P1——connect to external power supply, live line: L (220VAC)
P2——connect to external power supply, neutral line: N (0VAC)
P3、4、5、6——control external load, neutral line: N1、N2、N3、N4(0VAC)
P7——control external load, electrical heat: HEAT (control output 220VAC)
P8——control external load, health function: OXYGEN (control output 220VAC)
P9——control external load, humidification: HUMI (control output 220VAC)
P10——control external load, SWING(control output 220VAC)
P11——control external load, WATER PUMP(control output 220VAC)
P12——control external load, indoor fan motor low speed: L(control output 220VAC)
P13——control external load, indoor fan motor mid speed: M(control output 220VAC)
P14——control external load, indoor fan motor high speed: H(control output 220VAC)
P15——communication with fixed frequency single outdoor unit: COMM(0~220VAC)
P16——input control, signal live line: L’(220VAC)
P17——input control, signal neutral line: N’(0VAC)
CN1——input port of transformer (220VAC)
CN2——input port 1 of transformer (no use)
CN3——input port 2 of transformer (no use)
CN4——input port 3 of transformer (1-2、14VAC,3-4、12VAC)
CN5——input control, connecting port to wired controller: CONTROLLER(three bits: 1. power supply:
12VAC, 2. power supply: 0VAC, 3. communication: COMM.).
CN7——control external load, fresh air control: FRESH(1. blank, 2. power supply 0VDC, 3. control
output: 12VDC.)
CN8——input signal: FREEZE(no use)
CN9——input control(no use)
CN10——communication with fixed frequency single outdoor unit: (0~12VDC)
CN11——input signal, door switch: DOOR(1-2 short circuit is normal, cut off P8 output)
CN12——input signal, external alarm input: ALARM(1-3 short circuit is normal, if cut off, air
conditioner stops work.)
Note: For convertible type, cassette type, duct type units, CN11 and CN12 must be in short
circuit, or PCB will display failure information.
CN13——input signal, wiring port of remote receiver board: RECEIVE BOARD(1. power supply 5VDC,
2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer
Page 6
lamp 0VDC,6. signal output of power lamp 0VDC, 7. signal output of water pump running lamp 0VDC)
CN14——control external load, auto elevating function (1. signal of door switch close, 2. output of
elevating direction control 0VDC, 3. output of elevating power control 0VDC, 4. power supply 12VDC)
CN15——input signal, detecting water level of float switch (1-3 short circuit is normal, cut off shows
that level exceeds the limitation).If float switch cuts off or occurs other failure, LED1 will flash 10 times.
CN16——input control, wiring port of central controller: REMOTE(1、RS485-B,2、RS485-A。)
CN17——output signal, output signal of failure alarm, control external load, 12V/ALM(1. control output
0VDC, 2. power supply 12VDC)
CN18——output signal (no use)
CN19——control external load, swing 1(1、16VDC,2、0VDC,3、0VDC,4、0VDC,5、0VDC.)
CN20——control external load, swing 2(1、16VDC,2、0VDC,3、0VDC,4、0VDC,5、0VDC.)
CN21——input signal, spring switch, CHECK(1、input signal of earthing, 2. power supply 0VDC)
CN22——short circuit means selecting single split communication type.
CN23——short circuit means selecting multi split communication type.
Page 7
0010451167 PCB information – function selection(ON is 1, OFF is 0)
The standard condition for PCB in factory
SW1:4 bits are OFF
SW2:4 bits are OFF
SW3:4 bits are ON
SW4:2 bits are ON
SW5:4 bits are ON
SW1-SW2: used for indoor unit to set unit address from 1 to 16’
SW3-SW5: used for indoor unit to select different functions.(every dip switches are corresponding to
J1-J10.
SW2-4——logistic relationship of control function(door card control and remote/ wired control)0
means logistic relationship is “and”, 1 means the later coming is preferential.
J1,SW3-1——function selection-control type: 1 means remote control, 0 means wired control.
J2,SW3-2——function selection-temperature compensation in heating mode: 1means “yes”, 0means
“no”.
J3,SW3-3——function selection-outdoor communication: 1means “yes”, 0means “no”. This PCB
1/60——test in short circuit, but in operation short circuit mustn’t be permitted.
CHECK——short spring switch control, it also can be used as switch of convertible type except for
J6,SW4-2——function selection –health function: 1means common (indoor fan motor running); 0
means special (indoor, outdoor running).
J7,SW5-1——function selection –swing mode: 1 means common(simultaneous motor), 0 means
special (swing motor).
J8,SW5-2——function selection – system combination: 1means fixed frequency single unit, 0 means
fixed frequency multi split.
