met, the electric heating function will work. Quit condition: 1) ΔT≤1; 2) Thermostat OFF; 3) Tr>26; 4) Indoor motor stops; 5) Electric heating function start signal not available (cancelled); 6) The system in non-heating operation; 7) Tg>52
If one of the above conditions can be met, the electric heater will stop.
8. FAN mode control
The compressor and the outdoor motor will stop running, indoor motor can be set at high/med/low speed, the fan blade can swing or stay at one position. In this mode, you can set the TIMER and SLEEP function.
9. CLOCK setting and TIMER function
The unit can set 24-hour TIMER ON/OFF, and the min. unit is 1 minute, after being set, the timer lamp of indoor will be on, and after the timer is over, the timer lamp will be off. TIMER ON: RUN LED is off, compressor LED is off, and TIMER LED is on, the unit is in stop state.
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
45
When timer is over, the unit begins to run, and the timer LED is off. The unit operation begins from receiving the timer signal for the last time. The SLEEP function only can be set before the TIMER ON begins. TIMER OFF: the unit running, the timer LED on, while the timer is over, timer LED off, the unit will stop, the sleep can be set, the sleep time will replace the original time of TIMER ON/OFF. TIMER ON/OFF set at the same time: when the timer on/off is set, the timer LED will be off; the SLEEP function can be set, the sleep time will replace the original time of TIMER ON/OFF.
10 SLEEP function (energy saving function at night)
101 Standard sleep function: in cooling or dry mode, after running at SLEEP mode for 1 hour, the set temperature will rise 1, another 1 hour later, the set temperature will rise
another 1; the unit continues running for 6 hours, then the unit will stop.
10.2 Standard sleep function: in heating mode, after running at SLEEP mode for 1 hour, the set temperature reduces 2, another 1 hour later, the set temperature will
reduce 2, and another 3 hours later, the set temperature rises 1; the unit continues running for 3 hours, then the unit will stop.
10.3 Non-standard SLEEP function: the sleep function
can realize 1~8 hours sleep mode when being combined with the TIMER function.
1 When in Auto mode, the unit will make SLEEP operation due to the setting.
2 After setting SLEEP function, the clock can not be adjusted.
3 If sleep time is no more than 8 hours, when the time arrives, the unit wil shut off.
4 If sleep function is set after setting TIMER OFF function, the unit will execute as the SLEEP
function.
5 If SLEEP function is set, the TIMER function can not be set.
6 If sleep function is set after setting TIMER ON function, the sleep function only can be set
befroe the TIMER ON time arrives.
7 After setting sleep function, press CLOCK button to check the clock; press TEMP button to
display the set temperature, and press again to change the set temperature.
11 Water level inspection and water pump control
1) In COOL (including cooling state of AUTO mode and the compulsory cooling) and DRY mode, as long as the compressor runs, water pump will work; and once the compressor stops, water pump will stop 5 minutes later;
2) In standby state of cooling mode, heating mode and fan mode (including auto fan mode), after
water tank is full, the float switch will disconnect, if the controller detects this signal for 2 seconds, the water pump will begin to work. After the float resets, water pump will continue working and stops 5 minutes later;
3) If the water-full signal is detected for over 5 minutes, the compressor will stop; water pump will
work for 5 minutes and stop for 5 minutes, then repeat as a cycle, until the float resets, the water pump will stop 5 minutes later; if water pump has repeated for 4 cycles, the float can not reset, and the unit will alarm water drainage abnormal. And the water pump will continue the cycle.
12. System protection
12.1 3-minute protection for compressor startup After the compressor stops, at least 3 minutes later, the compressor can restart up; the compressor can restart up. Being electrifed for the first time, there is 3-minute delay protection.
12.2 Time shorting function If the time shorting port is in short circuit, the unit will perform a 1/60 time shorting control.
