TYA670D
Attention!
• Electrical equipment must be installed and
fi tted by qualifi ed electricians only.
z
i
6T1647A
Area
Line
Ptcp.
Nb.
KNX-DALI gateway
Gateway KNX-DALI
• Failure to observe the instructions may cause
damage to the device and result in fi re or other
hazards.
• This device is not suitable for disconnection of
the mains power supply.
• The DALI control voltage is a functional extra-low
voltage (FELV). During the installation,
ensure there is a safe separation between KNX
and DALI.
6LE001210A
TYA670D
Product description
The DALI TYA670D KNX gateway is used to
interface DALI lighting applications with the KNX
system.
Product characteristics
• Controls up to 64 DALI products in up to 32
groups
• Individual control, group control or general control
• 16 scenes
• Effect control for dynamic sequences and sets of
colours
• Reading of the status of DALI products via KNX,
e.g. light intensity, light fi tting fault, etc.
• Manual control of DALI groups
• Priority
• Feedback on the status of switching and the value
of light intensity in bus mode and manual mode
• General status feedback
• General command function
• Emergency lighting function
• Inhibition function for each group
• Separate switching and tripping delay
• Timer function with cut-off pre-warning
• Movement function : in combination with a
presence detector, reduction of the light intensity
when no movement is detected before turning off
• Online or of ine commissioning of DALI products
with ETS plug-ins
• Overload protection
• Overvoltage circuit breaker
• Possibility to replace an individual DALI product
without software during service
• Operating hours counter
• Delivery status : job-site mode, possibility of
ordering DALI groups using the keyboard. All
DALI products are ordered jointly.
Description
Da+
TYA670D
Da-
L
N
Area
Line
Ptcp.
Nb.
tebis
:.?nB
1 Keyboard for manual control
2 Push Button and LED indicator for addressing
3 KNX Connection
4 Display of Dali numbers
5 Connection to the network
6 Dali connection.
Control
Control Elements
TYA670D
4 Display of the DALI numbers
- 4
a
DALI Groups
- 4
b
Individual participants
7 Key
8 LED
9
A LED on : Individual participant or DALI group
Z
E LED on : Individual participant or DALI group
R
Operating mode
Bus mode controls via push button
Short-term
manual mode
Permanent
manual mode
H
- After the bus failure and a return to service, the
device operates in bus mode.
- After a power cut and a return to service, the
gateway operates in bus mode.
- Manual mode is disabled by a telegram in current
mode.
: manual control
on : Manual mode permanently enabled
Key : Turn on or adjust the light intensity 9
brighter
enabled : light intensity 1…100%
Key : Turn off or adjust the light intensity 9
darker
disabled: light intensity 0%
Key
: Turn off all DALI participants.
manual control using the
keyboard, automatic return to
bus mode
manual control exclusively via
the gateway
- In manual mode, a bus mode is not possible.
- In the event of a failure of the bus, manual
control is possible.
Enabling short-term manual mode
The operation of the keyboard is programmed and
is not locked.
- Press the
displayed on the screen, the
key brie y (<1 second). 01 is
LED remains
off or
est affi ché sur l’écran : la passerelle n’est
pas programmée, tous les participants DALI
connectés sont commande en commun. Dans
ce mode la commande individuelle de participant
n’est pas possible.
Disabling short-term manual mode
The gateway is in short-term manual mode.
- No manipulation for 5 seconds
or
- Short press on the
key (<1 second) until the
gateway exits short-term manual mode. The
display turns off.
Enabling permanent manual mode
The operation of the keyboard is programmed and
is not locked.
- Press the
The
key for at least 5 seconds.
LED is lit, 01 is displayed on the screen,
permanent manual mode is enabled.
or
is displayed on the screen: the gateway is not
-
programmed, all connected DALI participants are
jointly controlled. In this mode, individual control
of participants is not possible.
Disabling permanent manual mode
- Press the
The
key for at least 5 seconds.
LED turns off and bus mode is enabled.
Controlling the DALI participants
The gateway is in permanent or short-term manual
mode.
-
Press brie y on the key ( < 1 second) until the
n u m b er o f t he d e s i r e d DA LI p ar t i c ipa n t is di sp l a y e d
The
and LEDs display the status.
- Control the DALI participant with the key or
with the
key Short press : turns on and off
Long press : varies the light intensity 9 brighter/
darker
and LEDS display the status.
The
- In permanent manual mode, after having
been through all the available DALI participant
numbers, the gateway exits manual mode after
an additional press.
- The display 4 fi rst shows the number of
available DALI groups 4a, and then the individual
addresses of the DALI participants 4b.
Turning off all the DALI participants
The gateway is in permanent manual mode.
- Press the
key.
All DALI participants are switched off.
6LE001210A1

Locking the DALI participants or groups
individually
The gateway is in permanent manual mode.
