Wiring
Single Circuit Switching
With the Copper Link (1) in place, the
switch return can be wired to terminal
SW(A) or SW(B) to swtich all outgoing
ways.
Dual Circuit Switching
For dual circuit switching remove the
Copper Link (1). Terminal SW(A) will
switch outgoing ways marked as
Circuit A, and Terminal SW(B) will
switch outgoing ways marked as
circuit B.
Flexible Cords
Conductors of exible cords should
not be connected into the main terminal
block. A separate terminal block is
provided for connecting any switching
devices using a exible cord e.g. hager
EEK513W occpuancy sensor.
Maximum rating for this terminal block
is 10A.
Normally
open retractive
wall switch
Terminal
block
wall
switch
(grey)
klik.LDS with all ways switched by
a single hager EEK513W occupancy
sensor
Circuit B
LOOP
N
SW(B)
SW(A)
AUX
Copper Link (1)
Copper Link (2)
LOOP
NEUTRAL
SWITCH
RETURN
Circuit A
LOOP (brown)
NEUTRAL (blue)
Sw B (black)
Sw A (black)
EEK513W
klik.lighting distribution system
KLDS12
KLDS10
Wiring Diagrams
For emergency lighting arrangements
refer to the following wiring diagrams.
‘Local’ lighting switch control
E
N
Emergency
test
switch
To lighting distribution board
Centralised emergency test via keyswitch
L
Aux
Loop
N
Sw(B)
Sw(A)
Local lighting switch
Copper Link(2)
To other
LDS box
E
N
E
N
To lighting distribution board To lighting distribution board
Emergency test
switch N/C
‘Local’ lighting switch control
Permanent emergency feed
L
Local lighting switch
Zone lighting control
‘Local’ emergency test control
L
Zone switch to other LDS box
Aux
Copper Link(2)
Loop
N
Sw(B)
Sw(A)
Aux
Remove Copper Link(2)
Loop
N
Sw(B)
Sw(A)
To other
LDS Box
Hager Ltd
Hortonwood 50
KLDS8
Telford
Shropshire
TF1 7FT
Sales Hotline:
Tel: 01952 675612
Fax: 01952 675645
sales@hager.co.uk
Technical Support Line:
KLDS6
Tel: 01952 675689
technical@hager.co.uk
This product should be installed by a competent person
(e.g. a qualied electrician) in accordance with these
instructions and the appropriate clauses of the IEE Wiring
Regulations (BS7671).
KLDS4
469212C10 iss A

Hanging from ceiling suspension systems
A.
Attach spring channel nuts to ceiling
channel.
B.
Attach spring channel nuts to the
opposite end of suspension rod and
place in T-slot in box.
Mounting Positions
Top
Rear face
Bottom
There is a choice of three mounting
C.
positions top, bottom or rear face.
Fixed to trunking
A.
Remove end cover.
B.
Drill a 20mm dia hole in the base of the
lighting trunking at the position where
cable entry to the LDS box will be.Drill
a second hole 6mm dia clear to line up
with the xing hole at the non terminal
end of the LDS box.
A
B
4 way A = 155 B = 193
6 way A = 205 B = 243
8 way A = 255 B = 293
10 way A = 305 B = 343
Fixed to solid surface
A.
Remove end cover.
Fitting
postions
130mm
Drill holes through terminal end in
B.
recess on inside face of terminal
compartment through
the xing holes at t
end.
Fixing centres ‘A’ are
4 way = 208 8 way = 308
6 way = 258
dimples. Use
he non terminal
10 way = 358
A
To enable entry of wiring system
D.
remove appropriate knockouts
connect and terminate
C.
Using an appropriate conduit tting.
Attach the box to the trunking via the
20mm hole and use a M6 nut and bolt
through the 6mm hole. Run cables
through conduit tting and terminate
cables. (See wiring diagrams)
C.
To enable entry of wiring system
remove appropriate knockouts
connect and terminate conductors.
(See wiring diagrams)