12.3 High pressure protection
After compressor is running for 3 minutes, the unit will check the pipe pressure, when the pipe
pressure is too high, 30 seconds later, compressor and outdoor fan motor will stop, and then 3
minutes later, the unit will be normal. Within 30 minutes, if the compressor stops and will send
failure because of too high pressure for 3 times.
12.4 Low pressure protection
Ts
Ts +1
Ts +2
Ts
Ts -2
Ts -3
Ts -4
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
46
After compressor is running for 3 minutes, the unit will check the pipe pressure, when the pipe pressure is too low and low pressure switch is running for 30 senconds, compressor and outdoor fan motor will stop and will send failure
13. Trouble code
The remote receiver, wired controller and indoor PCB indicator all can indicate the failure code.
Remote
control
indoor
PCB flash
times
Wired
controll
er
display
Central controll
er
display
Fault description Possible cause Remedy
10 08(08H) 21D
Fault in drain system
Float switch is open 25m or longer
due to the signal, resumable
1 01(01H) 01D
Indoor ambient temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
2 02(02H) 02D
Indoor pipe temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
3 74(4AH) 11D
Outdoor ambient temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
4 73(49H) 12D
Outdoor pipe temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
5 72(48H) 10D
Overcurrent Detector CT current is above
the limit 3 times within 30m.
Need to be checked, reset
6 83(53H) 14D
High pressure malfunction
High pressure switch acts for 3 times in 30m
Need to be checked, reset
7 71(47H) 22D
Power failure
Wrong phase, phase failure or loss
Need to be checked, reset
8 07(07H) 06D
Communication failure between wired controller and indoor unit
communication abnormal for more than 4m continuously
due to the signal, resumable
9 06(06H) 05D
Communication failure between indoor and outdoor units
communication abnormal for more than 4m continuously
due to the signal, resumable
11 11( 0BH) 30D
External alarm signal input
External alarm is cut out for 10s or longer
due to the signal, resumable
12 03(03H) 20D
Fault in coil/suction line temp. sensor
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
13 13(0DH) 31D
Temperature shut-off
Directional valve malfunction repeats 3 times
Need to be checked, reset
14 76(4CH) 15D
Fault in discharging temp. sensor
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
15 05(05H) 17D
EEPROM error
EEPROM data loss Default
operation
16 84(54H) 26D
Low pressure malfunction
low pressure switch is activated
Need to be checked, reset
17 80(50H) 15D
Compressor overheat
Detected temperature of
discharge line is higher than 120
Resrorable when lower than 100
18 12(0CH) 23D
Fault in operation mode
Indoor units operate in
different modes
Resrorable in same o
peration
mode
19 75(4BH) 18D Outdoor coil
B(suction sensor-multi)
sensor broken down or short circuit for more than 2m continuously
due to the signal, resumable
20 77(4DH 15D Outdoor
sensor broken down or short due to the signal,
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
47
) discharge B (oil
temp. sensor-multi)
circuit for more than 2m continuously
resumable
21 20(32D) 07D
Module failure Module overheat, overcurrent,
short-circuit
due to the signal, resumable
22 36(54D) 08D
Fault in zero-load
Current sensor failure or
compressor is not started
due to the signal, resumable
14 Jumper selection (shows jumper connected, ON; ×shows jumper disconnected, OFF; * shows no limitation)
J1 J2 J3 J4 Wired control/ infrared control
/×
* * *
Temp. compensation available/not available
*
/×
* *
With/no outdoor PCB * *
/×
*
Cooling only/heat pump * * *
/×
J5 J6 Time shorting switch
/×
* * *
Forced or not *
/×
* *
Ornarment or not * *
×/
*
Oxygen or not * * *
×/
J7 J8 J9 J10 Other/2P convertible
/×
* * *
single split/ multi split *
/×
* *
Indoor unit address 0/other
* *
/×
*
2P convertible /single blade
* * *
/×
15. Network address selection (shows jumper connected, ON; ×shows jumper disconnected, OFF)
SW1 SW2 address 1 2 3 4 1 2 3 4 1
× × × × × × ×
2
× × × × × ×
3
× × × × × ×
4
× × × × ×
× shows
passive port
switch
control AND
5
× × × × × ×
6
× × × × ×
……
…… …… …… …… …… ……
126
×
127
×
128
showes
passive port
switch
control – the
later
entering in
priority
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
48
Commercial Air Conditioner
CIRCUIT DIAGRAM OF INDOOR UNIT
0010576546
(FREEZE) CN8
SW2
BL
P13
(HUMI)
(PUMP)
(HEAT)
Y
(L)
(FRESH)
P8 P9
P7
P12
P10
P11
(COMM)
W
(N')
(M)
(H)
SW3
P17
(L')
P14
P15
SW5
SW4
P16
CN4
CN17
CN5
MOTOR
FILTER
CN1
TRANS.