- Press briey on the
key ( < 1 second) until the
desired DALI number is displayed.
The
and LEDs display the status.
- Press the
and keys simultaneously for at
least 5 seconds.
The DALI number selected ashes on the display
screen.
The DALI participant or group is locked.
- Enable bus mode (leaving permanent manual
mode).
A locked DALI participant can be controlled in
manual mode.
Unlocking the DALI participants or groups
individually
The gateway is in permanent manual mode
- Press briey on the key
(<1 second) until the
desired DALI number is displayed.
- Press the
and keys simultaneously for at
least 5 seconds.
The DALI participant or group is released.
The display on the screen no longer ashes.
- Enable bus mode (leaving permanent manual
mode).
Connection
Bus 30 V
230 V 50/60 Hz
Area
Line
Ptcp.
Nb.
da da N L da da N L
L1
L2
L3
da+
da -
N
TYA670D
Electrical connection
DALI devices from some manufacturers have
expanded functions and can be controlled. In the
case of upgrades of existing DALI installations,
remove all the corresponding control devices.
The DALI control voltage is a functional extra-low
voltage (FELV).
Please distinctly separate the power supply
cabling from the cabling for the DALI bus.
G
Emergency lighting supplied by the central
emergency power supply
AC 230 V
C/DC 230 V
DALI
KNX
KNX
DALI
L, N
da
L, N
da
Emergency lighting, KNX supply and the DALI
gateway are supplied by the central emergency
power supply circuit.
C 230 V
C/DC 230 V
DALI
KNX
KNX
DALI
L, N
da
L, N
da
Commissioning
Downloading the physical address and the
application software
- Supply power to the product from the mains
- Connect the KNX bus
- Download the physical address
- Download the application software into the
device.
Programming is not possible if the product is not
powered via the mains.
Technical characteristics
KNX power supply 30 V DC
KNX power used
Mains power
Mains frequency
Total power dissipated max. 3 W
DALI voltage 16V DC
Number of DALI products (Electrical consumption
2 mA each) max. 64
DALI transmission rate 1200 bit / s
DALI protocol EN 62386
Length of the DALI cables
For cable cross section 1,5mm² max. 300 m
For cable cross section 1,0mm² max. 238 m
For cable cross section 0,75mm² max. 174 m
For cable cross section 0,5mm² max. 116 m
DALI connection capacity
0.2 … 4 mm² or 2 x 0.2 … 2,5 mm²
Flexible cable without lug 0,5 … 4 mm²
Flexible cable with lug 0.5 … 2,5 mm²
Operating temperature 5 °C … +45 °C
Storage temperature -25 °C … +70 °C
Assembly width 72 mm (4 modules)
Typ. 150 mW
110 / 240 V AC±10 %
50 / 60 Hz
What to do if…
1 The screen displays , the connected
DALI devices have no functions, no control
is possible
Cause : network
voltage on the DALI
bus
2
The screen displays bc in manual mode,
control of some light ttings is not possible.
Cause : the gateway is
not programmed
3
Some DALI devices have no functions
Cause : a load is
defective (e.g. : a lamp)
Cause : the DALI
product is defective
Press the keys simultaneously for at least 10
q
seconds. The DALI gateway recognizes the
DALI devices which have been replaced and
loads the necessary data.
the screen. Repeat the operation for each
defective product.
4
Manual control is not possible by means of
the keyboard
Cause : manual control
is not enabled
Cause : manual
control is disabled via
the bus
5
It is not possible to control the DALI group
Cause : DALI group
disabled via the bus or
manual control
6
No DALI group can be programmed
Cause : all the DALI
groups are disabled
via the bus or manual
control
Cause : permanent
manual mode is
enabled
Cause : the
programming LED is
ashinge
If the fault persists, re-download the
q
STYA670D application software.
Solution : correct the
installation wiring fault
Solution :
program the
gateway, commission
the DALI system
Solution :
replace the
load
Solution :
replace the
defective DALI product
and reconnect
LE is displayed on
Solution : reprogram the
device, enable manual
control (see Activating
manual mode)
Solution
manual control via the
bus
Solution :
DALI group via the bus
and disable manual
mode
Solution :
DALI groups via the
bus and disable manual
mode manuel
Solution :
permanent manual
mode
Solution :
the product from the
bus and restart after 5
seconds
: enable
enable the
enable the
disable
disconnect
- Connect the device.
- Connect the bus cable to the connection terminal.
Operation of the emergency lighting
The gateway can be used in emergency lighting
systems to supply central or decentralized power.
In the case of an emergency lighting system with
decentralized power supply, the emergency lighting
will be operated with individual batteries and
specialist DALI components.
Pay attention to the number of DALI participants
present in the emergency lighting.
G
22 6T7663A6LE001210A2