Haier 0010554405B User Manual

Installation Manual of Room Air Conditioner
Read this manual before installation Explain sufficiently the operating means to the user according to this manual.
Necessary Tools for Installation
1.Driver
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)
Accessory parts
No. Accessory parts
1
2
3
4
5
6
7
8
Remote controller
R-03 dry battery
Mounting plate
Drain hose
Steel nail, cement
4X25
Plastic cap
Screw
Drain-elbow
4X50
5.Torque wrench(17mm,22mm,26mm)
6.Pipe cutter
7.Flaring tool
8.Knife
Number of articles
1
2
Optional parts for piping
1
Mark
1
6
4
6
A
B
C
D
E
F
Heating insulating material
G
1
9.Nipper 12.Reamer
10.Gas leakage detector or soap-and-water solution
11.Measuring tape
Drawing for the installation of indoor and outdoor units
more than 5cm
Attention must be paid to the rising up of drain hose
Parts name
Non-adhesive tape
Adhesive tape
Saddle(L.S) with screws
Connecting electric cable for indoor and outdoor
Drain hose
Piping hole cover
more than 10cm
G
more than 10cm
F
A
1
4
1
1
1
2
1
10
11
12
13
14
15
9
Cover
Cushion
Connecting cable
Change for fresh air box
Change for fresh air tube(suit)
Outlet joint
Outlet joint
Note:1.Cooling only units don't have Drain-elbow
14
2. is only for the models of 18,22.
3.The models ZF don't have fresh function and accessory parts related with freshing.
No.0010554405B
Arrangement of piping directions
Rear left
Below
Rear right
Right
Left
The marks from to in the figure are the parts numbers.
The distance between the indoor unit and the floor should be more than 2m.
more than 60cm
A
C
more than 10cm
more than 10cm
12
13
D
E
more than 15cm
G
HSU-09C03/VA(ZXF) HSU-18C03/V(ZXF) HSU-09H03/VA(ZXF)
140 415 140
Floor fixing dimensions of the outdoor unit (Unit:mm)
HSU-12C03/VA(ZXF) HSU-12H03/VA(ZXF)
280
HSU-18H03/V(ZXF)
500140 140
Floor fixing dimensions of the outdoor unit (Unit:mm)
HSU-12H03/VB(ZXF) HSU-12H03/V(ZXF)
256
HSU-22C03/V(ZXF) HSU-22H03/V(ZXF) HSU-24C03/V(ZF) HSU-24H03/V(ZF) HSU-24H03/V(ZXF)
583 113.5113.5
Floor fixing dimensions of the outdoor unit (Unit:mm)
HSU-22C03/V(ZF) HSU-22H03/V(ZF) HSU-24C03/V(ZXF)
HSU-24HK0307
319.5
HSU-24HD0307
Fixing of outdoor unit
Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally.
When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails or wires in consideration of earthquake and strong wind.
If vibration may affect the house, fix the unit by attaching a vibration-proof mat.
Indoor Unit
Place, robust not causing vibration, where the body can be supported sufficiently. Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed. Place, possible to drain easily, where piping can be connected with the outdoor unit. Place, where cold air can be spread in a room entirely. Place, nearby a power receptacle, with enough space around. (Refer to drawings). Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left. In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened.
Selection of Installation Place
Outdoor Unit
Place, which is less affected by rain or direct sunlight and is sufficiently ventilated. Place, possible to bear the unit, where vibration and noise are not increased. Place, where discharged wind and noise do not cause a nuisance to the neighbors. Place, where a distance marked is available as illustrated in the above figure.
Power Source
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.
Install an exclusive branch circuit of the power.
A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.
Selection of pipe
To this unit, both liquid and gas pipes shall be insulated
as they become Iow temperature in operation.
Use optional parts for piping set or pipes covered with
equivalent insulation material.
Liquid pipe( )
Gas pipe( )
2
For 09 For 12,18 For 22,24
6.35mm(1/4")
9.52mm(3/8")
6.35mm(1/4")
12.7mm(1/2")
9.52mm(3/8")
15.88mm(5/8")
Indoor unit
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
70mm
A=170mm
Fit the level line
35
When the mounting plate is fixed side bar and lintel
Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten
the plate to the fixed mounting bar.
Refer to the previous article, " When the mounting plate is first fixed ", for the position of wall hole.
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 70 mm in diameter, slightly descending to outside the wall. Install piping hole cover and seal it off with putty after installation
Indoor side
Wall hole
70mm
Outdoor side
Thickness of wall
G
(Section of wall hole)
Piping hole pipe
3.Installation of the Indoor Unit
Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials.
3
Loading...
+ 5 hidden pages