SWITCH
(DOOR)
(CONTROLLER)
(FLOAT)
CN15
CN13
(UP-DOWN)
(12V/ALM)
CN14
A
B
(ALARM)
CN16
(REMOTE)
CN11
CN12
FLOAT
REMOTE
RECEIVER
REMOTE
CN2
P
CN1
MC1
COM
MC2
N
ON
12
ON
1234
CN19
CN20
3
W:WHITE B:BLACK R:RED Y:YELLOW OR:ORANGE BL:BLUE BR:BROWN Y/G:YELLOW/GREEN TRANS.:TRANSFORMER
FG
L
CONTROLLER
CENTRALIZED
RBLBBW
FUSE T2.0A/250VAC
(RECEIVE BOARD)
(SWING)
(OXYGEN)
OR
YY
M
SWING
MOTOR
M
FAN
MOTOR
M
2
11
1
4
8
7
9
10
CN21
CN7
FUSE
T6.3A/250VAC
T3.15A/250VAC
P4(N2)
POWER SUPPLY
M
P5(N3)
TO OUTDOOR UNIT
R
2
3
1
B
W
L
BR
BLNY/G
WRBWB
Y/G
OR
P1(L)
P2(N)
P3(N1)
FAN CAP.
Y/G
MOTOR
MOTOR
M
SWING
PUMP
R
P6(N4)
SW1
@
@
12
(ROOM/PIPE)
CN6
TEMP. SENSOR
SENSOR
PIPING TEMP.
ROOM
6
5
13
M
M
ON
1234
ON
1234
ON
1234
?
6. IN AC242ACBEA/AC242ACEAA, DASHED LINES MARKED @
CONNECTED
TO "1 , 2" ON TERMINAL BLOCK, AND THERE ARE NO
LINES BETWEEN "1 AND L" , "2 AND N".
IN *******BIA OR ******ERA TYPE,THE POWER SUPPLY COME FROM OUTDOOR UNIT,
AND THE FUSE TYPE IS T3.15A/250VAC
7.ABOUT THE TERMINAL BLOCK,MARK "BL" IS EQUAL "B" AND THE "BR" IS EQUAL "W".REFER TO OPERATION MANUAL TO SET SW1-SW5
NOTE:
1. PARTS 1 2 3 ARE NOT AVAILABLE
2. PARTS 4 5 6 ARE OPTIONAL, AND THE LINE MARKED 13 ONLY AVAILABLE IN CONVERTIBLE TYPE
3. PART 7 NOT AVAILABLE IN DUCT TYPE
4. PARTS AND CONNECTED WIRES IN DASHED FRAME 8 ONLY FOR AB14/182ACBEA
5.PARTS AND CONNECTED WIRES IN DASHED FRAME 9 10 ARE NOT AVAILABLE IN AD14/182AMBEA, AND IN
CONVERTIBLE TYPE,
CORRESPONDINGLY THERE IS A CLIP ON PCB.
PARTS AND
CONNECTED
WIRES IN DASHED FRAME 11 ONLY FOR
AC142/182/242ACBEA/AC
242ACEAA
TYPE .PARTS AND
CONNECTED
WIRES IN DASHED FRAME 12 DETERMINED BY
PRODUCTS TYPE.
