Hager KLDS8, KLDS4, KLDS6, KLDS10, KLDS12 Installation Instructions

Wiring
Single Circuit Switching
With the Copper Link (1) in place, the switch return can be wired to terminal SW(A) or SW(B) to swtich all outgoing ways.
Dual Circuit Switching
For dual circuit switching remove the Copper Link (1). Terminal SW(A) will switch outgoing ways marked as Circuit A, and Terminal SW(B) will switch outgoing ways marked as circuit B.
Flexible Cords
Conductors of exible cords should not be connected into the main terminal block. A separate terminal block is provided for connecting any switching devices using a exible cord e.g. hager EEK513W occpuancy sensor. Maximum rating for this terminal block is 10A.
Normally open retractive wall switch
Terminal block wall switch (grey)
klik.LDS with all ways switched by a single hager EEK513W occupancy sensor
Circuit B
LOOP
N
SW(B)
SW(A)
AUX
Copper Link (1)
Copper Link (2)
LOOP
NEUTRAL
SWITCH RETURN
Circuit A
LOOP (brown)
NEUTRAL (blue) Sw B (black) Sw A (black)
EEK513W
klik.lighting distribution system
KLDS12
KLDS10
Wiring Diagrams
For emergency lighting arrangements refer to the following wiring diagrams.
‘Local’ lighting switch control
N
Emergency
test
switch
To lighting distribution board
Centralised emergency test via keyswitch
L
Aux Loop
N Sw(B) Sw(A)
Local lighting switch
Copper Link(2)
To other LDS box
N
N
To lighting distribution board To lighting distribution board
Emergency test switch N/C
‘Local’ lighting switch control Permanent emergency feed
L
Local lighting switch
Zone lighting control ‘Local’ emergency test control
L
Zone switch to other LDS box
Aux
Copper Link(2)
Loop
N Sw(B) Sw(A)
Aux
Remove Copper Link(2)
Loop
N Sw(B) Sw(A)
To other LDS Box
Hager Ltd
Hortonwood 50
KLDS8
Telford Shropshire TF1 7FT
Sales Hotline: Tel: 01952 675612 Fax: 01952 675645 sales@hager.co.uk
Technical Support Line:
KLDS6
Tel: 01952 675689 technical@hager.co.uk
This product should be installed by a competent person (e.g. a qualied electrician) in accordance with these instructions and the appropriate clauses of the IEE Wiring Regulations (BS7671).
KLDS4
469212C10 iss A
Hanging from ceiling suspension systems
A.
Attach spring channel nuts to ceiling channel.
B.
Attach spring channel nuts to the opposite end of suspension rod and place in T-slot in box.
Mounting Positions
Top
Rear face
Bottom
There is a choice of three mounting
C.
positions top, bottom or rear face.
Fixed to trunking
A.
Remove end cover.
B.
Drill a 20mm dia hole in the base of the lighting trunking at the position where cable entry to the LDS box will be.Drill a second hole 6mm dia clear to line up with the xing hole at the non terminal end of the LDS box.
A B
4 way A = 155 B = 193 6 way A = 205 B = 243 8 way A = 255 B = 293 10 way A = 305 B = 343
Fixed to solid surface
A.
Remove end cover.
Fitting postions
130mm
Drill holes through terminal end in
B.
recess on inside face of terminal compartment through the xing holes at t end. Fixing centres ‘A’ are 4 way = 208 8 way = 308 6 way = 258
dimples. Use
he non terminal
10 way = 358
A
To enable entry of wiring system
D.
remove appropriate knockouts connect and terminate
C.
Using an appropriate conduit tting. Attach the box to the trunking via the 20mm hole and use a M6 nut and bolt through the 6mm hole. Run cables through conduit tting and terminate cables. (See wiring diagrams)
C.
To enable entry of wiring system remove appropriate knockouts connect and terminate conductors. (See wiring diagrams)