
GB
Design 10 Two Row Consumer Unit
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
ZD0829ZD0829
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act
shall be complied with.
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
Install in the horizontal plane only.
For guidance when making connections in a consumer unit electrical
safety rst /BEAMA document “Guidance for installers when making
connections in consumer units” is available from hager.co.uk/63026.htm
Important notice:
To prevent potential overheating from loose connections the installer
shall check connections are tight to the torque levels stated in these
Additional Extras
Accessory Ref.
Cable protector plate
Can be used on the rear knockouts to smooth any
sharp edges
Cable Clamp
Can be used to clamp meter tails in place when
entering main switch
instructions prior to energizing this board. This check should include
factory made connections which may have loosened in transit.
Good workmanship and proper materials must be applied by the installer.
The cable entry method shall, as far as reasonably practical, maintain the
non-combustable arrangement of the enclosure. Account shall be taken of
these instructions.
Wall Fixing:Removal of Front Cover:
Insulated:
VM02CE
Metal:
VM01CE
VA10MT
Lift door and loosen the two captive screws until the cover can be
removed. The units have multiple xing points that will suit No.8 & No.10 screws
Cable entry facilities:
These metal units are provided with knockouts suitable for
use with 100x50mm trunking, 50x50mm trunking, 40x25mm
trunking and also large rear knockouts. Grommet strip is
provide to protect the cables when entering the board.
Note: Only BASEC approved cable should be used
2
1.0mm
to 16mm2 for outgoing cables
1
Rear cable entries shall enter thorough selected rear Knockout; once
the Knockout is removed apply the grommet strip provided.
Grommet strip lengths: Small EKO – 79mm, Large EKO – 127mm
Rear EKO – 255mm
Up to 35.0mm2 for incoming live cables
Single conductors below 1.5mm² need to be doubled back in the terminal
bar
ZD0829 - Issue 4 9-16

Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth
connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this consumer unit, please consult us for spares or replacements.
Operating Instruction leaet is provided overleaf. This leaet should be left for the end user.
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Consumer Units incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main
switch with RCBO protection on all outgoing circuits should be used.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
Cable Access:
Cable access into the metal consumer unit must maintain the integrity of the non-combustable consumer unit so far as reasonably practicable. This can
generally be achieved by the installer ensuring that cable access holes they make in the enclosure do not to leave gaps greater than:
· 1.0 mm for the horizontal top surface and
· 2.5 mm for all other surfaces of the enclosure that are accessible after installation.
For rear cable access, the minimum number of knockout(s) shall be removed.
Tests on hager consumer units have indicated that there is no specic need for external re rated cable glands or intumescent sealing in addition to the
guidance below, with respect to achieving a non-combustible enclosure. However this does not preclude the designer/installer from using re rated cable
glands or external intumescent sealing should they consider necessary. Internal intumescent pads shall not be used.
1mm
1mm
2.5mm
2.5mm
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
2.5mm
2.5mm
5. Locate the device onto the din rail, and busbar. Ensure that the
busbar tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower
1. Isolate the electrical supply from the consumer unit.
2. Remove the front cover, by loosening the two captive
screws.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (g 1.)
g 1.
terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables,
please check the tightness of all cable connections. This should
include all factory made connections, which may have loosened
during installation or transit.
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the
technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
ZD0829 ZD0829
2
Hager Technical Help Line: 01952 675 689
Hager Technical Fax: 01952 675 557
Hager Technical E-mail: technical@hager.co.uk
Website: www.hager.co.uk
ZD0829 - Issue 4 9-16