WIRED CONTROLLER
10. Electric data
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
AC122ACERA AD122ALERA
AB122ACERA
CIRCUIT DIAGRAM OF INDOOR UNIT
0010576979
FUSE1
CN1
CN15
CN20
LOW
MID
HIGH
CN21
CN22
N2
TRANS.-I
CN4
SIGNAL
LED3
CN3
N
CN2
L
T3.15A/250VAC
CN13
TRANS.-II
CN12
CN11
REMOTE
CN10
FLOAT
CN8
ALARM
CN7
RECEVIER
CN6
STEPMOTOR
PIPE ROOM
CN14
CONTROLLER
CN16
CN17
N1
CN18
PUMP
M
WIRED CONTROLLER
ROOM TEMP. SENSOR
PIPING
TEMP.
SENSOR
RECEIVE BOARD
FLOAT SWITCH
REMOTE CENTRALIZED CONTROLLER
M
PUMP MOTOR
TRANSFORMER
BM4
ON
1234
ON 12
ON
1234
ON 1234
BM3
BM2
BM1
STEP MOTOR
1
Y/G
R
R
R Y BL W
BBW
W
Y
Y
32
Y/G
Y/G
NOTE:
1.THE PARTS IN DASHED FRAME ARE OPTIONAL
2.
REFER TO OPERATION MANUAL TO SET
BM3 AND BM4
3.USER SHOULD NOT TO SET BM1 AND BM2 W:WHITE B:BLACK BR:BROWN BL:BLUE R:RED Y:YELLOW Y/G:YELLOW/GREEN TEMP.:TEMPERATURE
LED2
LED1
Y/G
L
BL
BL
BR
BR
N
TO OUTDOOR UNITPOWER SUPPLY
Itophome
MOTOR CAPACITOR
M
FAN MOTOR
Y/G
49
CN4
CN15
CN17
CN20
CN21
CN22
CN6
CN7
CN8
CN10
CN11
CN12
CN13
CN14
LED1
LED2
BM2
BM1
BM3
BM4
CN19
CN16
CN3
CN1
CN2
CN18
0010452325E for AB122ACERA
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
50
CN12
CN15
CN16
CN11
CN17
LED1
CN14
CN13
CN20
SW3
SW2
CN21SW5
SW4
CN19
CN7
LED4
LED5
CN5
CN4
P5
P7
P9
P6
P8
P10
P12
P11
P15
P14
P13
P17
CN1
P4
P3
P2
P1
P16
CN8
CN6
SW1
0010451690E for AC122ACERA and AD122ALERA
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
51
Commercial Air Conditioner
REACT
OR
CAP
ACIT
OR BOARD
LX1
NOTES:
1.DASHED P
AR TS
ARE JUST
CAN SELECT
ONE BETWEEN
THIS TWO F
AN MOT
OR
2.P AR TS IN DASHED FRAMES
ARE OPTIONAL
3. THE LED1-5 ON LED BOARD ARE USED FOR ERROR ALARM
4.PLEASE DO NOT
PRESS SW1-4 IN DASHED FRAME
5.PLEASE DO NOT
CHANG THE DIP
SWITCH ON LED BOARD
CONDENSER INLET
TEMP
. SENSOR
DEFROST
TEMP.SENSOR
LOW PRESSURE
SWITCH
AMBIENT
TEMP. SENSOR
HIGH PRESSURE
SWITCH
M
EEV
P
CN3
CN18
CN16
P
CN17
CN8
CN10
CN6
CN7
SW3
SW1
SW2
CN5
CN15
SW4
CN1
1
T O INDOOR UNIT
P6 P5
P2
P3
P1
N
L
COM
W
R
R
R
BL
BL
BL
R
B
P4
1
2
3
Ground
MAIN BOARD
CN13
CN1
CN12
Y/G
Y/G
WIRING DIAGRAM OF OUTDOOR UNIT
0150501661
4-W
A Y
V AL
VE
COMPRESSOR DISCHARGE SENSOR
COMPRESSOR SUCTION SENSOR
ON
LED BOARD
LED3
LED4
LED5
1
4
3
4
3
5
1
2
3
4
6
7
5
7
1
2
LED1
LED2
AC F
AN MOT
OR
DC F
AN MOT
OR
M
SPDU
L(IN)
N(IN)
CN5
B:BLACK
BL:BLUE
W :WHITE
R:RED
Y/G:YELLOW/GREEN
TEMP
.:TEMPERA
TURE
CN2
Y/G
