This Consumer Unit and Hager devices conform with the following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Passed hot-wire fire test for “non-combustible enclosure” in context of Regulation 421.1.201
indent (i) in BS 7671.
ZD0828ZD0828
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer shall check connections are tight to the torque levels stated in these instructions
prior to energizing this board. This check should include factory made connections which may have loosened in transit.
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth
connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this consumer unit, please consult us for spares or replacements.
Operating Instruction leaet is provided overleaf. This leaet should be left for the end user.
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Consumer Units incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main
switch with RCBO protection on all outgoing circuits should be used.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
For guidance when making connections in a consumer unit electrical safety rst /BEAMA document
“Guidance for installers when making connections in consumer units” is available from
hager.co.uk/63026.htm
Cable Access:
Cable access into the metal consumer unit must maintain the integrity of the non-combustable
consumer unit so far as reasonably practicable. This can generally be achieved by the installer
ensuring that cable access holes they make in the enclosure do not to leave gaps greater than:
· 2.5 mm for all other surfaces of the enclosure that are accessible after installation.
For rear cable access, the minimum number of knockout(s) shall be removed.
Tests on hager consumer units have indicated that there is no specic need for external re rated
cable glands or intumescent sealing in addition to the guidance below, with respect to achieving a non-combustible enclosure.
However this does not preclude the designer/installer from using re rated cable glands or external intumescent sealing should
they consider necessary. Internal intumescent pads shall not be used.
Cables >1.5mm
Torque Settings
Consumer unit terminals
Earth and neutral terminal bars26.5221.51.510
Isolation
SB switch disconnectors26.53.63.63.63.615
Circuit protection
MTN MCB26.52.82.82.82.813
NBN/NCN/NDN MCB26.52.82.82.82.813
RCBO25.52.12.12.12.113
RCCB25.52.82.82.82.813
Pz No. (mm)
Tightening torque (N.m)
Single Cable Multi Cables Single CableMulti Cable
2
2.5mm
Cables ≤1.5mm
Tightening torque (N.m)
2
2.5mm
Cable Stripping
(mm)
1
ZD0828 - Issue 3 9-16
1
2
Remove internal chassis.
(No requirement to disconnect factory cable connections)
3
Box must be level at this stage
Pozi n°8 or n°10
Box dimensions on page 4
Back box xing points
Fixing height 1320mm ± 50mm from back box bottom
face to the nished oor (Part M)
5
Remove required KO’s before xing to stud wall &
use provided grommet strip or grommet accessory
VMGROM for cable protection
4
st
x
1
complete
Top & bottom edge to be ush with front of stud work, with
left and right edges protruding slightly from stud work
6
ZD0828ZD0828
2
Trim excess plaster from around
the box, loosely t x4 M5 wing
nut to back box
7
Push internal chassis
until it is ush with the
wall surface. Tighten x4
M5 wing nut to secure
internal chassis
The installer must ensure that all cables routed under the
chassis dinrail have adequate clearance and are NOT
subjected to any stress or pressure.
Offer up internal chassis, loacting chassis on
the metal studs
8
2nd x
complete
After wiring installation, offer up cover &
door assembly, secure with the captive
screws.
ZD0828 - Issue 3 9-16
Interface characteristics
Rated & operational voltage (Un / Ue)
230V a.c. 50Hz
Rated insulation voltage (Ui)
320V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (InA)
100A, 63A
Note: Dependent upon rating of main incoming device
Rated current of an Outgoing circuit (Inc)
Circuit next to an RCCB: MCB & RCBO 6-50A
(marked rated current on device)
All other circuits MCB 6A - 63A (marked rated current on device)
All other circuits RCBO 6A - 50A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
Annex ZB: 16 kA rms at 250V, power factor 0.6 with equipment and arrangements specied in Hager’s technical documentation /
catalogue.
Protection against electric shock
Consumer unit shall be installed in an electrical system conforming to the current edition of IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S when installed in an electrical installation complying with BS 7671
Hager recommends for TT systems a 100A type S time delayed RCCB or a main switch with RCBO protection only on all outgoing circuits.
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP2XC with Door Open / closed and full compliment of outgoing devices and or blanks tted.
Intended use
Intended for use in domestic (residential) or similar premises.
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
VM: Wall-mounted, enclosed assembly.
Mechanical impact protection
IK 05
The type of construction
Fixed parts
Type A DBO (Distribution board for use by ordinary persons)
Rated current of outgoing unit (Inc)
RCCB 80A (marked rated current on device)
Note: RDF only applies to continuously and simultaneously loaded
circuits.
In principle, this means adjacent circuit-breakers having a load
‘on’ time exceeding 30 minutes or where a load not exceeding 30
minutes has an ‘off’ time less than the ‘on’ time, will need to have
the rated diversity factor applied as indicated.
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please
call the technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Only equipment and arrangements specied in Hager’s
technical documentation / catalogue shall be used.
Isolate the electrical supply from the consumer unit.
1. Isolate the electrical supply from the consumer unit.
2. Remove the front cover, by loosening the two captive
screws.
3. Fully slacken the lower terminal of the device.
g 1.
4. Fully open the bottom device clip (g 1.)
5. Locate the device onto the din rail, and busbar. Ensure that the busbar
tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower
terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables,
please check the tightness of all cable connections. This should
include all factory made connections, which may have loosened during
installation or transit.
Use circuit as
normal
YES
Does device
stay ON?
Try & reset device once
MCB
or RCBO
T
T
ONON
ON
T
Blank RCCB RCBO (two module) MCB RCBO Switch
(one module)
START
MCB / Fuse
tripped
What device
is it?
RCCB
Try & reset device once
Use circuit as
normal
Does device
stay ON?
YES
NO
Turn OFF
all MCB / fuse*
devices
Reset RCCB
Does device
stay ON?
YES
Call an
electrician
NO
NO
Does device
supply socket
outlets
YES
Unplug all
appliances from
circuit and reset
device / replace fuse*
NOYES
Does device
stay ON?
Plug in & switch on
appliances one at a time
until device trips / blows,
identifying faulty appliance
Unplug faulty
appliance until
repaired. Reset device.
Other appliance may
be used
Call an
electrician
NO
Turn ON MCB / fuse*
devices one at a time
until RCCB trups again,
identifying faulty circuit
Size 4Size 5Size 6Size 7
VMLF110VMLF114-VMLF120
D
C
-VMLF710CVMLF712C VMLF716C
-VMLF810CVMLF812C VMLF816C
12 MOD16 MOD18 MOD22 MOD
A282282282282
B335407443515
A
E
C32323232
D298370406478
E252252252252
F72727272
B
F
4
ZD0828 - Issue 3 9-16