Hager SM213, SM214 User guide

SM213, SM214
Ethernet module JBUS/MODBUS for SM103E Ethernet module + RS485 for SM103E
§
User instructions
Contents
Preliminary operations ................................................... 1
General informations...................................................... 1
Installation ...................................................................... 3
Programmation............................................................... 5
Acces to programming mode (COde= 100) ....................... 5
Ethernet configuration on SM103E.................................. 6
IP adress .................................................................. 7
Mask ....................................................................... 8
Gateway ................................................................... 9
DHCP ...................................................................... 9
Parameters associated with the MODBUS RTU protocol ...........
and the RS485 gateway ............................................. 10
Communication address............................................. 11
Communication speed ............................................... 11
Communication parity................................................ 12
Communication stop bit ............................................. 12
To quit programming ................................................. 12
Web server.............................................................. 13
Environmental conditions and type of test ...................... 13
Technical characteristics ............................................. 14
Environmental conditions and type of test ...................... 14
Communication table................................................. 14
§
Preliminary operations
1
For personnel and product safety please read the contents of these operating instructions carefully before connecting. Check the following points as soon as you receive the package:
• the packing is in good condition
• the product has not been damaged during transit
• the product reference number conforms to your order
• the package contains the product and the operating instructions.
Functionalities and ethernet connections
• MODBUS/TCP protocols ...................................................
Communication: ........................................................... 502
Number of connections available: ................................... 4
• JBUS/MODBUS RTU over TCP protocol...........................
Communication : .......................................................... 503
Number of connections available: ................................... 4
Ethernet Module (ref. SM213)
• Link to an RJ45 connection.
• Protocole MODBUS/TCP and JBUS/MODBUS RTU with TCP.
• Web server for viewing the main values and product configuration.
A MODBUS address must be defined for SM103E to be able to use the MODBUS RTU protocol with TCP. Also, to use the RS485 gateway, a list must be defined of the para­meters to be used: speed, stop bit, parity.
• Web server...........................................................................
Number of connections available: ................................... 4
N.B.
The number of connections available depends on the brother used.
Ethernet
SM103E
RJ45
General informations
PLC
The module is available in 2 versions :
• Ethernet module (ref. SM213)
• Ethernet module with MODBUS RTU gateway (ref. SM214)
Functions
The optional ethernet module is linked to the SM103E and enables connections to be made to a type 10BaseT or 100BaseT ethernet network. It also enables the SM103E measurement units to be used and monitored from a PC or an PLC.
TCP/IP (RJ45) Max. 4 clients
Ethernet Module with MODBUS RTU gateway (ref. SM214)
• As well as ethernet communication (see optional ethernet SM213 module), the optional SM214 module provides an RS485 serial link (2 or 3 wires) in JBUS/MODBUS
®
protocol. It enables SM103E to be used from a PC or PLC.
This option’s gateway enables the module to be used as the master in an RS485 Jbus/Modbus network with a maximum of 246 slaves. To do this, it is necessary to configure a Jbus/Modbus address different to 255.
In a standard configuration, an RS485 link can connect 31 SM102E or SM103E units or any other communicating products with a PC or PLC over a distance of 1200 metres.
2
Recommendations
You should use a shielded twisted pair (LIYCY type). In a disturbed environment or large network (in terms of length) we recommend the use of a shielded twisted pair (type LIYCY-CY). A repeater (1 channel) or an arrestor (4 channels) should be used if you intend to exceed the distance (1200 m.) and/or maximum number (31) of SM103E. Please contact us for more information.
N.B.
A 120 ohm resistance (found on the additional module) must be fixed at both ends of the link.
N 1 N n
R=120Ω R=120Ω R=120Ω
+ - - +
Ethernet
RS485
R=120Ω
RJ45
SM103E
N 1 N 2 N n
R=120
Ethernet
RS485
R=120
SM103E
RJ45
MODBUS maximum of 246 slaves
PLC
TCP/IP Maximum of 4 clients
MODBUS maximum of 246 slaves
PLC
TCP/IP Maximum of 4 clients
~–1200 M or 32 UL
~–1200 M or 32 UL ~–1200 M or 32 UL
Repeater
Installation
3
The SM103E product must be disconnected.
The module is fitted onto the back of the SM103E. Its width is that of 2 single option slots and it can be placed in any slot.
2
Fix the module in one of the four positions.
1
Example of installation in slot 1.
4
Follow indications when connecting the terminal. Switch on voltage supply.