CN3
M
2
M
S(W)
V
COMPRESSOR
LX2
P
CON24
CON22
CN20
CON21
CON23
N
W
P(OUT+)
N(OUT
-)
C(T)
U
R
OR:ORANGE
R
W
B
P6
P7
CRANKCASE
HEA
TER
6
T25A
/250V
AC
FUSE101
AU122AEERA
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
52
Commercial Air Conditioner Model: AU242AGERA AB242ACERA
AC242ACERA AD242ALERA AD242AMERA
P5
P1
CN16
CN1
CN2
CN19
CN20
CN18
CN17
CN24
LED001
CN5 CN6
CN7 CN10
CN8
CN11 CN3
SW3 SW2
SW1
CN12
CN15
CN13
P7
P6
P8
P2
P3
P4
SW4
Ou tdoor PCB 0151800037
53
Commercial Air Conditioner
10.3 Sensor characteristic
Model Name Code Sub-part code characteristic
Outdoor
ambient temp.
sensor
0010450192 001A3800082
R25=10K±2.5%
B25/50=4200K±3%
Compressor
sunction sensor
001A3900062 /
R25=10K±3%
B25/50=3700K±3%
Outdoor defrost
sensor
0010450194 001A3800093
R25=10K±3%
B25/50=3700K±3%
Compressor
discharge
sensor
0010450196 001A3800096
R80=50K±3%
B25/80=4450K±3%
AU122AEERA
Condenser inlet
temp. sensor
0010451307 001A3800093
R25=10K±3%
B25/50=3700K±3%
Indoor ambient
temp. sensor
001A3900005 001A3900003
R25=23K±2.5%
B25/50=4200K±3%
AB122ACERA
AC122ACERA
Indoor coil
temp. sensor
001A3900006
001A3900004
R25=10K±3%
B25/50=3700K±3%
Indoor ambient
temp. sensor
0010451323
001A3900003
R25=23K±2.5%
B25/50=4200K±3%
AD122ALERA
Indoor coil
temp. sensor
001A3900006
001A3900004
R25=10K±3%
B25/50=3700K±3%
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
54
Commercial Air Conditioner
T()
Rnom(K)
T()
Rnom(K)
-20
90.79 24 10.43 68 2.09
-20
281.34
24
24.12
-19 85.72 25 10 69 2.03
-19
263.56
25
23
-18 80.96 26 9.59 70 1.96
-18
247.04
26
21.94
-17 76.51 27 9.21 71 1.9
-17
231.66
27
20.94
-16 72.33 28 8.84 72 1.85
-16
217.35
28
19.99
-15 68.41 29 8.48 73 1.79
-15
204.02
29
19.09
-14 64.73 30 8.15 74 1.73
-14
191.61
30
18.23
-13 61.27 31 7.83 75 1.68
-13
180.04
31
17.42
-12 58.02 32 7.52 76 1.63
-12
169.24
32
16.65
-11 54.97 33 7.23 77 1.58
-11
159.17
33
15.92
-10 52.1 34 6.95 78 1.54
-10
149.77
34
15.22
-9 49.4 35 6.68 79 1.49
-9
140.99
35
14.56
-8 46.86 36 5.43 80 1.45
-8
132.78
36
13.93
-7 44.46 37 5.6
-7
125.11
37
13.34
-6 42.21 38 5.59
-6
117.93
38
12.77
-5 40.08 39 5.73
-5
111.22
39
12.23
-4 38.08 40 5.52
-4
104.93
40
11.71
-3 36.19 41 5.32
-3
99.04
41
11.22
-2 34.41 42 5.12
-2
93.52
42
10.76
-1 32.73 43 4.93
-1
88.35
43
10.31
0 31.14 44 4.9
0
83.5
44
9.89
1 29.64 45 4.58
1
78.94
45
9.49
2 28.22 46 4.42
2
74.67
46
9.1
