Product name: DALI Gateway
Use: Gateway
Design: REG (rail-mounted device)
Order no.: 6 4540 020
1.2 Function
The DALI Gateway represents the interface between a KNX/EIB installation and a digital DALI
(Digital Addressable Lighting Interface) lighting system. The DALI Gateway allows the switching and
dimming of a maximum of 64 lamps including DALI device (e.g. electronic ballast). Each DALI lamp can
be assigned up to 32 different lighting groups that are controlled via the KNX/EIB. This permits the
integration of a room-specific light control of, for example, open-plan offices, multi-purpose rooms,
assembly shops and training classrooms and lecture rooms into the higher-level KNX/EIB building
management. In addition, the lighting groups can be integrated into up to 16 scenes that makes it
possible to recall pre-programmed light moods or to save new light scenarios.
The DALI Gateway permits the separate feedback of individual switching and brightness states of the
DALI groups to the KNX/EIB. In addition, the general DALI operating status can be reported to the
KNX/EIB (error status, short-circuit, status of supply voltage).
The controls (4 pushbuttons) on the front panel of the device permit to manually dim or switch the DALI
light groups on and off in parallel with the KNX / EIB even without bus voltage or in a unprogrammed
state (broadcast of all connected DALI lamps). This feature permits to quickly test the operability of
connected consumers.
The DALI Gateway is able to check the devices integrated into the DALI system for integrity. The
replacement of a defect electronic ballast device by a new one, for example, can be detected if the
“Automatic device replacement” has been activated. The decoding of the parameterized data into the
new electronic ballast device is carried out fully automatic by the Gateway without any special
commissioning. That makes the corrective maintenance of a DALI system much easier.
The configuration and commissioning of the DALI Gateway takes place via a plug-in that is integrated
into the ETS 3. For project design and commissioning of this device it is recommended to use the
ETS3.0d. The advantages with regard to downloading (shorter loading times) are available only if this
new ETS patch version or later versions are used. Other tools besides hardware and software are not
required for the commissioning of the device.
Seite 3 von 130
hager
Fitting, electrical connection and operation
The functionalities that can be preset with the ETS independently for each lighting group include, for
instance, separately parameterizable brightness ranges, extended feedback functions, disable function
or, alternatively, a forced-control position function, separately adjustable dimming response, time delay
and Staircase timer function with pre-warning and soft dimming functions.
Moreover, each lighting group can be integrated into up to 16 scenes with different brightness values.
Centralized switching of all groups is also possible. In addition, the brightness values of the groups can
be set separately in case of bus voltage failure or bus voltage return and after programming with the
ETS.
The Power for the DALI Gateway is entirely supplied by the separate mains connection. The mains
voltage has to be switched on for controlling the DALI interface or programming with the ETS. The
device is designed for fitting on mounting rails in closed compact boxes or in power distributions in
fixed installations in dry rooms.
2 Fitting, electrical connection and operation
2.1 Safety instructions
Electrical equipment must be installed and fitted only by qualified electricians. Observe the
current accident prevention regulations.
Failure to observe any of the installation instructions may cause damage to the device and
result in fire and other hazards.
Before working on the device or before replacing the connected DALI devices, disconnect the
supply voltage (by cutting out the circuit breaker) to avoid the risk of an electric shock.
The DALI Gateway is not suited for safe disconnection of the mains supply.
DALI is a functional extra-low voltage (FELV) device. Safe separation between KNX/EIB and
DALI and mains voltage in installations must be ensured. A minimum spacing of 4 mm must be
ensured between bus wires and DALI/mains conductors.
Do not open the device and do not operate it outside the scope of the technical specifications.
Seite 4 von 130
hager
2.2 Device components
Fitting, electrical connection and operation
(4)
(6)
da+ da-L
ALL OFF
ON/ OFF/
D A L I
N
(3)
(5)
(2)
(1)
(1): KNX/EIB bus connection
(2): Programming key and programming LED (red). The programming LED blinks slowly when the
safe-state mode is active.
(3): Screw terminals (L,N) for connection of mains voltage supply
(4): Screw terminals (da+, da-) for connection of DALI line
(5): 2-digit 7-segment display (red) for the display of the selected DALI group ("01"..."32" / blinking =
group disabled) in manual control mode or for the display of more information:
"
": Indicates DALI commissioning phase after an ETS programming operation or after mains
voltage return. The display duration depends on the number of connected DALI devices
(only briefly after mains voltage return).
"
": Display in an unprogrammed state during manual control.
": Display of a false connection to the DALI connection terminals (da+, da+). Mains voltage
"
connected. DALI Gateway does not operate. The Gateway is ready for operation only after
the error has been eliminated and after a new initialization (mains voltage return).
"
": Indicates the automatic device replacement (cf. Chapter "2.5 Operation").
": Indicates an error occurring during the automatic device replacement
"
(cf. Chapter "2.5 Operation").
The 7-segment display is switched off during bus mode.
(6): Keypad for manual operation with status LED
Seite 5 von 130
hager
Fitting, electrical connection and operation
2.3 Fitting and electrical connection
DANGER!
Electric shock in case of accidental contact with live parts. Electric shocks can be fatal.