3
1
2
3
4
4
Installation
Visual diagnostic
• LED indicators
LED Color Status Description
SYS - NOT LIT No internal electrical supply
Hardware is faulty
Yellow LIT Loading phase of the software,
waiting to start
FLASHING AT 1 sec. Error during the start-up phase
Green LIT Operating system functioning
COM Green LIT Normal operation
Red FLASHING Ethernet or RS485 communication error
LIT Abnormal operation, check the ethernet module
is correctly fitted
Link Green NOT LIT No connection to the ethernet network
LIT Ethernet Network connected
Activity Yellow FLASHING Sending/receiving ethernet frames
5
Programmation
x 1
x 1
x 1
conrm
x 1
3 sec
Access to programming mode (COdE = 100)
Programmation
6
x 4
x 4
x 4
x 1
Ethernet configuration on SM103E This involves setting up the IP parameters for
the SM103E connected to the gateway
IP address (Rth Adr IP):
[CLASS A].[CLASS B].[CLASS C].[CLASS D]
Subnet mask (Eth MASH):
[CLASS A].[CLASS B].[CLASS C].[CLASS D]
Gateway (Eth GATE):
[CLASS A].[CLASS B].[CLASS C].[CLASS D]
DHCP activation (Eth DHCP): Yes/No
The factory setting is:
IP 1address: 92.168.1.1
Subnet mask: 255.255.255.0
Gateway: 0.0.0.0
DHCP activation: NO
7
x 2
x 1
x 1
Programmation
IP address
Example: programming the address 191.158.1.7
CLASS D = 158
x 2
x 1
x 1
Example: programming the address 191.158.1.7
CLASS D = 158
8
x 4
Mask
Example: 255.255.255.0
Proceed as for the IP address
x 3
IP address
Example: programming the address 191.158.1.7
CLASS C = 1
Programmation
x 6
x 3
x 1
Example: programming the address 191.158.1.7
CLASS C = 7
9
Programmation
x 4
Gateway
Example: 0.0.0.0
Proceed as for the IP address
x 1
YES
NO
x 1
x 1
DHCP
The DHCP function is not recommended. Contact the administrator of the IT network.
10
Programmation
p.16
p.16
p.17
p.17
Previous menu
Previous menu
Parameters associated with the MODBUS RTU protocol and the RS485 gateway
Communication address
Communication speed
Communication parity
Communication stop bit
11
x 3
x 2
x 1
conrm
Programmation
Communication address
Example: COM ADR = 7
x 1
x 1
x 1
conrm
Communication speed
Example: BDS = 19 200 bauds
Programmation
12
x 1
x 1 (Odd)
x 2 (Even)
x 3 (No)
Communication parity
Example: PAr = EvEn
x 1
x 1
conrm
x 1 (2 bits)
x 2 (1 bits)
Communication stop bit
Example: STOP = 2
x 1
3 sec.
To quit programming
13
Programmation
Web server
The web server can be accessed by entering the product’s IP address into your internet browser.
IP address of the SM103E: 19.168.1.0 URL address: http://19.168.1.0
The web server display:
• The main SM103E database parameters.
• The main instantaneous and mean values measured and the meters.
Environmental conditions and type of test
Electromagnetic compatibility:
• Module connected to SM103E.
Performance criteria required
Emission general standard EN 61326-1 (2006)
Conducted emission EN 55011
Radiated emission EN 55011 Group 1, class B
Harmonic current emission EN 61000-3-2 Group 1, class B
Flicker, and voltage fluctuations EN 61000-3-3 Class A
Immunity general standard EN 61326-1 (2006)
Electrostatic discharges Air discharges Contact discharges
EN 61000-4-2 level = ± 8 kV level = ± 4 kV
B
Radiated electromagnetic field
80-1000 MHz 1000-000 MHz 000-700 MHz
EN 61000-4-3 AM : 1 kHz to 80 % level = 10 V/m level = 3 V/m level = 1 V/m
A
Electrical fast transient burst On power supply lines On I/O lines
EN 61000-4-4 level = ± 2 kV level = ± 1 kV
B
Surges 1,2/50 μs On AC power supply lines (MD) On AC power supply lines (MC) On I/O lines (MC)
EN 61000-4-5 level : ± 1 kV level : ± 2 kV level : ± 1 kV
B
Conducted disturbances inducted by AM radio frequency fields
EN 61000-4-6 level = 3 Vrm AM : 1 kHz to 80 %
A
Power frequency magnetic field 50 Hz
EN 61000-4-8 level = 30 A/m
A
Voltage variations/DIPS On power supply lines
EN 61000-4-11 Réduction 100 % ; 1 per Reduct 60 % ; 10 per Reduct 30 % ; 5 per Reduct > 95 % ; 50 per
B C C C
Technical characteristics
14
Operational temperature -10 to 55 °C Storage temperature -20 to 85 °C
Environmental conditions and type of test
• Conditions environnementales
Electrical specification RS485 EIA 2 fils half duplex Transmission speed 400 to 38400 Bit/s Stop bit 1, 2 Parity without, odd, even Maximum number of slaves 246
RS485
Electrical specification RJ45 IEEE 80-3 standard Insulation: 1500V Transmission speed 10MBits/s or 100MBits/s Stop bit MODBUS TCP
JBUS/MODBUS RTU over TCP
HTTP
Ethernet
C ommunication table
The communication tables are available on the CD-Rom supplied with the ethernet module SM213 and the ether­net/RS485 module SM214.
6S5080-02b
Hager 12.2011 OCOM 113007
www.hager.com
540299B_GB