3 26.4 47 4.26
3
70.65
47
8.74
4 25.61 48 4.11
4
66.88
48
8.39
5 24.41 49 3.97
5
63.33
49
8.05
6 23.27 50 3.83
6
60
50
7.73
7 22.2 51 3.7
7
56.86
51
7.43
8 21.18 52 3.57
8
53.91
52
7.14
9 20.21 53 3.45
9
51.13
53
6.86
10 19.3 54 3.33
10
48.51
54
6.6
11 18.43 55 3.22
11
46.04
55
6.34
12 17.61 56 3.11
12
43.72
56
6.1
13 16.83 57 3.11
13
41.52
57
5.87
14 16.09 58 2.9
14
39.45
58
5.65
15 15.38 59 2.81
15
37.5
59
5.44
16 14.71 60 2.72
16
35.66
60
5.24
17 14.08 61 2.63
17
33.92
18 13.48 62 2.54
18
32.27
19 12.9 63 2.49
19
30.72
20 12.36 64 2.38
20
29.25
21 11.84 65 2.3
21
27.86
22 11.34 66 2.23
22
26.54
23 10.87 67 2.16
23
25.3
R25=10KΩ±3% B25/50=3700K±3%
R25=23KΩ±2.5% B25/50=4200K±3%
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
55
Commercial Air Conditioner
T()
Rnom(K)
-30 11600 13 933.4 56 127.3
-29 10860 14 886.4 57 122.1
-28 10170 15 841.9 58 117.2
-27 9529 16 800 59 112.5
-26 8932 17 760.8 60 108
-25 8375 18 722.8 61 103.8
-24 7856 19 687.3 62 99.68
-23 7372 20 653.8
-22 6920 21 622
-21 6498 22 592
-20 6104 23 553.6
-19 5736 24 536.6
-18 5392 25 511.1
-17 5071 26 486.9
-16 4770 27 464
-15 4488 28 442.3
-14 4225 29 421.7
-13 3978 30 402.1
-12 3747 31 383.6
-11 3531 32 366
-10 3328 33 349.3
-9 3138 34 333.5
-8 2960 35 318.4
-7 2793 36 304.1
-6 2636 37 290.5
-5 2489 38 277.6
-4 2351 39 265.3
-3 2221 40 253.6
-2 2099 41 242.5
-1 1984 42 232
0 1877 43 221.9
1 1775 44 212.3
2 1680 45 203.2
3 1590 46 194.5
4 1506 47 186.3
5 1426 48 178.4
6 1351 49 170.9
7 1280 50 163.7
8 1214 51 155.9
9 1151 52 150.4
10 1092 53 144.2
11 1036 54 138.3
12 983.2 55 132.7
R80=50K±3% B25/80=4450K±3%
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
56
11. Troubleshooting
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
yes
if the refrigerant is normal
improve the ventilation condition
no
no
stop the unit, restart up until power module temperature has reduced
yes
if compressor wiring is
correct
yes
if compressor winding is normal, and the each phase resistor is in balance
no
compressor can not start up
no
wiring correctly
no
replace compressor
Alarm condition: ambient temperature sensor is in short circuit or open circuit
if sensor is fixed
well
Relocate
reconnect
no
check if the wiring is
correct according to
wiring diagram
Is sensor short-circuit or open-circuit?
Replace sensor
Is sensor resistance acceptable?