Before working on the device, cut out the mains supply and cover up live parts in the
surroundings!
Fitting
Fit the device by snapping it onto the mounting rail in acc. with DIN EN 60715. The screw terminals
should be on top.
• A KNX / EIB data rail is not required.
• Observe the temperature range (-5 °C ...+45 °C) and ensure sufficient cooling, if necessary.
Seite 6 von 130
hager
Fitting, electrical connection and operation
Connecting the device in order to supply the device electronics and the DALI interface with
power
Connect the mains voltage and the DALI system as shown in fig. 1 (connection example).
L1
L2
L3
N
da
da
da+ da-L
ALL OFF
ON/ OFF/
black
red
D A L I
EIB
L
N
N
da
da
DALI device
1
L
N
da
da
DALI device
2
(max. 64)
. . .
Fig. 1: Electrical connection of mains voltage and the DALI interface
• The DALI system voltage is a functional extra-low voltage (FELV). Thus, the DALI interface has to be
treated like a live line in compliance with the applicable installation prescriptions. The DALI Gateway
supplies the system voltage. The installation has to ensure that all
mains voltages of the connected
DALI devices as well as the mains voltage supply of the DALI Gateway will be switched off when
activating a DALI section.
• For a better overview in the installation it is recommended to pay attention to the polarity of the DALI
line. Basically, the compliance with the DALI polarity depends on the DALI devices that are used.
• DALI devices (max. of 64) can be connected to different phase conductors (L1, L2, L3).
Seite 7 von 130
hager
Fitting, electrical connection and operation
Removing other control facilities
DALI devices from some manufacturers feature extended functions (operation with mains voltage at the
DALI terminal). When using the DALI Gateway as a control unit in the DALI system, other existing
control posts – especially when refitting existing systems – have to be removed, if necessary, from the
installation!
Remove all
exist.
L1
L2
L3
N
da
da
corresponding control facilities as shown in figure 2 or ensure that no other control posts
L
da+ da-L
N
N
da
da
ALL OFF
ON/ OFF/
black
red
• Other control posts may also be, for instance, DALI centers, DALI potentiometers or similar control
components. These control posts have to be removed from the DALI system as well in order to
avoid system conflicts.
• Only one DALI Gateway may be operated in a closed DALI system.
• If the DALI gateway detects mains voltage at the DALI terminal (terminals da+ and da-), it will shut
off and display "
D A L I
EIB
Figure 2: Removing other control facilities in the DALI system
".
Seite 8 von 130
hager
Fitting, electrical connection and operation
Installing / removing the protective cap
To protect the bus lines against hazardous voltages, especially in the area of the connecting terminals,
a protective cap can be installed.
The cap is installed with the bus terminal in place and the connected bus line led out at the rear.
To install the cap: Slide the cap over the bus connecting terminal until it is heard to engage (cf. Fig.
3.A).
To remove the cap: Remove the cap by pressing the sides slightly and by pulling it out to the front
(cf. Fig. 3.B).
AB
Fig. 3: Installing / removing the protective cap
Seite 9 von 130
hager
Fitting, electrical connection and operation
2.4 Commissioning
After installation of the Gateway and connection of the bus line and the mains supply as well as the
DALI lines, the device can be put into operation. The following procedure is generally recommended...
DANGER!
Electric shock in case of accidental contact with live parts. Electric shocks can be fatal.
Before working on the device, cut out the mains supply and cover up live parts in the
surroundings.
Commissioning the device
Switch on the mains supply of the Gateway.
Switch on the bus voltage
Checking the voltages: the red programming LED must light up when the programming key is being
pressed.
Program and project the physical address with the ETS.
The DALI Gateway is configured via a plug-in which is integrated into the ETS database. Start the
plug-in (open the parameter view) and configure the KNX/EIB groups (cf. Chapter 4 “Software
description”). Do not yet commission the DALI!
Close the plug-in and download the application program with the ETS.
Restart the plug-in (open the parameter view) and commission the DALI (cf. Chapter 4 “Software
description”).
Close the plug-in in order to save the DALI configuration in the ETS database. Then proceed with
downloading the application program again.
The DALI Gateway is now ready for operation.
• ETS programming will not be possible if the mains voltage is not connected to the DALI Gateway.
• The ETS plug-in will display a message during the closing, if the application program of the DALI
Gateway has to be reprogrammed in the cases described.
Seite 10 von 130
hager
Fitting, electrical connection and operation
2.5 Operation
The DALI Gateway permits all lighting groups to be operated manually. The keypad features 4 function
keys and 3 status LEDs on the front panel of the device that can be used to set the following modes of
operation...
– Bus mode: operation via touch sensors or other bus devices
– Temporary manual control: local manual control via keypad, automatic return to bus mode,
– Permanent manual control: local manual control via keypad
• The control modes can be enabled or disabled via parameter settings in the ETS.
• In manual control mode the groups cannot be controlled via the bus.
• Manual control is possible only while the actuator is supplied with power from the mains. The manual
control mode will be terminated in case of a bus voltage return or mains voltage failure. While in
broadcast mode (unprogrammed DALI Gateway), a bus voltage return cannot abort the manual
control.
