Hager VML410AH Installation Instructions

Height
Width
Depth 1
Height
Width
Depth
ZD
0820 - Issue 6
ZD0820
ZD0820
ZD0820
ZD0820
ZD
0820 - Issue 6
Design 10 / 30 Consumer Unit
Installation Instructions / Data Sheet
Design 10 / 30 Consumer Unit
Installation Instructions / Data Sheet
Use circuit as
normal
Call an
electrician
YES
NO YES
Does device
NO
Does device
supply socket
appliances from circuit and reset
Does device
stay ON?
NO
outlets
YES
Unplug all
device
stay ON?
Try & reset device once
Plug in & switch on appliances one at a time until device trips / blows,
identifying faulty appliance
Device Tripped
MCB
or RCBO
What device
Please refer to additional leaet included with the consumer unit.
appliance until
repaired. Reset device.
Other appliance may
START
is it?
AFDD
Unplug faulty
be used
RCCB
Try & reset device once
Call an
electrician
Use circuit as
all MCB / fuse*
Reset RCCB
NO
Turn ON MCB / fuse* devices one at a time
until RCCB trups again,
identifying faulty circuit
normal
YES
Does device
stay ON?
NO
Turn OFF
devices
Does device
stay ON?
YES
Installation Instructions:
All product(s) must be installed by a suitably competent electrician Giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used.
Install in the horizontal plane only.
For guidance when making connections in a consumer unit electrical safety rst / BEAMA document “Guidance for installers when making connections in consumer units” is available from hager.co.uk/63026.htm
Wall Fixing:
Design 10 / 30 Consumer Unit
GB
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards: Consumer Unit: BS EN 61439-3 including Annex ZB. Switch-disconnectors: BS EN 60947-3. Residual Current Circuit Breaker (RCCB): BS EN 61008-1 Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1 Miniature Circuit Breaker (MCB): BS EN 60898-1 Arc Fault Detection Devices: BS EN 60626 Surge Protection Devices: BS EN 61643
Important notice:
To prevent potential overheating from loose connections the installer shall check connections are tight to the torque levels stated in these instructions prior to energizing this board. This check should include factory made connections which may have loosened in transit.
Good workmanship and proper materials must be applied by the installer. The cable entry method shall, as far as reasonably practical, maintain the non-combustable arrangement of the enclosure. Account shall be taken of these instructions.
For guidance on RCD selection, AFDD selection and more, see the related BEAMA guide in our BEAMA guide web page - hager.co.uk/18thedition.
Cable entry facilities:
* Important note: Fuse carriers must not be opened or closed with the
main switch in the ON position.
Design 10 Dimensions (mm)
Height 246 246 246 246 246 246
Width 155 227 299 370 406 478
Depth 1 83 83 83 83 83 83
Depth 2
Depth 2 100 100 100 100 100 100
Boards with Square Knockouts Number of Knockouts
Top Face 30 x 25 2 2 2 2 2 2
Top Face 40 x 30 0 2 4 4 6 6
Back 100 x 50 1 1 1 3 3 3
Bottom Face 30 x 25 2 3 4 4 5 5
Design 30 Dimensions (mm)
Height 240 240 240 240 240 240
Width 149 221 293 364 400 472
Depth 102.5 102.5 102.5 102.5 102.5 102.5
Top Face 30 x 25 2 2 2 2 2 2
Top Face 40 x 30 0 2 4 4 6 6
Back 100 x 50 1 1 1 3 3 3
Bottom Face 30 x 25 2 3 4 4 5 5
Enclosure Size
2 3 4 5 6 7
Enclosure Size
2 3 4 5 6 7
Number of Knockouts
Design 10 Dual Row Dimensions (mm)
Enclosure Size
3 (2) 4 (2) 5 (2) 6 (2) 7 (2)
486 486 486 486 486
227 299 370 406 478
83 83 83 83 83
100 100 100 100 100
Number of Knockouts
2 2 2 2 2
2 4 4 6 6
2 2 6 6 6
3 4 4 5 5
Design 30 Dual Row Dimensions (mm)
Enclosure Size
3 (2) 4 (2) 5 (2) 6 (2) 7 (2)
480 480 480 480 480
221 293 364 400 472
102.5 102.5 102.5 102.5 102.5
Number of Knockouts
2 2 2 2 2
2 4 4 6 6
2 2 6 6 6
3 4 4 5 5
The units have multiple xing points that will suit No.8 & No.10 screws
Rear cable entries shall enter thorough selected rear Knockout; once the Knockout is removed apply the appropriate cable entry plate (full list on page 4). Cable entry plates are available to clip into the knockout hole and provide a safe edge to bring cables in.
Note: Only BASEC approved cable should be used 1.0mm outgoing cables
2
Up to 35.0mm to be doubled back in the terminal bar.
for incoming live cables. Single conductors below 1.5mm² need
2
to 16mm2 for
These metal units are provided with knockouts suitable for use with 100x50mm trunking, 50x50mm trunking and also large rear knockouts.
Accessories Comparison
Surface Mounted Consumer Units
Design 10Design
Feature Description
Meter tail entry plate (VM04CE)
Top wall cable entry plates (VM03CE)
When clipped into place, the moulding holes allows meter tails and CPC to enter the board safely
Specially designed for our square knockouts, these plates provide more options for cable entry. When used with
30
50x50mm trunking, IP ratings can be achieved.
Blind cable entry plates (VM04CB,
A blank plate for drilling which allows the installer to decide on the method of incoming cables - compression gland etc.
VM03CB)
Rear cable entry plate (VM02CE)
Cable clamp (VA10MT)
Stand-off plate (VM01SP)
Allows cables to enter the rear of the board without the risk of damage from sharp edges.