Replace sensor
yes
yes
yes
no
no
no
1) Sensor failure
Replace PCB
Check if the power normal
outdoor indicator indicate the above failure
check if the any current among compressor input port U-V-W is over high
check if the system is blocked
yes
yes
no
check if module bottom temperature is over high, more than 90degree
if ventilation beside the module radiator is good
yes
compressor startup procedure is abnormal, and vibrates seriously
2) Outdoor power module failure The following troubleshooting is available for: a. IPM failure(00001) b. Compressor U-phase,V-phase and W-phase over-current(00101), total unit over-current(00101) c. Compressor start-up abnormal(10001), Compressor jam(01111), Compressor phase loss(11110), Module lack-voltage protection(11011), Detect PFC over-current(01100), PFC voltage abnormal(11111)
yes
yes
if the total load is too big
no
adjust the power supply as 220-230VAC, 50Hz
if the total unit
operate normally
replace the module
no
57
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
no
yes
Alarm condition: outdoor DC motor is blocked rotor or broken, abnormal.
outdoor indicator LED indicate DC motor abnormal
3) Outdoor DC motor abnormal
adjust fan blade to make it run normally
adjust lead wire of fan motor
yes
no
Check if the lead wire of DC motor is broken or short-connected
Check if the outdoor unit fan blade is blocked by some objects
Replace motor
Warning: For outdoor DC fan motor, forbidden to pull off the plug when being electrified.
4) Communication error between indoor and outdoor units
indoor unit troubleshooting
no
check if the failure is eliminated
yes
compressor can not startup after unit is switched on for 4 minutes, indoor failure indicator flashes 9 times
no
check if wiring between indoor and outdoor is correct, power supply is 50Hz
if indoor unit alarms other failure codes
check if the indoor PCB worked normally
yes
eliminate other faults
adjust wiring and power supply, note not connect the outdoor connecting port 1/2 wrong
Replace outdoor PCB
no
no
check the indoor wires, confirm the normal operation of indoor PCB
yes
5) Compressor discharging temperature protection Alarm condition: Within one hour after compressor is running, compressor discharging temperature is
over 115degree for 3 times continously.
adjust piping
no
no
replace sensor
yes
replace PCB
yes
no
check if discharging temp. sensor resistance is normal
check if refrigerant is too much or too less
check if the system piping is blocked
adjust refrigerant
yes
outdoor indicator indicate the above failure
58
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
if high pressure switch is normal
check if the refrigerant is too much or less by the pressure gauge
no
no
yes
outdoor failure indicator indicate high pressure failure
check if the wiring between indoor and outdoor is correct
no
outdoor indicator shows power faliure
check if power supply is normal
yes
no
adjust power supply as 50HZ
220-230VAC
EEPROM data is missing, replace PCB
check if EEPROM welded points on outdoor PCB is in good condition
outdoor indicator shows the above failures
yes
no
adjust EEPROM welded point
outdoor indicator shows the above failures
replace the outdoor module
when compressor starting up, unit stops abnormally and can not start up normally
yes
6) Outdoor high pressure protection Alarm condition: When compressor running, high pressure is over 4.5 MPa for 30 seconds continously
check if the piping is blocked
yes
adjust refrigerant
adjust piping
yes
replace sensor
7) Outdoor power supply is abnormal Alarm condition: if power supply is not 50Hz as standard, which will affect the normal communication and
cause air conditioner bad operation.