• In bus mode, the manual control can be disabled via a telegram. An activated disable function will
terminate the manual control.
• Further details concerning the manual control, especially with respect to the available parameter
settings and the interaction with other functions of the Gateway, can be found in chapter 4. "Software
description" of this documentation.
Seite 11 von 130
hager
Controls and indicators for manual control
Fitting, electrical connection and operation
(1)
(2)
ALL OFF
(3)
ON/ OFF/
(8)
(4)
(5)
Fig. 4: Controls and indicators for manual control
key:
(1)
Activates / deactivates manual control
(2) LED
LED ON indicates permanent manual control.
(3) ON/
Short press: Group ON / Long press: increases brightness of group.
(4) Status LED ON/
Indicates a group that is switched on (brightness: 1...100%) when LED ON in manual control
mode ).
(5) OFF/
Short press: Group OFF / Long press: reduces brightness of group.
(6) Status LED OFF/
Indicates a group that is switched off (brightness: 0%) when LED ON in manual control mode.
(7) ALL OFF key:
All groups off (only in permanent manual control mode).
(8) 7-segment display::
Indicates the selected DALI group for the manual control
("01"..."32" /blinking = group disabled). In addition, the following information can be displayed
during a manual control...
"
collectively controls all DALI devices present in the system via a broadcast command as there
have been no group assignments yet (requires ETS commissioning).
"
of connected DALI devices. The display will extinguish, if the device replacement could be
completed without error.
"
replacement could not be carried out. The display will automatically extinguish after 3 seconds.
:
key
:
key:
:
": Manual control in unprogrammed state (broadcast mode). In this case, the DALI Gateway
": Indicates the automatic device replacement. The display duration depends on the number
": Indicates an error that occurred during the automatic device replacement. The device
(6)
(7)
Seite 12 von 130
hager
Fitting, electrical connection and operation
Priorities
The DALI Gateway distinguishes between different functions that can affect a DALI group. In order to
prevent conflicting output states, each available function has been assigned a certain priority. The
function with the higher priority overrides the one with the lower priority.
st
– 1
Priority: Manual control mode (highest priority)
nd
– 2
Priority: Forced-control position or disable function
rd
– 3
Priority: Direct bus mode (“Switching” & “Dimming” & “Brightness value” objects, scenes, centra
function)
Switching on the temporary manual control for the broadcast function
The manual control for the broadcast function can be utilized while the DALI Gateway is in the
unprogrammed state. As in this case no group configurations have been stored due to a missing ETS
programming, the DALI Gateway will collectively control the connected DALI devices in manual control
per broadcast command.
The DALI Gateway has not yet been programmed via the ETS.
Press the key briefly (< 1 s).
" is shown on the 7-segment display.
"
• After 5 s without key-press, the Gateway will deactivate the manual control for the broadcast.
• The Gateway is delivered with the broadcast mode activated. After programming via the ETS, it is
also possible to reactivate the broadcast mode any time by unloading the application program via the
ETS.
Switching on the temporary manual control for broadcast
The DALI Gateway has not yet been programmed via the ETS.
Temporary manual control mode for the broadcast has been activated.
No key-press for 5 s
- or -
Press key twice.
- or -
Switch off mains voltage supply.
Temporary manual control mode for broadcast has now been terminated. The 7-segment display will
extinguish.
• When shutting off the temporary manual control mode for broadcast, the state selected by manual
control will not change.
Switching on permanent manual control mode for broadcast
The DALI Gateway has not yet been programmed via the ETS.
Manual control mode or temporary manual control mode for broadcast has not been activated.
Press the key for at least 5 s.
The
status LED is illuminated. "" is shown on the 7-segment display. Permanent manual
control mode for broadcast has been activated
Seite 13 von 130
hager
Fitting, electrical connection and operation
Switching on the permanent manual control mode for broadcast
Permanent manual control mode for broadcast has been activated.
Press the key for at least 5 s
- or -
Switch off mains voltage supply.
Permanent manual control mode for broadcast has now been terminated. The
7-segment display will extinguish.
• When shutting off the temporary manual control mode for broadcast, the state selected by manual
control will not change.
Operating DALI devices in manual control mode for broadcast
The DALI Gateway has not yet been programmed via the ETS.
Manual control mode (permanent or temporary) has been activated.
Operate the devices by pressing the ON/ key or OFF/ key.
Brief press: Collective switch on/off.
Long press: Collective increase/decrease of brightness.
Long press & releasing: Stopping collective dimming.
All connected DALI devices will immediately execute the corresponding commands.
Switching off all DALI devices in manual control mode for broadcast
Permanent manual control mode for broadcast has been activated:
Press the ALL OFF key.
All connected DALI devices will be immediately switched off (brightness: 0 %). The devices are not
locked. Collective activation is again possible after shutoff.
• The "ALL-OFF" function is not available in temporary manual control mode.
Activating temporary manual control mode
If the DALI Gateway has been programmed at least once via the ETS, at least one DALI group will be
created and configured. In this case, the created groups can be individually controlled via manual
control. The broadcast mode will be deactivated.