J9,SW5-3——function selection –group control: 1 stands for the master unit (its address in wired
controller is 0), 0 stands for the slave units (the address should be set by the dip switch, their addresses
only can be in the range: 1~15)
J10,SW5-4——function selection –preset: 1 no meaning, 0 no meaning
Page 8
0010451167 PCB information- control type
Control type selection between remote and wired: select by dip switch J1, SW3-1(1 means remote control;
0means wired control).
For remote control type, please use remote controller YR-H71, and a remote receiver is equipped with
indoor unit. For wired control type, wired controller YR-E12 will be used, 3-core shied wire is equipped with
indoor unit.
Door card control: controls ON/OFF, the start up setting will comply with last time request memorized
according to condition memorize function. Its difference with emergency switch of convertible type unit lies:
the emergency switch control will perform in the condition: 24degrees, auto fan speed in auto mode.
The function combination between door card and remote/wired control type: select by dip switch: SW2-4(0
means “and”, 1 means later coming is preferential.)
Dip switch position in wired control type: Only one indoor unit of all indoor units connected with wired
controller is the master unit, whose address is 0, function selection switch(J9,SW5-3)is 1. The others are
slave units, and the quantity can be 0~15, whose addresses are(SW1:1~4)from 1 ~15, and cannot
repeat.
Wiring request in wired control type: the wired controller ports A-B-C are connected with indoor port CN5
(1-2-3) through 3-core shield wire. Requirements:
1. Port A only connects with either of indoor port CN5(1)
2. Port B connects with port CN5 (2) of all indoor units.
3. Port C connects with port CN5 (3) of all indoor units.
Dip switch position in central control type: the addresses (SW1:1~4;SW2:1~4)of indoor units connected
with central controller can not repeat. In principle, they should be in the order from small to big.
Wiring request in central control type: port A-B is connected with indoor port CN16(A-B)through 2-core
shield wire. Requirements:
1. Port A connects with port CN16(A)of all indoor units.
2. Port B connects with port CN16(B)of all indoor units.
When only use remote control type, please select remote control unit, and install according to installation
manual, there is no other special request.
When only use wired control type, please select wired control unit, and install according to installation
manual. When control multi indoor units, take care the requirements of dip switch and wiring, there is no
other special request.
When only use central control type, please firstly install according to air conditioner requests and set the
dipswitch, there is no other special request.
When central control type(128×)and remote control type are used simultaneously, set the dip switch
according to central control type, there is no other special request.
When central control type(128×)and wired control type (16×)are used simultaneously, max. indoor
Page 9
units sets: 128×16 can be controller. Address setting of central controller can be met firstly, and then
modulate the address setting of slave unit wired controlled.
LED in indoor PCB:
1. LED1:is the state lamp for remote receiver as well as failure lamp. If indoor unit is normal, LED1 is on,
or if failure occurs, LED1 flashes regularly, and you can adjust failure type according to the flash times.
2. LED2:is used for multi split units as communication lamp. If communication between indoor and
outdoor is normal, LED2 will be on.
3. LED3:is used for single split units as communication lamp. If communication between indoor and
outdoor is normal, LED3 will be on.
4. LED4、LED5:is the lamp that shows the data receiving or sending between wired controller and PCB,
If LED4、LED5 be on in turn, communication between wired controller and PCB is normal.
outdoor ambient temp. sensor failure
or 4-way valve broken down in heating mode
outdoor coil temp. sensor failure
over-current protection failure or phase sequence fault
refrigerant system pressure too high or low
communication between indoor PCB and receiver panel failure
communication between indoor PCB and outdoor PCB
drainage failure
Note: For convertible type unit, drainage failure is not available.
Wired control type unit failure code:for old wired controller
Failure description Failure code on wired
controller
Indoor ambient temp. sensor abnormal E1
Indoor coil temp. sensor abnormal E2
Outdoor ambient temp. sensor abnormal E3
Outdoor coil temp. sensor abnormal E4
Over current protection E5
Over high or low pressure protection E6
Communication between panel and indoor
E8
abnormal
Communication between indoor and outdoor
E9
abnormal
Water pump failure E0
indoor running
lamp flash times
1
2
3
4
5
6
8
9
10
Page 11
Failure code with wired controller YR-E12:
For
remote
type, flash
times
10 08 21 Drainage system failure Float switch broken down for more than
1 01 01 Indoor ambient temp. sensor
2 02 02 Indoor coil temp. sensor failuresensor broken down or short circuit for
3 4A 11 Outdoor ambient temp. sensor
4 49 12 Outdoor coil temp. sensor
5 48 10 Over-current protection CT check abnormal 3 times in 30m
6 53 14 High pressure abnormal High pressure switch acts 3 times in 30m
8 07 06 Communication between wired
9 06 05 Communication between
11 0B 30 Outside alarm signal input Outside signal broken down for more than