hager VC, VH Installation Instructions Manual

VC & VH Consumer Unit
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards: Consumer Unit: BS EN 61439-3 including Annex ZB. Switch-disconnectors: BS EN 60947-3. Residual Current Circuit Breaker (RCCB): BS EN 61008-1 Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1 Miniature Circuit Breaker (MCB): BS EN 60898-1
Installation Instructions:
All product(s) must be installed by a suitably competent electrician Giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice: To prevent potential overheating from loose connections the installer shall check connections are tight to the torque levels stated in these instructions prior to energizing this board. This check should include factory made connections which may have loosened in transit.
Tightening torque values to be applied (Nm)
Switch-disconnector’s: 40A & 63A: 2.8 Nm Switch-disconnector’s: 100A: 3.3 Nm RCCB’s 40A & 63A: 2.8 Nm RCCB’s 80A & 100A: 3.3 Nm MCBs: 2.8 Nm RCBO’s: 2.8 Nm Earth & Neutral terminal bar connections: 2.0 Nm Single conductors below 1.5mm² need to be doubled back in the terminal bar Front metal cover xing screws: 2.0 Nm
Good workmanship and proper materials must be applied by the installer.
Metalclad units are provided with knockouts for standard 20, 25, and 32mm conduit and large rear knockouts.
Insulated units are provided with breakouts for standard mini trunking.
Rear cable entries should be scored along the weak point with a sharp knife, and tapped sharply to remove.
Pull and lift the terminal bar support away from the unit resting the rail supported by the earth strap. After xing conduit/ cable glands, locate the rail support and press down.
Note: Only BASEC approved cable should be used
1.0mm
2
to 16mm2 for outgoing cables up to 35.0mm2 for incoming live cables Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Cable entry facilities:
Metal Unit - Removing and replacing the terminal rail for cabling:
GB
1
ZD0632 - Issue 5 03-15
ZD0632ZD0632
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this consumer unit, please consult us for spares or replacements. Operating Instruction leaet is provided overleaf. This leaet should be left for the end user. Single conductors below 1.5mm² need to be doubled back in the terminal bar. Consumer Units incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main switch with RCBO protection on all outgoing circuits should be used. Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
IP Ratings:
Cable access into the consumer unit must maintain the integrity so far as reasonably practicable. In essence, for surfaces accessible after installation, this means maintaining the requirement for the horizontal top surface of the enclosure to provide a degree of protection of at least IP4X and elsewhere, IP 2XC. For rear cable access, the minimum number of knockout(s) shall be removed.
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Hager Technical Help Line: 01952 675 689 Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk E-mail us: info@hager.co.uk
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used. Isolate the electrical supply from the consumer unit.
1. Isolate the electrical supply from the consumer unit.
2. Remove the front cover.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (g 1.)
5. Locate the device onto the din rail, and busbar. Ensure that the busbar tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables, please check the tightness of all cable connections. This should include all factory made connections, which may have loosened during installation or transit.
g 1.
IP Code Description
IP2XC Protection against access
with a tool (2.5mm diameter, 100mm long) making contact with live hazardous parts
IP4X A probe of 1mm diameter
shall not enter the enclosure
Insulated Unit - Removing and replacing the top wall for top surface cabling (IP4X using foam inserts; 1mm2 - 10mm2 conductors BS6004)
1. Press in with index nger on one end release clip while pressing in with thumb on the inner release clip repeat on the other and lifting the wall away from the unit.
2. After xing the unit, to replace and reseal, place one of the foam seal strips in the underside of the wall feature and the other in the base (behind the cables). Locate the wall and press down. Additional xing points are provided.
Max outgoing top entry cable size 10mm
2
CSA. Max incoming Main tails top entry cable size 25mm2 CSA. If larger cables are needed, then enter from any other cable entry point other than top.
2
ZD0632 - Issue 5 03-15
ZD0632 ZD0632
IP2XC
IP2XC
IP4X