The DALI Gateway has been programmed at least once via the ETS.
Manual control has been enabled in the ETS.
Press the key briefly (< 1 s).
The group number “01” will be shown on the 7-segment display.
• After 5 s without a key-press, the Gateway automatically returns to the bus mode.
• The Gateway is delivered with the broadcast mode activated. After programming via the ETS, the
broadcast mode can be reactivated any time by unloading the application program via the ETS.
status LED and the
Seite 14 von 130
hager
Fitting, electrical connection and operation
Deactivating the temporary manual control mode
Temporary manual control mode has been activated.
No key-press for 5 s
- or -
select all groups successively by a brief press of the key. Now press the key once more.
- or -
Shut off power supply or reset bus (bus voltage return).
The temporary manual control mode is now terminated. The 7-segment display will extinguish.
• When shutting off the temporary manual control mode, the state selected by manual control will not
change. If, however, a forced-control position or a disable function has been activated via the bus
prior or during the manual control, the DALI Gateway will execute the disable or forced responses for
the affected groups.
Activating the permanent manual control mode
The DALI Gateway has been programmed at least once via the ETS.
Manual control has been enabled in the ETS. Bus mode or temporary manual control mode has been
activated.
Press the key for at least 5 s
The
Permanent manual control mode is now activated:
Deactivating permanent manual control mode
Permanent manual control mode is activated.
Press the key for at least 5 s
- or -
Shut off power supply or reset bus (bus voltage return).
The permanent manual control mode for broadcast has now been terminated. The
the 7-segment display will extinguish.
• Depending on how the Gateway has been parameterized in the ETS, the groups will be set to the
state last adjusted via manual control or to the state internally tracked (direct control, forced-control
position / disable function) when shutting off the permanent manual control.
status LED lights up. The group number “01” will be shown on the 7-segment display.
status LED and
Seite 15 von 130
hager
Fitting, electrical connection and operation
Controlling a DALI group manually
The DALI Gateway has been programmed at least once via the ETS.
Manual control mode (permanent or temporary) has been activated.
Select desired group: Press the key briefly (repeatedly, if necessary).
The 7-segment display will display the group number of the activated DALI group. The "ON/
(1...100 %) or "OFF/
Control the group by pressing the ON/ or OFF/ key.
" (0 %) status LED on the keypad indicates the brightness of the group.
Brief press: Switching on/off.
Long press: Increasing/decreasing brightness.
Long press & releasing: Stop dimming.
The activated DALI group will immediately execute the corresponding commands.
Switching off all groups
Permanent manual control mode has been activated:
Press the ALL OFF key.
All groups are shut off immediately (brightness: 0 %). The groups are not locked. Subsequently, they
can again be individually controlled.
• The "ALL-OFF" function is not available in temporary manual control mode.
Disabling bus mode of individual groups manually
The DALI Gateway has been programmed at least once via the ETS.
Permanent manual control mode has been activated:
The disabling of the bus mode must have been enabled in the ETS.
Select group: Press the key briefly (repeatedly, if necessary)
The 7-segment display will display the group number of the activated DALI group. The "ON/
(1...100 %) or "OFF/
Press the ON/ and OFF/ keys simultaneously for at least 5 s.
" (0 %) status LED on the keypad indicates the brightness of the group.
The relevant DALI group is now disabled (no bus mode possible).
The 7-segment display for the relevant group is blinking.
• To unlock, proceed in the same way.
• A group that has been disabled manually can only be operated in the permanent manual control
mode.
"
"
Seite 16 von 130
hager
Fitting, electrical connection and operation
DALI device replacement
After the start of the automatic device replacement, the DALI Gateway can check the DALI system for
the integrity of the DALI devices that have been previously put into operation. If, for instance, the
installer has replaced a defect DALI electronic ballast device with a new one, the DALI Gateway is able
to program the new electronic ballast device with the project data of the failed electronic ballast device.
Thus, it is possible to replace a failed DALI device by a simple operation on the device without having
to set parameters with the ETS.
The DALI Gateway has been programmed at least once via the ETS.
The automatic device replacement must be activated in the ETS.
Bus and mains voltage (on all DALI devices) must be switched on.
The DALI system must have already been put into operation via the ETS plug-in.
Only one
The device must be in bus mode (no active manual control)
Press the and ALL OFF keys simultaneously for at least 10 s.
The automatic device replacement will be activated. The time required for this operation depends on
the number of DALI devices available in the system. The 7-segment display indicates "
during the device replacement. If the replacement has been successful, the display will extinguish.
• All other functions of the DALI Gateway are paused during the device replacement. The Gateway
tracks all bus states received during the device replacement and regularly analysizes the values
tracked last (switching, dimming, brightness value, scenes, central function, forced-control position,
disable function) at the end of the automatic device replacement. The device replacement will
interrupt any active forced-control position or disable function which will be activated again at the end
of the replacement, if, in the meantime, the functions have not been deactivated via the bus. The
behaviour as at the beginning of these functions will not be executed again.
• Make sure that only one DALI device is being replaced in the way described. In case several
electronic ballast devices have failed (possibly not connected to mains voltage) and been replaced,
the electronic ballast devices cannot be positively identified and automatically be configured. In this
case, a new DALI commissioning via the ETS plug-in is required.