adjust wiring
8) EEPROM failure(01110), Compressor parameter error(10010) Alarm condition: EEPROM is fault or data is missing
9) Circuit error detected by current(10011), Module error(01101), Module PWM select circuit error(01011) Alarm condition: when compressor is running, the unit will be abnormal or stop
Replace the outdoor PCB
yes
59
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
measure actual pressure by a pressure gauge to adjust the output failure
Lack of refrigerant, charge additional refrigerant and check if piping leaks, if yes, replace piping
check if high pressure is low,too
yes
check if piping is blocked
dredge piping
yes
replace pressure switch
low pressure abnormal
no
yes
check if the wiring between outdoor PCB and module is correct
compressor not start up, outdoor alarms, check if there is other failure
outdoor indicator flashes 22 times
yes
no
no
eliminate other failures
replace PCB
yes
if problem is solved
no
outdoor indicator flashes 24 times
adjust wiring
replace module
Alarm condition: outdoor system pressure is lower than 0.05MPa
no
yes
no
refrigerant charging amount is not appropriate, recharging or remove some refrigerant
yes
repair 4-way valve
no
relpace outdoor PCB
check if the direction of 4-way valve is correct
clean indoor/outdoor heat exchanger
check if indoor evaporator or outdoot condenser is too dirty
yes
check if the 4-way valve
port of PCB output 230V
check if outdoor pressure is normal
no
yes
outdoor failure lamp indicates 28
(12) 4-way valve reversing failure, systerm lack of refrigerant or discharging side dirty and blocked
Alarm condition: alarm and stop the unit when Td-Tci<=25 and lasts for 1 minute after the compressor has started for 10 minutes check in heating mode, confirm the failure if it occurs 3 times in 1 hour
(13) systerm lack of refrigerant or discharging side dirty and blocked
Alarm condition: alarm and stop the unit when Td-Tci>=25 and lasts for 1 minute after the compressor
has started for 10 minutes in cooling mode, confirm the failure if it occurs 3 times in 1 hour
outdoor failure lamp indicates 29
check if outdoor pressure is normal
refrigerant charging amount is not appropriate, recharging or remove some refrigerant
no
yes
check if indoor evaporator or outdoot condenser is too dirty
yes
yes
clean indoor/outdoor heat exchanger
10) Communication failure between outdoor PCB and module
11) Outdoor low pressure abnormal
60
Commercial Air Conditioner
12. Noise level
Noise level-AD122ALERA
9
1317212529333741454953
25
31. 5
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
6300
8000
10000
12500
160000
20000
Third octave band frequency Hz
Sound pressure level DB
heating low
heating middle
heating high
super heating high
cooling low
cooling middle
cooling high
super cooling high
fan low
fan middle
fan high
super fan high
Noise level-AB122ACERA
1014182226303438424650
54
2
5
3
1. 5
4
0
5
0
6
3
8
0
1
00
1
25
1
60
2
00
2
50
3
15
4
00
5
00
6
30
8
00
1
00
0
1
25
0
1
60
0
2
00
0
2
50
0
3
15
0
4
00
0
5
00
0
6
30
0
8
00
0
1
00
00
1
25
00
1
60
00
0
2
00
00
Third octave band frequency Hz
Sound pressure level DB
heating low
heating middle
heating high
cooling low
cooling middle
cooling high
fan low
fan middle
fan high
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Commercial Air Conditioner
Noise level-AU122AEERA
7
111519232731353943475155596367
2
5
3
1.5
4
0
5
0
6
3
8
0
1
00
1
25
1
60
2
00
2
50
3
15
4
00
5
00
6
30
8
00
1
000
1
250
1
600
2
000
2
500
3
150
4
000
5
000
6
300
8
000
1
0000
1
2500
1
60000
2
0000
Third octave band frequency Hz
Sound pressure level DB
heating low
heating middle
heating high
cooling low
cooling middle
cooling high
fan low
fan middle
fan high
Noise level-AC122ACERA
1014182226303438424650
2
5
3
1.
5
4
0
5
0
6
3
8
0
1
00
1
25
1
60
2
00
2
50
3
15
4
00
5
00
6
30
8
00
1
00
0
1
25
0
1
60
0
2
00
0
2
50
0
3
15
0
4
00
0
5
00
0
6
30
0
8
00
0
1
00
00
1
25
00
1
60
00
0
2
00
00
Third octave band frequency Hz
Sound pressure level DB
heating low
heating middle
heating high
cooling low
cooling middle
cooling high
fan low
fan middle
fan high
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Commercial Air Conditioner
Sincere Forever
Haier Group
Haier Industrial Park, No.1, Haier Road
266101, Qingdao, China
http://www.haier.com
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA