Hager NDN106 Technical data

NDN106A
MCB 1P 10kA/15kA D-6A 1M
Architecture
Neutral position without neutral
Number of poles 1 P
Type of pole 1 P
Fixing mode Din-Rail
Curve D
Rated operational voltage Ue 230 / 400 V
Rated current 6 A
Type of supply voltage AC
Voltage
Rated insulation voltage 500 V
Rated impulse withstand voltage 6000 V
Electric current
Rated service breaking capacity Ics AC according IEC 60898-1 7.5 kA
Technical characteristics NDN106A4 Page 1/2
Electric current / temperature
Rating current 30°C 6 A
Rating current 30°C according to IEC 60947-2 6.73 A
Dimensions
Depth of installed product 70 mm
Height of installed product 83 mm
Width of installed product 17.5 mm
Power
Total power loss under IN 1.33 W
Endurance
Electric endurance in number of cycles 4000
Number of mechanical operations 20000
Capacity
Number of modules 1
Installation, mounting
Tightening torque 2,8Nm
Equipment
Can be accessorized Yes
Standards
Standard text EN 60898-1 ; IEC 60947-2
European directive WEEE concerned
Safety
Protection index IP IP20
Use conditions
Storage temperature -25/80 °C
temperatur
Operating temperature -25/70 °C
Technical characteristics NDN106A4 Page 2/2
Loading...