• If an error has occurred during the device replacement, the 7-segment display will indicate ""
(Error) for 3 s. The procedure has to be carried out again by following the requirements and details
as mentioned above.
This signalling will take place even if the automatic device replacement has been activated without a
prior DALI device replacement.
DALI device may have failed and may be replaced.
" (Learn)
Seite 17 von 130
hager
Technical data
3 Technical data
Type of protection: IP 20
Safety class: III
Mark of approval: KNX / EIB / VDE
Ambient temperature: -5 °C ... +45 °C
Storage / transport temperature: -25 °C ... +70 °C
(Storage above + 45 °C reduces the lifetime)
Mounting position: optional (screw terminals preferably on top)
Minimum distances: none
Type of fastening: Snap-fastening on DIN rail in closed cabinets (e.g. small
distributions, etc.) / KNX / EIB data rail not required.
KNX / EIB supply
Voltage: 21…32 V DC SELV
Power consumption: typically 150 mW
Connection: standard KNX/EIB bus connection terminal
External supply
Voltage: 110...240 V AC +10 % / -15 %, 50/60 Hz
Power consumption: max. 6 W
Connection:
Total power loss: max. 3 W
Response to bus voltage failure: depending on parameterization
Response to bus voltage failure
Response to bus voltage return:
Response to mains voltage return:
with screw terminals:
0,5…4 mm² solid and stranded wire without ferrule
0,5…2,5 mm² stranded wire with ferrule
Max. tightening torque: 0.8 Nm
(cf. chapter 4. "Software description")
As per parameterization, the device can report the supply voltage
failure to the bus. Afterwards, the device will completely shut
down.
depending on parameterization
(cf. chapter 4. "Software description")
The device will briefly initialize ("
" display) and is then ready
for operation. As per parameterization, the device can report the
return of supply voltage to the bus.
The brightness of a DALI group depends on the parameterization
(cf. Chapter 4. “Software description”).
Seite 18 von 130
hager
DALI:
Voltage: typically 16 V DC
with over-voltage protection
Current: typically 128 mA, max. 200 mA temporarily
designed for a maximum of 64 DALI devices at 2 mA
with short-circuit and overload protection
Transmission rate 1200 bit/s
Protocol: acc. to DIN EN 60929 appendix E4
Cable lengths between
Gateway and device:
∅ 1,5 mm²
∅ 1,0 mm²
∅ 0,75 mm²
∅ 0,5 mm²
Resistivity:
Cable type: Specified by functional extra-low voltage. (FELV) /
max. 300 m
max. 238 m
max. 174 m
max. 116 m
max. 4
Preferably 2 free wires of a NYM installation line.
Technical data
Seite 19 von 130
hager
Software specifications
4 Software description
4.1 Software specifications
ETS search paths: - Illumination / Dimmer / DALI Gateway
BAU used: TPUART + µC
KNX/EIB type class: 3b - device with cert. PhL + stack
Configuration: S-mode standard
PEI type: "00"
PEI connector: no connector
Applications:
No. Summarized description: Name Version Executable from
Hex
/ "0"
Dec
mask version
1 Multi-functional control of up to 32 DALI
groups with adjustable dimming response,
time functions, scenes, disable function or
forced-control position, Soft-ON or SoftOFF functions and extended feedback.
Centralized switching of all outputs is also
available. In addition, the brightness values
of the DALI groups can be separately
adjusted in case of bus voltage failure or
return or after programming with the ETS.
DALI Gateway
C00C02 EN
DALI Gateway
C00C12 EN
0.2 (english)
for ETS 3.0
Versions a…c
1.2 (english)
for ETS3.0 from
version d
onwards
705
Seite 20 von 130
hager
"DALI Gateway C00Cx2" software
Scope of functions
4.2 "DALI Gateway C00Cx2" software
4.2.1 Scope of functions
General:
• Control of a maximum of 64 DALI devices in a max. of 32 groups.
• Manual control of the groups independent of the bus (site operation with broadcast control).
• Feedback of DALI error status or short-circuit and supply voltage failure message.
• Central switching function.
• Incorporation of the groups into up to 16 light-scenes possible.
Channel-oriented:
• Each group features the full scope of functions without any restrictions. All channel-oriented
functions can be parameterized separately for each group. This feature permits independent and
multi-functional control of the DALI devices. However, the Staircase timer function can only be
parameterized for groups 1 ... 16.
• Switching feedback and brightness value: active (after changes or cyclical transmission to the bus)
or passive (object read-out function) feedback function.
• Adjusting the limit values for brightness is possible.
• Dimming response can be parameterized.
• Soft-On or Soft-Off function.
• Disable function or, alternatively, forced-control position function can be parameterized for each
group. With the disable function, blinking of lighting groups is possible.
• Timer functions (ON-delay, OFF-delay, staircase lighting function, also with pre-warning function).
• Response to bus voltage failure and bus voltage return as well as after ETS programming can be
adjusted for each group.
Plug-in:
• Convenient DALI commissioning without additional software components.