Incoming meter tails can be safely secured, eliminating stress within the switch terminal.
Provides 12mm of clearance at the rear of the consumer unit to allow surface mounted cables to enter the board from the rear.
Included with board Available as an accessory
* Knockouts available by choice on Design 30 range. References ending with a ‘K’ contain knockouts.
1
2
ZD
0820 - Issue 6
ZD0820
ZD0820
ZD0820
ZD0820
ZD
0820 - Issue 6
Design 10 / 30 Consumer Unit
Installation Instructions / Data Sheet
Design 10 / 30 Consumer Unit
Installation Instructions / Data Sheet
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this consumer unit, please consult us for spares or replacements. Operating Instruction leaet is provided overleaf. This leaet should be left for the end user. Single conductors below 1.5mm² need to be doubled back in the terminal bar. Consumer Units incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main switch with RCBO protection on all outgoing circuits should be used. Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
1mm
2.5mm
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used.
1. Isolate the electrical supply from the consumer unit.
2. Remove the front cover, by loosening the two captive screws.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (g 1.)
5. Locate the device onto the din rail, and busbar. Ensure that the busbar tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables, please check the tightness of all cable connections. This should include all factory made connections, which may have loosened during installation or transit.
For
boards with Surge Protection fitted (References ending in SPD)
D
GREEN/CLEAR
RE
Where surge protective devices (SPDs) or other equipment are likely to influence the verification test, or be damaged, such equipment shall be disconnected before carrying out the insulation resistance test.
3
1mm
2.5mm
g 1.
Cable Access:
Cable access into the metal consumer unit must maintain the integrity of the non­combustable consumer unit so far as reasonably practicable. This can generally be achieved by the installer ensuring that cable access holes they make in the enclosure do not to leave gaps greater than:
· 1.0 mm for the horizontal top surface and
· 2.5 mm for all other surfaces of the enclosure that are accessible after installation.
For rear cable access, the minimum number of knockout(s) shall be removed.
Tests on hager consumer units have indicated that there is no specic need for external re rated cable glands or intumescent sealing in addition to the guidance below, with respect to achieving a non-combustible enclosure. However this does not preclude the designer/installer from using re rated cable glands or external intumescent sealing should they consider necessary. Internal intumescent pads shall not be used.
Selection of RCDs
Different types of RCD exist, depending on their behaviour in the presence of DC components and frequencies.
Overload protection of switches and RCCBs This can be achieved by;
Method 1
Ensure the sum of the rated current of the downstream MCBs do not exceed the rated current of the switch or RCCB (Inc). This method would however need to consider the consequences of any spare ways and later additions.
Method 2
Ensure that the rated current of a switch or RCCB (Inc), stated by the assembly manufacturer, is not less than the rating of the upstream OCPD. For a domestic installation this could be a 100A cut-out fuse.
Method 3
Select a consumer unit or distribution assembly that only utilises RCBOs on outgoing circuits. Consideration will still need to be given as to the rated current of the main switch.
For more information on these subjects we have made the relevant BEAMA guides available on our 18th edition hub on our website at hager.co.uk/18thedition
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Technical Service Centre: 01952 675 689 Technical Fax: 01952 675 557 Technical E-mail: technical@hager.co.uk
Website: hager.co.uk
Torque Settings
Cables >1.5mm
Tightening torque (N.m)
Pz No. (mm)
Consumer unit terminals
Earth and neutral terminal bars 2 6.5 2 2 1.5 1.5 10
Isolation
Switch Disconnectors / Surge 2 6.5 3.6 3.6 3.6 3.6 15
Circuit protection
MCB 2 6.5 2.8 2.8 2.8 2.8 13
RCBO 2 5.5 2.1 2.1 2.1 2.1 13
RCCB 2 5.5 2.8 2.8 2.8 2.8 13
AFDD 2 2 2.1 2.1 2.1 2.1 13
Single Cable Multi Cables Single Cable Multi Cable
2
Cables ≤1.5mm
Tightening torque (N.m)
2
Cable Stripping (mm)
Interface characteristics
Rated & operational voltage (Un / Ue)
230V a.c. 50Hz
Rated insulation voltage (Ui)
320V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (InA)
100A, 63A, 40A, 80A - (VM/VML933H)
Note: Dependent upon rating of main incoming device
Rated current of an Outgoing circuit (Inc)
MCB 6A - 63A (marked rated current on device) RCBO 6A - 50A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
Annex ZB: 16 kA rms at 250V, power factor 0.6 with equipment and arrangements specied in Hager’s technical documentation / catalogue.
Protection against electric shock
Consumer unit shall be installed in an electrical system conforming to the current edition of IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
1way = 1.0 2way – 3way = 0.8 4way – 5way = 0.7 6way – 9way = 0.6 10way and above = 0.5
Rated frequency (fn)
50 Hz
Pollution degree
2
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S when installed in an electrical installation complying with BS 7671 Hager recommends for TT systems a 100A type S time delayed RCCB or a main switch with RCBO protection only on all outgoing circuits.
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP2XC with Door Open / closed and full compliment of outgoing devices and or blanks tted. Note: Where cables are installed through top wall of enclosure, gaps of IP4X to be maintained.
Intended use
Intended for use in domestic (residential) or similar premises.
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
VML: Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection
IK 05
The type of construction
Fixed parts
Type A DBO (Distribution board for use by ordinary persons)
4
Rated current of outgoing unit (Inc)
RCCB 40A -100A (marked rated current on device)
Note: RDF only applies to continuously and simultaneously loaded circuits.
In principle, this means adjacent circuit-breakers having a load ‘on’ time exceeding 30 minutes or where a load not exceeding 30 minutes has an ‘off’ time less than the ‘on’ time, will need to have the rated diversity factor applied as indicated.