• Test function for all created DALI groups or DALI devices: central ON/OFF switching, individual
hardware check (ON / OFF, brightness value preset, device status), individual group check
(switching, dimming) and scene check.
• Export and import of preset parameters in XML format.
• Printing function for creating a configuration report (overview of group assignments or of the entire
device configuration).
Seite 21 von 130
hager
"DALI Gateway C00Cx2" software
Software information
4.2.2 Software information
ETS project design and commissioning
For creating a project and for the commissioning of this device it is recommended to use the ETS3.0d
version. Advantages with regards to downloading (significantly shorter loading times) can be expected
only if this ETS patch version or later versions are used. The advantages result from the use of the new
mask version 7.5 and the ETS3 support.
The product database required for the ETS3.0d is offered in the *.VD4 format. The corresponding
application program has the version number “1.1”. For older versions of the ETS3 a separate product
database is available in the *.VD2 format. The application program for these ETS versions is version
"0.1".
As far as the scope of functions described in this documentation is concerned, there is no difference
between the two application programs.
When older ETS versions are updated to the level of version ETS3.0d or to that of later versions, an
additional tool in the form of an ETS add-in is available. This tool is capable of converting older product
databases of application version "0.1", for instance from existing ETS2 projects, into the new
application format (version "1.1"). This feature permits making use of the advantages of the ETS3.0d
application in an easy way and without creating any changes to the project design. The ETS3 add-in
can be obtained separately from the manufacturer and is free of charge.
Safe-state mode
If the device - for instance as a result of errors in the project design or during commissioning - does not
work properly, the execution of the loaded application program can be paused by activating the safestate mode. In the safe-state mode, the outputs cannot be controlled via the bus. A manual control for
broadcast is the only feature that can be activated. The Gateway remains passive in safe-state mode
since the application program is not being executed (state-of-execution: terminated). Only the system
software is still functional so that the ETS diagnosis functions and also the programming of the device
continue to be possible.
Activating safe-state mode
Disconnect the mains voltage supply.
Press the programming key and keep it pressed.
Switch on the mains voltage supply. Release the programming key only after the programming LED
starts blinking slowly.
The safe-state mode is now activated. With another brief press on the programming key, the
programming mode can be switched on and off as usual also in the safe-state mode. The
programming LED will nonetheless continue to blink independent of the programming mode as long
as the safe-state mode remains active.
• The safe-state mode can be terminated by switching off the mains voltage supply or by programming
with the ETS.
• For the activation of the safe-state mode, the bus voltage does not have to be switched on.
Unloading the application program
The application program can be unloaded via the ETS. In this case, only manual control is possible for
the broadcast of connected DALI devices.
Seite 22 von 130
hager
"DALI Gateway C00Cx2" software
Object table
4.2.3 Object table
Number of communication objects: 216
Number of addresses (max): 254
Number of assignments (max): 255
Dynamic table management: no
Maximum table length: 255
Objects affecting several channels:
Function: Scenes
Object Function Name Type DP type Flag
208
Description: 1-byte object for recalling scenes or for storing new scene values.
Function: DALI fault and performance monitoring
Extension unit Scenes 1- byte 18.001 C, W, -, (R)
1
Object Function Name Type DP type Flag
210
Feedback DALI error status 1-byte --- C, W, T, (R) 1
2
Description: 1-byte object for transmitting the error status of DALI devices that are connected
individually to the system to the bus. The following bit assignment is used:
Bit 0…5: number of the DALI device (0…63)
Bit 6: lamp error (0 = no error, 1 = error)
Bit 7: electronic ballast error (0 = no error, 1 = error)
Independent of the feedback parameter setting, this object can always receive
telegrams (ValueWrite) as a transmission request. A received telegram will be
immediately answered via this object (ValueWrite) by transmitting the current internal
object status. Bits 0...5 in a request telegram must include the number of the DALI
device. Bits 6 and 7 have to be set to “1”. Otherwise, the request telegram will be
ignored.
1
Each communication object can be read-out. The readout requires the setting of the R flag.
2
Depending on the parameterization the feedback objects are either actively transmitting (T flag) or can be passively read-out (R flag).
Seite 23 von 130
hager
"DALI Gateway C00Cx2" software
Object table
Function: DALI monitoring
Object Function Name Type DP type Flag
211
Message DALI voltage failure 1-bit 1.005 C, -, T, (R)
Description: 1-bit object for reporting a mains voltage failure at the DALI Gateway.
(mains voltage available = 0, mains voltage failure = 1)
Function: DALI monitoring
Object Function Name Type DP type Flag
212
Message DALI short-circuit 1-bit 1.005 C, -, T, R1
Description: 1-bit object for reporting a short-circuit in the DALI line.
(no short-circuit = 0, short-circuit = 1)
Function: Central function
Object Function Name Type DP type Flag
213
Switching Central function 1-bit 1.001 C, W, – (R)1
Description: 1-bit object for the central switching of assigned DALI groups. The polarity can be
parameterized.
Function: Manual control
1
Object Function Name Type DP type Flag
214
Disable Manual control 1-bit 1.003 C, W, – (R)1
Description: 1-bit object for disabling the keys for manual control on the device. The polarity can be
parameterized.
Function: Manual control
Object Function Name Type DP type Flag
215
Status Manual control 1-bit 1.002 C, -, T, (R)
1
Description: 1-bit object for the status transmission of manual control. The object is "0", when
manual control is deactivated (bus mode). The object is "1", when manual control is
activated. The user can determine whether the temporary or the permanent manual
control will be displayed as status information.
1
Each communication object can be read-out. The readout requires the setting of the R flag.
Seite 24 von 130
hager
"DALI Gateway C00Cx2" software
Object table
Channel-oriented objects:
Function: Output switching
Object Function Name Type DP type Flag
0, 7, 14, … , 105
112, 118, …, 202
Switching
Group 1 ... 32 1-bit 1.001 C, W, -, (R)
Description: 1-bit object for switching a DALI group on or off
("1" = switching on; "0" = switching off).
Function: Output relative dimming
Object Function Name Type DP type Flag
1, 8, 15, … , 106
113, 119, …, 203
Dimming
Group 1 ... 32 4-bit 3.007 C, W, – (R)
Description: 4-bit object for the relative dimming of a DALI group.
Function: Output absolute dimming
1
1
Object Function Name Type DP type Flag
2, 9, 16, … , 107
114, 120, …, 204
Brightness value
Group 1 ... 32 1-byte 5.001 C, W, – (R)
1
Description: 1-byte object for setting an absolute dimming value (brightness value 0...255)
by the bus.
Function: Absolute dimming feedback
Object Function Name Type DP type Flag
3, 10, 17, … , 108
115, 121, …, 205
Brightness value
feedback
Group 1 ... 32 1-byte 5.001 C, -, T, (L)
1 2
Description: 1-byte object for transmitting feedback of an adjusted dimming value
(brightness value 0…255) to the bus.
Function: Switching feedback
Object Function Name Type DP type Flag
4, 11, 18, … , 109
116, 122, …, 206
Switching feedback
Group 1 ... 32 1-bit 1.001 C, -, T,( R)
1 2
Description: 1-bit object for transmitting feedback to the bus signalling the switching state
(“1” = switched on / “0” = switched off).
1
Each communication object can be read-out. The readout requires the setting of the R flag.
2
Depending on the parameterization the feedback objects are either actively transmitting (T flag) or can be passively read-out (R flag).
Seite 25 von 130
hager
"DALI Gateway C00Cx2" software
Object table
3
Function: Staircase timer function
Object Function Name Type DP type Flag
5, 12, 19, … , 110
Staircase timer
function start/stop
Description: 1-bit object for activating or deactivating the switching time of the Staircase timer
function of an output ("1" = on / "0" = off).
Function: Disable function
Object Function Name Type DP type Flag
6, 13, 20, … , 111
117, 123, …, 207
Disable Group 1 ... 32 1-bit 1.003 C, W, – (R)
Description: 1-bit object for disabling a group (polarity is parameterizable).
Function: Forced-control position function
Object Function Name Type DP type Flag
6, 13, 20, … , 111
117, 123, …, 207
Forced-control
position
Description: 2-bit object for the forced-control position of a group. The polarity will be provided by
the telegram.
Group 1 ... 16 1-bit 1.010 C, W, -, (R)
Group 1 ... 32 2-bit 2.001 C, W, – (R)
1
1
1
3
The Staircase timer function can only be parameterized for the first 16 groups.
1
Each communication object can be read-out. The readout requires the setting of the R flag.
Seite 26 von 130
hager
"DALI Gateway C00Cx2" software
Functional description
4.2.4 Functional description
4.2.4.1 Application basics
DALI
The DALI Gateway represents the interface between a KNX/EIB building installation and a digital DALI
(Digital Addressable Lighting Interface) lighting system. Normally, all DALI systems are room-oriented
and deal with the high demands on functional light management in, for example, offices, training and
conference rooms. Often, these applications make it necessary to incorporate the room-oriented DALI
system also into the KNX/EIB facility management across buildings. That makes it possible not only to
control the DALI lighting system via the sensor components of the KNX/EIB but also to incorporate the
shutter, heating and air conditioning systems already existent in the buildings into the light
management.
A DALI system can address a maximum of 64 devices. The Gateway itself does not count as a device.
The DALI Gateway offers 32 KNX/EIB controllable groups that are parameterized in the ETS 3 similar
to a dimming actuator channel. There are several communication objects available at the bus that
permit, among other things, the switching, the dimming, the setting of brightness values or the time or
scene control of a group. During the DALI commissioning, the DALI devices (max. of 64) will be
optionally assigned one or several groups of the Gateway (cf. figure 5 on the following page). It is the
group assignment that makes it possible to control the DALI devices individually (individual assignment
– only one device in the group) or collectively (multiple assignment – several devices in a group) via the
KNX/EIB.
A multiple assignment of DALI devices is possible for the groups 1...16 of the DALI Gateway. In this
case the addressing takes place at the DALI via group addresses that the DALI Gateway configures
“hidden” to the user. The DALI Gateway handles them independently. During the DALI commissioning,
all affected devices will be automatically programmed.
The groups 17...32 accept only individual assignments. Each group can be assigned only one DALI
device. In this case, the DALI addressing takes place via an internally specified individual address.
Only one device can be uniquely addressed via this individual address. This individual address will also
be automatically assigned by the DALI Gateway during the DALI commissioning.
The DALI commissioning takes place entirely via the plug-in embedded in the ETS 3 via the KNX/EIB
bus line. No additional tool and no special programming link is required.
The commissioning of the DALI devices as well as the DALI configuration or the DALI addressing takes
place fully automatic via the plug-in and the DALI Gateway. Only the assignment between the DALI
device and the group must be carried out ‘manually’ in the commissioning environment of the plug-in.
Different test or detection functions (separate switching on, switching off or blink function) available in
the plug-in make it also considerably easier to commission the different DALI devices.
Seite 27 von 130
hager
"DALI Gateway C00Cx2" software
Functional description
Group 2
Lamp 5
Lamp 4
Lamp 1
Group 1
Lamp 7
Lamp 6
Lamp 3
Lamp 2
Group 3
Lamp 9
Lamp 8
Lamp 11
Lamp 10
Figure 5: Example of a grouping in the DALI system
In the example of a grouping (cf. Figure 5) each one of the drawn-in lamps features a DALI device
which is assigned one or several groups. In the example, lamp 1 is part of an individual group. This
lamp can be controlled separately from the other lamps. The other lamps belong to group 2. Hence,
they are collectively controlled. In addition, the lamps 2, 3, 6 and 7 can be controlled via group 3. Thus,
groups 2 and 3 assigned to these lamps overlap.
• DALI devices that are assigned several groups will always adjust to the state that has been adjusted
last via one of the assigned groups. In this case, the feedback of the switching status or the
brightness value of a group is not always unique.
Example 1(cf. Figure 5): Group 2 is set to 10% brightness. Group 3 is then dimmed to a brightness
value of 20%. The lamps of group 3 will accept the brightness value of 20% which was invoked last.
The feedback of group 2 remains on 10% although some of the devices belonging to the group have
been set to 20% brightness.
Example 2: group 2 is switched on and assumes the brightness value of 100%. Internally, the state
of group 3 remains set at 0% brightness (OFF). The brightness of group 3 is now increased. The
lamps of group 3 will adapt to the dimming (increasing brightness starting at minimum brightness)
even though these lamps have already been switched on via group 2.
Basically, the assignment of DALI devices to groups is arbitrary. For the reasons mentioned above it
is recommended not to assign the devices to several groups at the DALI. Preferably, the devices
should be allocated to separate instead of overlapping groups. A KNX/EIB link via the group
addressing in the ETS is also preferred.
Seite 28 von 130
hager
"DALI Gateway C00Cx2" software
Functional description
The DALI Gateway acts as the central control component (master-controller) in the system that also
ensures the power supply of the DALI interface. The DALI devices, e.g. DALI electronic ballast,
function as slaves that transmit back the states or status reports to the master only upon request. It is
the function of the DALI Gateway only to transmit control commands received by the KNX/EIB to the
DALI line as well as to control the devices. Further DALI control components in multi-master mode, e.g.
an additional DALI center, a DALI potentiometer or power switching pushbuttons, are unnecessary and
can lead in some individual cases to malfunction in the DALI system. Therefore, it is necessary to
remove other control components from the system – especially when refitting existing DALI systems.
The DALI system is then entirely controlled by components of the KNX/EIB (cf. figure 6).
Figure 6: Schematic diagram of a KNX/EIB-DALI system interconnection
(example: DALI electronic ballast in different groups)
Seite 29 von 130
hager
"DALI Gateway C00Cx2" software
Functional description
The communication via the DALI Gateway between the KNX/EIB and the DALI interface is bidirectional. On the one hand, the Gateway receives telegrams from the KNX/EIB that either directly
influence the brightness status of a DALI group (e.g. by switching, dimming, setting the brightness
value or scene recall) or indirectly adjust it (e.g. via time, disable or forced-control position functions).
Thus, the DALI Gateway internally always detects the current brightness states of the groups and
forwards brightness commands to the DALI devices which will then adjust to the corresponding
brightness.
On the other hand, the internally tracked switching or brightness states of the groups can be reported
back to the KNX/EIB. The transmission of status information of the DALI devices (lamp error, electronic
ballast error) or the Gateway (mains voltage failure, DALI short-circuit) to the bus is possible.
In addition, all groups controllable by up to 32 KNX/EIBs can be integrated in 16 independent scenes.
In a scene, brightness values can be separately parameterized for each DALI group in the ETS. They
can also be adjusted any time later during the on-going operation.
• If the DALI devices have been assigned several groups (overlapping groups) and if these groups
have been assigned a common scene, the devices will adjust to the brightness value of the group
with the highest number.
Example: An electronic ballast device has been assigned groups 1 and 2. Both groups have been
assigned scene 1. When recalling a scene, group 1 is to adjust to a brightness of 10 % and group 2
to 20 %. If scene 1 is recalled the electronic ballast device is adjusted to 20 % brightness since
group 2 has the higher group number.
Seite 30 von 130
Loading...
+ 100 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.